CONSTANTFLOW
Volume Flow Controllers
for constant volume systems
Type EN

TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Telephone +49/28 45/2 02-0


Telefax
+49/28 45/2 02-2 65
e-mail trox@trox.de
www.troxtechnik.com

Contents Description
Description
Application
Construction Dimensions Accessories
Dimensions
Aerodynmic and acoustic quick selection

2
3
4
5
6

Type EN volume flow controller

TROX Type EN and END volume flow controllers are mechanical


system-powered controllers and were developed for the control
of flow rates in constant volume systems. The controllers are
suited for both supply air and extract air.
EN: Controller for nominal sizes 200 x 100 to 600 x 600
END: Controller for nominal sizes 200 x 100 to 600 x 600
with additional acoustic cladding
Each controller is set up to a reference flow rate and has been
subjected to an aerodynamic function test.
The required flow rate can be easily set without tools using an
external scale. To simplify installation, the controllers can be
ordered and fitted by nominal size. The required flow rate can
then be easily and accurately set during commissioning.
The EN controllers are also available with additional acoustic
cladding to reduce case-radiated noise (END). For more
stringent noise requirements the TX silencer can be used.
The controller operates without an external power supply.
A control damper blade, shaft mounted supported on bearings,
is adjusted by the aerodynamic forces such that the preset flow
rate is held constant over the entire differential pressure range.
Aerodynamic forces from air flow create a closing force on the
damper blade. A self inflating bellows amplifies this force, acting
2

Nomenclature Air-regenerated noise


Air-regenerated noise
Case-radiated noise
Order details

8
9
10
11

Type END volume flow controller

simultaneously as an oscillation damper. This closing force is


counteracted by a leaf spring that unrolls over a cam plate. The
cam plate is designed such that as the pressure differential
changes, the damper blade adjusts to keep a constant flow rate
within close tolerances.
Further, current information on application and selection can be
found in the Technical Documentation download area of our
website.
Also available on the Internet is the Air terminal units on-line
programme for the design and selection of our units.
Cam
plate

Closing
Control
force damper blade

Leaf spring

Bellows

Application
Inexpensive commissioning

Simplified installation

By a simple step and without need for preliminary measurements, the required flow rate value can be set using the pointer
against the externally mounted scale of the Type EN or END .
The advantage over conventional balancing dampers is that
there is no need for repeated measurement and readjustment
by a qualified commissioning engineer.

The Type EN and END volume flow controllers are fitted with
flanges on both ends. This ensures very low leakage at the joint.

Should the system pressure change, e.g. by opening or closing


of duct sections, the flow rates in the entire system will alter if
balancing dampers are used; however, this is not the case if the
Type EN and ENS volume flow controllers are used.

Acoustic requirements
Depending on requirements, a TX silencer may be supplied to
reduce the air-regenerated noise.
(installed by others).

The controller reacts immediately and adjusts the damper blade


position directly, so that the flow rate set is kept constant over
the entire differential pressure range.
The Type EN controllers can be fitted with an electric actuator
for setpoint value readjustment.

Type EN volume flow controller with actuator

> 400 mm
Type EN volume flow controller, H =
(Two controllers used)

TX silencer

Construction Dimensions Accessories


Characteristics
Mechanical system-powered, without external power supply
Suitable for supply and extract air
Correct operation, even under unfavourable upstream and downstream conditions (straight length required upstream 1.5 W, downstream 0.5 W)
Close tolerances on flow rate
Flow rate setting using pointer on external scale, scale accuracy
approximately 4 %
Flow rate range 4 : 1
Damper blade shaft supported in bearings
Bellows also acts as an oscillation damper
Differential pressure range 50 to 1000 Pa
Independent of orientation
Damper blade mechanisms maintenance-free
Operating temperature range 10 to 50 C

Constructional features
Rectangular form, rigid frame
Flanged at both ends, suitable for fitting System 30 connecting
sections
Casing
Casing and damper blade made of galvanised sheet steel
Stainless steel leaf spring
Polyurethane bellows
Plain bearings with PTFE coating

