Fault Level
Fault Level
Fault Level
11 kV
11000
UoM
Volts
40
kA
762
MVA
Voltage factor
1.1
1.05
VCB
Impedance
ZQ
0.175
Resistance
RQ
0.035
Reactance
XQ
0.171
Cable 1
No. of runs
Cable 1
3x240
3
Route Length
VCB
11 kV
VCB
Cable 2
11/3.5 kV
4000 kVA
Cable Resistance
Cable Reactance
Net Cable Resistance
1.2
kM
0.16
0.085
0.0640
/km
/km
XC1
0.0340
0.245
Isc
28.51
kA
Cable 2
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance
RC2
3x240
1
0.1
0.16
0.085
0.0160
kM
/km
/km
XC2
0.0085
ST
MVA
kV
kV
RC1
Remarks
Assumed in the absence of the
information
For MV System up to 35 kV (In
Accordance with IEC 60909)
For 415 V System (In Accordance with
IEC 60909)
RQ = 0.2 ZQ (In Accordance with IEC
60909)
ONAN, OCTC
Power Transformer
Rated Capacity
Rated Primary Voltage
Rated Secondary Voltage
VT
4
11
3.5
Dyn 1
IT
659.8
Amp
% Impedance
uT
6.25
QT
27000
Transformer Impedance
ZT
0.1914
Transformer Resistance
RT
0.0207
(Q / (3 * IT2)
Tap 5% @ 2.5
XT
0.1903
Transformer Reactance
(ZT2 - RT2)
As two identical transformers are connected in parallel, its Impedance, resistance & reactance shall be divided by
2.
RT1
0.0103
Equivalent Transformer Resistance
Equivalent Transformer Reactance
XT1
0.0951
The reactance & resistance calculated for HV Section must be recalculated for the LV network via multiplication
by square of the voltage ratio of the transformer.
N1
0.101
Square of the voltage Ratio
Equivalent reactance up to Power Trafo
X1
0.1168
R1
0.0220
X1
0.1168
R1
0.0220
Busduct
Neglected for the purpose of calculation
Busduct
VCB
3.3 kV
Total Impedance
Symmetrical S/C Current (rms) at 3.3 kV
SWGR Bus
VCB
Cable 3
HT JB on Ground
0.119
Isc
18.71
kA
Cable 3
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance
RC3
3x185
1
0.35
0.21
0.075
0.0735
/km
/km
XC3
0.0263
Cable 4
3x70
SR Machine
HT LBS
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance
Net Cable Reactance
RC4
1
0.22
0.354
0.093
0.0779
/km
/km
XC4
0.0205
VT
NA
0.63
3.3
0.433
MVA
kV
kV
840.0
Amp
630 kVA
Distribution Transformer
Rated Capacity
Rated Primary Voltage
Rated Secondary Voltage
IT
% Impedance
uT
QT
8500
Transformer Impedance
ZT
0.0149
Transformer Resistance
RT2
0.0040
(Q / (3 * IT2)
Transformer Reactance
XT2
0.0143
(ZT2 - RT2)
3.3/.433 kV
SR Trafo
Dyn 1
ACB
ST
The reactance & resistance calculated for HV Section must be recalculated for the LV network via multiplication
by square of the voltage ratio of the transformer.
433 V
SR MCC
N2
0.017
0.017
0.007
0.019
14.18
kA
Isc
Rev 0