A1000
A1000
Technical Manual
Type: CIMR-AA
, CIMR-AB
CIMR-AT
Models: 200 V Class: 0.4 to 110 kW
400 V Class: 0.4 to 355 kW
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
Receiving
Mechanical Installation
Electrical Installation
Parameter Details
Troubleshooting
Specifications
Parameter List
MEMOBUS/Modbus
Communications
Standards Compliance
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Quick Reference
Easily Set Parameters for Specific Applications
Preset parameter defaults are available for setting up applications. Refer to Application Selection on page 108.
A1000 can operate synchronous PM motors. Refer to Subchart A-3: Operation with Permanent Magnet Motors on page 106.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 114.
Standards Compliance
Refer to European Standards on page 520 and Refer to UL Standards on page 526.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Table of Contents
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
I.
1.
RECEIVING .......................................................................................................... 27
1.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A1000 Model Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Model Number and Nameplate Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Drive Models and Enclosure Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP20/NEMA Type 1 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP00 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.
16
16
16
16
17
17
18
19
22
23
24
25
28
29
29
30
31
31
33
34
34
34
37
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
40
42
42
42
44
47
3.
4.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
6.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7.
8.
10
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
A.
SPECIFICATIONS.............................................................................................. 395
A.1 Heavy Duty and Normal Duty Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
A.2 Three-Phase 200 V Class Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397
A.3 Three-Phase 400 V Class Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
A.4 Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
A.5 Drive Watt Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
A.6 Drive Derating Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
Carrier Frequency Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403
Altitude Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
B.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
11
C.
D.
12
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
13
14
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
i
Preface & General Safety
This section provides safety messages pertinent to this product that, if not heeded, may result
in fatality, personal injury, or equipment damage. Yaskawa is not responsible for the
consequences of ignoring these instructions.
I.1 PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
I.2 GENERAL SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
15
i.1 Preface
i.1
Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection
and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa
accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances
should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without
exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All
systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with
appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa
must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in
conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESSED
OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims
arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of Variable A1000-Series Drives. Read this manual
before attempting to install, operate, maintain, or inspect a drive and keep it in a safe, convenient location for future
reference. Be sure you understand all precautions and safety information before attempting application.
Applicable Documentation
The following manuals are available for A1000 series drives:
A1000 Series AC Drive Quick Start Guide
ALM
REV
DRV
FOUT
This guide is packaged together with the product. It contains basic information required to install and wire the drive, in addition to
an overview of fault diagnostics, maintenance, and parameter settings. It is meant to get the drive ready for a trial run with the
application and for basic operation.
LO
RE
ESC
RESET
ENTER
RUN
STOP
CIMR-AA2A0021FAA
200V 3Phase 5.5kW/3.7kW
S/N:
WARNING
AVERTISSMENT NPJT31470-1
Risque de dcharge lectrique.
Hot surfaces
Surfaces Chaudes
400V
(
YEC_com
mon
Symbols
Note: Indicates a supplement or precaution that does not cause drive damage.
TERMS
16
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
i.2
General Safety
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed
according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could
result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
17
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings
in this manual.
WARNING
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Crush Hazard
Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental
dropping of the load.
The drive does not possess built-in load drop protection for lifting applications.
Failure to comply could result in death or serious injury from falling loads.
Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry.
18
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac
maximum (200 V Class) and 480 Vac maximum (400 V Class).
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Application Notes
Selection
Installing a Reactor
Figure i.1
4000
Power Supply
Capacity (kVA)
600
Reactor
unnecessary
0
60
400
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
19
For specialized motors, make sure that the motor rated current is less than rated output current for the drive. When
running more than one motor in parallel from a single drive, the capacity of the drive should be larger than 1.1 times of
the total motor rated current.
Starting Torque
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower
torque than when running from line power. To get more starting torque, use a larger drive or increase both the motor and
drive capacity.
Emergency Stop
When the drive faults out, the output is shut off. This, however, does not stop the motor immediately. Some type of
mechanical brake may be needed if it is necessary to halt the motor faster than the Fast Stop function is able to.
Options
The B1, B2, +1, +2, and +3 terminals are used to connect optional devices. Connect only A1000-compatible devices.
Repetitive Starting/Stopping
Cranes (hoists), elevators, punching presses, and other such applications with frequent starts and stops often exceed
150% of their rated current values. Heat stress generated from repetitive high current can shorten the life span of the
IGBTs. The expected lifesaving for the IGBTs is about 8 million start and stop cycles with a 4 kHz carrier frequency and
a 150% peak current.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. The user can also
choose to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive. This will help keep
peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during
the initial test run, and make adjustments accordingly.
For crane-type applications using an inching function in which the motor is quickly started and stopped, Yaskawa
recommends the following to ensure motor torque levels:
Select a large enough drive so that peak current levels remain below 150% of the drive rated current.
The drive should be one frame size larger than the motor.
Installation
Enclosure Panels
Keep the drive in a clean environment by either selecting an area free of airborne dust, lint, and oil mist, or install the
drive in an enclosure panel. Be sure to leave the required space between drives to provide for cooling, and that proper
measures are taken so that the ambient temperature remains within allowable limits. Keep flammable materials away
from the drive. If the drive must be used in an area where it is subjected to oil mist and excessive vibration, protective
designs are available. Contact Yaskawa or your Yaskawa agent for details.
Installation Direction
The drive should be installed upright as specified in the manual. For more information on installation, Refer to
Mechanical Installation on page 42.
Settings
Motor Code
If using OLV/PM designed for permanent magnet motors, make sure that the proper motor code has been set to
parameter E5-01 before performing a trial run.
Upper Limits
The drive is capable of running the motor up to 400 Hz. Due to the danger of accidentally of operating at high speed, be
sure to set the upper limit for the frequency. The default setting for the maximum output frequency is 60 Hz.
DC Injection Braking
Motor overheat can result if there is too much current used during DC Injection Braking, or if the time for DC Injection
Braking is too long.
20
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Acceleration and deceleration times are affected by how much torque the motor generates, the load torque, and the inertia
moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long
as the Stall Prevention function is operating. For faster acceleration and deceleration, install one of the braking options
available or increase the capacity of the drive.
Compliance with Harmonic Suppression Guidelines
A1000 conforms to strict guidelines in Japan covering harmonic suppression for power conversion devices. Defined in
JEM-TR201 and JEM-TR226 and published by the Japan Electrical Manufacturers Association, these guidelines define
the amount of harmonic current output acceptable for new installation. Instructions on calculation harmonic output are
available at www.e-mechatronics.com.
General Handling
Wiring Check
Never connect the power supply lines to output terminals U/T1, V/T2, or W/T3. Doing so will destroy the drive. Be sure
to perform a final check of all sequence wiring and other connections before turning the power on. Make sure there are
no short circuits on the control terminals (+V, AC, etc.), as this could damage the drive.
Selecting a Circuit Breaker or Leakage Circuit Breaker
Yaskawa recommends installing Earth Leakage Circuit Breaker (ELCB) to the power supply side. The ELCB should be
designed for use with an AC drive (e.g. Type B according to IEC 60755).
Select a MCCB (Molded Case Circuit Breaker) or ELCB with a rated current that is 1.5 to 2 times higher than the rated
current of the drive in order to avoid nuisance trips caused by harmonics in the drive input current. Also refer to
Installing a Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit Breaker (ELCB) on page 387.
Magnetic Contactor Installation
Use a magnetic contactor (MC) to ensure that power to the drive can be completely shut off when necessary. The MC
should be wired so that it opens when a fault output terminal is triggered.
Avoid switching a magnetic contactor on the power supply side more frequently than once every 30 minutes. Frequent
switching can cause damage to the drive.
Inspection and Maintenance
Capacitors in the drive take time to discharge even after the power has been shut off. After shutting off the power, wait
for at least the amount of time specified on the drive before touching any components.
The heatsink can become quite hot during operation, and proper precautions should be taken to prevent burns. When
replacing the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down.
Even when the power has been shut off for a drive running a PM motor, voltage continues to be generated at the motor
terminals while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
Applications where the machine can still rotate even though the drive has fully stopped should have a load switch
installed to the output side of the drive. Yaskawa recommends manual load switches from the AICUT LB Series by
AICHI Electric Works Co., Ltd.
Do not allow an external force to rotate the motor beyond the maximum allowable speed, also when the drive has been
shut off.
Wait for at least the time specified on the warning label after opening the load switch on the output side before
inspecting the drive or performing any maintenance.
Do not open and close the load switch while the motor is running, as this can damage the drive.
If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped
before closing the load switch.
Wiring
All wire ends should use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal
manufacturer for crimping.
Transporting the Drive
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
21
The cooling fan of a standard motor is usually designed to sufficiently cool the motor at the rated speed. As the selfcooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the
motor. To prevent motor damage from overheat, reduce the load torque as the motor slows.
Figure i.2 shows the allowable load characteristics for a Yaskawa standard motor. A motor designed specifically for
operation with a drive should be used when 100% continuous torque is needed at low speeds.
Figure i.2
60
50
YEC_common
Continuous operation
3 6
20
60
Frequency (Hz)
Insulation Tolerance
Consider voltage tolerance levels and insulation in applications with an input voltage of over 440 V or particularly long
wiring distances. Contact Yaskawa or your Yaskawa agent for consultation.
High Speed Operation
Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its
rated speed. Contact the motor or machine manufacturer.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full
understanding of the load torque characteristics for the application.
Vibration and Shock
A1000 lets the user choose between high carrier PWM control and low carrier PWM. Selecting high carrier PWM can
help reduce motor oscillation.
Take particular caution when using a variable speed drive for an application that is conventionally run from line power at
a constant speed. If resonance occurs shock-absorbing rubber should be installed around the base of the motor and the
Jump frequency selection should be enabled to prevent continuous operation in the resonant frequency range.
Audible Noise
Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from
the motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min,
however, can create unpleasant motor noise.
Using a Synchronous Motor
Contact Yaskawa or your Yaskawa agent if you plan to use any other synchronous motor not endorsed by Yaskawa.
A single drive is not capable of running multiple synchronous motors at the same time. Use a standard induction motor
for such setups.
22
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Because the rated current will differ from a standard motor, be sure to check the maximum current when selecting a
drive. Always stop the motor before switching between the number of motor poles. If a regen overvoltage fault occurs or
if overcurrent protection is triggered, the motor will coast to stop.
Submersible Motor
Because motor rated current is greater than a standard motor, select the drive capacity accordingly. Be sure to use a large
enough motor cable to avoid decreasing the maximum torque level on account of voltage drop caused by a long motor
cable.
Explosion-Proof Motor
Both the motor and drive need to be tested together to be certified as explosion-proof. The drive is not designed for
explosion proof areas.
Furthermore, if an encoder is attached to an explosion-proof motor make sure the encoder is explosion-proof too. Use an
insulating signal converter for connecting the encoder signal lines to the drives speed feedback option card.
Geared Motor
To avoid gear damage when operating at low speeds or very high speeds, make sure that both the gear and lubricant are
rated for the desired speed range. Consult with the manufacturer for applications that require operation outside the rated
speed range of the motor or gear box.
Single-Phase Motor
Variable speed drives are not designed for operation with single phase motors. Using capacitors to start the motor causes
excessive current to flow and can damage drive components. A split-phase start or a repulsion start can end up burning
out the starter coils because the internal centrifugal switch is not activated. A1000 is for use with three-phase motors
only.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
23
Uras vibrator is a vibration motor that gets power from centrifugal force by rotating unbalanced weights on both ends of
the shaft. After considering the points below, consult with a your Yaskawa representative to determine the best solution
for the application.
Uras vibrator should be used within the drive rated frequency.
Use V/f Control.
Increase the acceleration time five to fifteen times longer than would normally be used due to the high amount of load
inertia of an Uras vibrator. Increase drive capacity for applications that require an acceleration time of less than 5 s.
Drive may have trouble starting due to undertorque that results from erratic torque (static friction torque at start).
Motor with Brake
Caution should be taken when using a drive to operate a motor with a built-in holding brake. If the brake is connected to
the output side of the drive, it may not release at start due to low voltage levels. A separate power supply should be
installed for the motor brake. Motors with a built-in brake tend to generate a fair amount of noise when running at low
speeds.
Notes on Power Transmission Parts (belts, chains, gear boxes, ...)
Installing a drive in a machine that was directly connected to the power supply allows to adjust the machine speed.
Continuous operation above or below the rated speed can wear on lubrication material in gear boxes and other power
transmission parts. In order to avoid machine damage make sure lubrication is sufficient within the whole speed range.
Note that operation above the rated speed can increase the noise generated by the machine.
WARNING
Hot surfaces
ALM
REV
DRV
FOUT
YEC_common
LO
RE
ESC
RESET
ENTER
RUN
STOP
CIMR-AA2A0021FAA
200V 3Phase 5.5kW/3.7kW
S/N:
AVERTISSMENT NPJT31470-1
WARNING
Hot surfaces
Surfaces Chaudes
Warning Label
400V
(
24
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Warranty Information
Warranty Period
This drive is warranted for 12 months from the date of delivery to the customer or 18 months from the date of shipment
from the Yaskawa factory, whichever comes first.
Scope of Warranty
Inspections
Customers are responsible for periodic inspections of the drive. Upon request, a Yaskawa representative will inspect the
drive for a fee. If the Yaskawa representative finds the drive to be defective due to Yaskawa workmanship or materials
and the defect occurs during the warranty period, this inspection fee will be waived and the problem remedied free of
charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the
warranty period, Yaskawa will provide a replacement, repair the defective product, and provide shipping to and from the
site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with the drive is not due to defective
workmanship or materials, the customer will be responsible for the cost of any necessary repairs. Some problems that are
outside the scope of this warranty are:
Problems due to improper maintenance or handling, carelessness, or other reasons where the customer is determined to
be responsible.
Problems due to additions or modifications made to a Yaskawa product without Yaskawas understanding.
Problems due to the use of a Yaskawa product under conditions that do not meet the recommended specifications.
Problems caused by natural disaster or fire.
After the free warranty period elapses.
Replenishment or replacement of consumables or expendables.
Defective products due to packaging or fumigation.
Malfunction or problems caused by program that has been made by customers using DriveWorksEZ.
Other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan. However, after-sales service is available for customers outside of Japan
for a reasonable fee.
Contact your local Yaskawa representative for more information.
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawas defective products whether
within or outside of the warranty period are NOT covered by warranty.
Restrictions
A1000 was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives
or health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health
care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa
representatives or the nearest Yaskawa sales office.
This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in
any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a
facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the
likelihood of any accident.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
25
26
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
1
Receiving
This chapter explains how to inspect the drive upon receipt, and gives and overview of the
different enclosure types and components.
1.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 GENERAL DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 MODEL NUMBER AND NAMEPLATE CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 DRIVE MODELS AND ENCLOSURE TYPES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 COMPONENT NAMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
28
29
31
33
34
27
1.1
Section Safety
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the
operating speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the
additional heating with the intended operating conditions.
28
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
1.2
General Description
Motor Power
(kW)
0.4
0.75
1.1
1.5
2.2
3.0
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
220
250
315
355
2A0006
5 <1>
2A0004
3.5
2A0008
6.9 <1>
2A0006
6
2A0010
8 <1>
2A0008
8
2A0012
11 <1>
2A0010
9.6
2A0018
14 <1>
2A0012
12
2A0021
17.5 <1>
2A0018
17.5
2A0030
25 <1>
2A0021
21
2A0040
33 <1>
2A0030
30
2A0056
47 <1>
2A0040
40
2A0069
60 <1>
2A0056
56
2A0081
75 <1>
2A0069
69
2A0110
85 <1>
2A0081
81
2A0138
115 <1>
2A0110
110
2A0169
145 <2>
2A0138
138
2A0211
180 <2>
2A0169
169
2A0250
215 <2>
2A0211
211
2A0312
283 <2>
2A0250
250
2A0360
346 <2>
2A0312
312
2A0415
415 <2>
2A0360
360
2A0415
415
4A0004
3.4
4A0002
2.1
4A0005
4.8
4A0004
4.1
4A0007
5.5
4A0005
5.4
4A0009
7.2
4A0007
6.9
4A0011
9.2
4A0009
8.8
4A0018
14.8
4A0011
11.1
4A0023
18
4A0018
17.5
4A0031
24 <1>
4A0023
23
4A0038
31 <1>
4A0031
31
4A0044
39 <1>
4A0038
38
4A0058
45 <1>
4A0044
44
4A0072
60 <1>
4A0058
58
4A0088
75 <1>
4A0072
72
4A0103
91 <1>
4A0088
88
4A0139
112 <2>
4A0103
103
4A0165
150 <2>
4A0139
139
4A0208
180 <2>
4A0165
165
4A0250
216 <2>
4A0208
208
4A0296
260 <2>
4A0250
250
4A0362
304 <2>
4A0296
296
4A0414
370 <2>
4A0362
362
4A0515
450 <3>
4A0414
414
4A0515
515
4A0675
605 <3>
4A0675
675
<1> These values assume the carrier frequency is not set higher than 8 kHz.
<2> These values assume the carrier frequency is not set higher than 5 kHz.
<3> These values assume the carrier frequency is set to 2 kHz.
Note: Current derating is required when setting the carrier frequency higher. Refer to Carrier Frequency Derating on page 402 for
details.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Receiving
29
V/f
Parameter Setting
A1-02 = 0
Basic Description
Type of
Applications
Motor Type
Multi Motor
Motor data
unknown
High Speed
Accuracy
High Speed
Response
Zero Speed
Control
Torque Control
Operation
Torque Limit
Operation
PG Option Card
Control
Characteristics
V/f control
IM
YES
Induction Motors
V/f w/PG
OLV
A1-02 = 1
A1-02 = 5
A1-02 = 6
A1-02 = 7
Comments
YES
N/A
N/A
N/A
N/A
N/A
N/A
N/A
YES
YES
YES
YES
YES
YES
N/A
N/A
YES
YES
N/A
YES
YES
N/A
N/A
N/A
YES
N/A
YES
YES
N/A
N/A
N/A
YES
N/A
YES
YES
N/A
N/A
YES
YES
N/A
N/A
YES
N/A
PG-B3 or
PG-X3
N/A
PG-B3 or
PG-X3
N/A
N/A
PG-X3
Speed Control
Range
1:40
1:40
1:200
1:1500
1:20
1:100
1:1500
Speed Accuracy
2 to 3%
0.03%
0.2%
0.02%
0.2%
0.2%
0.02%
Speed Response
3 Hz
(approx.)
3 Hz
(approx.)
10 Hz
50 Hz
10 Hz
10 Hz
50 Hz
200% at 0.3
Hz
200% at 0
r/min
100% at 5%
speed
200% at
0 r/min
200% at
0 r/min
Stationary
Line to
line
resistance
Stationary
Line to
line
resistance
ASR
Inertia
Encoder
Offset
Rotational
Rotational Stationary
Stationary
Stationary Line to
Line to
Line to
line
line
line
resistance
resistance
resistance ASR
Inertia
Auto-Tuning
Energy
Saving
Tuning
Line to
line
resistance
Energy
Saving
Tuning
Line to
line
resistance
Torque Limit
N/A
N/A
YES
YES
N/A
YES
YES
Torque Control
N/A
N/A
N/A
YES
N/A
N/A
YES
N/A
N/A
N/A
YES
N/A
N/A
YES
N/A
N/A
N/A
YES
N/A
N/A
YES
Speed Search
YES
YES
YES
YES
YES
YES
Energy-Saving
Control
YES
YES
YES
YES
N/A
YES (IPM
motors only)
YES (IPM
motors only)
High Slip
Braking
YES
YES
N/A
N/A
N/A
N/A
N/A
Feed Forward
Control
N/A
N/A
N/A
YES
N/A
N/A
YES
Kinetic Energy
Buffering
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
N/A
N/A
N/A
N/A
N/A
N/A
YES
N/A
N/A
YES
Overvoltage
Suppression
YES
YES
YES
YES
YES
YES
YES
High Frequency
Injection
N/A
N/A
N/A
N/A
N/A
YES
N/A
Droop Function
Zero Servo
Control
Overexcitation
Deceleration
Inertia Tuning,
ASR Tuning
30
A1-02 = 3
V/f control
Open Loop
Open Loop
Closed Loop
using motor Open Loop Closed Loop
Vector control
Vector control
Vector control
speed
Vector control Vector control
for IPM
for PM motors
for PM motors
feedback
motors
IM
IM
IM
PM
IPM
PM
N/A
N/A
N/A
N/A
N/A
N/A
ApplicationSpecific
A1-02 = 2
CLV
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
1.3
Nameplate
Figure 1.1
YEC_common
CIMR-AA2A0021FAA
MODEL :
MAX APPLI. MOTOR : 5.5kW / 3.7kW REV : A
INPUT : AC3PH 200-240V 50/60Hz 24A/18.9A
OUTPUT : AC3PH 0-240V 0-400Hz 21A/17.5A
MASS : 3.5 kg
PRG : 1010
O/N
:
S/N
:
AC drive model
Input specifications
Output specifications
Lot number
Serial number
FILE NO : E131457
TYPE 1 ENCLOSURE
IP20
IND.CONT.EQ.
7J48 B
Software version
PASS
MADE IN JAPAN
Enclosure type
Drive
A1000
Series
No.