EN END

approx.
100

Additional acoustic cladding


Outer cover in galvanised sheet steel
Sound-absorbent lining
Structure-borne noise isolation
Cannot be retrofitted
Actuators
For setpoint readjustment
24 VAC or 230 VAC power
Factory-fitted
Small footprint thanks to compact construction
TX silencer
Suitable for EN/END controllers
Casing in galvanised sheet steel
Mineral wool lining conforming to DIN 4102, fire rating class A2,
with RAL quality mark RAL-GZ 388, biodegradable as defined by
TRGS 905 as well as EU directive 97/69/EC
Mineral wool faced with glass-fibre fabric providing protection
against erosion by air flow up to a maximum air velocity of 20 m/s,
inert to fungal and bacterial growth
Air heater
Suitable for EN/END controllers
See leaflet 5/20/EN/... for dimensions and technical data

Slot 20 x 13
(M8 on END type)

38

400

 13

EN

500
1500

Connection section

BxH

30

Connection of rectangular duct

Compressible seal,
supplied by customer

Rectangular duct

TX

Dimensions

Dimensions in mm

Weight in kg

EN

END

BxH

200

100

300

EN

END

TX

234

134

276

176

280

180

10

334

134

376

176

380

180

10

12

300

150

334

184

376

226

380

230

6.5

11

15

300

200

334

234

376

276

380

280

12

20

400

434

234

476

276

480

280

15

25

500

534

234

576

276

580

280

11

17

29

600

634

234

676

276

680

280

13

20

34

434

284

476

326

480

330

10

17

27

500

534

284

576

326

580

330

12

18

30

600

634

284

676

326

680

330

14

22

36

434

334

476

376

480

380

12

18

29

500

534

334

576

376

580

380

13

19

34

600

634

334

676

376

380

380

15

22

40

434

434

476

476

480

480

18

26

39

500

534

434

576

476

580

480

17.5

25.5

42

600

634

434

676

476

680

480

18

26

45

534

534

576

576

580

580

18.5

28

45

634

534

676

576

680

580

19

29

50

634

634

676

676

680

680

20

30

55

400

400

400

500

250

300

400

500

600

600

600

Aerodynamic and Acoustic Quick Selection


System attenuation in dB/Oct. acc. to VDI 2081 (values incorporated into the quick selection table)
fm in Hz

63

125

250

500

1000

2000

4000

8000

Duct bend attenuation

Room attenuation

End reflection

10

Correction for distribution into the duct system (values incorporated into the quick selection table)
.
V

m3/h

500

1000

2000

4000

6000

8000

10000

12000

l/s

139

278

556

1111

1667

2222

2778

3333

11

12

13

14

dB per octave

Quick selection of sound pressure level in dB(A)


pg = 100 Pa

.
V

200 100

40
80
120
160
300
65
130
195
260
300 150 105
210
315
420
300 200 130
260
390
520
400
210
420
630
840
500
230
460
690
920
600
255
510
765
1020
400 250 220
440
660
880
500
300
600
900
1200
600
320
640
960
1280

.
V

pg min
in Pa

LpA
without
silencer

m3/h

mm

l/s

BxH

EN

TX 1)

144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

10
30
65
110
10
30
70
120
10
30
65
110
10
30
65
110
10
30
75
110
10
30
65
110
10
25
50
110
5
25
50
110
10
30
65
110
5
25
50
110

pg = 200 Pa

pg = 500 Pa

Air-regenerated noise Case-radiated noise 2) Air-regenerated noise Case-radiated noise 2) Air-regenerated noise Case-radiated noise 2)

32
38
42
43
35
41
43
44
38
42
44
45
42
43
44
44
39
40
41
42
37
38
38
39
35
36
37
37
41
41
42
43
38
39
40
41
37
37
38
38

LpA1

LpA2

LpA3

LpA

with
without
with
without
TX
additional additional silencer
silencer acoustic acoustic
cladding cladding

18
27
32
35
20
29
34
36
22
29
34
37
21
26
30
32
20
24
28
31
18
23
26
29
17
22
25
28
20
25
29
31
19
23
27
30
17
22
26
28

