Professional Documents
Culture Documents
Rolling Sphere Tool Guide PDF
Rolling Sphere Tool Guide PDF
I.
I.
Calculate Protection
II.
III.
References
Calculate Protection
Test the coverage provided by the lightning shielding system. The tool will provide the
geometric zones of protection. It may be appropriate to trace these protection zones on
plan and section views of the substation to accurately identify protected and unprotected
areas.
In this section the following topics are explained. (Use the links below to navigate to a
specific topic.)
Shielding Configuration
BIL
h(e)
r(c)
h(m)
h(w)
d(max)
sin
R (triple mast)
R (triple wire)
b
r(2)
Shielding Configuration
Select from one of the standard shielding configurations to test its coverage. Each one
requires different input parameters. Depending on their locations, multiple masts and
wires can provide added coverage beyond their individual contributions. This calculator
can help determine this added coverage when selecting the appropriate configuration. If
the desired configuration is not listed, divide the testing area into configurations that are
listed. Alternatively, use the single mast and wire configurations to determine strike
distances for each individual shielding electrode and determine the protected areas
graphically.
Page 1 of 14
v1.2
h(e)
Height of equipment refers to the equipment or bus needing protection (in feet). As h(e)
increases, the maximum distance from the shielding device (r) must shrink to keep the
equipment under the rolling sphere. Surge impedance (Z(s)) of a conductor is also
affected by h(e). A conductor farther from the ground has greater surge impedance than a
conductor closer to the ground.
Page 2 of 14
v1.2
R(0) = r l
Three-conductor bundle:
R (0) = 3 r l 2
Four-conductor bundle:
R(0) = 4
2 r l3
n-conductor bundle:
R (0 ) = 0.5 l 'n n
2 r
l'
where
r
l
l
n
h(m)
Height of mast refers to the height of the shielding mast above ground (in feet). A mast
height greater than or equal to the strike distance provides the most protection. For
masts, the value of the coefficient k from Eq 5-1B of IEEE 998-1996 is 1.2. When
calculations require multiple masts, the shortest mast should be used for h(m).
Page 3 of 14
v1.2
d(max)
Maximum distance refers to the greatest horizontal distance (in feet) two masts or two
wires can be placed from each other and still provide protection for equipment between
them, provided that the equipment does not exceed a height of h(e). If d(1), d(2), or d(3)
exceeds d(max), then the bottom of the sphere penetrates below the equipment height,
even if it rests atop the shielding electrodes. To find d(max) between a wire and mast,
conservatively select the Double Wire configuration. d(max) is calculated according to
the following equation from Exhibit B.5-5 of IEEE 998-1996:
For a mast:
d (max) = 2 S 2 (S h(m) + h(e) )
For a wire:
d (max) = 2 S 2 (S h( w) + h(e) )
where
d
S
h(m)
h(w)
h(e)
Page 4 of 14
v1.2
2.2 BIL
Zs
I ( s ) = 2kA
where
BIL is the Basic Impulse Level rating of the insulation in kV
Z(s) is the surge impedance of the conductor in
Z(s)
Surge impedance refers to the impedance of the conductor that the lightning surge is
passing through in . There is no input for this in the tool because it is approximated
from the EPRI Red Book by Eq 12.5.5.
Surge impedance:
Z ( s ) = 60 ln(2h(e) / r (c))
where
h(e) is the height of the equipment or bus above ground (in feet)
r(c) is the radius or effective radius of the conductor (in feet)
Page 5 of 14
v1.2
r
Radius of protection refers to the distance (in feet) from the shielding electrode to the
edge of protection for a given equipment height. It is calculated according to the
following equations from Camden:
For a mast:
r = S 2 ( S h(m)) 2 S 2 ( S h(e)) 2
r = S S 2 ( S h(e))2
for h(m) S
For a wire:
r = S 2 ( S h( w)) 2 S 2 ( S h(e)) 2
where
S
h(m)
h(w)
h(e)
Page 6 of 14
v1.2
r(1)
r1 is the radius (in feet) of the curvature of the unprotected area originating a distance of x
from the midpoint of two structures, as defined above. r1 is calculated according to the
following equation from Camden:
Radius:
r (1) = S 2 ( S h(e)) 2
Page 7 of 14
v1.2
2
a(a d (1))(a d (2))(a d (3))
d (2)d (3)
where
a = 12 (d (1) + d (2) + d (3))
d(1), d(2), and d(3) are distances between masts as described in the
diagram
R (triple mast)
R for the triple mast calculation describes the horizontal distance (in feet) from the masts
to the center of the rolling sphere resting on top of the three masts. From the triangle
formed by the three masts, a circumscribed circle of radius R can be created. The center
of the rolling sphere is directly above this point. This is also from the Law of Sines and
is calculated for masts according to the following equation from Camden:
Triple mast calculation:
R=
d (1)
2 sin
where
d(1) is the distance between masts 1 and 2 (in feet)
sin is the sine of the angle opposite d(1)
Note: If triple mast (R) is greater than the strike distance (S), then the masts are too far
apart for the rolling sphere to rest on top of them and the double mast calculation should
be used. If triple mast (R) is less than the strike distance (S), then the rolling sphere can
sit on the three masts without touching the ground. It is further necessary to determine if
the sphere reaches the equipment (see calculation for b).