YEC_common
Region
Code
USA
Japan
China
Europe
Asia
A
No.
A
0004
F
Enclosure
Type
Customized
Specifications
No.
Standard model
IP00
NEMA
Type 1
No.
A
K
M
No.
2
Voltage Class
3-phase, 200-240 Vac
N
S
A
Receiving
CIMR - A A 2
Design
Revision
Order
Environmental
Specification <1>
Standard
Gas-resistant
Humidity- and
dust-resistant
Oil-resistant
Vibration-resistant
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
31
Heavy Duty
No.
Rated Output
Current A
No.
Rated Output
Current A
0004
0.75
3.5
0004
0.4
0006
1.1
6.0
0006
0.75
3.2
5
0008
1.5
8.0
0008
1.1
6.9
0010
2.2
9.6
0010
1.5
0012
3.0
12
0012
2.2
11
0018
3.7
17.5
0018
3.0
14.0
0021
5.5
21
0021
3.7
17.5
0030
7.5
30
0030
5.5
25
0040
11
40
0040
7.5
33
0056
15
56
0056
11
47
0069
18.5
69
0069
15
60
0081
22
81
0081
18.5
75
0110
30
110
0110
22
85
0138
37
138
0138
30
115
0169
45
169
0169
37
145
0211
55
211
0211
45
180
0250
75
250
0250
55
215
0312
90
312
0312
75
283
0360
110
360
0360
90
346
0415
110
415
0415
110
415
Rated Output
Current A
Three-Phase 400 V
Normal Duty
Heavy Duty
No.
Rated Output
Current A
No.
0002
0.75
2.1
0002
0.4
1.8
0004
1.5
4.1
0004
0.75
3.4
0005
2.2
5.4
0005
1.5
4.8
0007
3.0
6.9
0007
2.2
5.5
0009
3.7
8.8
0009
3.0
7.2
0011
5.5
11.1
0011
3.7
9.2
0018
7.5
17.5
0018
5.5
14.8
0023
11
23
0023
7.5
18
0031
15
31
0031
11
24
0038
18.5
38
0038
15
31
0044
22
44
0044
18.5
39
0058
30
58
0058
22
45
0072
37
72
0072
30
60
0088
45
88
0088
37
75
0103
55
103
0103
45
91
0139
75
139
0139
55
112
0165
90
165
0165
75
150
0208
110
208
0208
90
180
0250
132
250
0250
110
216
0296
160
296
0296
132
260
0362
185
362
0362
160
304
0414
220
414
0414
185
370
0515
250
515
0515
220
450
0675
355
675
0675
315
605
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
Note: Refer to Drive Models and Enclosure Types on page 33 for differences regarding enclosure protection types and component
descriptions.
32
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
1.4
Three-Phase
200 V Class
Three-Phase
400 V Class
4A0002F
4A0004F
4A0005F
4A0007F
4A0009F
4A0011F
4A0018F
4A0023F
4A0031F
4A0038F
4A0044F
4A0058F <2>
4A0072F <2>
4A0088F <2>
4A0103F <2>
4A0139F <2>
4A0165F <2>
4A0208F <2>
4A0250F <2>
4A0296F <2>
4A0362F <2>
IP00 Enclosure
CIMR-A
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
<1>
2A0110A
2A0138A
2A0169A
2A0211A
2A0250A
2A0312A
2A0360A
2A0415A
<1>
<1>
<1>
<1>
<1>
<1>
<1>
Receiving
Voltage Class
<1>
<1>
<1>
<1>
4A0058A
4A0072A
4A0088A
4A0103A
4A0139A
4A0165A
4A0208A
4A0250A
4A0296A
4A0362A
4A0414A
4A0515A
4A0675A
<1> Removing the top protective cover from a IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection but still keeps IP20 conformity.
<2> Special order required. Contact your Yaskawa sales representative.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
33
1.5
Component Names
This section gives and overview of the drive components described in this manual.
Note: 1. See Using the Digital Operator on page 93 for a description of the operator keypad.
2. The drive may have no cooling fans or only one cooling fan depending on the model.
<1>
B - Cooling fan
<1>
C - Mounting hole
D - Heatsink
H -Rubber bushing
D
J - Front cover
K
L - Digital Operator
M - Terminal cover
M
N
<1> The following drive models have a single cooling fan: CIMR-A2A0018F and 0021F, CIMR-A4A0007F through 0011F.
Drives CIMR-A2A0004F through 0012F and CIMR-A4A0002F through 0005F do not have a cooling fan or a cooling fan cover.
IP00 Enclosure
Three-Phase AC200 V CIMR-A2A0110A, 0138A
B - Cooling fan
C - Mounting hole
D - Heatsink
E - Optional 24 V DC power supply connector cover
F - Terminal board
G - Front cover
D
G
H
J - Digital operator
J
K
K - Drive Cover
L - Terminal cover
L
34
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
D - Terminal board
E - Fan guard
F - Cooling fan
G - Fan unit
H - Front cover
I - USB port (type-B)
J - Digital operator
I
J
M - Terminal cover
K
B - Heatsink
D - Terminal board
E - Fan guard
Receiving
F - Cooling fan
G - Fan unit
C
H
D
I
J
K - Digital operator
L - Front cover screw
M - Drive cover
N - Terminal cover
N
<1> The following drive models come with a built-in circulation fan.
CIMR-A2A0360, 2A0415
CIMR-A4A0362
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
35
D - Terminal board
E - Fan guard
F - Cooling fan
G - Fan unit
M
N
D
H - Circulation fan
I - Front cover
B - Heatsink
C - Terminal board
D - Fan guard
E - Cooling fan
F - Fan unit
G - Circulation fan
H - Circuitboard cooling fan
G
A
N
L
I
J
M
O
K
36
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Front Views
Figure 1.2
CIMR-A2A0110A
CIMR-A2A0012F
I
I
J
J
A
A
B
G
H
G
YEC_TMonly
Receiving
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
37
38
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
2
Mechanical Installation
This chapter explains how to properly mount and install the drive.
2.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2.2 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
39
2.1
Section Safety
WARNING
Fire Hazard
Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet.
Failure to comply could result in overheating and fire.
When multiple drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the
enclosure does not exceed 40C.
CAUTION
Crush Hazard
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Equipment Hazard
Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during drive
installation and project construction.
Failure to comply could result in damage to the drive.
Place a temporary cover over the top during installation. Be sure to remove the temporary cover before start-up, as the
cover will reduce ventilation and cause the unit to overheat.
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and
may lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is
required continuously at low speed, consider using a special drive or vector-control motor. Select a motor that is
compatible with the required load torque and operating speed range.
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special
attention to the motor insulation voltage or use a drive-rated motor with reinforced insulation.
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously
operated at a constant speed.
Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the
machine.
The motor may require more acceleration torque with drive operation than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor.
The rated input current of submersible motors is higher than the rated input current of standard motors.
Select an appropriate drive according to its rated output current. When the distance between the motor and drive is
long, use a cable thick enough to connect the motor to the drive to prevent motor torque reduction.
40
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
NOTICE
Mechanical
Installation
The current rating differs for a motor with variable pole pitches differs from a standard motor.
Check the maximum current of the motor before selecting the drive capacity. Only switch motor poles when the motor
is stopped. Switching between motor during run will trigger overcurrent protection circuitry or result in overvoltage
from regeneration, and the motor will simply coast to stop.
When using an explosion-proof motor, it must be subject to an explosion-proof test in conjunction with the
drive.
This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is
not explosion-proof, always install it in a safe place.
Never lift the drive up while the cover is removed.
This can damage the terminal board and other components.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
41
2.2
Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in an environmental matching the
specifications below.
Table 2.1 Installation Environment
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
Humidity
Storage Temperature
-20 to +60C
Surrounding Area
Altitude
1000 m, up to 3000 m with derating (for details, refer to Altitude Derating on page 404)
Vibration
10 to 20 Hz at 9.8 m/s2
20 to 55 Hz at 5.9 m/s2 (Models CIMR-A2A0004 to 2A0211 and 4A0002 to 4A0165) or,
2.0 m/s2 (Models CIMR-A2A0250 to 2A0415 and 4A0208 to 4A0675)
Orientation
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the
temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
OK
Not Good
Not Good
42
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_common
Side Clearance
Top/Bottom Clearance
A 50 mm minimum
B 30 mm minimum
C 120 mm minimum
D Airflow direction
YEC_common
Top/Bottom Clearance
Mechanical
Installation
B
B
A 50 mm minimum
B 30 mm minimum
C 2 mm minimum
D 120 mm minimum
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
43
Drive
Operator
Comm Port
S / N : J007XE273710001
common_
TMonly
Communication Cable Connector
44
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
1.6
15
78
90
S / N : J007XE273710001
7.9
60
YEC_TMonly
44
minimum
50
Unit: mm
There are two ways the digital operator can be mounted to an enclosure:
1. External/face-mount installs the operator outside the enclosure panel
2. Internal/flush-mount installs the operator inside the enclosure panel
Installation Method
External/Face-Mount
Internal/Flush-Mount
Description
Model
Required Tools
EZZ020642A
EZZ020642B
Mechanical
Installation
Note: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during
installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.8.
2. Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in
Figure 2.7.
Figure 2.6
Digital Operator
M3 6
Phillips recessed
pan head machine screw 2
Enclosure panel
common_TMonly
Unit: mm
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
45
22
2
22
26
78
common_TMonly
22
14
Unit: mm
Internal/Flush-Mount
An internal flush-mount requires an installation support set that must be purchased separately. Contact your Yaskawa
representative to order an installation support set and mounting hardware. Figure 2.9 illustrates how to attach the
Installation Support Set A.
1. Cut an opening in the enclosure panel for the digital operator as shown in Figure 2.10.
2. Mount the digital operator to the installation support.
3. Mount the installation support set and digital operator to the enclosure panel.
Figure 2.8
Enclosure panel
Digital Operator
Installation Support Set A
M4 10
Phillips truss head screw 4
(for panel widths between 1 and 1.6)
M3 6
Phillips recessed
pan head machine screw 2
common_TMonly
Unit: mm
120
89 +0.5
0
Figure 2.9
common_TMonly
45
59 +0.5
0
Unit : mm
46
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Three-Phase
400 V Class
2A0004F
2A0006F
2A0008F
2A0010F
2A0012F
2A0018F
2A0021F
2A0030F
2A0040F
2A0056F
2A0069F
2A0081F
4A0002F
4A0004F
4A0005F
4A0007F
4A0009F
4A0011F
4A0018F
4A0023F
4A0031F
4A0038F
4A0044F
48
2A0110A
2A0138A
2A0169A
2A0211A
2A0250A
2A0312A
2A0360A
2A0415A
4A0058A
4A0072A
4A0088A
4A0103A
4A0139A
4A0165A
4A0208A
4A0250A
4A0296A
4A0362A
4A0414A
4A0515A
4A0675A
50
Mechanical
Installation
IP00 Enclosure
Page
Three-Phase
200 V Class
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
47
H1
H0
H
1.5
4-d
W1
H1
1.5
4-d
W1
D1
H2
H3
H2
t1
W
Figure 1
Figure 2
4-d
t2
YEC_common
H3
H2
H1
H0
W1
t1
D1
t1
D1
Max.8
Max.8
Figure 3
W1
H0
H1
H2
H3
D1
t1
t2
Weight
(kg)
0004
140
260
147
122
248
38
M5
3.1
0006
140
260
147
122
248
38
M5
3.1
0008
140
260
147
122
248
38
M5
3.2
0010
140
260
147
122
248
38
M5
3.2
0012
140
260
147
122
248
38
M5
3.2
140
260
164
122
248
55
M5
3.5
140
260
164
122
248
55
M5
3.5
0030
140
260
167
122
248
55
M5
4.0
0040
140
260
167
122
248
55
M5
4.0
0056
180
300
187
160
284
75
M5
5.6
0069
220
350
197
192
335
78
M6
8.7
220
365
197
192
350
335
15
78
M6
9.7
0018
0021
0081
48
Dimensions (mm)
Figure
1
<1>
2
<1>
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Dimensions (mm)
Figure
W1
H0
H1
H2
H3
D1
t1
t2
Weight
(kg)
23
0110
254
534
258
195
400
385
7.5
134
100
2.3
2.3
M6
0138
279
614
258
220
450
435
7.5
164
100
2.3
2.3
M6
28
0169
329
730
283
260
550
535
7.5
180
110
2.3
2.3
M6
41
329
730
283
260
550
535
7.5
180
110
2.3
2.3
M6
42
456
960
330
325
705
680
12.5
255
130
3.2
3.2
M10
83
0312
456
960
330
325
705
680
12.5
255
130
3.2
3.2
M10
88
0360
504
1168
350
370
800
773
13
368
130
4.5
4.5
M12
108
0211
0250
3
<2>
<1> Removing the top protective cover from a IP20/NEMA Type 1 drive voids NEMA Type 1 protection but still keeps IP20 conformity.
<2> Special order required. Contact your Yaskawa sales representative.
Dimensions (mm)
H
W1
H0
H1
H2
H3
D1
t1
t2
Weight
(kg)
0002
140
260
147
122
248
38
M5
3.2
0004
140
260
147
122
248
38
M5
3.2
0005
140
260
147
122
248
38
M5
3.2
0007
140
260
164
122
248
55
M5
3.4
0009
140
260
164
122
248
55
M5
3.5
140
260
164
122
248
55
M5
3.5
0011
0018
1
<1>
140
260
167
122
248
55
M5
3.9
0023
140
260
167
122
248
55
M5
3.9
0031
180
300
167
160
284
55
M5
5.4
0038
180
300
187
160
284
75
M5
5.7
0044
220
350
197
192
335
78
M6
8.3
0058
254
465
258
195
400
385
7.5
65
100
2.3
2.3
M6
23
0072
279
515
258
220
450
435
7.5
65
100
2.3
2.3
M6
27
0088
329
630
258
260
510
495
7.5
120
105
2.3
3.2
M6
39
0103
329
630
258
260
510
495
7.5
120
105
2.3
3.2
M6
39
7.5
180
110
2.3
2.3
M6
45
46
0139
329
730
283
260
550
535
0165
<2>
329
730
283
260
550
535
7.5
180
110
2.3
2.3
M6
0208
456
960
330
325
705
680
12.5
255
130
3.2
3.2
M10
87
0250
504
1168
350
370
800
773
13
368
130
4.5
4.5
M12
106
0296
504
1168
350
370
800
773
13
368
130
4.5
4.5
M12
112
0362
504
1168
350
370
800
773
13
368
130
4.5
4.5
M12
117
Mechanical
Installation
Figure
<1> Removing the top protective cover from a IP20/NEMA Type 1 drive voids NEMA Type 1 protection but still keeps IP20 conformity.
<2> Special order required. Contact your Yaskawa sales representative.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
49
t2
H2
H1
H
W1
Max 10
D1
Max 10
YEC_common
t1
Figure 1
4-d
W1
t1
H2
H1
t2
Max 7.7
D1
D
Max 7.7
Figure 2
YEC_common
4-d
W1
t1
H2
H1
t2
D1
Max 6
Max 6
Figure 3
50
YEC_common
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Dimensions (mm)
Figure
W1
H1
H2
D1
t1
t2
Weight
(kg)
0110
250
400
258
195
385
7.5
100
2.3
2.3
M6
21
0138
275
450
258
220
435
7.5
100
2.3
2.3
M6
25
0169
325
550
283
260
535
7.5
110
2.3
2.3
M6
37
0211
325
550
283
260
535
7.5
110
2.3
2.3
M6
38
0250
450
705
330
325
680
12.5
130
3.2
3.2
M10
76
0312
450
705
330
325
680
12.5
130
3.2
3.2
M10
80
0360
500
800
350
370
773
13
130
4.5
4.5
M12
98
0415
500
800
350
370
773
13
130
4.5
4.5
M12
99
Dimensions (mm)
W
W1
H1
H2
D1
t1
t2
Weight
(kg)
0058
250
400
258
195
385
7.5
100
2.3
2.3
M6
21
0072
275
450
258
220
435
7.5
100
2.3
2.3
M6
25
0088
325
510
258
260
495
7.5
105
2.3
3.2
M6
36
0103
325
510
258
260
495
7.5
105
2.3
3.2
M6
36
0139
325
550
283
260
535
7.5
110
2.3
2.3
M6
41
325
550
283
260
535
7.5
110
2.3
2.3
M6
42
0208
450
705
330
325
680
12.5
130
3.2
3.2
M10
79
0250
500
800
350
370
773
13
130
4.5
4.5
M12
96
0296
500
800
350
370
773
13
130
4.5
4.5
M12
102
0165
Figure
0362
0414
0515
500
800
350
370
773
13
130
4.5
4.5
M12
107
500
950
370
370
923
13
135
4.5
4.5
M12
125
670
1140
370
440
1110
15
150
4.5
4.5
M12
216
670
1140
370
440
1110
15
150
4.5
4.5
M12
221
Mechanical
Installation
0675
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
51
52
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3
Electrical Installation
This chapter explains proper procedures for wiring the control circuit terminals, motor, and
power supply.
3.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 STANDARD CONNECTION DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 MAIN CIRCUIT CONNECTION DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 TERMINAL BLOCK CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 TERMINAL COVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 DIGITAL OPERATOR AND FRONT COVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 TOP PROTECTIVE COVER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 MAIN CIRCUIT WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.9 CONTROL CIRCUIT WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.10 CONTROL I/O CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.11 TERMINAL A2 ANALOG INPUT SIGNAL SELECTION . . . . . . . . . . . . . . . . . . . . .
3.12 CONNECT TO A PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.13 MEMOBUS/MODBUS TERMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.14 EXTERNAL INTERLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.15 WIRING CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
54
56
58
59
61
63
66
67
75
81
85
86
87
88
89
53
3.1
Section Safety
DANGER
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the drive to a combustible surface. Never place combustible materials on the drive.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
When installing dynamic braking options, perform all wiring exactly as specified in the wiring diagrams
provided.
Failure to do so can result in fire. Improper wiring may damage braking components.
54
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
CAUTION
Do not carry the drive by the front cover or the terminal cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Electrical Installation
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a dynamic braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
55
3.2
Connect the drive and peripheral devices as shown in Figure 3.1. It is possible to set and run the drive via the digital
operator without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up
Programming & Operation on page 91 for instructions on operating the drive.
NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable
codes. The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum
(200 V Class) and 480 Vac maximum (400 V Class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the
motor insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference
value), connect it to a photocoupler output (P1, P2, PC). Improper application of peripheral devices could result in damage to the
photocoupler output of the drive.
Figure 3.1
<4>
Terminals -, +1, +2, B1, B2 are
for connection options. Never
connect power supply lines to
these terminals
ELCB (MCCB)
r1
s1
t1
+2
Fuse
R/L1
+1
T/L3
Drive
<5>
SA
TRX
S2
External fault
S3
Fault reset
S4
TB1
A+
A
B+
B
Z+
Z
Multi-speed step 1
S5
SD
FE
Multi-speed step 2
S6
Jog speed
S7
External Baseblock
S8
PGB3
S1
SA
MC MA
TRX
Fault relay
contact
Multi-function
digtial inputs
(default setting)
CN5-C
Option board
connectors
MA
CN5-A
MB
MC
+V
A1
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 k)
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 k)
4 to 20 mA / 0 to 20 mA (250 )
Analog Input 3
(Aux. frequency reference)
0 to +10 Vdc (20 k)
A2
A3
AC
M1
M2
DIP Switch S1
V
P1
<9>
P2
PC
0V
<8> V Power supply, -10.5 Vdc, max. 20 mA
Termination resistor
(120 , 1/2 W)
DIP
Switch S2
R+
R
A track monitor
B track monitor
CN5-B
Multi-function
analog/ pulse
train inputs
PG
AO
IG
BO
IG
ZO
IG
+24 V
2 k
YEC_common
TB2
IP
IG
SC
<8>
MP
AC
0V
FM
<10>
S+
MEMOBUS/Modbus
comm. RS485/422
max. 115.2 kBps
FM
S
Safety
switch
Ground
<6>
THRX
V
W
W/T3
MC
U/T1
Control Circuit
M
Cooling fan
B2
B1
MC
t1
V/T2
FV
FW
s1
Main Circuit
S/L2
ON
FU
r1
Braking resistor
(option) <3>
Jumper
200 to 240 VT
50/60 Hz
2MCCB
MC
Three-phase R
power supply S
DC reactor <1>
Thermal relay
(option)
(option) <2>
<13>
IG
AM
AC
S2
Safe Disable inputs H1
S1
H2
<11>
0V
AM
<13>
E (G)
Open
Safety relay /
controller
Wire
jumper
<12>
EDM
HC
shielded line
DM
56
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
<1> Remove the jumper when installing a DC reactor. Models CIMR-A2A0110 through 2A0415 and 4A0058 through 4A0675 come with a
built-in DC reactor.
<2> When installing a dynamic braking option, a thermal relay sequence should also be set up to shut off power to the drive in case overheat
occurs.
<3> The drives protection function for the internal braking transistor needs to be disabled (L8-55 = 0) if using a regen unit such as a regen
converter or some type of dynamic braking options (and therefore not the internal braking transistor). If left enabled, a braking resistor fault
(rF) may result. Make sure Stall Prevention is disabled (L3-04 = 0) whenever using a regenerative converter, a regenerative unit or a dynamic
braking option. If left enabled, the drive may not stop within the specified deceleration time.