22
30
34
37
25
33
37
40
27
34
39
42
29
33
36
39
29
33
36
39
26
31
34
37
25
30
33
35
29
33
36
38
27
32
35
37
26
30
33
36

<
24
29
32
17
26
32
35
19
27
32
36
19
24
28
31
19
25
28
32
16
23
27
30
16
22
26
30
18
24
27
30
17
23
27
31
16
22
26
29

41
46
49
51
43
49
50
52
46
49
51
52
51
52
52
53
48
49
49
50
46
47
47
48
44
44
45
46
49
51
51
52
47
48
49
49
45
46
47
48

LpA1

LpA2

LpA3

LpA

with
without
with
without
TX
additional additional silencer
silencer acoustic acoustic
cladding cladding

22
32
38
41
25
34
39
42
28
35
40
42
30
34
38
41
28
33
36
39
26
31
35
37
25
30
33
36
29
33
37
39
27
32
35
38
25
30
34
37

29
36
40
44
32
39
43
46
34
40
45
48
37
41
44
46
36
41
44
46
34
39
42
44
33
37
41
43
36
41
43
46
36
40
43
45
34
38
41
45

21
29
34
38
24
32
37
40
25
32
38
41
27
32
36
39
26
32
36
40
25
31
35
38
24
30
34
37
26
32
35
38
26
31
35
38
24
30
34
38

47
52
56
58
50
55
57
58
52
56
57
58
57
59
60
60
55
56
57
57
53
54
54
55
50
51
52
53
56
57
58
58
54
55
56
56
52
53
54
55

LpA1

LpA2

LpA3

with
without
with
TX
additional additional
silencer acoustic acoustic
cladding cladding

28
36
43
47
30
39
44
47
33
40
44
47
37
41
45
47
35
39
43
45
33
37
41
43
32
36
40
42
35
39
43
46
34
38
42
44
32
36
40
43

35
41
46
49
38
44
48
51
40
46
50
53
43
48
51
53
43
47
50
52
41
45
48
50
39
44
47
50
43
47
50
52
42
47
49
51
40
45
48
51

26
34
39
42
29
36
41
44
30
37
42
45
33
39
42
45
33
39
43
45
31
37
41
44
30
36
40
44
33
38
41
44
32
38
41
44
31
36
40
44

1) also to be taken into consideration


< indicates values below 15
2) 4 dB/octave ceiling reduction and 5 dB/octave room attenuation have been allowed for in the calculation of case-radiated noise
Acoustic data for differential pressure up to 1000 Pa, see on-line design programme Air terminal units.

Aerodynamic and Acoustic Quick Selection




EN

LW2
LW3

 Additional acoustic cladding


 TX silencer
 End reflection based on diffuser

LW

without additional acoustic cladding

with additional acoustic cladding

Room
without additional
LpA2 acoustic cladding

LpA3

with additional
acoustic cladding
Microphone

LpA

without silencer

LpA1

with TX silencer

Nomenclature, see page 8

Quick selection of sound pressure level in dB(A)


pg = 100 Pa

.
V

400 300

315
630
945
1260
500
375
750
1125
1500
600
420
840
1260
1680
400 400 420
840
1260
1680
500
460
920
1380
1840
600
510
1020
1530
2040
500 500 600
1200
1800
2400
600
640
1280
1920
2560
600 600 840
1680
2520
3360

.
V

pg min
in Pa

LpA
without
silencer

m3/h

mm

l/s

BxH

EN

TX 1)

1134
2268
3402
4536
1350
2700
4050
5400
1512
3024
4536
6048
1512
3024
4536
6048
1656
3312
4968
6624
1836
3672
5508
7344
2160
4320
6480
8640
2304
4608
6912
9216
3024
6048
9072
12096

13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5
13
9
6
5

50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

10
30
70
110
10
30
65
110
10
25
60
100
10
30
70
125
10
30
65
110
5
20
45
110
10
30
65
110
5
30
45
80
5
25
55
95

pg = 200 Pa

pg = 500 Pa

Air-regenerated noise Case-radiated noise 2) Air-regenerated noise Case-radiated noise 2) Air-regenerated noise Case-radiated noise 2)

