Earth-fault Relay
Product Guide
SPAJ 140 C
SPAJ 140 C
1MRS750361-MBG
Issued: April 1999
Status: Updated
Version: C/18.04.2006
Data subject to change without notice
Features
Powerful software support for parameterization of the relay, for reading measured
and recorded values, events, etc., and for
storing readings
Application
Design
SPAJ 140 C
1MRS750361-MBG
Data communication
The relay is provided with a serial interface
on the rear panel. By means of a bus connection module type SPA-ZC 17 or SPA-ZC 21
the relay can be connected to the fibre-optic
SPA bus. The bus connection module type
SPA-ZC 21 is powered from the host relay,
whereas the bus connection module SPAZC 17 is provided with a built-in power unit,
which can be fed from an external secured
power source. The relay communicates with
higher-level data acquisition and control systems over the SPA bus.
Self-supervision
The relay incorporates a sophisticated selfsupervision system with auto-diagnosis,
which increases the availability of the relay
and the reliability of the system. The selfsupervision system continuously monitors the
hardware and the software of the relay. The
system also supervises the operation of the
auxiliary supply module and the voltages
generated by the module.
When a permanent internal relay fault is
detected, the IRF indicator on the relay front
panel is lit. At the same time the output relay
of the self-supervision system operates and a
fault message is transmitted to the higherlevel system over the serial bus. Further, in
most fault situations, a fault code is shown in
the display of the protection relay module.
The fault code indicates the type of the fault
that has been detected.
Technical data
SPAJ 140 C
1MRS750361-MBG
Rated current In
1A
5A
continuously
4A
20 A
for 10 s
25 A
100 A
for 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
50 Hz or 60 Hz
Thermal withstand
capability
Dynamic current
withstand capability
25-27
25-26
Rated current In
1A
5A
continuously
4A
20 A
for 10 s
25 A
100 A
for 1 s
100 A
500 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
50 Hz or 60 Hz
Thermal withstand
capability
Dynamic current
withstand capability
Tripping
Signalling
Terminals
65-66, 74-75
70-71-72, 68-69,
77-78, 80-81
Rated voltage
250 V ac/dc
Continuous carry
5A
5A
30 A
10 A
15 A
8A
220 V dc
1A
0.15 A
110 V dc
3A
0.25 A
48 V dc
5A
1A
SPAJ 140 C
1MRS750361-MBG
Data communication
Terminals
10-11
18265 V dc or
80265 V ac
220 mA
Transmission mode
Data code
ASCII
4800 or 9600 Bd
SPA-ZC 21BB
SPA-ZC 21MM
SPA-ZC 17BB
SPA-ZC 17MM
SPTU 240R1
110/120/230/240 V ac,
110/125/220 V dc,
80265 V ac/dc
SPTU 48R1
24/48/60 V dc,
1880 V dc
under quiescent
conditions
~4 W
under operating
conditions
~6 W
Power consumption
Stage I>
Stage I>>
at definite time
0.55.0 In
0.540.0 In and
at inverse time
0.52.5 In
50 ms
40 ms
0.05300 s
0.04300 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
RI type inverse
RXIDG type inverse
Time multiplier k
0.051.0
40 ms
40 ms
Retardation time
<30 ms
0.96
2% of set value or 25 ms
Operation accuracy
3% of set value
3% of set value
SPAJ 140 C
1MRS750361-MBG
Stage I0>
Stage I0>>
Start current
0.10.8 In
0.110.0 In and
60 ms
40 ms
0.05300 s
0.05300 s
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
RI type inverse
RXIDG type inverse
Time multiplier k
0.051.0
40 ms
40 ms
Retardation time
<30 ms
0.96
0.96
2% of set value or 25 ms
Operation accuracy
3% of set value
3% of set value
Interference tests
Insulation resistance
(IEC 60255-5)
>100 M, 500 V dc
High-frequency (1 MHz)
disturbance test (IEC 60255-221), common mode
2.5 kV
High-frequency (1 MHz)
disturbance test (IEC 60255-221), differential mode
1.0 kV
4 kV, 5/50 ns
2 kV, 5/50 ns
Electrostatic discharge
(IEC 60255-22-2 and IEC 610004-2), air discharge
8 kV
Electrostatic discharge
(IEC 60255-22-2 and IEC610004-2), contact discharge
6 kV
Variation voltage
68265 V
Interruption 80 V - 50%
0200 ms
Interruption 80 V - 100%
030 ms
0160 ms
SPAJ 140 C
1MRS750361-MBG
Environmental conditions
Seismic test
(ANSI/IEEE C37.98-1987),
operating basis earth-quake test
0.55.25 g
Seismic test
(ANSI/IEEE C37.98-1987), safe
shut down earth-quake test
0.57.5 g
Vibration test
Shock/bump test
(IEC 60255-21-2)
20 g, 1000 bumps/direction
Corrosion test
Battelle test
-10+55C
-40+70C
<95%, +40C, 96 h
IP 54
Weight
~3.5 kg
SGB/8
SGB/5
SGB/4
SGB/3
SGB/2
SGB/1
+ -
Io>>
Io>
3I>>
3I>
RESET
RC SETTINGS
U1
I/O
IRF
TS1
74 75
SGR3/3
SGR3/2
5A
1A
5A
1A
5A
1A
62 61 70 71 72
T9
SGR3/4
5A
1A
SPAJ 140 C
U3
U2
10
SGR3/5
11
SS1
77 78
SGR1/1
7 8 9 25 26 27
SGR1/3
1 23 4 5 6
SGR1/5
63
SGR3/6
START 2
SGF/4
SGR1/7
START 1
0.1...1s
T7
T5
T3
T1
C
SS2
80 81
SIGNAL 1
SGR2/1
IRF
SGR2/3
EXTERNAL
CONTROL
SGR2/5
SGR3/1
U aux
B
SS3
68 69
SIGNAL 2
SGR2/2
- (~)
SGR2/7
SGR2/4
+ (~)
SGR2/6
SGR2/8
Fig. 8
-
SGB/6
SGB/7
A
TS2
65 66
TRIP
LATCHING
SGR1/2
SGR1/4
SGR1/6
SGR1/8
L1
L2
L3
SPA-ZC_
R
T8
T6
T4
T2
Tx
U1
TRIP
SERIAL
PORT
Rx
SPAJ 140 C
Block diagram
BSPAJ140
SGR3/8
SGR3/7
Mounting and
dimensions
SPAJ 140 C
1MRS750361-MBG
Flush mounting
250
142
216
34
139 1
136
162
129 1
186
30
Panel cutout
dim100
Fig. 1
Semi-flush mounting
a
Raising frame
SPA-ZX 111
SPA-ZX 112
SPA-ZX 113
176
136
96
74
114
154
SFM100_1
Fig. 2
Projecting mounting
When projecting mounting is preferred, a
relay case type SPA-ZX 110 is used. The
relay case for projecting mounting is provided with front connectors.
SPA-ZX110
SPA-ZX115
158
115
+0,4
10
263
6
21,5
312
292
+0,4
177 0 (4U)
101,6
482,6 0 (19")
6
115
98
104_6_10
Fig. 3
10
Ordering
SPAJ 140 C
1MRS750361-MBG
Ordering example
2. Order number
RS 611 006-AA
3. Rated values
In=5 A, fn=50 Hz
4. Auxiliary voltage
Uaux =110 V dc
5. Accessories
6. Special requirements
Order numbers
Combined overcurrent and earth-fault relay
SPAJ 140 C without test adapter
References
Additional information
Users manual and technical description Combined
overcurrent and earth-fault relay SPAJ 140 C
1MRS 750629-MUM EN
11