<4> Self-cooling motors do not require wiring that would be necessary with motors using a cooling fan.
<5> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option).
<6> For control modes that do not use a motor speed feedback signal, PG option card wiring is not necessary.
<7> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Use jumper S3 to select
sink or source, and an internal or external power supply.
<8> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and AC, as
this can cause erroneous operation or damage the drive.
<9> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<10> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
<11> The sink/source setting for the Safe Disable input is the same as with the sequence input. Jumper S3 has the drive set for an external power
supply. When not using the Safe Disable input feature, remove the jumper shorting the input and connect an external power supply. Refer to
Figure 3.35 for instructions.
<12> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
<13> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as
a feedback-type of signal.
<14> Note that if the drive is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a sequence to interrupt
power when a fault occurs will result in shutting off the power to the drive as the drive attempts to restart itself. The default setting for L5-02
is 0 (fault output not active during restart attempt).
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal
parameters are properly set. Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire
control, a momentary closure on terminal S1 may cause the drive to start.
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control terminals and ensure
parameter b1-17 is set to 0 (drive does not accept a run command at power up (default). If the drive is wired for 3-Wire sequence but
set up for 2-Wire sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will
rotate in reverse direction at power up of the drive and may cause injury.
WARNING! When using the automatic fault restart function while the wiring is made to shut off the power supply when a drive fault
occurs, make sure the drive is set not to trigger a fault output during fault restart (L5-02=0, default). Otherwise the fault restart function
can not work properly.
Electrical Installation
WARNING! When the application preset function is executed (or A1-06 is set to any value other than 0) the drive I/O terminal functions
change. This may cause unexpected operation and potential damage to equipment or injury.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
57
3.3
Refer to diagrams in this section when wiring the drives main circuit. Connections may vary based on drive capacity.
The DC power supply for the main circuit also provides power to the control circuit.
NOTICE: Do not use the negative DC bus terminal - as a ground terminal. This terminal is at high DC voltage potential. Improper
wiring connections could damage the drive.
YEC_common
DC reactor
(option)
+1
Jumper
B2
+2
B1
Drive
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Motor
YEC_common
Use terminals +1 and
for DC power supply
+1
B1
B2
Drive
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Motor
YEC_common
Braking Unit
(option)
+3
Drive
3 Phase power supply
200 to 240 Vac, 50 to 60 Hz
380 to 480 Vac, 50 to 60 Hz
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Motor
58
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3.4
Figure 3.5 shows the different main circuit terminal arrangements for the drive capacities.
Figure 3.8
CIMR-A2A0056
CIMR-A4A0031, 0038, 0044
CIMR-A2A0030, 0040
CIMR-A4A0018, 0023
B2
B1
+1
+2
B1
+1
+2
U/T1
B1
B2
V/T2 W/T3
S/L2
CIMR-A2A0069, 0081
+1
T/L3
+1
+2
U/T1
V/T2 W
CIMR-A2A0110, 0138
CIMR-A4A0058, 0072
+2
B1
B2
B1
T/L3
S/L2
U/T1
+1
V/T2
W/T3
Electrical Installation
R/L1
B2
CIMR-A4A0088, 0103
YEC_TMonly
R/L1
S/L2
T/L3
+1
+3
U/T1
V/T2
+1
R/L1
W/T3
<1>
+3
S/L2
T/L3
U/T1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
V/T2
W/T3
59
CIMR-A4A0515, 0675
CIMR-A4A0414
+1
+3
R/L1
S/L2
T/L3
U/T1
V/T2
+1
+3
R/L1
S/L2
T/L3
W/T3
U/T1
V/T2
W/T3
YEC_TMonly
Figure 3.5 Main Circuit Terminal Block Configuration
<1>
60
Terminal board design differs slightly for models CIMR-A2A0250 through 2A0415 and 4A0208 through 4A0362.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3.5
Terminal Cover
Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is
complete.
YEC_common
Figure 3.6 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
2. Push in on the hook located on the bottom of the terminal cover, and gently pull forward. This should remove the
terminal cover.
Figure 3.11
Figure 3.7 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
Electrical Installation
YEC_common
Figure 3.12
YEC_common
Figure 3.8 Reattaching the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
61
YEC_common
Figure 3.9 Removing the Terminal Cover on an IP00 Enclosure Drive
YEC_common
Figure 3.10 Removing the Terminal Cover on an IP00 Enclosure Drive
YEC_common
62
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3.6
The digital operator can be detached from the drive for remote operation, or when the front cover has to be opened to
install an option card.
NOTICE: Be sure the digital operator has been removed prior to opening the front cover or reattaching it. Leaving the digital operator
plugged into the drive when removing the front cover can result in erroneous operation caused by a poor connection. Before
reattaching the operator make sure the front cover has been firmly fastened back into place.
YEC_common
Figure 3.12 Removing the Digital Operator
Electrical Installation
YEC_common
Figure 3.13 Reattaching the Digital Operator
After removing the terminal cover and the digital operator, loosen the screw that affixes the front cover (model CIMRA2A0056, 4A0031, 4A0038 do not use a screw to affix the front cover). Pinch inwards on hooks found on each side of
the front cover, then pull forward to remove it from the drive.
Figure 3.18
YEC_common
Figure 3.14 Remove the Front Cover (2A0004 to 2A0081 and 4A0002 to 4A0044)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
63
YEC_common
Hook
Front cover
installation screw
Hook
Free hooks on both
sides of the cover
Figure 3.15 Remove the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A0675)
4. First unhook the left side of the front cover, then swing the left side towards you as shown in the figure below
until the cover comes off.
Figure 3.20
YEC_common
Figure 3.16 Remove the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A0675)
64
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Reverse the instructions given in Remove the Front Cover (2A0004 to 2A0081 and 4A0002 to 4A0044) on page 63 to
reattach the front cover. Pinch inwards on the hooks found on each side of the front cover while guiding it back into the
drive. Make sure it clicks firmly into place.
2A0110 to 2A0415 and 4A0058 to 4A0675
1. Slide the front cover so that the hooks on the top connect to the drive.
Figure 3.21
YEC_c
ommon
Figure 3.17 Reattach the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A0675)
Electrical Installation
2. Once the hooks have connected to the drive, press firmly on the cover to make sure it locks into place.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
65
3.7
Drive models CIMR-A2A0004 to 0081 and 4A0002 to 0058 are designed with NEMA Type 1 specifications, and have
a top protective cover on the top. Removing this top protective cover voids the NEMA Type 1 conformance but still
keeps a protection degree in accordance with IP20 enclosure.
YEC_common
YEC_common
Figure 3.19 Reattaching the Top Protective Cover
66
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3.8
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit
in the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the lifetime of the
DC bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from
switching the drive on and off more than once every 30 minutes.
Model
CIMR-A
400 V
Class
Type
2A0004 to 2A0081
2A0110, 2A0138
2A0169 to 2A0415
4A0002 to 4A0044
4A0058 to 4A0072
4A0088 to 4A0675
Function
Page
R/L1
S/L2
56
56
385
For connection
of the drive to a DC power supply (terminals +1
and are not EU or UL approved)
of dynamic braking options
of a DC reactor
389
Grounding terminal
73
T/L3
U/T1
V/T2
Drive output
W/T3
B1
Braking resistor
B2
+2
+1
+3
not available
Insulation Cap
Use insulation caps when wiring the drive with crimp terminals. Take particular care to ensure that wiring does not touch
neighboring terminals or the surrounding case.
Electrical Installation
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
67
Insulation Barrier
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 wire resistance (/km) wire length (m) current (A) 10-3
Refer to instruction manual TOBPC72060000 for braking unit or braking resistor unit wire gauges.
Use terminal +1 and the negative terminal when connecting a braking resistor, regenerative converter, or a regen unit.
Refer to UL Standards Compliance on page 526 for information on UL compliance.
68
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
2A0004
2A0006
2A0008
2A0010
2A0012
2A0018
Terminal
2A0069
2A0081
2A0110
Recommended
Gauge
mm2
Applicable
Gauge
mm2
2.5 to 6
2 to 5.5
14
14 to 10
2.5
2 to 5.5
14
14 to 10
2.5
2.5 to 6
, +1, +2
2 to 5.5
14 to 10
2.5 to 6
B1, B2
2 to 5.5
14 to 10
2.5 to 6
2 to 5.5
10
14 to 10
2.5
2.5 to 6
2 to 5.5
12
14 to 10
2.5
2.5 to 6
2 to 5.5
14
14 to 10
2.5
2.5 to 6
, +1, +2
2 to 5.5
14 to 10
2.5 to 6
B1, B2
2 to 5.5
14 to 10
2.5 to 6
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
3.5
2 to 5.5
10
12 to 10
2.5
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
, +1, +2
3.5
2 to 5.5
14 to 10
2.5 to 6
2 to 5.5
14 to 10
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
5.5
3.5 to 5.5
10
12 to 10
2.5 to 6
3.5
3.5 to 5.5
10
12 to 10
2.5
2.5 to 6
, +1, +2
5.5
3.5 to 5.5
12 to 10
4 to 6
2.5 to 6
2A0056
Applicable
Gauge
AWG, kcmil
B1, B2
2A0040
Recommended
Gauge
AWG, kcmil
2A0030
Applicable
Gauge
mm2
B1, B2
2A0021
Recommended
Gauge
mm2
2 to 5.5
14 to 10
3.5
3.5 to 5.5
10
12 to 10
4 to 6
14
5.5 to 14
10 to 6
4 to 16
5.5 to 14
10 to 6
4 to 16
, +1, +2
14
5.5 to 14
10 to 6
6 to 16
B1, B2
3.5
2 to 5.5
14 to 10
4 to 6
5.5
5.5 to 8
10 to 8
6 to 10
Screw
Size
Tightening
Torque
Nxm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M6
4 to 6
(35.4 to 53.1)
14
14
8 to 6
10
6 to 16
14
8 to 14
8 to 6
10
6 to 16
, +1, +2
14
14
16
B1, B2
5.5
3.5 to 5.5
12 to 10
4 to 6
5.5
5.5 to 8
10 to 8
10
6 to 10
22
14 to 22
6 to 4
16
16 to 25
14
14 to 22
6 to 4
16
16 to 25
, +1, +2
22
14 to 22
6 to 4
16 to 25
B1, B2
14
5.5 to 14
10 to 6
6 to 10
M5
2 to 2.5
(17.7 to 22.1)
8 to 14
8 to 6
16
10 to 16
M6
4 to 6
(35.4 to 53.1)
M8
9 to11
(79.7 to 97.4)
30
22 to 30
4 to 3
25
16 to 25
22
14 to 30
4 to 3
16
16 to 25
, +1, +2
30
22 to 30
4 to 3
25
B1, B2
14
8 to 14
8 to 6
10 to 16
M5
2 to 2.5
(17.7 to 22.1)
8 to 22
6 to 4
16
16 to 25
M6
4 to 6
(35.4 to 53.1)
M8
9 to11
(79.7 to 97.4)
38
30 to 38
3 to 2
35
25 to 35
30
22 to 38
3 to 2
25
25 to 35
, +1, +2
38
30 to 38
3 to 2
25 to 35
B1, B2
14
14
16
M5
2 to 2.5
(17.7 to 22.1)
14
14 to 22
6 to 4
16
16 to 25
M6
4 to 6
(35.4 to 53.1)
M8
9 to 11
(79.7 to 97.4)
38
30 to 50
1/0
3 to 1/0
35
25 to 50
38
30 to 50
1/0
3 to 1/0
35
25 to 50
, +1
60
38 to 60
2 to 1/0
35 to 50
B1, B2
22
14 to 50
6 to 1/0
16 to 50
14
14 to 38
6 to 4
16
16 to 25
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
Table 3.2 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
69
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
Terminal
Recommended
Gauge
mm2
Applicable
Gauge
mm2
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm2
Applicable
Gauge
mm2
60
50 to 60
2/0
1 to 2/0
50
35 to 70
60
50 to 60
2/0
1 to 2/0
50
35 to 70
, +1
80
60 to 80
1/0 to 3/0
50 to 70
B1, B2
30
22 to 60
4 to 2/0
25 to 70
22
22 to 38
25
25
50 to 95
80
60 to 100
4/0
2/0 to 4/0
70
80
60 to 100
4/0
3/0 to 4/0
70
50 to 95
50 2P
50 to 100
1 to 4/0
35 to 95
60
50 to 100
1/0 to 4/0
50 to 95
22
22 to 60
4 to 2
35
25 to 35
, +1
+3
Screw
Size
Tightening
Torque
Nxm (lb.in.)
M10
18 to 23
(159 to 204)
M8
9 to 11
(79.7 to 97.4)
M10
18 to 23
(159 to 204)
M8
9 to 11
(79.7 to 97.4)
M10
18 to 23
(159 to 204)
M8
9 to 11
(79.7 to 97.4)
M12
32 to 40
(283 to 354)
100
80 to 100
1/0 2P
1/0 to 2/0
95
70 to 95
50 2P
50 to 60
1/0 2P
1/0 to 2/0
95
70 to 95
, +1
50 2P
50 to 100
1 to 4/0
35 to 95
80
60 to 100
1/0 to 4/0
50 to 95
22
22 to 60
4 to 1/0
50
25 to 50
80 2P
38 to 150
3/0 2P
3/0 to 300
95 2P
95 to 150
80 2P
38 to 150
3/0 2P
3/0 to 300
95 2P
95 to 150
, +1
80 2P
80 to 150
3/0 to 300
70 to 150
+3
80 2P
30 to 150
2 to 300
35 to 150
M10
18 to 23
(159 to 204)
22
22 to 150
3 to 300
95
95 to 150
M12
32 to 40
(283 to 354)
80 2P
70 to 150
4/0 2P
3/0 to 300
95 2P
95 to 150
80 2P
70 to 200
3/0 2P
3/0 to 300
95 2P
95 to 150
M12
32 to 40
(283 to 354)
, +1
150 2P
80 to 150
3/0 to 300
70 to 150
+3
80 2P
80 to 150
3/0 to 300
70 to 150
M10
18 to 23
(159 to 204)
38
38 to 150
2 to 300
95
95 to 150
M12
32 to 40
(283 to 354)
100 2P
80 to 325
250 2P
4/0 to 600
240
95 to 300
100 2P
80 to 325
4/0 2P
4/0 to 600
240
95 to 300
M12
32 to 40
(283 to 354)
, +1
150 2P
125 to 325
250 to 600
125 to 300
+3
80 2P
80 to 325
3/0 to 600
70 to 300
M10
18 to 23
(159 to 204)
38
38 to 200
1 to 350
120
120 to 240
M12
32 to 40
(283 to 354)
125 2P
100 to 325
350 2P
250 to 600
120 2P
95 to 300
125 2P
125 to 325
300 2P
300 to 600
300
95 to 300
M12
32 to 40
(283 to 354)
, +1
200 2P
150 to 325
300 to 600
150 to 300
+3
100 2P
80 to 325
3/0 to 600
70 to 300
M10
18 to 23
(159 to 204)
60
60 to 200
1 to 350
120
120 to 240
M12
32 to 40
(283 to 354)
Screw
Size
Tightening
Torque
Nxm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
+3
4A0002
4A0004
70
Terminal
Recommended
Gauge
mm2
Applicable
Gauge
mm2
Applicable
Gauge
AWG, kcmil
Applicable
Gauge
mm2
2 to 5.5
14
14 to 10
2.5
2.5 to 6
2 to 5.5
14
14 to 10
2.5
2.5 to 6
, +1, +2
2 to 5.5
14 to 10
2.5 to 6
B1, B2
2 to 5.5
14 to 10
2.5 to 6
2 to 5.5
12
14 to 12
2.5
2.5 to 4
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4A0005
4A0007
4A0009
4A0011
Terminal
4A0023
4A0031
4A0038
4A0044
4A0058
4A0103
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm2
Applicable
Gauge
mm2
2.5 to 6
2 to 5.5
14
14 to 10
2.5
2 to 5.5
14
14 to 10
2.5
2.5 to 6
, +1, +2
2 to 5.5
14 to 10
2.5 to 6
B1, B2
2 to 5.5
14 to 10
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
2 to 5.5
12
14 to 10
2.5
2.5 to 6
2 to 5.5
14
14 to 10
2.5
2.5 to 6
, +1, +2
2 to 5.5
14 to 10
2.5 to 6
Screw
Size
Tightening
Torque
Nxm (lb.in.)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M4
1.2 to 1.5
(10.6 to 13.3)
M5
2 to 2.5
(17.7 to 22.1)
M5
2 to 2.5
(17.7 to 22.1)
2 to 5.5
14 to 10
2.5 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
3.5
2 to 14
10
12 to 6
2.5
2.5 to 16
3.5
2 to 14
10
12 to 6
2.5
2.5 to 16
, +1, +2
3.5
2 to 14
12 to 6
4 to 16
2 to 5.5
12 to 10
4 to 6
3.5
2 to 5.5
10
14 to 10
2.5
2.5 to 6
5.5
3.5 to 14
10
10 to 6
2.5 to 16
5.5
3.5 to 14
10
10 to 6
2.5 to 16
, +1, +2
5.5
3.5 to 14
12 to 6
4 to 16
2 to 5.5
12 to 10
4 to 6
3.5
3.5 to 5.5
10
12 to 10
4 to 6
14
5.5 to 14
8 to 6
6 to 16
5.5 to 8
10 to 6
6 to 16
, +1, +2
14
5.5 to 14
10 to 6
6 to 16
B1, B2
3.5
2 to 8
10 to 8
6 to 10
M5
2 to 2.5
(17.7 to 22.1)
5.5
5.5 to 8
10 to 8
6 to 10
M6
4 to 6
(35.4 to 53.1)
M5
2 to 2.5
(17.7 to 22.1)
B1, B2
B1, B2
14
14
8 to 6
10
10 to 16
14
8 to 14
8 to 6
6 to 16
, +1, +2
14
14
6 to 16
B1, B2
5.5
3.5 to 8
10 to 8
6 to 10
M5
2 to 2.5
(17.7 to 22.1)
5.5 to 14
10 to 6
10
6 to 16
M6
4 to 6
(35.4 to 53.1)
14
14 to 22
6 to 4
16
16 to 25
14
14 to 22
6 to 4
16
16 to 25
M6
, +1, +2
14
14 to 22
6 to 4
16 to 25
4 to 6
(35.4 to 53.1)
B1, B2
5.5 to 8
10 to 8
6 to 10
M5
2 to 2.5
(17.7 to 22.1)
8 to 14
8 to 6
16
10 to 16
M6
4 to 6
(35.4 to 53.1)
14
14
6 to 4
16
10 to 16
14
14
6 to 4
16
10 to 16
, +1
22
14 to 38
6 to 1
16 to 35
M8
B1, B2
14
8 to 14
8 to 4
10 to 16
9 to 11
(79.7 to 97.4)
8 to 14
8 to 6
16
10 to 16
22
14 to 22
4 to 3
16
16 to 25
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
M8
9 to 11
(79.7 to 97.4)
22
14 to 22
4 to 3
25
16 to 25
, +1
30
22 to 38
4 to 1
25 to 35
B1, B2
4A0088
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
mm2
B1, B2
4A0018
Recommended
Gauge
mm2
14
14 to 22
6 to 3
16 to 25
14
14 to 22
16
16 to 25
30
22 to 50
3 to 1/0
25
16 to 50
30
22 to 50
3 to 1/0
25
25 to 50
, +1
38
30 to 50
3 to 1/0
25 to 50
+3
22
14 to 50
6 to 1/0
16 to 50
22
14 to 22
6 to 4
16
16 to 25
38
30 to 50
1/0
2 to 1/0
35
25 to 50
38
30 to 50
2 to 1/0
35
25 to 50
, +1
60
30 to 50
3 to 1/0
25 to 50
+3
30
22 to 50
4 to 1/0
25 to 50
22
14 to 22
6 to 4
16
16 to 25
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
71
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
Terminal
Recommended
Gauge
mm2
Applicable
Gauge
mm2
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm2
Applicable
Gauge
mm2
60
38 to 100
3/0
1/0 to 4/0
50
35 to 95
60
50 to 100
2/0
1/0 to 4/0
50
35 to 95
, +1
100
60 to 100
1/0 to 4/0
50 to 95
+3
50
30 to 100
3 to 4/0
25 to 95
22
22
25
25
80
60 to 100
4/0
3/0 to 4/0
70
50 to 95
80
80 to 100
4/0
3/0 to 4/0
70
70 to 95
50 2P
50 to 100
1 to 4/0
35 to 95
+3
60
50 to 100
1/0 to 4/0
50 to 95
22
22 to 30
4 to 2
35
25 to 35
150
30 to 150
300
2 to 300
95
35 to 95
150
30 to 150
300
2 to 300
95
35 to 95
80 2P
38 to 150
1 to 250
35 to 150
+3
80
22 to 80
3 to 3/0
25 to 70
22
22 to 150
4 to 300
50
50 to 150
150
38 to 325
400
1 to 600
120
95 to 300
, +1
, +1
Screw
Size
Tightening
Torque
Nxm (lb.in.)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M10
18 to 23
(159 to 204)
M12
32 to 40
(283 to 354)
150
38 to 325
400
1/0 to 600
120
95 to 300
, +1
200
80 to 325
3/0 to 600
70 to 300
+3
125
38 to 325
1 to 325
35 to 300
22
22 to 200
2 to 350
70
70 to 240
200
80 to 325
500
2/0 to 600
185
95 to 300
200
80 to 325
500
2/0 to 600
185
95 to 300
, +1
325
80 to 325
3/0 to 600
70 to 300
+3
150
38 to 325
1 to 325
35 to 300
M10
18 to 23
(159 to 204)
30
30 to 200
2 to 350
95
95 to 240
M12
32 to 40
(283 to 354)
M12
32 to 40
(283 to 354)
250
80 to 325
4/0 2P
3/0 to 600
240
95 to 300
250
80 to 325
4/0 2P
3/0 to 600
240
95 to 300
, +1
325
100 to 325
4/0 to 600
95 to 300
+3
200
80 to 325
3/0 to 600
70 to 300
M10
18 to 23
(159 to 204)
30
30 to 200
1 to 350
120
120 to 240
M12
32 to 40
(283 to 354)
100 2P
80 to 150
300 2P
4/0 to 300
95 2P
95 to 150
125 2P
80 to 150
300 2P
4/0 to 300
95 2P
95 to 150
, +1
150 2P
80 to 150
3/0 to 300
70 to 150
M12
32 to 40
(283 to 354)
+3
80 2P
80 to 150
3/0 to 300
70 to 150
38
38 to 100
1 to 3/0
95
35 to 95
125 2P
80 to 150
3/0 4P
3/0 to 300
120 2P
95 to 150
150 2P
80 to 150
4/0 4P
3/0 to 300
150 2P
95 to 150
, +1
60 4P
60 to 150
1/0 to 300
70 to 150
M12
32 to 40
(283 to 354)
+3
100 2P
60 to 150
1/0 to 300
70 to 150
60
50 to 150
1/0
1/0 to 300
150
50 to 150
80 4P
80 to 150
300 4P
4/0 to 300
95 4P
95 to 150
80 4P
80 to 150
300 4P
4/0 to 300
95 4P
95 to 150
, +1
125 4P
60 to 150
1/0 to 300
70 to 150
M12
32 to 40
(283 to 354)
+3
60 4P
60 to 150
1/0 to 300
70 to 150
60
70 to 150
2/0
2/0 to 300
95 2P
60 to 150
72
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
50 m or less
100 m or less
Carrier Frequency
15 kHz or less
5 kHz or less
2 kHz or less
Note: When setting carrier frequency in a drive running multiple motors, calculate the cable length as the total distance of wiring to all
motors that are connected.