43
44
44
44
40
41
42
42
38
39
40
40
45
46
46
47
42
43
44
44
41
41
42
42
44
46
46
46
42
43
44
44
43
45
46
46

LpA1

LpA2

LpA3

LpA

with
without
with
without
TX
additional additional silencer
silencer acoustic acoustic
cladding cladding

22
27
31
33
20
25
29
31
18
23
27
29
24
29
33
35
22
26
30
33
19
24
28
31
24
28
32
35
21
26
30
32
23
28
32
34

32
37
39
41
30
35
37
40
28
32
35
37
35
39
42
44
32
37
39
42
31
35
38
40
36
40
43
45
34
38
41
43
35
41
43
45

21
27
31
34
20
26
29
32
18
23
27
30
24
30
33
36
22
27
30
33
21
26
29
32
25
30
34
36
23
28
31
34
25
31
34
36

51
52
53
53
48
49
50
50
47
47
48
49
53
54
55
55
51
52
52
53
49
49
50
50
52
54
54
55
50
51
52
52
52
53
54
54

LpA1

LpA2

LpA3

LpA

with
without
with
without
TX
additional additional silencer
silencer acoustic acoustic
cladding cladding

30
35
39
41
28
33
36
39
27
31
35
37
32
37
41
43
30
34
38
40
28
32
36
39
31
36
40
42
29
34
38
40
31
35
40
42

40
44
47
49
38
42
45
47
36
40
43
45
42
47
49
52
40
45
47
49
39
43
46
47
43
48
51
53
42
46
48
50
44
48
50
52

29
35
38
41
28
33
37
40
26
31
35
38
32
37
40
43
30
35
38
41
28
33
36
39
33
38
41
44
31
36
39
42
33
38
41
43

58
59
59
60
55
56
57
57
53
54
55
55
60
60
61
62
57
58
59
59
55
56
57
57
59
60
60
61
57
58
58
59
58
59
60
61

LpA1

LpA2

LpA3

with
without
with
TX
additional additional
silencer acoustic acoustic
cladding cladding

37
41
45
47
34
39
43
45
33
37
41
44
39
43
47
49
36
40
44
46
34
38
42
45
38
42
46
48
35
40
44
46
37
41
46
48

46
50
53
55
44
49
51
53
42
46
49
51
49
53
56
57
46
51
53
55
45
49
52
53
49
53
56
58
47
52
54
56
49
53
56
58

36
41
44
47
34
40
43
46
32
37
41
44
38
43
46
49
36
41
44
47
34
39
42
45
39
44
47
49
36
42
45
47
39
44
47
49

1) also to be taken into consideration


2) 4 dB/octave ceiling reduction and 5 dB/octave room attenuation have been allowed for in the calculation of case-radiated noise
Acoustic data for differential pressure up to 1000 Pa, see on-line design programme Air terminal units.

Nomenclature Air-regenerated Noise


Nomenclature

 LW

fm
LW

 LW1

in Hz: Octave band centre frequency


in dB: Sound power level of air-regenerated noise in
the room (low pressure) side ducting
in dB: Sound power level of case-radiated noise
in dB: Sound power level of case-radiated noise
with additional acoustic cladding
in dB: A-weighted sound pressure level of airregenerated noise in the room, system attenuation taken into account
in dB: A-weighted sound pressure level of airregenerated noise in the room with TX silencer,
system attenuation taken into account
in dB: A-weighted sound pressure level of caseradiated noise in the room, system attenuation
taken into account
in dB: A-weighted sound pressure level of caseradiated noise in the room with additional
acoustic cladding, system attenuation taken
into account

LW2
LW3
LpA
LpA1
LpA2
LpA3

V
 V
 pg
 pg min

in dB: Correction value for case-radiated noise


without additional acoustic cladding
in dB: Correction value for case-radiated noise
with additional acoustic cladding
in m3/h
or l/s: Flow rate
in  %: Flow rate tolerance from setpoint value
in Pa: Total pressure differential
in Pa: Minimum total pressure differential

All sound power levels are based on 1 pW, all sound pressure
levels on 20 Pa.
All noise levels measured in a reverberation chamber.
The sound power data was determined and corrected according
to DIN EN ISO 5135, February 1999.