Page 8 of 14
v1.2
where
a = 12 (d (1) + d (2) + d (3))
d(1), d(2), and d(3) are the distances between supports as described in the
diagram
Note: If the triple wire (R) is greater than the strike distance (S), then the shield wires are
too far apart for the rolling sphere to rest on top of them and the double wire calculation
should be used. If the triple wire (R) is less than the strike distance (S), then the rolling
sphere can sit on the three shield wires without touching the ground. It is further
necessary to determine if the sphere reaches the equipment (see the following calculation
for b).
Page 9 of 14
v1.2
Note: If b is larger than the strike distance (S), then the sphere is entirely above the
equipment, otherwise the circular cross section of the sphere at h(e) (the equipment
height), must be determined (see calculation for r(2)).
r(2)
r(2) refers to the radius (in feet) of the unprotected area created by a sphere resting on top
of three shielding electrodes penetrating below the equipment height. r(2) is the circular
cross section of the sphere at the equipment height and is calculated according to the
following equation from Camden:
Radius of the unprotected area:
r ( 2) = S 2 b 2
r (2) = 0 ft
for S > b
for S b
where
S
b
v1.2
Failure Rate
S(m)
I(sm)
P(f)
P(I)
N
F
d(u)
The distance to unprotected equipment (in feet) from a shielding electrode refers to the
minimum desired value for radius of protection, r, necessary to obtain total shielding of
all energized equipment. It is determined graphically by measuring the distance between
the insufficient shielding electrode and the furthest point of unprotected equipment. This
should be greater than the actual value of r, otherwise there is no need to calculate failure
probability; a negative value of F will result.
T
The average annual isokeraunic level (T) refers to the average number of thunderstormdays in a year. A thunderstorm-day is a day where thunder was heard at least once. The
linked map shows the average isokeraunic level for the U.S. as recorded by the National
Weather Service.
A
A refers to the area (in square feet) of the unprotected region which can be calculated
graphically by the user.
S(m)
S(m) refers to the strike distance required to produce d(u). In other words, it is the
minimum desired value for strike distance that would have protected all energized
equipment. S(m) is calculated using the same equations from Camden used to calculate
the radius of protection, r, substituting the values of d(u) for r and S(m) for S. It then
solves for S(m).
Page 11 of 14
v1.2
P(f)
P(f) refers to the probability that a lightning stroke inside the unprotected area will cause
insulation failure. It is calculated according to the following equation from Camden:
Probability of failure:
P ( f ) = P(< I sm ) P (< I s )
where
I(sm) is the minimum stroke current in kA required to produce S(m)
I(s) is the stroke current in kA
P(<I(sm)) [or 1-P(I(sm))] is the probability that a stroke is less than I(sm)
P(<I(s)) [or 1-P(I(s))] is the probability that a stroke is less than I(s).
Note: P(I(sm)) and P(I(s)) are calculated by the tool according to Eq 2-2B of
IEEE 998-1996 (see calculation for P(I)).
P(I)
P(I) refers to the probability that the peak current in any stroke will exceed a given
current, I. It is calculated according to Eq 2-2B of IEEE 998-1996:
Probability that peak current exceeds I:
P( I ) =
1
I
1+
24
2.6
where
I is the specified crest current of the stroke (in kiloamperes)
Page 12 of 14
v1.2
F
Failure rate of insulation within the unprotected area describes the number of years
between failures. It is up to the user to decide upon an acceptable failure rate for a
specific substation. F is calculated according to the following equation from Camden:
Failure rate:
F=
1
P( f ) N
where
P(f) is the probability of failure from a stroke
N is the number of strokes in the unprotected area per year
Page 13 of 14
v1.2
References
Page 14 of 14
v1.2