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: Ground to 100 or less, 400 V class:
Ground to 10 or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical
equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could
result in abnormal operation of drive or equipment.
Refer to Figure 3.21 when using multiple drives. Do not loop the ground wire.
Figure 3.25
OK
OK
Not Good
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Electrical Installation
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and
minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment
chassis, which could result in death or serious injury.
73
Wire the main circuit terminals after the terminal board has been properly grounded.
Models CIMR-A2A0004 through 0081 and 4A0002 through 0044 have a cover placed over the DC bus and braking
circuit terminals prior to shipment to help prevent miswiring. Cut away covers as needed for terminals using wire cutters.
Figure 3.26
A Protecting Cover
Figure 3.22 Protecting Cover to Prevent Miswiring (CIMR-A2A0056)
74
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
3.9
YEC_TMonly
Drive
Control Circuit
Multi-function
digtial inputs
(default setting)
S1
S2
External fault
S3
Fault reset
S4
Multi-speed step 1
S5
Multi-speed step 2
S6
Jog speed
S7
External Baseblock
S8
<1>
SC
CN5-C
Option board
connectors
CN5-B
MA
CN5-A
MB
MC
<3>
2 k
Multi-function
analog/ pulse
train inputs
+V
A1
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 k)
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 k)
4 to 20 mA / 0 to 20 mA (250 )
Analog Input 3
(Aux. frequency reference)
0 to +10 Vdc (20 k)
A2
A3
AC
M1
M2
DIP Switch S1
V
P1
<4>
P2
PC
0V
<3> V Power supply, -10.5 Vdc, max. 20 mA
Termination resistor
(120 , 1/2 W)
R+
R
0V
FM
<5>
S+
MEMOBUS/Modbus
comm. RS485/422
max. 115.2 kBps
MP
AC
DIP
Switch S2
FM
S
Safety
switch
Electrical Installation
+24 V
<8>
IG
AM
AC
S2
Safe Disable inputs H1
S1
H2
<6>
0V
AM
<8>
E (G)
Open
Safety relay /
controller
Wire
jumper
<7>
DM
shielded line
main circuit terminal
Supplying power to the control circuit separately from the main circuit requires 24 V power supply (option).
This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Use jumper S3 to
select sink or source and internal or external power supply.
The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and
AC, as this can cause erroneous operation or damage the drive.
Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
The sink/source setting for the Safe Disable input is the same as with the sequence input.
Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for
use as a feedback-type of signal.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
75
Input Terminals
Table 3.5 lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Table 3.5 Control Circuit Input Terminals
Type
Multi-Function
Digital Inputs
Safe Disable
Inputs
Analog Inputs /
Pulse Train Input
No.
S1
S2
S3
S4
S5
S6
S7
S8
Photocoupler
24 Vdc, 8 mA
Set the S3 jumper to select between sinking, sourcing mode, and the power supply.
Refer to Sinking/Sourcing Mode Switch for Digital Inputs on page 81.
Page
431
SC
H1
H2
24 Vdc, 8 mA
One or both open: Output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and HC to use the Safe
Disable inputs. Set the S3 jumper to select between sinking, sourcing mode, and the
power supply as explained for multi-function input terminals in Sinking/Sourcing
Mode Switch for Digital Inputs on page 81. <1>
HC
RP
138
244
+V
137
-V
530
A1
137
237
A2
137
138
239
A3
137
AC
0V
137
E (G)
<1> Setting jumper S3 for an external power supply makes the wire link between terminals H1, H2, and H2 ineffective. Remove the wire link and
connect an external power supply that can supply terminals H1, H2, and HC continuously.
76
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Multi-Function
Digital Output <1>
Multi-Function
Photocoupler
Output
Monitor Output
No.
N.O.
MB
N.C. output
MC
M1
M2
P1
Page
227
227
48 Vdc, 2 to 50 mA <2>
227
32 kHz (max)
244
242
P2
PC
MP
FM
AM
0V
DM+
DM-
Outputs status of Safe Disable function. Closed when both Safe Disable
channels are closed. Up to +48 Vdc 50 mA
AC
Safety Monitor
Output
MA
520
<1> Refrain from assigning functions to terminals M1 and M2 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a flywheel diode as shown in the Figure 3.24 when driving a reactive load such as a relay coil. Make sure the diode rating is greater
than the circuit voltage.
Figure 3.28
YEC_common
C Coil
D 50 mA or less
Electrical Installation
MEMOBUS/Modbus
Communication
<1>
No.
Signal Name
R+
R-
S+
S-
IG
Shield ground
RS-485/422
MEMOBUS/Modbus
communication protocol
115.2 kbps (max.)
0V
<1> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position. For more information on
the termination resistor, see Control I/O Connections on page 81.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
77
Terminal Configuration
Control circuit terminals should are arranged as shown in Figure 3.25.
Figure 3.29
YEC_common
DM
DM+
H2
H1
HC
S
S+
R
R+
IG
MP
RP
E(G) FM AC AM P1 P2 PC SC
SC A1 A2 A3 +V AC -V
MA MB MC
M1 M2 E(G)
S1 S2 S3 S4 S5 S6 S7 S8
A Terminal Block (TB 6)
B Terminal Block (TB 5)
C Terminal Block (TB 4)
Terminal board arrangement appears below. The exact location of the labeling may vary by model.
Figure 3.31
YEC_common
Inside of the Terminal Cover
(CIMR-A2A0004 to 2A0081, 4A0002 to 4A0044)
78
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
TB1, TB2
Screw
Size
Tightening
Torque
Nxm
(lb.in.)
M3.5
0.8 to 1.0
(7.1 to 8.6)
0.5 to 2
(20 to 14)
0.75
(18)
E (G)
M3.5
0.8 to 1.0
(7.1 to 8.6)
0.5 to 2
(20 to 14)
1.25
(12)
0.22 to 0.25
(1.9 to 2.2)
0.75
(18)
Terminal
Block
Terminal
M2
Ferrule-Type Terminal
Applicable wire size Recomm. mm2 Applicable wire size Recomm. mm2
mm2
mm2
(AWG)
(AWG)
(AWG)
(AWG)
Wire Type
0.25 to 0.5
(24 to 20)
0.5
(20)
6 mm
d1
YEC_common
d2
L (mm)
d1 (mm)
d2 (mm)
0.25 (24)
AI 0.25-6YE
10.5
0.8
0.34 (22)
AI 0.34-6TQ
10.5
0.8
0.5 (20)
AI 0.5-6WH
14
1.1
2.5
Manufacturer
Electrical Installation
PHOENIX CONTACT
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
Figure 3.28 for details. Prepare the ends of the control circuit wiring as shown in Figure 3.30. Refer to Wire Size and
Torque Specifications on page 79.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
79
B
A
Preparing wire
terminal ends
C
YEC_common
TB6
TB5
TB4
Use the space above TB2 to wire TB4 through TB6 as illustrated in Figure 3.29.
Figure 3.35
YEC_common
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires (treating
wire ends as shown in Figure 3.30 and connect the shield to the ground terminal of the drive.
Figure 3.36
A Drive side
B Connect shield to ground terminal of
drive.
C Insulation
80
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_common
S7
S8
YEC_common
IP24 V
(24 V)
Electrical Installation
SC
Figure 3.39
S7
S8
SC
IP24 V
(24 V)
YEC_common
Figure 3.33 Source Mode (+24 V Common), Internal Power Supply
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
81
YEC_common
S7
S7
S8
S8
IP24 V
(24 V)
SC
IP24 V
(24 V)
SC
+24 V
+24 V
S8
S8
IP24 V
(24 V)
SC
IP24 V
(24 V)
SC
+24 V
+24 V
H1
H1
H2
H2
HC
HC
YEC_common
Source Mode
Sink Mode
Figure 3.35 Power Supply Inputs Instead of the Safe Disable Feature
82
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Controller
MA
M1
During
Run
Relay
SA
Relay
SA
MB
Max
250 Vac
MC
M2
Max 48 Vdc
Relay
P1
Max 48 Vdc
Relay
Speed Agree 1
P2
YEC_TMonly
PC
1.5 k
5V
8V
10 k
10 V
Note: The load resistance needed in order to get a certain high level voltage VMP can be calculated by:
RL = VMP
2 / (12 - VMP)
Electrical Installation
4 k
Figure 3.42
Load Impedance
MP
VMP
RL
AC
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
83
12 to 15 Vdc 10%
1.0 k or higher
Figure 3.43
Load Impedance
MP
Sink Current
AC
84
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Dip Switch S1
V
YEC_common
Setting
Description
V (left position)
Electrical Installation
H3-09
Parameter Name
Description
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Setting
Range
Default
Setting
0 to 3
85
3.12 Connect to a PC
3.12 Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to the USB port of a PC using a USB 2.0, AB type cable (sold separately). DriveWizard Plus can
then be used to monitor drive performance and manage parameter settings. Contact Yaskawa for more information on
DriveWizard Plus.
Figure 3.45
USB Cable
(Type-AB)
(Type-B)
(Type-A)
PC
YEC_common
Figure 3.40 Connecting to a PC (USB)
86
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Description
ON
OFF
Figure 3.46
YEC_TMonly
ON
O
N
DIP Switch S2
OFF
(OFF: default)
Electrical Installation
Note: Refer to the MEMOBUS/Modbus Communications on page 487 for details on MEMOBUS/Modbus.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
87
Drive Ready
When the Drive ready signal has been set to one of the multi-function contact outputs, that output will close whenever
the drive is ready to accept a Run command or is already running. Under the following conditions the Drive ready signal
will switch off and remain off, even if a Run command is entered:
Output Signal
Parameter Setting
MA, MB, MC
Fault
M1-M2
Drive Ready
H2-01 = 06
Ready1
Ready2
Fault1
Fault2
Operation
Circuit
Stop
Drive Ready
Drive Ready
common_
TMonly
Run
Figure 3.47
Drive 1
Controller
MA
Relay 1
Run
S1
SC
Fault
Output
SA
MB
Max
250 Vac
Relay 1
Fault 1
MC
Relay 2
SA
Relay 2
Ready 1
M1
Drive Ready
M2
Drive 2
common_
TMonly
Controller
MA
Relay 1
Run
S1
SC
Fault
Output
SA
MB
Max
250 Vac
Relay 1
Fault 2
MC
Relay 2
SA
Relay 2
Ready 2
M1
Drive Ready
M2
88
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Item
Page
33
Make sure you have the correct braking resistors, DC reactors, noise filters, and other peripheral devices.
379
379
Installation area and physical setup
Ensure that the area surrounding the drive complies with specifications.
42
The voltage from the power supply should be within the input voltage specification range of the drive.
196
The voltage rating for the motor should match the drive output specifications.
31
452
31
452
Confirm proper branch circuit protection as specified by national and local codes.
56
Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3.
58
10
73
11
Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.
68
Use the correct wire gauges for the main circuit. Refer to Wire Gauges and Tightening Torque on page 68.
68
When using comparatively long motor cable, calculate the amount of voltage drop.
68
12
If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly.
73
13
73
14
Tightly fasten all terminal screws (control circuit terminals, grounding terminals).
Refer to Wire Gauges and Tightening Torque on page 68.
68
Power supply
Drive
MC1
Electrical Installation
Set up overload protection circuits when running multiple motors from a single drive.
OL1
M1
MC2
15
OL2
M2
MCn
OLn
Mn
Note: Close MC1 through MCn before operating the drive (MC1 through MCn cannot be switched off during run).
16
If using a dynamic braking option, install a magnetic contactor. Properly install the resistor, and ensure that overload protection shuts off the
power supply.
17
Verify phase advancing capacitors, input noise filters, or ground fault circuit interrupters are NOT installed on the output side of the drive.
18
75
19
79
20
If using a 3-wire sequence, properly set parameters for multi-function contact input terminals S1 through S8, and properly wire control
circuits.
21
79
22
23
68
24
25
Ensure that no frayed wires on the terminal block are touching other terminals or connections.
26
27
28
385
terminal.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
89
90
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4
Start-Up Programming & Operation
This chapter explains the functions of the digital operator and how to program the drive for
initial operation.
4.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
4.2 USING THE DIGITAL OPERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4.3 THE DRIVE AND PROGRAMMING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.4 START-UP FLOWCHARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
4.5 POWERING UP THE DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
4.6 APPLICATION SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
4.7 AUTO-TUNING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
4.8 NO-LOAD OPERATION TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
4.9 TEST RUN WITH LOAD CONNECTED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
4.10 VERIFYING PARAMETER SETTINGS AND BACKING UP CHANGES . . . . . . . 127
4.11 TEST RUN CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
91
4.1
Section Safety
DANGER
WARNING
92
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.2
Use the digital operator to enter run and stop commands, display data, edit parameters, as well as display fault and alarm
information.
14
13
12
ALM
REV
DRV
11
YEC_common
FOUT
10
1
ESC
LO
RE
RESET
ENTER
RUN
8
7
STOP
Name
Function
ESC Key
RESET Key
RUN Key
Up Arrow Key
Scrolls up to display the next item, selects parameter numbers and increments setting values.
Scrolls down to display the next item, selects parameter numbers and increments setting values.
ENTER Key
Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). The LED
is on when the drive is in the LOCAL mode (operation from keypad).
RUN Light
Lit while the drive is operating the motor. Refer to page 95 for details.
LO/RE Light
Lit while the operator is selected to run the drive (LOCAL mode). Refer to page 95 for details.
6
7
10
ESC
RESET
RUN
STOP
ENTER
LO
RE
RUN
LO
RE
11
12
13
14
<1> The STOP key has highest priority. Pressing the STOP key will always cause the drive to stop the motor, even if a Run command is active at
any external Run command source. To disable the STOP key priority, set parameter o2-06 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. To disable the LO/RE key to prohibit switching
between LOCAL and REMOTE, set parameter o2-01 to 0.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
93
Start-Up Programming
& Operation
No.
Flashing
LED
Text
LED
Text
LED
Text
LED
V
<1>
<1>
none
none
Lit
Flashing
REV
DRV FOUT
DRV
ALM
REV
DRV
FOUT
As illustrated in this
manual
Off
ALM
ALM
REV
DRV
ALM
FOUT
94
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Lit
Flashing
Off
During run
Examples
<1> Refer to Figure 4.2 for the difference between flashing and flashing quickly.
Figure 4.2
1s
ON
ON
common_TM
only
Flashing
Flashing
quickly
ON
ON
ON
ON
/
Frequency setting
RUN LED
during stop
0 Hz
RUN
RUN
STOP
STOP
6 Hz
OFF
OFF
ON
OFF
common_TM
only
Start-Up Programming
& Operation
Flashing
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
95
REV
ALM
DRV FOUT
DRV
DRIVE MODE
<1>
Forward Selection
Reverse Selection
Output Frequency
Output Current
Output Voltage
XX
Monitor Display
X XX
XX
XX XX
XX
XX XX
XX
PROGRAMMING MODE
Verify Menu
X
Set Up Mode
XX XX
YEC_common
XX
XX
XX XX
XX
X XX
XX
X XX
XX
Auto-Tuning
XX
96
Reverse can only be selected when the drive is set for LOCAL. Details on switching between forward and reverse can be found in
Navigating the Drive and Programming Modes on page 97.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.3
The drive has a Programming Mode to program the drive for operation, and a Drive Mode used to actually run the motor.
Drive Mode: In the Drive Mode, the user can start the motor and observe operation status with the monitors that are
available. Parameter settings cannot be edited or changed when in the Drive Mode.
Programming Mode: The Programming Mode allows access to edit, adjust, and verify parameters, as well as perform
Auto-Tuning. Unless set to allow a Run command, the drive will not accept a Run command when the digital operator is
in the Programming Mode.
Note: If parameter b1-08 is set to 0 the drive will accept a Run command only in the Drive Mode. When editing parameters, the user
must first exit the Programming Mode and enter the Drive Mode before starting the motor.
Note: To allow the drive to run the motor while in the Programming Mode, set b1-08 to 1.
Contents
Operator Display
DIGITAL OPERATOR JVOP-182
Power Up
Frequency Reference
(default)
REV
ALM
DRV FOUT
DRV
YEC_c
ommon
Description
This display screen allows the user to monitor and change the frequency reference while the drive is running. Refer
to The Drive and Programming Modes on page 97.
Note: The user can select the data displayed when the drive is first powered up with parameter o1-02.
This display shows the direction that has been selected when the drive is controlled by a REMOTE source.
When the drive is set for LOCAL, the user can switch between FWD and REV as shown below.
DIGITAL OPERATOR JVOP-182
Forward/Reverse
REV
ALM
DRV FOUT
DRV
- Forward rotation
- Reverse rotation
Note: For applications that should not run in reverse (fans, pumps, etc.), set parameter b1-04 = 1 to prohibit the
motor from rotating in reverse.
Drive Mode
REV
Output Current
Display
REV
Drive Mode
REV
Monitor Display
ALM
DRV FOUT
DRV
ALM
Shows the data that selected for display by the user in parameter o1-01. The default setting displays drive output
voltage (o1-01 = 106). Refer to o1: Digital Operator Display Selection on page 450.
DRV FOUT
DRV
REV
DRV FOUT
DRV
Output Voltage
Reference
(default)
ALM
DRV FOUT
DRV
FOUT
Start-Up Programming
& Operation
Output Frequency
Display
ALM
YEC_
common
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
97
Contents
Operator Display
ALM
REV
Verify Menu
DRV
FOUT
ALM
Programming
Mode
REV
Setup Group
DRV
FOUT
REV
DRV
Programming
Mode
REV
DRV
Frequency Reference
REV
YEC_
common
ALM
FOUT
Drive Mode
Lists all parameters that have been edited or changed from default settings.
Changes: Verify Menu on page 99.
FOUT
Auto-Tuning Mode
YEC_
common
ALM
Parameter Setting
Mode
Description
DRV FOUT
DRV
YEC_
common
ALM
Figure 4.5 illustrates how to change the frequency reference from F 0.00 (0 Hz) to F 6.00 (6 Hz) while in the Drive
Mode. This example assumes the drive is set to LOCAL.
Figure 4.5
Frequency reference
display at power up
ALM
REV
DRV FOUT
DRV
REV
DRV FOUT
DRV
ALM
YEC_TMonly
Figure 4.5 Setting the Frequency Reference while in the Drive Mode
Note: The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is
entered. This feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency
reference as soon as changes are made without requiring the ENTER key, set o2-05 to 1.
98
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Display/Result
DIGITAL OPERATOR JVOP-182
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Press the
or
Press the
Press
Press
Press
Press the
Press
or
two times.
or
to view the current setting value (10.0 s). Left digit flashes.
12.
ALM
DRV FOUT
DRV
Press
Press
REV
Start-Up Programming
& Operation
1.
REV
Press the
ALM
DRV FOUT
DRV
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
99
Display/Result
DIGITAL OPERATOR JVOP-182
1.