Air-regenerated noise

4000

8000

63

125

250

500

1000

2000

4000

8000

63

125

250

500

1000

2000

4000

8000

600

2000

500

1000

400 250

500

600

fm in Hz

250

500

fm in Hz

125

400

fm in Hz
63

300 200

LW in dB

m3/h

300 150

pg = 500 Pa

LW in dB

l/s

300

pg = 200 Pa

LW in dB

.
V

BxH

mm
200 100

pg = 100 Pa

40
80
120
160
65
130
195
260
105
210
315
420
130
260
390
520
210
420
630
840
230
460
690
920
255
510
765
1020
220
440
660
880
300
600
900
1200
320
640
960
1280

144
288
432
576
234
468
702
936
378
756
1134
1512
468
936
1404
1872
756
1512
2268
3024
828
1656
2484
3312
918
1836
2754
3672
792
1584
2376
3168
1080
2160
3240
4320
1152
2304
3456
4608

42
51
56
60
43
52
57
61
44
53
58
62
49
59
64
68
48
58
63
67
43
53
59
63
40
49
55
59
47
57
62
66
45
55
61
65
41
51
57
61

41
51
56
60
43
53
59
63
45
55
61
65
37
46
51
54
42
50
55
59
42
51
56
59
43
51
56
60
40
48
53
57
42
51
56
60
43
51
56
60

31
39
44
47
34
43
48
51
38
46
51
54
37
44
49
52
37
44
48
51
33
40
45
48
31
38
42
45
38
45
49
52
37
44
48
51
34
41
45
48

31
38
42
44
35
42
46
48
39
46
50
52
41
46
49
51
41
46
49
51
38
44
47
49
37
42
45
47
43
48
51
53
42
47
50
52
40
45
48
50

34
40
44
46
37
44
47
50
41
47
51
53
46
49
51
52
45
48
50
52
43
46
48
50
42
45
47
48
47
50
52
54
46
49
51
53
45
48
50
51

36
41
44
45
39
44
46
48
42
46
49
51
45
49
51
53
44
48
50
52
42
45
48
49
40
44
46
48
46
49
52
53
44
48
51
52
43
46
49
50

30
37
40
43
32
39
42
45
34
40
44
47
39
44
46
48
39
44
46
48
37
42
44
46
36
40
43
45
40
44
46
48
39
43
46
48
38
42
44
46

22
30
34
37
24
31
35
38
25
32
36
39
34
38
40
42
33
37
40
41
31
35
38
39
30
34
36
38
34
38
40
42
33
37
39
41
31
35
37
39

46
55
60
64
47
56
61
65
48
57
62
66
55
65
71
75
54
64
70
74
49
59
65
69
46
56
61
65
53
63
68
73
51
61
67
71
47
57
63
69

45
55
61
65
48
57
63
67
50
59
65
69
45
54
59
62
50
58
63
67
50
59
64
67
51
59
64
68
48
56
61
65
51
59
64
68
51
59
64
69

37
45
50
54
41
49
54
57
44
52
57
60
45
52
56
59
44
51
56
59
41
48
52
55
38
45
50
53
46
53
57
60
44
52
56
59
42
49
53
57

37
44
48
51
42
48
52
55
46
52
56
59
48
53
56
58
47
52
55
58
45
50
53
55
43
48
51
54
50
55
58
60
49
54
57
59
47
52
55
58

40
46
50
52
43
50
53
56
47
53
57
59
53
56
58
60
52
55
57
59
50
53
55
57
49
52
54
55
54
58
59
61
53
57
59
60
52
55
57
59

45
49
52
54
47
52
54
56
50
54
57
59
54
58
60
62
53
57
59
61
51
55
57
59
49
53
55
57
55
59
61
63
54
58
60
62
52
56
58
60

41
47
50
53
42
49
52
55
44
50
54
57
50
54
57
59
50
54
57
59
48
53
55
57
47
51
54
56
50
55
57
59
50
54
57
59
48
53
55
58