2.
Press
3.
Press
or
Press the
ALM
DRV FOUT
DRV
to enter the list of parameters that have been edited from their original default settings.
REV
or
100
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Figure 4.6
DIGITAL OPERATOR JVOP-182
REV
ALM
DRV FOUT
DRV
REV
Frequency reference
appears when
powered up
DRV
ALM
FOUT
Press until
appears
DIGITAL OPERATOR JVOP-182
REV
<1>
DRV
REV
DRV
ALM
YEC_TMonly
FOUT
ALM
FOUT
Parameter Display
REV
DRV
REV
DRV
DRV
DRV
<2>
Operator
<2>
ALM
ALM
FOUT
REV
FOUT
REV
Control Circuit
Terminal
<2>
ALM
FOUT
ALM
FOUT
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
Name
Parameter
E1-09
b1-01
E1-13
Base Voltage
b1-02
E2-01
b1-03
E2-11
C1-01
Acceleration Time 1
E5-01
C1-02
Deceleration Time 1
E5-02
C6-01
E5-03
C6-02
E5-04
d1-01
Frequency Reference 1
E5-05
d1-02
Frequency Reference 2
E5-06
d1-03
Frequency Reference 3
E5-07
d1-04
Frequency Reference 4
E5-09
d1-17
E5-24
E1-01
H4-02
E1-04
H4-05
E1-05
Maximum Voltage
L1-01
E1-06
Base Frequency
L3-04
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Start-Up Programming
& Operation
101
The operation can be switched between LOCAL and REMOTE either by using the LO/RE key on the digital operator or
a digital input.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Display/Result
YEC_c
ommon
REV
REV
2.
Press
. The LO/RE light will light up. The drive is now in LOCAL.
key again.
YEC_
common
ALM
DRV FOUT
DRV
ALM
DRV FOUT
DRV
ESC
LO
RE
RESET
ENTER
RUN
STOP
102
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.4
Start-Up Flowcharts
The flowcharts in this section summarize basic steps required to start the drive. Use the flowcharts to determine the most
appropriate start-up method for a given application. The charts are intended as a quick reference to help familiarize the
user with start-up procedures.
Flowchart
Subchart
Objective
Page
103
A-1
104
A-2
High-performance operation using Open Loop Vector (OLV) or Closed Loop Vector (CLV) motor control
105
A-3
106
Note: To set up the drive using one of the Application Presets, refer to Application Selection on page 108.
START
Install and wire the drive as explained in Chapters 1, 2, and 3
Application Presets
A1-06 used ?
YES
NO
Refer to
Application
Selection section
Start-Up Programming
& Operation
Control Mode
A1-02 =
0: V/f
1: V/f w/PG
To
Flowchart A-1
2: OLV
3: CLV
5: OLV/PM
6: AOLV/PM
7: CLV/PM
To
Flowchart A-3
To
Flowchart A-2
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
103
From
Flowchart
A
Is there a
PG encoder
on the motor?
YES
NO
Set or verify the V/f pattern settings E1-.
Set or verify the V/f pattern
settings E1-.
Enter the number of motor poles to E2-04 (or E4-04 for motor 2).
Energy Savings
(b8-01 = 1) or
Speed Estimation Speed Search
(b3-24 = 1) enabled
when b3-01 = 1
or L2-01 = 1,2 ?
NO
YES
Perform Rotational
Auto-Tuning for V/f Control
(T1-01 = 3)
YES
Is the motor cable longer than
50 meters?
NO
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Return to
Flowchart
A
Figure 4.8 Simple Motor Setup with Energy Savings or Speed Search
104
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
From
Flowchart
A
YES
NO
NO
YES
<2>
YES
Perform Stationary
Auto-Tuning 2 (T1-01 = 4)
Perform Rotating
Auto-Tuning (T1-01 = 0)
NO
Perform Stationary
Auto-Tuning 1 (T1-01 = 1)
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Is there a PG
encoder on the
motor?
NO
YES
Should the
drive set ASR gain
automatically?
YES
NO
Start-Up Programming
& Operation
NO
YES
4
Run the machine and check for desired
operation.
Return to
Flowchart
A
<1> The load must be decoupled from the motor to properly perform Rotational Auto-Tuning.
<2> Rotational Auto-Tuning can still be performed if the load is 30% or less, though Stationary Auto-Tuning will probably yield better control
performance.
<3> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<4> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB Ride-Thru function.
Figure 4.9 Flowchart A2: High Performance Operation Using OLV or CLV
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
105
From
Flowchart
A
YES
NO
Perform PM Stationary
Auto-Tuning (T2-01 = 1)
<1>
NO
YES
Perform PM Stationary
Auto-Tuning for Stator
Resistance (T2-01 = 2)
Run the motor without load; check the rotation direction and
operation.Verify external signal commands to the drive work as desired.
Is there a PG
encoder on the
motor?
NO
YES
YES
Should the drive set ASR gain
automatically?
NO
NO
YES
Return to
Flowchart
A
<1> Enter the motor code to E5-01 when using a Yaskawa PM motor (SMRA Series, SSR1 Series, and SST4 Series). If using a motor from another
manufacturer, enter FFFF.
<2> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<3> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward and the KEB Ride-Thru function.
Figure 4.10 Operation with Permanent Magnet Motors
106
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.5
Description
Ensure the power supply voltage is correct:
200 V class: 3-phase 200 to 240 Vac 50/60 Hz
400 V class: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.
Drive output terminals and motor
terminals
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
No.
Name
Normal Operation
YEC_co
mmon
Fault
YEC_
common
REV
DRV FOUT
DRV
REV
Description
ALM
is lit.
ALM
ALM
DRV FOUT
DRV
Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 310
for more information and possible solution.
and
are lit.
Start-Up Programming
& Operation
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
107
4.6
Application Selection
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to
values appropriate for the application that was selected. In addition, the parameters most likely to be changed are
assigned to the group of User Parameters, A2-01 through A2-16. User Parameters are part of the Setup Group, and
provide quicker access to by eliminating the need to scroll through multiple menus.
An Application Preset can either be selected from the Application Selection display in the Setup Group (Refer to
Simplified Setup Using the Setup Group on page 100) or in parameter A1-06. The following presets can be selected:
Note: An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to
initialize the drive by setting A1-03 to 2220 or 3330 prior to selecting an Application Preset.
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change
the I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
No.
A1-06
Parameter Name
Setting Range
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist
7: Crane
Application Presets
Default
Name
Control Method Selection
Default Setting
0: V/f Control
b1-04
1: Reverse Prohibited
C1-01
Acceleration Time 1
1.0 s
C1-02
Deceleration Time 1
1.0 s
C6-01
Duty Rating
1: Normal Duty
E1-03
0FH
E1-07
30.0 Hz
E1-08
50.0 V
L2-01
1: Enabled
L3-04
1: Enabled
Parameter Name
Frequency Reference Selection
No.
E1-08
Parameter Name
Mid Output Frequency Voltage
b1-02
E2-01
b1-04
H1-05
C1-01
Acceleration Time 1
H1-06
C1-02
Deceleration Time 1
H1-07
E1-03
L5-01
E1-07
108
Parameter Name
Default Setting
A1-02
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Duty Rating
0: Heavy Duty
L3-04
1: Enabled
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
No.
Parameter Name
C1-02
Deceleration Time 1
b1-01
E2-01
b1-02
L3-04
C1-01
Acceleration Time 1
Parameter Name
Default Setting
0: V/f Control
1: Reverse Prohibited
b1-04
C6-01
Duty Selection
1: Normal Duty
E1-03
0FH
E1-07
30.0 Hz
E1-08
50.0 V
L2-01
1: Enabled
L3-04
1: Enabled
Parameter Name
No.
Parameter Name
b1-01
E1-07
b1-02
E1-08
b1-04
E2-01
b3-01
H1-05
C1-01
Acceleration Time 1
H1-06
C1-02
Deceleration Time 1
H1-07
E1-03
L5-01
Default Setting
0: V/f Control
b1-04
1: Reverse Prohibited
b1-17
C6-01
Duty Rating
1: Normal Duty
C6-02
3: 8.0 kHz
H2-03
L2-01
2: CPU Power Active - Drive will restart if power returns prior to control power
supply shut down.
L8-03
L8-38
Parameter Name
No.
d2-02
b1-02
E1-03
b1-03
E1-04
b1-04
E2-01
C1-01
Acceleration Time 1
H3-11
C1-02
Deceleration Time 1
H3-12
C6-02
L2-01
d2-01
o4-12
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
b1-01
Start-Up Programming
& Operation
No.
A1-02
109
Parameter Name
Default Setting
0: V/f Control
b1-04
1: Reverse Prohibited
C1-01
Acceleration Time 1
5.0 s
C1-02
Deceleration Time 1
5.0 s
C6-01
Duty Rating
0: Heavy Duty
E1-03
0FH
L2-01
1: Enabled
L3-04
1: Enabled
Parameter Name
No.
Parameter Name
E1-03
b1-02
E1-07
b1-04
E1-08
C1-01
Acceleration Time 1
E2-01
C1-02
Deceleration Time 1
Parameter Name
Default Setting
b1-01
0: Operator
b6-01
3.0 Hz
b6-02
0.3 s
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Duty Rating
0: Heavy Duty
C6-02
2: 5 kHz
d1-01
Frequency Reference 1
6.0 Hz
d1-02
Frequency Reference 2
30.0 Hz
d1-03
Frequency Reference 3
60.0 Hz
E1-03
0FH
H2-01
5: Frequency Detection 2
H2-02
L2-03
0.3 s
L3-04
0: Disabled
L4-01
2.0 Hz
L4-02
0.0 Hz
L6-01
L6-02
2%
L6-03
0.5 s
L8-05
1: Enabled
L8-07
1: Enabled
L8-38
1: Enabled below 6 Hz
L8-41
110
Parameter Name
No.
d1-02
Parameter Name
A1-02
Frequency Reference 2
b1-01
d1-03
Frequency Reference 3
b6-01
E1-08
b6-02
H2-01
C1-01
Acceleration Time 1
L1-01
C1-02
Deceleration Time 1
L4-01
C6-02
L6-02
d1-01
Frequency Reference 1
L6-03
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Notes on Controlling the Brake when Using the Hoist Application Preset
Prevent accidental Brake Release during Baseblock
The hoist application selection uses the frequency detection function for controlling the brake.
Although the drive output will be shut off, the drive still maintains the frequency reference if the Run command remains
active when an external Baseblock command is given (H1- = 8 or 9). Disable the frequency detection during
baseblock by setting parameter L4-07 = 0 to prevent the brake remaining open while the drive is in baseblock.
Controlling the Brake in Closed Loop Vector Control
For hoist applications using Closed Loop Vector Control, Yaskawa recommends setting the During frequency output
signal to a digital output (H2-01 = 37 for terminal M1-M2) in order to control the brake. This way, the brake will always
close during baseblock, and the setting of parameter L4-07 as described above will not affect brake control.
Brake Control During Safe Disable Input
If the Safe Disable input is triggered, the drive output will shut off and the frequency reference will reset to 0. The brake
will also close, regardless if the Run command is active. The Run command must be cycled before the drive can restart.
Related Parameter Settings
The table below shows the parameter settings needed when using output terminals M1-M2 as brake control output.
Parameter
Setting
Comment
H2-01
L4-01
L4-02
L4-07
b2-01
0.1 to 0.5 Hz
H2-01
37
<1> This is the setting recommended when using Open Loop Vector Control. If using V/f Control, set the level as the motor rated slip frequency
plus 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend to slip. Make sure this value is greater
than the minimum output frequency and greater than the value of L4-02, as shown in the diagram below. If set too high, however, there may be
a jolt at start.
<2> Hysteresis for Frequency detection 2 can be adjusted by the Frequency detection width (L4-02) between 0.0 and 0.5 Hz. If the load slips during
stop, make changes in steps of 0.1 Hz until the load no longer slips.
Figure 4.11
L4-01
L4-02
Output
frequency
Frequency
Dectection 2
time
ON
YEC_TM
only
OFF
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Function
Frequency Detection 2 Digital Output
(for brake control)
111
Drive
Holding brake
auxilary relay coil
MA
UP
Safety
Circuit
MB
S1 Forward Run
DOWN
MC
S2 Reverse
Run
Fast/Slow
BR
YEC_TM
only
Fault Contact
S6 Multi-speed
step 2
M1
SC
M2
Frequency Detect 2
or During Frequency
Output
The brake should release just a bit after the Run command is issued, allowing the motor to build up torque. If using the
V/f, V/f w PG or OLV control modes and the Frequency detection 2 signal controls the brake, the motor can be given
time to build up torque by setting the brake release level in parameter L4-01. Additionally, DC Injection Braking at
start can be applied. If using CLV or CLV/PM and the During frequency output signal controls the brake, initial
excitation should be enabled. Set the initial excitation time to parameter b2-03.
The time chart below gives a an example sequence.
Figure 4.13
S1-SC
UP
S6-SC
Fast/Slow
OFF
ON
OFF
ON
b6-02
Input
d1-03
Output frequency
0
d1-01
b2-04
b6-01
Time
DC Injection braking
b2-01 (Zero speed level) or E1-09 (Min. output frequency) <1>
Output
M1-M2
Frequency Detection 2
(H2-01 = 05)
YEC_TM
only
OFF
ON
Holding brake
Closed Open
Closed
<1> The drive brakes at the frequency set to b2-01 or E1-09, whichever value is higher.
Figure 4.13 Holding Brake Time Chart (V/f, V/f w/PG, OLV)
Figure 4.14
S1-SC
UP
S6-SC
Fast/slow
OFF
ON
OFF
ON
Input
d1-03
YEC_TM
only
L4-01
During Run 2
(H2-01 = 37)
ON
Time
Zero speed control
b2-01 (Zero speed level) or E1-09 (Min. output frequency) <1>
OFF
Open
Closed
Output
M1-M2
d1-01
Output frequency
0
Holding brake
Closed
b2-04
<1> The drive brakes at the frequency set to b2-01 or E1-09, whichever value is higher.
Figure 4.14 Holding Brake Time Chart (CLV)
112
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Default Setting
A1-02
Control Mode
0: V/f Control
b1-01
0: Operator
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
0: Heavy Duty
C6-02
2: 5 kHz
d1-01
Frequency Reference 1
6.0 Hz
d1-02
Frequency Reference 2
30.0 Hz
d1-03
Frequency Reference 3
60.0 Hz
H1-05
3: Multi-Step Speed 1
H1-06
4: Multi-Step Speed 2
H2-02
L3-04
0: Disabled
L8-05
1: Enabled
L8-07
L8-38
1: Enabled below 6 Hz
L8-41
Parameter Name
No.
Frequency Reference 3
C1-01
Acceleration Time 1
E2-01
C1-02
Deceleration Time 1
H1-05
C6-02
H1-06
d1-01
Frequency Reference 1
H2-01
d1-02
Frequency Reference 2
L1-01
Start-Up Programming
& Operation
d1-03
Parameter Name
b1-01
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
113
4.7 Auto-Tuning
4.7
Auto-Tuning
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of AutoTuning used differs further based on the control mode and other operating conditions. Refer to the tables below to select
the type of Auto-Tuning that bests suits the application. Directions on how to execute Auto-Tuning are listed in Start-Up
Flowcharts on page 103.
Note: The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set to A1-02. If the control
mode is for an induction motor, the Auto-Tuning parameters for PM motors will not be available. If the control mode is for a PM
motor, the Auto-Tuning parameters for induction motors will not be available. Inertia Tuning and ASR Gain Tuning parameters
and setting options will be visible only when the drive is set for operation with Closed Loop Vector or CLV/PM.
Setting
Rotational Auto-Tuning
Control Mode
V/f
V/f w/PG
OLV
CLV
T1-01 = 0
Motor can be decoupled from the load and rotate freely while AutoTuning is performed.
Motor and load can not be decoupled but the motor load is below 30%.
Rotational Auto-Tuning gives the most accurate results, and is therefore
highly recommended if possible.
N/A
N/A
YES
YES
Stationary Auto-Tuning 1
T1-01 = 1
Motor and load can not be decoupled and the load is higher than 30%.
A motor test report listing motor data is not available.
Automatically calculates motor parameters needed for vector control.
N/A
N/A
YES
YES
Stationary Auto-Tuning 2
T1-01 = 4
Motor and load can not be decoupled and the load is higher than 30%.
A motor test report is available. Once the no-load current and the rated
slip have been entered, the drive calculates and sets all other motorrelated parameters.
N/A
N/A
YES
YES
T1-01 = 2
The drive is used in V/f Control and other Auto-Tuning selections not
possible.
Drive and motor capacities differ.
Tunes the drive after the cable between the drive and motor has been
replaced with a cable over 50 m long. Assumes Auto-Tuning has already
been performed.
Should not be used for any vector control modes unless the motor cable
has changed.
YES
YES
YES
YES
T1-01 = 3
YES
YES
N/A
N/A
Table 4.20 lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting AutoTuning. The information needed is usually listed on the motor nameplate or in the motor test report provided by the
motor manufacturer. Also refer to page 104 and 105 for details on Auto-Tuning process and selections.
Table 4.20 Auto-Tuning Input Data
Tuning Type (T1-01)
Input Value
Input
Parameter
Unit
0
Standard
1
Stationary 1
2
Line-to-Line
Resistance
3
Rotational for V/f
Control
4
Stationary 2
YES
T1-02
kW
YES
YES
YES
YES
T1-03
Vac
YES
YES
N/A
YES
YES
T1-04
YES
YES
YES
YES
YES
T1-05
Hz
YES
YES
N/A
YES
YES
T1-06
YES
YES
N/A
YES
YES
T1-07
r/min
YES
YES
N/A
YES
YES
T1-08
YES <1>
YES <1>
N/A
N/A
YES <1>
T1-09
N/A
YES
N/A
N/A
YES
T1-10
Hz
N/A
N/A
N/A
N/A
YES
T1-11
N/A
N/A
N/A
YES
N/A
114
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1- and E5- when a PM motor is used. In Closed Loop
Vector Control, the Auto-Tuning process will also set some F1- parameters for speed feedback detection.
Table 4.21 Types of Auto-Tuning for Permanent Magnet Motors
Type
Setting
T2-01 = 0
PM Stationary Auto-Tuning
Control Mode
OLV/PM
AOLV/PM
CLV/PM
YES
YES
YES
T2-01 = 1
YES
YES
YES
T2-01 = 2
Useful to tune the drive when the motor data were set up manually or by
motor code and the cable is longer than 50 m. Should also be performed if
the cable has changed after earlier tuning.
YES
YES
YES
T2-01 = 3
N/A
N/A
YES
Table 4.22 lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting AutoTuning. The information needed is usually listed on the motor nameplate or in the motor test report provided by the
motor manufacturer. Also refer to page 106 for details on the tuning mode selection and the tuning process.
Table 4.22 Auto-Tuning Input Data
Tuning Type (T2-01)
Input Value
Input
Parameter
Unit
Control Mode
A1-02
5, 6, 7
6, 7
6, 7
5, 6, 7
Motor Code
T2-02
<1>
<1>
<1>
<2>
<2>
<2>
<2>
2
Phase
Resistance
1
Stationary
3
Z-Pulse
Offset
Motor Type
T2-03
N/A
N/A
N/A
YES
YES
N/A
N/A
T2-04
kW
N/A
YES
YES
YES
YES
N/A
N/A
T2-05
Vac
N/A
YES
YES
YES
YES
N/A
N/A
T2-06
N/A
YES
YES
YES
YES
YES
N/A
T2-07
Hz
N/A
YES
N/A
YES
N/A
N/A
N/A
N/A
T2-08
N/A
YES
YES
YES
YES
N/A
T2-09
r/min
N/A
N/A
YES
N/A
YES
N/A
N/A
T2-10
YES
YES
YES
N/A
N/A
N/A
N/A
d-axis inductance
T2-11
mH
YES
YES
YES
N/A
N/A
N/A
N/A
q-axis inductance
T2-12
mH
YES
YES
YES
N/A
N/A
N/A
N/A
T2-13
mVs/rad (el.)
YES
YES
YES
N/A
N/A
N/A
N/A
T2-14
mVmin (mech.)
YES
YES
YES
N/A
N/A
N/A
N/A
T2-15
N/A
N/A
N/A
YES
YES
N/A
N/A
T2-16
YES <4>
N/A
YES <4>
N/A
YES <4>
N/A
N/A
Z Pulse Offset
T2-17
deg (mech.)
YES <4>
N/A
YES <4>
N/A
YES <4>
N/A
N/A
Start-Up Programming
& Operation
0
Parameter Calculation
<1> Input the motor code when using the YASKAWA motor. Select FFFF when using the motor by other manufacturers.
<2> T2-02 is not available.
<3> Only parameter T2-13 or T2-14 has to be input. Select one and leave the other empty.
<4> Input data is needed for CLV/PM only.
Inertia Tuning can be performed when the drive is using Closed Loop Vector control for either IM or PM motors. Inertia
Tuning automatically calculates load and motor inertia, and optimizes settings related to the KEB Ride-Thru function
(KEB 2) and Feed Forward control.
ASR Gain Auto-Tuning performs the same operation as Inertia Tuning, but also optimizes speed control loop settings.