34
41
46
49
36
43
47
50
37
44
48
51
46
50
52
54
45
49
52
53
43
47
49
51
41
45
48
49
45
49
52
53
45
49
51
52
43
47
49
51

49
58
63
67
50
59
64
68
51
59
65
68
60
70
75
79
59
69
74
78
54
64
70
74
51
60
66
70
58
68
73
77
56
66
72
76
52
62
68
73

49
58
64
68
51
60
66
70
53
63
68
72
51
60
65
68
56
64
70
73
56
65
70
73
57
65
70
74
54
62
67
71
57
65
70
74
57
65
70
75

42
50
55
58
45
54
58
62
49
57
62
65
51
58
62
65
50
57
61
64
47
54
58
61
44
51
55
58
51
58
63
66
50
57
61
64
47
54
59
63

42
49
53
56
47
53
57
60
51
57
61
64
53
58
61
63
52
57
60
63
50
55
58
60
48
53
56
59
55
60
63
65
54
59
62
64
52
57
60
63

45
51
54
57
48
54
58
60
51
57
61
64
58
62
64
65
58
61
63
64
56
59
61
62
54
57
59
61
60
63
65
66
59
62
64
65
57
60
62
64

51
55
58
60
54
58
61
63
56
61
63
65
61
65
68
69
60
64
67
68
58
62
64
66
56
60
62
64
62
66
68
70
61
65
67
69
59
63
65
67

48
54
58
61
50
56
60
62
52
58
62
64
58
63
65
67
58
63
65
67
56
61
63
65
55
59
62
64
59
63
66
67
58
63
65
67
57
61
64
66

43
50
55
58
45
52
56
59
46
53
57
60
55
59
61
63
54
58
61
62
52
56
58
60
50
54
57
58
54
58
61
62
53
57
60
61
52
56
58
60

Acoustic data for differential pressure up to 1000 Pa, see on-line design programme Air terminal units.

Air-regenerated Noise
Air-regenerated noise calculation procedure

Example
Vmax = 420 l/s or 1512 m3/h
 pg = 100 Pa
Required sound pressure level in the room 45 dB(A)
For further assumptions, see calculation procedure

Given:

fm
LW (page 8)

63 125 250 500 1000 2000 4000 8000


58 50 44 46
48
48
44
37

Distribution

Duct bend

End reflection

12

Sound power
level to room

40

36

33

37

40

40

36

29

26 16

19

29

36

37

33

24

Calculation procedure

Room attenuation

Quick selection:
EN/400 x 200
Air-regenerated noise
LpA = 40 dB(A)

A-weighting
Corrected level

Case-radiated noise
LpA2 = 33 dB(A)
Sound pressure level in the room = 41 dB(A)
(after logarithmic addition, as the unit is in the false ceiling of
the room, see drawing page 7)

14

Sound pressure level of the air-regenerated noise


LpA approx. 41 dB(A)

Air-regenerated noise

63

125

250

500

1000

2000

4000

8000

63

125

250

500

1000

2000

4000

8000

m3/h

l/s

8000

600 600

4000

600

315 1134
630 2268
945 3402
1260 4536
375 1350
750 2700
1125 4050
1500 5400
420 1512
840 3024
1260 4536
1680 6048
420 1512
840 3024
1260 4536
1680 6048
460 1656
920 3312
1380 4968
1840 6624
510 1836
1020 3672
1530 5508
2040 7344
600 2160
1200 4320
1800 6480
2400 8640
640 2304
1280 4608
1920 6912
2560 9216
840 3024
1680 6048
2520 9072
3360 12096

2000

500 500

fm in Hz

1000

600

fm in Hz

500

500

fm in Hz
250

400 400

LW in dB

125

600

pg = 500 Pa

LW in dB

63

500

pg = 200 Pa

LW in dB

.
V

BxH

mm
400 300

pg = 100 Pa

50
60
66
70
47
57
62
66
44
53
59
63
52
62
68
72
47
57
63
67
44
54
59
63
49
59
65
69
45
55
61
65
48
58
63
67