Table 4.23 Inertia and Speed Control Loop Tuning
Type
Setting
IM Motor
PM Motor
Inertia Tuning
T1-01 = 8
T2-01 = 8
Lets the motor rotate at a certain speed and applies a test signal. The response to the test
signals are analyzed, and adjustments are made to parameters controlling the Feed
Forward and KEB Ride-Thru functions (KEB 2, L2-29 = 1).
T1-01 = 9
T2-01 = 9
Performs the same operation as Inertia Tuning, but also adjusts the ASR gain according
to the response to the test signal.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Control Mode
CLV
CLV/PM
YES
YES
YES
YES
115
4.7 Auto-Tuning
Table 4.24 explains that data that must be entered in order to perform the Inertia Tuning and ASR Gain Auto-Tuning.
Refer to Auto-Tuning for Permanent Magnet Motors on page 115 for details.
Table 4.24 Auto-Tuning Input Data
Tuning Type (T1-01 or T2-01)
Input Value
Input Parameter
Unit
8
Inertia Tuning
9
ASR Gain Tuning
T3-01
Hz
YES
YES
T3-02
rad
YES
YES
Motor inertia
T3-03
kgm2
YES
YES
T3-04
Hz
N/A
YES
Auto-Tuning Type
Digital Input
Rotational Auto-Tuning
Digital Output
Functions the same as during normal operation
Stationary Auto-Tuning 1
IM Motor
Stationary Auto-Tuning 2
PM Stationary Auto-Tuning
PM Stationary Auto-Tuning for Stator Resistance
Inertia Tuning
ASR Gain Auto-Tuning
116
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Stationary Auto-Tuning 1 and 2
Perform these tuning methods when using a vector control mode but Rotational Auto-Tuning cannot be performed.
Check the area around the motor to ensure that nothing will accidentally cause the motor to rotate during the AutoTuning process.
Use Stationary Auto-Tuning 1 when the motor test report is not available. If the motor test report is available, perform
Stationary Auto-Tuning 2 instead.
Perform when entering motor data manually while using motor cables longer than 50 m.
If the motor cables have been replaced with line over 50 m long after Auto-Tuning as already been performed, then
execute Stationary Auto-Tuning for line-to-line resistance.
Notes on Inertia Tuning and ASR Gain Auto-Tuning
WARNING! Electrical Shock Hazard. When executing Inertia Tuning or ASR Gain Auto-Tuning, voltage is applied to the motor even
before it rotates. Do not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock.
Both tuning methods must be performed with the machine connected to the motor but without load applied.
The motor will rotate during the Auto-Tuning process. Make sure the areas around the motor and connected machinery
are clear.
The drive will let the system rotate at a certain speed while superimposing a sine wave test signal. Make sure this
tuning process does not cause any problem or malfunction in the machine before using it.
Ensure the motor-mounted brake is fully released if installed.
Connected machinery should be allowed to rotate the motor.
A
DIGITAL OPERATOR JVOP-182
YEC_common
REV
B
ALM
DRV FOUT
DRV
A During Auto-Tuning
REV
DRV
ALM
ALM
FOUT
B Auto-Tuning Aborted
Start-Up Programming
& Operation
1.
2.
3.
4.
5.
6.
Press the
or
REV
ALM
DRV FOUT
DRV
Press
Press
Display/Result
<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1- = 16).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
117
4.7 Auto-Tuning
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in Selecting the Type of Auto-Tuning.
Step
1.
2.
3.
4.
5.
Press
Press
Press
Press
Press
Display/Result
6.
7.
Note: 1. For details on each setting, Refer to Parameter Settings during Induction Motor Auto-Tuning: T1 on page 119.
2. To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death
or serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in
improper operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Note: These instructions continue from Step 7 in Enter Data from the Motor Nameplate.
Step
1.
Display/Result
to confirm.
2.
Press
to activate Auto-Tuning.
flashes. The drive begins by injecting current into the motor for
about 1 min, and then starts to rotate the motor.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The
second digit indicates the type of Auto-Tuning being performed.
3.
118
REV
ALM
DRV FOUT
DRV
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
Name
Setting Range
Default
T1-00
1 or 2
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E3- and E4- for motor 2. Make sure that motor 2 is connected to the
drive for Auto-Tuning.
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used. Refer to Auto-Tuning for Induction Motors on page 114 for details on the
different types of Auto-Tuning.
No.
T1-01
Name
Setting Range
Default
Setting Range
Default
Start-Up Programming
& Operation
0.00 to 650.00 kW
Name
T1-02
Name
Setting Range
Default
T1-03 <1>
0.0 to 255.5 V
200.0 V
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
119
4.7 Auto-Tuning
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. For optimal performance in OLV or CLV, the motor
rated current should be between 50 and 100% of the drive rated current. Enter the current at the motor base speed.
No.
Name
Setting Range
Default
T1-04
E2-11 (E4-11)
Name
Setting Range
Default
T1-05
0.0 to 400.0 Hz
<1>
Name
Setting Range
Default
T1-06
2 to 48
Name
Setting Range
Default
T1-07
0 to 24000 r/min
<1>
Name
Setting Range
Default
T1-08
0 to 60000 ppr
<1>
Name
Setting Range
Default
T1-09 <1>
0 A to [T1-04]
(Max: 0 to 2999.9)
<1> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01.
The value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer
to Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
120
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
T1-10: Motor Rated Slip
Sets the rated slip for the motor.
The default setting displayed is the motor rated slip for a Yaskawa motor calculated from the output power set in T1-02.
Enter the data listed on the motor test report.
No.
Name
Setting Range
Default
T1-10
0.00 to 20.00 Hz
Name
Setting Range
Default
T1-11
0 to 65535 W
E2-11 (E4-11)
No.
T2-01
Name
Setting Range
Default
0 to 2 (OLV/PM, AOLV/PM)
0 to 3, 8, 9 (CLV/PM)
Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ by the
control mode that has been selected. Refer to E5: PM Motor Settings on page 207 for motor codes.
No.
Name
Setting Range
Default
T2-02
0000 to FFFF
Name
Setting Range
Default
T2-03
PM Motor Type
0, 1
0: IPM motor
1: SPM motor
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Selects the type of Auto-Tuning to be performed. Refer to Auto-Tuning for Permanent Magnet Motors on page 115 for
details on different types of Auto-Tuning.
121
4.7 Auto-Tuning
T2-04: PM Motor Rated Power
Specifies the motor rated power in kilowatts.
No.
Name
Setting Range
Default
T2-04
0.00 to 650.00 kW
Depending on o2-04
Name
Setting Range
Default
T2-05 <1>
0.0 to 255.0 V
200.0 V
<1> The setting range and default value shown here is for a 200 V class drive. These values double when using a 400 V class unit.
Name
Setting Range
Default
Depending on o2-04
Name
Setting Range
Default
T2-07
0.0 to 400.0 Hz
87.5 Hz
Name
Setting Range
Default
T2-08
2 to 48
Name
Setting Range
Default
T2-09
0 to 24000 r/min
1750 r/min
Name
Setting Range
Default
T2-10
0.000 to 65.000
Depending on T2-02
122
No.
Name
Setting Range
Default
T2-11
0.00 to 600.00 mH
Depending on T2-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.7 Auto-Tuning
T2-12: PM Motor q-Axis Inductance
Enter the q axis inductance per motor phase.
No.
Name
Setting Range
Default
T2-12
0.00 to 600.00 mH
Depending on T2-02
Name
Setting Range
Default
T2-13
0, 1
0: mV (r/min)
1: mV (rad/sec)
Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor
Induction Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.
Name
Setting Range
Default
T2-14
0.1 to 2000.0
Depending on T2-02
Name
Setting Range
Default
T2-15
0 to 120%
30%
No.
Name
Setting Range
Default
T2-16
0 to 60000 ppr
1024 ppr
Name
Setting Range
Default
T2-17
0.0 deg
Description
C5-01
N/A
YES
C5-17 (C5-37)
Motor Inertia
YES
YES
8
Inertia Tuning
9
Speed Control Loop (ASR) Tuning
C5-18 (C5-38)
YES
YES
L3-24
YES
YES
L3-25
YES
YES
n5-03
YES
YES
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Start-Up Programming
& Operation
Enter the number of pulses from the PG encoder per motor rotation. Set the actual number of pulses for one full motor
rotation.
123
4.7 Auto-Tuning
T3-01: Inertia Tuning Frequency Reference
Sets the frequency of the test signal applied to the motor during Inertia Tuning. Although this setting rarely needs to be
changed, increasing the value may be beneficial when working with high inertia loads.
No.
Name
Setting Range
Default
T3-01
0.1 to 20.0 Hz
3.0 Hz
Name
Setting Range
Default
T3-02
0.5 rad
Name
Setting Range
Default
T3-03
Motor Inertia
Depending on E2-11
Note: The display resolution depends on the rated output power of the drive after the Drive Duty has been set in parameter C6-01.
Drives with a maximum output up to 37 kW will display this value in units of 0.0001 kgm2. Drives with a maximum output 37 to
185 kW will display this value in units of 0.001 kgm2. Refer to A1000 Model Selection on page 29 for details.
124
No.
Name
Setting Range
Default
T3-04
0.1 to 50.0 Hz
10.0 Hz
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4.8
1.
DRV FOUT
DRV
REV
2.
Press the
ALM
DRV FOUT
DRV
REV
ESC
LO
RE
RESET
ENTER
RUN
STOP
Off
On
DIGITAL OPERATOR JVOP-182
DRV FOUT
DRV
REV
LO
RE
ESC
3.
Press
RESET
to give the drive a Run command. RUN will light and the motor will rotate at 6 Hz.
ALM
Start-Up Programming
& Operation
Step
RUN
ENTER
STOP
Off
On
Motor
4.
Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
Forward
5.
REV
6.
STOP to stop the motor. RUN flashes until the motor comes to a
ESC
LO
RE
RESET
ENTER
RUN
Flashing
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
ALM
DRV FOUT
DRV
STOP
Off
125
4.9
126
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
o2-03
A1-03
Parameter Name
Description
User Parameter
Default Value
Lets the user create a set of default settings for a User Initialization.
0: Saved/Not set
1: Set Defaults - Saves current parameter settings as the default values for a User Initialization.
2: Clear All - Clears the currently saved user settings. After saving the user parameter set value, the items of
1110 (User Parameter Initialize) are displayed in A1-03 (User Parameter Default Value).
Initialize Parameters
0 to 2
0 to 5550
Access Level
Selection
0 to 2
A2-01
to
A2-32
User Parameters
1 to 32
Parameters selected by the user are saved as User Parameters. This includes recently viewed parameters or parameters
specifically selected for quick access.
If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32. Parameters A2-01
through A2-16 must be manually selected by the user.
If A2-33 is set to 0, then recently viewed parameters will not be saved to the group of User Parameters. A2-
parameters are now available for manual programming.
b1-01 to
o-
A2-33
User Parameter
Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for
quick access. The most recently changed parameter is saved to A2-17. The second most recently changed parameter is
saved to A2-18.
0, 1
A1-01
Parameter
Name
Description
Start-Up Programming
& Operation
Setting
Range
No.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
127
Copy Function
Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive
supports the following copy options:
LED Operator (standard in all models)
The LED operator used to operate the drive also supports copying, importing, and verifying parameter settings. Refer
to o3: Copy Function on page 290 for details.
LCD Operator
The optional LCD operator also supports copying, importing, and verifying parameter settings. Refer to the manual
supplied with the LCD operator for instructions.
USB Copy Unit and CopyUnitManager
The copy unit is an external option connected to the drive to copy parameter settings from one drive and save those
settings to another drive. Refer to the manual supplied with the USB Copy Unit for instructions.
The CopyUnitManager is a PC software tool. It allows the user to load parameter settings from the Copy Unit onto a
PC, or from the PC onto a Copy Unit. This is useful when managing parameters for various drives or applications.
Refer to the manual supplied with the CopyUnitManager for instructions.
DriveWizard Plus
DriveWizard is a PC software tool for parameter management, monitoring, and diagnosis. DriveWizard can load, store,
and copy drive parameter settings. For details, refer to Help in the DriveWizard software.
128
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Checklist
Page
107
196
Check the items that correspond to the control mode being used.
WARNING! Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to
comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on
terminal S1 may cause the drive to start.
No.
Checklist
Page
Select the best V/f pattern according to the application and motor characteristics.
Example: If using a motor with a rated frequency of 60.0 Hz, set E1-03 to 1.
Perform Rotational Auto-Tuning for V/f Control if using Energy Saving functions.
114
Setup the PG feedback parameters correctly and make sure the encoder pulse counting direction is correct.
209
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
175
Open Loop Vector Control (A1-02 = 2) or Closed Loop Vector Control (A1-02=3)
9
119
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if possible.
175
121
12
121
13
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02.
175
Start-Up Programming
& Operation
121
15
Set the proportional gain for ASR speed control to C5-01 and the integral time to C5-02. Perform ASR Tuning if possible.
175
16
121
Checklist
Page
17
The
18
To give a Run command and frequency reference from the digital operator, press
102
20
If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/T1, V/T2, W/T3) or change
parameter b1-14.
107
21
Set the correct values for the motor rated current (E2-01, E4-01, E5-03) and motor protection (L1-01) to ensure motor thermal protection.
22
If the Run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE and be sure the LO/RE
light is out.
102
23
If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0 to 10 V) or the correct
current input signal level (4 to 20 mA or 0 to 20 mA).
137
24
137
25
When current input is used, switch the drives built-in DIP switch S1 from the V-side to I-side. Set the level for current signal used to H3-09
(set 2 for 4 to 20 mA, or 3 for 0 to 20 mA).
137
26
137
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
129
130
No.
Checklist
Page
27
If the frequency reference is supplied via one of the analog inputs, make sure the analog input produces the desired frequency reference. Make
the following adjustments if the drive does not operate as expected:
Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1, H3-11 for input A2, H3-07
for analog input A3) until the frequency reference value reaches the desired value.
Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2, H3-08 for
analog input A3) until the frequency reference value reaches the desired minimum value.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5
Parameter Details
5.1 A: INITIALIZATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 B: APPLICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 C: TUNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 D: REFERENCE SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 E: MOTOR PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 F: OPTION SETTINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 H: TERMINAL FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.8 L: PROTECTION FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.9 N: SPECIAL ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.10 O: OPERATOR RELATED SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.11 U: MONITOR PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
132
137
166
182
196
209
217
247
278
287
294
131
5.1 A: Initialization
5.1
A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
A1: Initialization
A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No.
Parameter Name
Setting Range
Default
A1-00
Language Selection
0 to 7
<1>
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
Parameter Name
Setting Range
Default
A1-01
0 to 2
Access is restricted to parameters A1-01, A1-04, A1-06, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all
A2 parameters cannot be modified.
If a digital input terminal programmed for Program lockout (H1- = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
If parameters are changed via serial communication, then it will not be possible to edit or change parameters settings
with the drives digital operator until an Enter command is issued to the drive from the serial communication.
A1-02: Control Method Selection
Selects the Control Method (also referred to as the control mode) the drive uses to operate the motor. If the drive is set
up to run two motors, then A1-02 determines the control mode for motor 1.
No.
Parameter Name
Setting Range
Default
A1-02
0, 1, 2, 3, 5, 6, 7
<1>
132
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.1 A: Initialization
Control Modes for Induction Motors (IM)
Setting 0: V/f Control for Induction Motors
V/f Control is for simple speed control and multiple motor applications with low demands to dynamic response or speed
accuracy. This control mode should be used when the motor parameters are unknown and Auto-Tuning cannot be
performed. The speed control range is 1:40.
Setting 1:V/f Control with PG Speed Feedback
For general-purpose applications that do not require high dynamic response but high speed accuracy. This mode should
be used if the motor parameters are unknown and Auto-Tuning cannot be performed. The speed control range is 1:40.
Setting 2: Open Loop Vector Control
For general, variable-speed applications with a speed control range of 1:120 that require precise speed control, quick
torque response, and high torque at low speed without using a speed feedback signal from the motor.
Setting 3: Closed Loop Vector Control
For general, variable-speed applications that requiring precise speed control down to zero speed, fast torque response, or
precise torque control. A speed feedback signal from the motor is required. The speed control range is up to 1:1500.
Control Modes for Permanent Magnet Motors (SPM or IPM)
Setting 5: Open Loop Vector Control for PM
Use this mode for variable torque applications and take advantage of the energy saving capabilities of a PM motor. Using
this mode, the drive can control an SPM or IPM motor with a speed range of 1:20.
Setting 6: Advanced Open Loop Vector Control for PM
This control mode can be used to operate an IPM motor for constant torque applications. Using High Frequency
Injection, a speed control range as high as 1:100 is possible. Refer to Control Mode Selection on page 30 for details.
Setting 7: Closed Loop Vector Control for PM
This mode can be used for high precision control of a PM motor in constant torque or variable torque applications. The
speed control range reaches 1:1500. A speed feedback signal is required.
A1-03: Initialize Parameters
No.
Parameter Name
Setting Range
Default
A1-03
Initialize Parameters
Drive parameters are reset to values selected by the user as User Settings. User Settings are stored when parameter o2-03
is set to 1: Set defaults.
Note: A user-initialization resets all parameters to a user-defined set of default values that were previously saved to the drive. To
clear the user-defined default values, set parameter o2-03 to 2.
Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as Forward run and
Reverse run, respectively. For more on digital input functions, refer to Setting 40, 41: Forward run, Reverse run
command for 2-wire sequence on page 224.
Setting 3330: 3-Wire Initialization
The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as Run, Stop,
and Forward/Reverse respectively. Also refer to digital input functions, Setting 0: 3-Wire Sequence on page 218.
Setting 5550: oPE04 Reset
If parameters on a certain drive have been edited and then a different terminal block is installed with different settings
saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the
terminal block memory, set A1-02 to 5550.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
133
Parameter Details
Resets parameters back to the original default values. After initialization, the setting for A1-03 automatically returns to 0.
5.1 A: Initialization
Notes on Parameter Initialization
The parameters shown in Table 5.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330.
Although the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application
preset is selected.
Table 5.1 Parameters not Changed by Drive Initialization
No.
Parameter Name
A1-00
Language Selection
A1-02
C6-01
Duty Selection
E1-03
E5-01
F6-08
L8-35
Installation Selection
o2-04
Drive/kVA Selection
Parameter Name
A1-04
Password
A1-05
Password Setting
Setting Range
Default
0000 to 9999
0000
The user can set a password for the drive to restrict access. The password is set to A1-05 and must be entered to A1-04 to
unlock parameter access. Until the correct password is entered, the following parameters cannot be viewed or edited: A101, A1-02, A1-03, A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set a new password. Here, the password set is 1234. An explanation
follows on how to enter the password to unlock the parameters.
Table 5.2 Setting the Password for Parameter Lock
Step
Display/Result
DIGITAL OPERATOR JVOP-182
1.
2.
3.
5.
Note: Because A1-05 is hidden, it will not be displayed by simply pressing the
7.
8.
9.
10.
134
Press the
Use
Press
ALM
DRV FOUT
DRV
4.
6.
REV
key.
05 flashes
key.
and
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.1 A: Initialization
Table 5.3 Check to see if A1-02 is locked (continuing from step 10 above)
Step
1.
Press
Display/Result
to display A1-02.
02 flashes
2.
3.
4.
Press
Press
and
Press
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
Step
1.
2.
Press
Press
Display/Result
4.
5.
6.
7.
8.
9.
10.
11.
Press
to scroll to A1-04.
Press
Press
Press
Use
Press
to display the value set to A1-02. If the first 0 blinks, parameter settings are unlocked.
and
to change the value if desired (though changing the control mode at this point is not typically done).
OLV
Note: Parameter settings can be edited after entering the correct password. Performing a 2-wire or 3-wire initialization resets the
password to 0000. Reenter the password to parameter A1-05 after drive initialization.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
135
Parameter Details
3.
5.1 A: Initialization
No.
Parameter Name
Setting Range
Default
A1-07
0 to 2
If a digital input is programmed for DWEZ enable/disable (H1- = 9F), DWEZ will be enabled when the input is
disabled.
Parameter Name
Setting Range
Default
A2-01 to A2-32
User Parameters 1 to 32
b1-01 to o2-08
<1> A1-06 determines how parameters edited by the user are saved to the list of Preferred Parameters, A2-01 through A2-32. Refer to Application
Selection on page 108 for details.
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2- parameters. If A1-01
is then set to 1, the access level can be restricted so that users can only set and refer to the specific parameters saved as
User Parameters.
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
No.
Parameter Name
Setting Range
Default
A2-33
0 or 1
Determined by A1-06
To manually select the parameters listed in the User Parameter group, set A2-33 to 0.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18,
and so on. User Parameters can be accessed using the Setup Mode of the digital operator.
136
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
5.2
b: Application
Parameter Name
Setting Range
Default
b1-01
0 to 4
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or
A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Table 5.5 for the
input used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
A1
A2
A3
Parameter Settings
Signal Level
Notes
Function Selection
Gain
Bias
0 to 10 Vd
H3-01 = 0
H3-01 = 1
H3-02 = 0
(Frequency Reference Bias)
H3-03
H3-04
H3-10 = 0
(Frequency Reference Bias)
H3-11
H3-12
H3-06 = 0
(Frequency Reference Bias)
H3-07
H3-08
0 to 10 Vd
H3-09 = 0
H3-09 = 1
0 to 10 Vd
H3-05 = 0
H3-05 = 1
Figure 5.1
Drive
Drive
A1 Analog Input 1
4 k
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A2 Analog Input 2
A3 Analog Input 3
A3 Analog Input 3
-V
-V
Parameter Details
2 k
Use the wiring example shown in Figure 5.1 for any other analog input terminals. When using input A2 make sure DIP
switch S1 is set for voltage input.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
137
5.2 b: Application
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 5.6 to set terminal A2 for current input.
Table 5.6 Analog Input Settings for Frequency Reference Using a Current Signal
Terminal
A2
Signal Level
Parameter Settings
Signal Level Selection
Function Selection
Gain
Bias
4 to 20 mA
H3-09 = 2
0 to 20 mA
H3-09 = 3
H3-10 = 0
(Frequency Bias)
H3-11
H3-12
Notes
Make sure to set DIP switch S1 on the
terminal board to I for current input.
Figure 5.2
DIP switch S1
V
Drive
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs.
Refer to Multi-Step Speed Selection on page 182 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications
This setting requires that the frequency reference is entered via the RS-485/422 serial communications port (control
terminals R+, R-, S+, S-). For instructions, see MEMOBUS/Modbus Communications on page 487.
Setting 3: Option card
This setting requires that the frequency reference is entered via an option board plugged into connector CN5-A on the
drives control board. Consult the manual supplied with the option board for instructions on integrating the drive with the
communication system.
Note: If the frequency reference source is set for an option PCB (b1-01 = 3), but an option board is not installed, an OPE05 Operator
Programming Error will be displayed on the digital operator and the drive will not run.
If b1-01 is set to 4, the frequency reference must be provided by a pulse train signal to terminal RP. Follow the directions
below to make sure the pulse signal is working properly.
Verifying Pulse Train is Working Properly
Parameter b1-02 determines the Run command source 1 in the REMOTE mode.
No.
Parameter Name
Setting Range
Default
b1-02
0 to 3
Setting 0: Operator
When the b1-02 = 0, the LO/RE light will switch on and the RUN key will enter a Run command to start the drive.
138
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Setting 1: Control Circuit Terminal
This setting requires that the Run and Stop commands are entered from the digital input terminals. The following
sequences can be used:
2-wire sequence 1:
Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-03 = 2220, presets the terminals S1 and S2 to
these functions. This is the default setting of the drive. Also refer to Setting 40, 41: Forward run, Reverse run
command for 2-wire sequence on page 224.
2-wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Also refer to Setting 42, 43: Run and direction command for 2-wire sequence 2
on page 224.
3-wire sequence:
Three inputs (Start-Stop-FWD/REV). Initialize the drive by setting A1-03 = 3330 presets the terminals S1, S2, and S5
to these functions. Also refer to Setting 0: 3-Wire Sequence on page 218.
Setting 2: MEMOBUS/Modbus Communications
To issue a Run command via serial communications, set b1-02 to 2 and connect the RS-485/422 serial communication
cable to control terminals R+, R-, S+, and S- on the removable terminal block. For instructions, Refer to MEMOBUS/
Modbus Communications on page 487.
Setting 3: Option Card
To issue the Run command via the communication option board, set b1-02 to 3 and plug a communication option board
into the CN5-A port on the control PCB. Refer to the manual supplied with the option board for instructions on
integrating the drive into the communication system.
Note: If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the
digital operator and the drive will not run.
Parameter Name
Setting Range
Default
b1-03
0 to 3
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed
Control or Short Circuit Braking, depending on the selected control mode. Refer to b2-01: DC Injection Braking Start
Frequency on page 144 for details.
Setting 1: Coast to stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled
deceleration) to stop. The stopping time is determined by the inertia and the friction in the driven system.
Figure 5.3
Run
command
ON
Output
frequency
OFF
Motor speed
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by
the active deceleration time. The default deceleration time is set to parameter C1-02.
139
5.2 b: Application
Setting 2: DC Injection Braking to stop
When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time
(L2-03). Once the minimum baseblock time has expired, the drive will brake the motor by injecting DC current into the
motor windings. The stopping time is significantly faster than when compared with simply coasting to stop. The level of
current used for DC Injection Braking is set by parameter b2-02 (default = 50%).
Note: This function is not available in the control modes for PM motors (A1-02 = 5, 6, 7).
Figure 5.4
Run
command
ON
OFF
DC Injection Braking
with the current set in
b2-02
Output
frequency
Motor speed
Motor coasts
Minimum Baseblock
Time (L2-03)
The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the
Run command is removed. It can be calculated by:
DC Injection brake time
Figure 5.5
b2-04
10%
100%
(Maximum output
frequency)
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. If a Run command
is input before the time t (value of C1-02) has expired, the drive will not start. A Run command activated during time t
must be cycled after t has expired in order to start the drive.
Figure 5.6
Run command
Output
frequency
ON
OFF
ON
OFF
ON
140
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration
time.
Figure 5.7
Output frequency
when Stop command
was entered
Min output
frequency
100%
(Max output
frequency)
Parameter Name
Setting Range
Default
b1-04
0 or 1
Parameter Name
Setting Range
Default
b1-05
0 to 3
The drive adjusts the motor speed following the speed reference, even if the frequency reference is below the setting of
parameter E1-09. When the Run command is removed and the motor speed is smaller than the setting of b2-01, Zero
Speed Control (not position lock) is performed for the time set in parameter b2-04 before the drive output shuts off.
Figure 5.8
Run
Command
OFF
ON
common_TMonly
E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.
Motor
Speed
Parameter Details
Zero Speed
Control
Zero Speed
Control
b2-01 Zero
Speed Level
b2-03
Zero Speed Time at Start
E1-09
b2-04
Zero Speed Time at Stop
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
141
5.2 b: Application
Setting 1: Coast to Stop
The motor is started first when the frequency reference exceeds the setting of parameter E1-09. Once the motor is
running and the frequency reference falls below E1-09 the drive output is shut off and the motor coasts. When the motor
speed falls below the zero speed level set in parameter b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 5.9
OFF
Run
Command
ON
E1-09 Min.
Frequency
Frequency
reference
Zero Speed
Control
b2-01 Zero
Speed Level
Motor
Speed
common_TMonly
Motor
Coasts
b2-03
Zero Speed Time at Start
b2-04
Zero Speed Time at Stop
Whenever a Run command is active and the frequency reference is smaller than the value of parameter E1-09, the drive
runs the motor at the speed set in E1-09. When the Run command is removed, the drive decelerates the motor. As soon as
the motor speed reaches the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 5.10
OFF
Run
Command
ON
E1-09 Min.
Frequency
common_TMonly
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.
Run at
E1-09
Run at
E1-09
Zero Speed
Control
b2-01 Zero
Speed Level
Motor
Speed
b2-04
Zero Speed Time at Stop
b2-03
Zero Speed Time at Start
The drive applies Zero Speed Control whenever the frequency reference setting is below the value of parameter E1-09.
When the Run command is removed, Zero Speed Control is activated for the time set in b2-04, even if it was already
active before.
Figure 5.11
OFF
Run
Command
ON
E1-09 Min.
Frequency
common_TMonly
Frequency
reference
Zero
IM: Initial Excitation Speed
PM: Zero Spd. Contr. Control
Zero Speed
Control
b2-01 Zero
Speed Level
Motor
Speed
b2-03
Zero Speed Time at Start
E1-09
b2-04
Zero Speed Time at Stop
Name
Setting Range
Default
b1-06
0 or 1
The state of a digital input is read once. If the state has changed, the input command is immediately processed. With this
setting the drive responds more quickly to digital inputs, but a noisy signal could cause erroneous operation.
142
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Setting 1: Read twice
The state of a digital input is read twice. Only if the state does not change during the double reading, the input command
is processed. This reading process is slower but more resistant against noisy signals.
b1-07: LOCAL/REMOTE Run Selection
The drive has three separate control sources that can be switched using digital inputs (H1- = 1 (LOCAL/REMOTE
Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator. Refer to Setting 1: LOCAL/REMOTE
selection on page 218, Refer to Setting 2: External reference 1/2 selection on page 219 and Refer to o2-01: LO/RE
(LOCAL/REMOTE) Key Function Selection on page 288 for details.
LOCAL: Digital operator. The digital operator is used to set the frequency reference and Run command.
REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run
command may already be present at the location the source was switched to. Parameter b1-07 can be used to determine
how the Run command is treated in this case.
No.
Parameter Name
Setting Range
Default
b1-07
0 or 1
When the Run command source is different in the old and new source (e.g., the old source was the terminals and the new
source is serial communication), and the Run command is active at the new source as the switch over occurs, the drive
will not start or will stop operation if it was running before. The Run command has to be cycled at the new source in
order to start the drive again.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was running before.
WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating
machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
No.
Parameter Name
Setting Range
Default
b1-08
0 to 2
Parameter Details
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and AutoTuning Mode). If required by the application, set b1-08 to allow the drive to run while in the Programming Mode.
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
Parameter Name
Setting Range
Default
b1-14
0 or 1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
143
5.2 b: Application
Setting 0: Standard phase order
Setting 1: Switched phase order
Parameter Name
Setting Range
Default
b1-15
0 to 4
Parameter Name
Setting Range
Default
b1-16
0 to 3
Parameter Name
Setting Range
Default
b1-17
0 or 1
If an external Run command is active when the drive is powered up, then the drive will start to operate the motor as soon
as it gets ready for operation (i.e., once the internal start up process is complete).
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will
begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe
prior to powering up the drive. Failure to comply may cause serious injury.
Name
Setting Range
Default
b2-01
0.0 to 10.0 Hz
Determined by A1-02
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG and OLV (A1-02 = 0, 1, 2)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at stop. Once the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
Figure 5.12
DC Injection
Braking
Time
b2-04
Figure 5.12 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as
the frequency falls to the value set to E1-09.
144
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
OLV/PM and AOLV/PM (A1-02 = 5, 6)
For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. Once the output
frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC
Injection Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after ShortCircuit Braking is complete.
Figure 5.13
Short Circuit
Braking
DC Injection
Braking
Output
frequency
Time
b2-13
b2-04
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop.
Once the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter
b2-04 if b1-05 = 0.
Figure 5.14
Zero Speed
Control
Output
frequency
Time
b2-04
Name
Setting Range
Default
b2-02
0 to 100%
50%
Name
Setting Range
Default
b2-03
0.00 to 10.00 s
0.00 s
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), DC Injection or Speed Search should
be used to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur.
Name
Setting Range
Default
b2-04
0.00 to 10.00 s
Determined by A1-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should
only be increased to the level necessary to hold the motor shaft.
145
5.2 b: Application
b2-08: Magnetic Flux Compensation Value
Sets the magnetic flux compensation at start as a percentage of the no-load current value (E2-03). This function allows
better more flux to develop, making it easier to start machines that require high starting torque or motors with a large
rotor time constant.
No.
Name
Setting Range
Default
b2-08
0 to 1000%
0%
When a Run command is issued, the DC current level injected into the motor changes linearly from the level set to b2-08
to E2-03 within the time set to b2-03.
Figure 5.15
Output frequency
common_TMonly
b2-08
E2-03
Magnetizing Current
Reference
b2-03
Time
Note that the level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor
rated current, whichever value is smaller.
Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to b2-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.
Name
Setting Range
Default
b2-12
0.00 to 25.50 s
0.00 s
Note: Short Circuit Braking cannot prevent a PM motor from being rotated by an external force. To prevent the load from rotating the
motor, use DC Injection.
Name
Setting Range
Default
b2-13
0.00 to 25.50 s
0.50 s
146
No.
Name
Setting Range
Default
b2-18
0.0 to 200.0%
100.0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
ON
Decel time
set to b3-03
OFF
Selected
frequency
reference
Output
frequency
common_TMonly
Output
current
b3-05
When Speed Search is applied automatically with the Run command, the drive waits for the minimum baseblock time
L2-03 before Speed Search is started. If L2-03 is smaller than the time set in parameter b3-05, then b3-05 is used as the
wait time.
Figure 5.17
OFF
ON
Run command
Max. output frequency
or the specified
frequency reference
Selected
frequency
reference
Output
frequency
common_TMonly
b3-02
Output current
Minimum Baseblock Time (L2-03)
Figure 5.17 Current Detection Speed Search at Start or Speed Search Command by Digital Input
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
147
Parameter Details
5.2 b: Application
Notes on Using Current Detection Type Speed Search
Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection
Speed Search.
Current Detection Speed Search is not available when using Open Loop Vector Control for PM motors.
Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing
Speed Search after power is restored following a momentary power loss.
Speed Estimation Type Speed Search (b3-24 = 1)
This method can be used for a single induction motor connected to a drive. It should not be used if the motor is one or
more frame sizes smaller than the drive, at motor speeds above 200 Hz, or when using a single drive to operate more than
one motor.
Speed Estimation is executed in two steps as described below.
Step 1: Back EMF Voltage Estimation
This method is used by Speed Search after short baseblock (e.g., a power loss where the drives CPU kept running and
the Run command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage. It
outputs the estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that, the
motor is accelerated or decelerated to the frequency reference starting from the detected speed. If there is not enough
residual voltage in the motor windings to perform the calculations described above, then the drive will automatically
proceed to step 2.
Figure 5.18
AC power
supply
ON
OFF
Starts at the speed
that was detected
Output
frequency
Selected
frequency
reference
common_TMonly
Output
current
Several miliseconds
Min. Baseblock Time
(L2-03)
b3 -05 <1>
Once AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than the minimum
baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored before starting Speed
Search.
Current Injection is performed when there is not enough residual voltage remaining in the motor. This might occur after
after longer power losses, when Speed Search is applied with the Run command (b3-01 = 1), or if an External search
command is used. It injects the DC current set in b3-06 to the motor and detects the speed by measuring the current
feedback. The drive outputs the detected frequency and increases the voltage using the time constant set in parameter L204 while looking at the motor current. If the current is higher than the level in b3-02, then the output frequency is
reduced. When the current falls below b3-02, the motor speed is assumed to be found and the drive starts to accelerate or
decelerate to the frequency reference.
148
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
Figure 5.19
Run command
ON
OFF
Frequency reference
set to the drive
Starts at the speed
speed that was detected
Output
frequency
b3-02
Output
current
common_TMonly
1.0 s
The wait time for Speed Search (b3-05) determines the lower limit.
Rotational Auto-Tuning for V/f Control (T1-01 = 3) needs to be first performed if you plan to use Speed Estimation in
V/f Control. Perform Stationary Auto-Tuning for Line-to-Line Resistance (T1-01 = 2) again if the there is a change in
the cable length between the drive and motor.
Use Current Detection to search for speeds beyond 200 Hz, if the application is running multiple motors from the same
drive, or if the motor is considerably smaller than the capacity of the drive.
Speed Estimation may have trouble finding the actual speed if the motor cable is very long. Current Detection should
be used in such situations.
Use Current Detection instead of Speed Estimation when operating motors smaller than 1.5 kW. Speed Estimation can
end up stopping smaller motors, as it might not be able to detect the speed or rotation direction of such small motors.
Short Circuit Braking is recommended instead of Speed Search when using OLV/PM and AOLV/PM along with a
fairly long motor cable.
Use Short Circuit Braking instead of Speed Search if attempting to find the speed of a motor coasting faster than 200
Hz in OLV/PM and AOLV/PM.
Activating of Speed Search
1. Automatically activate Speed Search with every Run command. Here, external Speed Search commands are ignored.
2. Activate Speed Search using the digital input terminals.
The following input functions for H1- can be used.
Table 5.7 Speed Search Activation by Digital Inputs
Setting
Description
b3-24 = 0
61
62
b3-24 = 1
Activate Speed Estimation Speed Search
To activate Speed Search by a digital input, the input must always be set together with the Run command, or the Run
command must be entered after the Speed Search command is given.
3. After automatic fault restart
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically
perform Speed Search as specified by b3-24 following a fault.
4. After momentary power loss
This mode requires that the Power Loss Ride-Thru function be enabled always or at least enabled during CPU
operation (L2-01 = 1 or 2). Refer to L2-01: Momentary Power Loss Operation Selection on page 252
5. After external baseblock is released
The drive will resume the operation starting with Speed Search if the Run command is present and the output
frequency is above the minimum frequency when the Baseblock command (H1- = 8 or 9) is released. For this
operation mode, set the operation during an external Baseblock command to hold the output frequency (H1-13 = 0).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
149
Parameter Details
Speed Search can be activated as described below. Note that the Speed Search type must be selected in parameter b3-24
independent of the activation method.
5.2 b: Application
b3-01: Speed Search Selection at Start
Determines if Speed Search is automatically performed when a Run command is issued or not.
No.
Parameter Name
Setting Range
Default
b3-01
0 or 1
Determined by A1-02
Setting 0: Disabled
When the Run command is entered, the drive starts operating at the minimum output frequency. If external Speed Search
1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
Speed Search is performed whenever the Run command is entered. The drive begins running the motor once Speed
Search is complete.
b3-02: Speed Search Deactivation Current
Sets the operating current for Speed Search as a percentage of the drive rated current. Normally there is no need to
change this setting. If the drive has trouble restarting, try lowering this value.
No.
Name
Setting Range
Default
b3-02
0 to 200%
Determined by A1-02
Note: When parameter A1-02 = 0 (V/f Control) the factory default setting is 120. When parameter A1-02 = 2 (Open Loop Vector) the
factory default setting is 100.
Name
Setting Range
Default
b3-03
0.1 to 10.0 s
2.0 s
Name
Setting Range
Default
b3-04
10 to 100%
Determined by o2-04
Name
Setting Range
Default
b3-05
0.0 to 100.0 s
0.2 s
Name
Setting Range
Default
b3-06
0.0 to 2.0
Determined by o2-04
Note: If Speed Estimation is not working correctly even after adjusting b3-06, try using Current Detection Speed Search instead.
150
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
b3-10: Speed Search Detection Compensation Gain
This parameter sets the gain for the detected motor speed of the Speed Estimation Speed Search. The setting should be
increased only if an overvoltage fault occurs when the drive restarts the motor.
No.
Name
Setting Range
Default
b3-10
1.00 to 1.20
1.05
Parameter Name
Setting Range
Default
b3-14
0 or 1
Determined by A1-02
Setting 0: Disabled
The drive uses the frequency reference to determine the direction of motor rotation in order to restart the motor.
Setting 1: Enabled
The drive detects the motor rotation direction in order to restart the motor.
b3-17: Speed Search Restart Current Level
A large current can flow into the drive if there is a fairly large difference between the estimated frequency and the actual
motor speed when performing Speed Estimation. This parameter sets the current level at which Speed Estimation is
restarted, thus avoiding overcurrent and overvoltage problems. Set as a percentage of the drive rated current.
No.
Name
Setting Range
Default
b3-17
0 to 200%
150%
Name
Setting Range
Default
b3-18
0.00 to 1.00 s
0.10 s
No.
Name
Setting Range
Default
b3-19
0 to 10
Parameter Details
Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts
exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.
5
No.
Parameter Name
Setting Range
Default
b3-24
0 or 1
Name
Setting Range
Default
b3-25
0.0 to 30.0 s
0.5 s
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
151
5.2 b: Application
Name
Setting Range
Default
b4-01
0.0 to 3000.0 s
0.0 s
b4-02
0.0 to 3000.0 s
0.0 s
Multi-function Contact
Input: Timer Function
ON
Multi-function Contact
Output: Timer Function
ON
b4-01
On (Closed)
Off (Open)
ON
On (Closed)
Off (Open)
ON
b4-02
b4-01
common_TMonly
b4-02
152
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
PID Operation
To better demonstrate how PID works, the diagram below shows how the PID output changes when the PID input
(deviation) jumps from 0 to a constant level.
Figure 5.21
PID input
Time
PID output
I control
common_TMonly
D control
PID Output
P control
Time
Description
Sensors Used
Speed Control
Machinery speed is fed back and adjusted to meet the target value. Synchronous control is performed using speed data from
other machinery as the target value
Tachometer
Pressure
Fluid Control
Temperature Control
Pressure sensor
Thermocoupler, Thermistor
Analog Input A1
Set H3-02 = C
Analog Input A2
Set H3-10 = C
Analog Input A3
MEMOBUS/Modbus Register 0006H
Pulse Input RP
Parameter b5-19
Parameter Details
Set H3-06 = C
Set bit 1 in register 000FH to 1 and input the setpoint to register 0006H
Set H6-01 = 2
Set parameter b5-18 = 1 and input the PID setpoint to b5-19
Note: A duplicate allocation of the PID setpoint input will result in an oPE alarm.
The PID feedback signal can be input from one of the sources listed below.
Table 5.9 PID Feedback Sources
PID Feedback Source
Settings
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Analog Input A3
Set H3-06 = B
Pulse Input RP
Set H6-01 = 1
Note: A duplicate allocation of the PID feedback input will result in an oPE alarm.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
153
5.2 b: Application
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed below. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.10 PID Differential Feedback Sources
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16
Analog Input A2
Set H3-10 = 16
Analog Input A3
Set H3-06 = 16
Note: A duplicate allocation of the PID differential feedback input will result in an oPE alarm.