42
50
55
59
43
52
57
60
44
52
57
61
42
50
55
59
42
51
56
59
42
51
56
60
42
51
56
60
42
51
56
60
44
52
57
61

42
50
54
57
40
47
51
54
37
45
49
52
46
54
58
61
43
50
54
57
41
48
52
55
47
54
58
61
44
51
55
58
47
54
59
62

47
52
55
57
45
50
53
56
44
49
52
54
52
57
60
62
49
54
57
59
48
53
56
58
53
58
61
63
51
56
59
61
54
60
63
65

50
54
56
57
49
52
54
55
47
51
53
54
54
57
59
61
52
55
57
59
51
54
56
57
55
59
60
62
54
57
59
60
56
60
62
63

49
53
55
56
47
51
53
55
45
49
51
53
52
56
58
60
50
54
56
58
48
52
54
56
53
57
59
60
51
55
57
58
53
57
59
61

42
46
49
51
41
45
47
49
39
44
46
48
44
48
51
52
42
46
49
51
41
45
47
49
44
48
51
52
42
46
49
51
44
48
51
53

36
40
42
44
34
38
40
42
32
36
39
40
37
41
44
45
35
39
41
43
33
37
40
41
36
40
43
44
35
39
41
43
36
40
42
44

57
66
72
76
53
63
69
73
50
60
65
69
58
68
74
78
54
63
69
73
50
60
66
70
56
65
71
75
52
61
67
71
54
64
70
74

50
58
63
67
51
60
65
68
52
60
65
69
50
58
63
67
50
59
64
67
51
59
64
68
50
59
64
68
51
59
64
68
52
60
65
69

50
57
61
64
47
55
59
62
45
52
56
59
54
61
65
68
51
58
62
65
48
55
59
62
54
61
66
69
51
59
63
66
55
62
66
69

54
59
62
64
52
57
60
62
50
55
58
61
58
63
66
68
56
61
64
66
54
59
62
64
60
65
68
70
58
63
66
68
61
66
69
71

57
61
63
64
56
59
61
62
55
58
60
61
61
65
66
68
59
63
65
66
58
61
63
64
62
66
68
69
61
64
66
67
64
67
69
70

58
62
64
66
56
60
62
64
55
58
61
62
62
65
68
69
59
63
65
67
57
61
64
65
62
66
68
70
60
64
66
68
63
67
69
70

53
57
60
61
51
56
58
60
50
55
57
59
55
59
61
63
53
57
60
61
52
56
58
60
55
59
61
63
53
57
60
62
55
59
62
63

47
51
54
55
46
50
52
54
44
48
50
52
49
53
55
57
47
51
53
55
45
49
52
53
48
52
55
56
46
50
53
54
48
52
54
56

61
71
77
81
58
68
73
77
55
64
70
74
63
73
79
83
58
68
74
78
55
65
70
74
60
70
76
80
56
66
72
76
59
69
74
78

56
64
69
73
57
66
71
74
58
66
71
75
56
64
69
73
56
65
70
73
57
65
70
74
57
65
70
74
57
65
70
74
58
66
71
75

56
63
67
70
53
60
64
67
51
58
62
65
60
67
71
74
56
64
68
71
54
61
65
68
60
67
71
74
57
64
68
71
61
68
72
75

59
64
67
69
57
62
65
67
55
60
63
66
63
68
71
73
61
66
69
71
59
64
67
69
65
70
73
75
63
68
71
73
66
71
74
76

63
66
68
69
61
65
67
68
60
63
65
67
67
70
72
73
65
68
70
71
63
67
68
70
68
71
73
74
66
70
71
73
69
72
74
76

65
69
71
73
63
67
69
71
62
65
68
69
69
72
75
76
66
70
72
74
65
68
71
72
69
73
75
77
67
71
73
75
70
74
76
78

61
65
68
70
60
64
67
68
58
63
65
67
63
67
70
72
61
65
68
70
60
64
67
68
63
67
70
71
61
66
68
70
63
67
70
72

56
60
63
64
55
59
61
63
53
57
59
61
58
62
64
66
56
60
62
64
54
58
60
62
57
61
64
65
55
59
62
63
57
61
63
65

Acoustic data for differential pressure up to 1000 Pa, see on-line design programme Air terminal units.

Case-radiated Noise
Case-radiated noise calculation procedure
fm
63 125 250 500 1000 2000 4000 8000
58 50 44 46
48
48
44
37
LW (page 8)
4
5
4
9
13
16
16
11
LW
54 45 40 37
35
32
28
26
LW2
Ceiling reduction
4
4
4
4
4
4
4
4
Room attenuation
6
6
5
5
4
4
4
4
A-weighting
26 16 9 3
0
1
1
1
Corrected level
18 19 22 25
27
25
21
17

Sound pressure level of case-radiated noise


LpA2 approx. 32 dB(A)
Result: In a deviation from the quick selection, different
room attenuation values have been assumed.
However, the result remains within the requirement.

Correction values for case-radiated noise in dB(A)


Installation location

LW / LW1

LW / LW1 in dB, related to fm in Hz


63

125

250

500

1000

2000

4000

8000

LW

13

16

16

11

LW1

10

19

25

29

28

20

EN

approx. 6 m

EN

LW2 = LW  LW

END (with acoustic cladding)


approx. 6 m
Rigid insulation supplied by others

END

LW3 = LW  LW1

10

Order Details
Specification text *
Rectangular volume flow controllers for constant volume
systems, mechanical system-powered (external power supply
not required), for supply and extract air, in 19 nominal sizes.
Consists of a casing with a control damper blade shaft
mounted, supported on bearings with a bellows and an
external cam plate with leaf spring.
Special features:
Mechanical system-powered, without external power
supply
Low-friction bellows, also operates as an oscillation
damper
The flow rate can be set with an external scale
Close tolerances on flow rate
Independent of orientation and maintenance-free
The casing has flanges on both ends suitable for System 30
connecting sections. Differential pressure range 50 to 1000 Pa,
flow rate range 4 : 1.
Materials:
Casing and control damper blade are made of galvanised
sheet steel, the control damper blade shaft is supported by
plain bearings with PTFE bearing coating. Polyurethane
bellows.

Options:
Actuator, 24 VAC or 230 VAC for setpoint value readjustment.
Additional acoustic cladding to reduce case-radiated
noise. Consists of 40 mm mineral wool and outer cover of
galvanised sheet steel. This gives a reduction of caseradiated noise of minimum 5 dB providing the upstream
and downstream ducting has a rigid external insulation.
Cannot be retrofitted.
TX silencer, for the reduction of air-regenerated noise,
insertion loss approx. 9 dB at 250 Hz. Lining of mineral wool
conforming to DIN 4102, fire rating class A2, with RAL quality mark RAL-GZ 388, biodegradable pursuant to TRGS 905
and EU directive 97/69/EG. Mineral wool faced with fibreglass as protection against erosion, suitable for air velocities
up to 20 m/s, inert to fungal and bacterial growth.

* Text for standard construction;


for the actuators, see the design programme or price list

Order code
/

EN

END

Materials
Standard construction,
galvanised sheet steel,
no entry required
Surface powder-coated (RAL 7001)

TX
Type
Silencer

BxH

EN

TX

B 50

.
.
Vmin Vmax

Actuator
Make
Actuator
Accessories

IE
EE
EO
EE
EE
P

without actuator,
no entry required

Setpoint readjustment option


-P1

See design programme or price list


for actuators

400 x 200
Design changes reserved All rights reserved TROX GmbH (08/2008)

Type
Volume flow controller
With additional
acoustic cladding

400 x 200

BxH

Remarks:
The basic construction of controller is supplied with a set
reference flow rate (the required flow rate should be set on site
by the customer).
The minimum and maximum setpoint flow rates are set on the
construction with an actuator.

Note:
400 mm high EN flow rate controllers consist of two controllers
mounted one above the other.
Each controller should then be set to 50 % of the required flow
rate on site. These units can only be supplied as EN/END constant
flow controllers, but not with actuators.

EN order example

TX order example

Make: TROX
Type: EN / 400 x 200

Make: TROX
Type: TX / 400 x 200

11