154
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Pulse Input
PID Feedback
Pulse Input
b5-19
PID Target
Pulse Input
Option Card
Serial Comm
not 16
H3-02/10=B
H6-01=1
H6-01=2
H3-02/10=C
b5-18=1
Off
Derivative
+
Time 2 or 4
b5-05
b5-01
1 or 3
Adjusted
PID Feedback
(U5-06)
Parameter Details
Z-1
PID Soft
Starter b5-17
PID Feedback
(U5-01)
not B
not 1
not 2
not C
b5-01 = 3/4
not 1
PID Differential
Feedback
(U5-05)
b5-01 = 1/2
PID Mode
H3-02/10
= 16
Frequency Reference 1 to 16
d1-01 to d1-16
PID Input
Limit
b5-35
PID Input
(U5-02)
0
1
PID Input
Characteristic
H1-=35 or
b5-09
-1
Proportional
Gain
b5-02
1
I-time
b5-03
1/s
Z-1
Integral Hold
H1-=31
PID Ouput
(U5-03)
+
+
+
+
Derivative
Time
b5-05
Z-1
0
1
+ +
2 or 4
1 or 3
Lower Limit 0
Upper Limit
Fmax x109%
-1
PID Output
Characteristic
b5-09
b5-08
PID Delay
Time
Lower Limit
Fmax x109%
Upper Limit
Fmax x109%
PID Output
Upper/Lower
Limit
b5-06 / b5-34
b5-01
Integral Reset
H1-=30
I - limit
b5-04
Enabled
Disabled
+
-
SFS
C1-
b5-07
PID Offset
PID Output
Gain
b5-10
Always 1 when
b5-01 = 3/4
RUN
On/Off
Output
Frequency
b5-11
Delay
Timer
b5-16
Sleep Function
b5-15
Sleep Level
Frequency
Reference
b1-01/15
YEC_TMonly
Frequency Reference
5.2 b: Application
Figure 5.22
155
5.2 b: Application
b5-01: PID Function Setting
Enables or disables the PID operation and selects the PID operation mode.
No.
Parameter Name
Setting Range
Default
b5-01
0 to 4
The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
Setting 2: Output frequency = PID output 2
The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.
Setting 3: Output frequency = frequency reference + PID output 1
The PID controller is enabled and the PID output is added to the frequency reference. The PID input is D controlled.
Setting 4: Output frequency = frequency reference + PID output 2
The PID controller is enabled and the PID output is added to the frequency reference. The PID feedback is D controlled.
b5-02: Proportional Gain Setting (P)
Sets the P gain that is applied to the PID input. A large value will tend to reduce the error, but may cause instability
(oscillations) if set too high. A low value may allow too much offset between the setpoint and feedback.
No.
Name
Setting Range
Default
b5-02
0.00 to 25.00
1.00
Name
Setting Range
Default
b5-03
0.0 to 360.0 s
1.0 s
Name
Setting Range
Default
b5-04
0.0 to 100.0%
100.0%
Note: On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of
oscillation. To suppress this oscillation, a limit can be applied to the integral output by programming b5-04.
Name
Setting Range
Default
b5-05
0.00 to 10.00 s
0.00 s
156
No.
Name
Setting Range
Default
b5-06
0.0 to 100.0%
100.0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
b5-07: PID Offset Adjustment
Sets the offset added to the PID controller output. Set as a percentage of the maximum frequency.
No.
Name
Setting Range
Default
b5-07
-100.0 to 100.0%
0.0%
Name
Setting Range
Default
b5-08
0.00 to 10.00 s
0.00 s
Note: Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant
frequency. Increasing this time constant may reduce the responsiveness of the drive.
Parameter Name
Setting Range
Default
b5-09
0 or 1
A positive PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output
A positive PID input causes a decrease in the PID output (reverse acting).
b5-10: PID Output Gain Setting
Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01
= 3 or 4).
No.
Name
Setting Range
Default
b5-10
0.00 to 25.00
1.00
Determines whether a negative PID output reverses the direction of drive operation or not. When the PID function is used
to trim the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited (same
as b5-11 = 1).
No.
Parameter Name
Setting Range
Default
b5-11
0 or 1
Negative PID output will be limited to 0 and the drive output will be stopped.
Setting 1: Reverse Enabled
Negative PID output will cause the drive to run in the opposite direction.
PID Feedback Loss Detection
The PID feedback loss detection function can detect broken sensors or broken sensor wiring. It should be used whenever
PID control is enabled to prevent critical machine conditions (e.g., acceleration to max. frequency) caused by a feedback
loss.
Feedback loss can be detected in two ways:
Feedback Low Detection
Detected when the feedback falls below a certain level for longer than the specified time. This function is set up using
parameters b5-12 to b5-14.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
157
5.2 b: Application
Feedback High Detection
Detected when the feedback rises beyond a certain level for longer than the specified time. This function is set up using
parameters b5-12, b5-36, and b5-37.
The following figure explains the working principle of feedback loss detection when the feedback signal is too low.
Feedback high detection works in the same way.
Figure 5.23
PID
Feedback
Detection
Loss Level
(b5-13)
common_TMonly
time
no FbL
detection
PID Feedback
Loss Detection Time
(b5-14)
FbL detection
PID Feedback
Loss Detection Time
(b5-14)
Parameter Name
Setting Range
Default
b5-12
0 to 5
A digital output set for PID feedback low (H2- = 3E) will be triggered if the PID feedback value is below the
detection level set to b5-13 for the time set to b5-14 or longer. A digital output set for PID feedback high (H2- =
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the times set to
b5-37. Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the
feedback value leaves the loss detection range, the output is reset.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FBL - Feedback
Low alarm will be displayed and a digital output set for PID feedback low (H2- = 3E) will be triggered. If the
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a FBH - Feedback High alarm
will be displayed and a digital output set for PID feedback high (H2- = 3F) will be triggered. Both events trigger
an alarm output (H1- = 10). The drive will continue operation. When the feedback value leaves the loss detection
range, the alarm and outputs are reset.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FbL - Feedback Low
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a
FbH - Feedback High fault will be displayed. Both events trigger a fault output (H1- = E) and cause the drive to
stop the motor.
Setting 3: Digital output only, even if PID is disabled by digital input
Same as b5-12 = 0. Detection is still active even if PID is disabled by a digital input (H1- = 19).
Setting 4: Feedback loss alarm, even if PID is disabled by digital input
Same as b5-12 = 1. Detection is still active even if PID is disabled by a digital input (H1- = 19).
Setting 5: Feedback loss fault, even if PID is disabled by digital input
Same as b5-12 = 2. Detection is still active even if PID is disabled by a digital input (H1- = 19).
158
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
b5-13: PID Feedback Low Detection Level
Sets the feedback level used for PID feedback low detection. The PID feedback has to fall below this level for longer
than the time b5-14 before feedback loss is detected.
No.
Name
Setting Range
Default
b5-13
0 to 100%
0%
Name
Setting Range
Default
b5-14
0.0 to 25.5 s
1.0 s
Name
Setting Range
Default
b5-36
0 to 100%
100%
Name
Setting Range
Default
b5-37
0.0 to 25.5 s
1.0 s
PID Sleep
The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep
operation level for a certain time. The drive will resume operating once the PID output or frequency reference rises above
the PID Sleep operation level for the specified time. An example of PID Sleep operation appears in the figure below.
Figure 5.24
PID Output
PID Sleep Level ( b5-15)
Sleep Delay Time
b5-16
Run
common_TMonly
b5-16
Stop
Parameter Details
Internal Run
command
External Run
command
During Run
The PID Sleep function is always active, even if PID control is disabled.
The PID Sleep function stops the motor according to the stopping method in b1-03.
The parameters necessary that control the PID Sleep function are explained below.
b5-15: PID Sleep Function Start Level
Sets the level that triggers PID Sleep.
The drive goes into Sleep mode if the PID output or frequency reference is smaller than b5-15 for longer than the time set
in b5-16. It resumes the operation when the PID output or frequency reference is above b5-15 for longer than the time set
in b5-16.
No.
Name
Setting Range
Default
b5-15
0.0 to 400.0 Hz
0.0 Hz
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
159
5.2 b: Application
b5-16: PID Sleep Delay Time
Sets the delay time to activate or deactivate the PID Sleep function.
No.
Name
Setting Range
Default
b5-16
0.0 to 25.5 s
0.0 s
Name
Setting Range
Default
b5-17
0.0 to 6000.0 s
0.0 s
Parameter Name
Setting Range
Default
b5-18
0 or 1
Setting 0: Disabled
Name
Setting Range
Default
b5-19
0.00 to 100.00%
0.00%
Parameter Name
Setting Range
Default
b5-20
0 to 3
Setting 0: Hz
The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined
Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID
monitors U1-01 and U1-04.
160
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower
limit is disabled when set to 0.00%
No.
Name
Setting Range
Default
b5-34
-100.0 to 100.0%
0.00%
Name
Setting Range
Default
b5-35
0 to 1000.0%
1000.0%
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user defined display for the PID
setpoint (b5-19) and PID feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
Name
Setting Range
Default
b5-38
1 to 60000
Determined by b5-20
b5-39
0 to 3
Determined by b5-20
Name
Setting Range
Default
b5-40
0 or 1
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference
Fine-Tuning PID
Once PID control parameters have been set, fine-tuning may be required. Follow the directions below.
Table 5.11 PID Fine Tuning
Goal
Tuning Procedure
Result
Response
Before adjustment
After adjustment
Time
Response
After adjustment
Before adjustment
Time
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
161
5.2 b: Application
Goal
Tuning Procedure
Result
Before adjustment
Response
After adjustment
Time
Before adjustment
Response
After adjustment
Time
OFF
Run Command
OFF
ON
common_TMonly
b6-01
b6-03
Output Frequency
b6-02
b6-04
Name
Setting Range
Default
b6-01
0.0 to 400.0 Hz
0.0 Hz
b6-02
0.0 to 10.0 s
0.0 s
Name
Setting Range
Default
b6-03
0.0 to 400.0 Hz
0.0 Hz
0.0 to 10.0 s
0.0 s
b6-04
162
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
= 100% Load
= 90% Load
= 80% Load
fref_A = constant
= 90% Load
fref_A = constant
common_TMonly
fref_B increase
fref_B decrease
= 80% Load
= 90% Load
= 100% Load
= 90% Load
Parameter Name
Setting Range
Default
b7-01
0.0 to 100.0%
0.0%
Figure 5.27
Speed
Speed reference
Droop control gain
b7-01
common_TMonly
Torque
0
100%
Parameter Name
Setting Range
Default
b7-02
0.03 to 2.00 s
0.05 s
Parameter Name
Setting Range
Default
b7-03
0, 1
Setting 0: Disabled
Setting 1: Enabled
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
163
5.2 b: Application
Parameter Name
Setting Range
Default
b8-01
0 or 1
Determined by A1-02
Setting 0: Disabled
Setting 1: Enabled
Name
Setting Range
Default
b8-02
0.0 to 10.0
Determined by A1-02
Name
Energy Saving Control Filter Time Constant
Setting Range
Default
0.00 to 10.00 s
Determined by
A1-02 and o2-04
Name
Setting Range
Default
b8-04
0.00 to 655.00
Determined by
C6-01, E2-11, and o2-04
Note: This default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically
when Auto-Tuning for Energy Saving is performed (Refer to Auto-Tuning on page 114).
164
No.
Name
Setting Range
Default
b8-05
0 to 2000 ms
20 ms
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.2 b: Application
b8-06: Search Operation Voltage Limit (V/f, V/f w/PG)
Sets the voltage limit for the optimal output voltage detection of Speed Search as a percentage of the maximum output
voltage. During the search operation, the drive will keep the output voltage above this level to prevent motor stalling.
Note: If set too low, the motor may stall with a sudden increase to the load. Disabled when b8-06 = 0. Setting this value to 0 does not
disable Energy Saving.
No.
Name
Setting Range
Default
b8-06
0 to 100%
0%
OFF
ON
Run command
ON
OFF
common_TMonly
Motor Speed
b2-01
DC Injection Braking
start frequency
Zero Servo
Operation
When Zero Servo is active, the deviation between the rotor position and the zero position is displayed in monitor U6-22
(monitor value must be divided by 4 to get the deviation in actual encoder pulses).
Note: 1. The Run command must remain on when using the Zero Servo function. If the Run command is switched off, then Zero Servo will no
longer be able to hold the load in place.
2. When the Zero Servo command has shut off, the Zero Servo Completion digital output width also shuts off.
3. Avoid using Zero Servo to lock 100% load for long periods, as this can trigger a fault. If such loads need to be held in place for long
periods, either make sure the current is less than 50% of the drive rated current during Zero Servo, or use a larger capacity drive.
4. If the load rotates the motor when using CLV/PM, a dv4 fault may occur. To prevent this, either increase the Zero Servo gain (b9-01)
or increase the number of pulses set to F1-19 that are required to trigger dv4.
Name
Setting Range
Default
b9-01
0 to 100
Name
Setting Range
Default
b9-02
0 to 16383
10
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
165
Parameter Details
A digital output programmed for Zero Servo complete (H2- = 72) is turned on when the rotor position is within the
zero position, plus or minus the Zero Servo completion width set in parameter b9-02.
5.3 C: Tuning
5.3
C: Tuning
C parameters are used to set the acceleration and deceleration characteristics, as well as S-curves. Other parameters in
this group cover settings for slip compensation, torque compensation, and carrier frequency.
Parameter Name
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
C1-05
C1-06
C1-07
C1-08
Setting Range
Default
10.0 s
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the
time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Accel/decel times 1 are active by default if no input is set. The accel/decel times 2, 3, and 4 can be activated by digital
inputs (H1- = 7 and 1A) as explained in Table 5.12.
Table 5.12 Accel/Decel Time Selection by Digital Input
Active Times
Acceleration
Deceleration
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
C1-08
Figure 5.29 shows an operation example for changing accel/decel. times. The example below requires that the stopping
method be set for Ramp to stop (b1-03 = 0).
Figure 5.29
Output
frequency
Accel Time 1
(C1-01)
Decel Time 1
Decel Time 3
Decel Time 2
(C1-02)
Accel Time 3 (C1-06)
Accel Time 2 (C1-04)
(C1-05)
(C1-03)
Accel Time 4
(C1-07)
Decel Time 1
(C1-02)
Decel Time 4
(C1-08)
Decel Time 1
(C1-02)
Time
FWD (REV)
Run command
ON
OFF
ON
ON
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1- = 7)
ON
OFF
ON
ON
OFF
ON
Accel/Decel Time Selection 2
(Terminals S1 to S8, H1- = 1A)
166
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a digital input (H1-= 16), parameters C1-01 to C1-04 become accel/
decel time 1 and 2 for motor 1, while C1-05 to C1-08 become accel/decel time 1 and 2 for motor 2. Accel/decel times 1
and 2 can be switched for each motor using a digital inputs set to H1- = 7 like shown in Table 5.13.
Note: 1. The motor 2 selection function cannot be used when PM motor is used.
2. The digital input setting Accel/Decel time 2 selection (H1- = 1A) cannot be used together with motor 1/2 switching. Trying to
do so triggers an oPE03 error, indicating a contradictory multifunction input settings.
Accel
Decel
Accel
Open
C1-01
C1-02
C1-05
Decel
C1-06
Closed
C1-03
C1-04
C1-07
C1-08
The drive can switch between different acceleration and deceleration times automatically. The drive will switch from
accel/decel time 4 in C1-07 and C1-08 to the default accel/decel time in C1-01 and C1-02 (C1-05 and C1-06 for motor 2)
when the output frequency exceeds the frequency level set in parameter C1-11. When it falls below this level, the accel/
decel times are switched back. Figure 5.30 shows an operation example.
Note: Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level
set to C1-11. For example, if accel/decel time 2 is selected, the drive will use this time only and not switch from accel/decel time
4 to the selected one.
Figure 5.30
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-07
setting
C1-01
setting
C1-02
setting
C1-08
setting
When the output frequency C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)
No.
Parameter Name
Setting Range
Default
C1-11
0.0 to 400.0 Hz
0.0 Hz
Parameter Name
Setting Range
Default
C1-09
10.0 s
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the
time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
167
Parameter Details
Sets the frequency at which the drive switches between accel/decel time settings. Refer to Switching Accel/Decel Times
by a Frequency Level on page 167.
5.3 C: Tuning
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid
this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast Stop time to C1-09.
Parameter Name
Setting Range
Default
C1-10
0 or 1
The accel/decel times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. If any of the parameters C1-01 to
C1-09 is set to 600.1 seconds or more, then C1-10 cannot be set to 0.
Setting 1: 0.1 s units
The accel/decel times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.
Parameter Name
C2-01
Setting Range
C2-02
C2-03
C2-04
Default
Determined by A1-02
0.00 to 10.00 s
0.20 s
0.20 s
0.00 s
FWD run
REV run
C2-02
Output
frequency
C2-03
common_TMonly
C2-04
C2-01
C2-04
C2-01
C2-02
C2-03
Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2
Actual decel time = decel time setting + (C2-03 + C2-04) / 2
168
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
C3-01: Slip Compensation Gain
This parameter sets the gain for the motor slip compensation function. Although this parameter rarely needs to be
changed, adjustments might be needed under the following circumstances:
If the motor at constant speed is slower than the frequency reference, increase C3-01.
If the motor at constant speed is faster than the frequency reference, decrease C3-01.
No.
Parameter Name
Setting Range
Default
C3-01
0.0 to 2.5
Determined by A1-02
Note: Default setting is 0.0 in V/f Control (A1-02 = 0), and 1.0 in Open Loop Vector Control (A1-02 = 2). In Closed Loop Vector
Control, slip compensation is used correct inaccuracies that can result from temperature fluctuation in the rotor.
Parameter Name
Setting Range
Default
C3-02
0 to 10000 ms
Determined by A1-02
Note: Default for V/f Control (A1-02 = 0) is 2000 ms. Default for Open Loop Vector Control (A1-02 = 2) is 200 ms.
Parameter Name
Setting Range
Default
C3-03
0 to 250%
200%
The slip compensation limit is constant throughout the constant torque range (frequency reference E1-06). In the
constant power range (frequency reference E1-06), it is increased based on C3-03 and the output frequency as shown in
the following diagram.
Figure 5.32
E1-04
E1-06 C3-03
C3-03
Parameter Details
common_TMonly
Output Frequency
E1-06
Base
Frequency
E1-04
Maximum
Frequency
Parameter Name
Setting Range
Default
C3-04
0 to 2
Setting 0: Disabled
Slip compensation is not provided. Depending on the load and mode of operation, the actual motor speed will be lower or
higher than the frequency reference.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
169
5.3 C: Tuning
Setting 1: Enabled (6 kHz and above)
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)
Slip compensation is enabled during regenerative operation, and at frequencies as low as 2 Hz. The drive uses the motor
rated slip set in E2-02 to automatically calculate the frequency range where compensation will be disabled.
C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
If the input power supply voltage is low or the motor has a high voltage rating, this function can help improve the speed
precision when moving heavy loads at high speeds. When this function is enabled, the reduction in flux causes a slightly
higher current at high speed. Keep this in mind when selecting the drive.
No.
Parameter Name
Setting Range
Default
C3-05
0 or 1
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Setting Range
Default
C3-21
0.0 to 2.5
Determined by E3-01
Note: Default setting is 0.0 in V/f Control (A1-02 = 0). Default setting is 1.0 in Open Loop Vector Control (A1-02 = 2) and Closed
Loop Vector Control (A1-02 = 3). In Closed Loop Vector Control, slip compensation gain acts as an adaptable gain.
Parameter Name
Setting Range
Default
C3-22
0 to 10000 ms
Determined by A1-02
Note: The default for V/f Control (A1-02 = 0) is 2000 ms. The default for Open Loop Vector Control (A1-02 = 2) is 200 ms.
Parameter Name
Setting Range
Default
C3-23
0 to 250%
200%
The slip compensation limit is constant throughout the constant torque range (frequency reference E3-06). In the
constant power range (frequency reference E3-06), it is increased based on C3-23 and the output frequency as shown in
the following diagram.
170
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Figure 5.33
E3-04
E3-06 C3-23
common_TMonly
C3-23
Output Frequency
E3-06
Base
Frequency
E3-04
Maximum
Frequency
Parameter Name
Setting Range
Default
C3-24
0 to 2
Setting 0: Disabled
Setting 1: Enabled (6 kHz and above)
Setting 2: Enabled (compensation provided wherever possible)
Parameter Name
Setting Range
Default
C4-01
0.00 to 2.50
Determined by A1-02
The drive controls the motor excitation current (d-axis current) and torque producing current (q-axis current) separately.
Torque compensation affects the torque producing current only. C4-01 works as a factor of the torque reference value that
builds the torque producing current reference.
Adjustment
Although this parameter rarely needs to be adjusted, changing the torque compensation gain in small steps of 0.05 may
help in the following situations:
Increase this setting when using a long motor cable.
Decrease this setting when motor oscillation occurs.
Adjust C4-01 so that the output current does not exceed the drive rated current.
Note: 1. Refrain from adjusting torque compensation in Open Loop Vector Control, as it can have a negative effect on torque accuracy.
2. Refrain from adjusting this parameter in OLV/PM. Too high a value can cause overcompensation, resulting in motor oscillation.
Parameter Name
Setting Range
Default
C4-02
0 to 60000 ms
Determined by A1-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
171
Parameter Details
The drive calculates the motor primary voltage loss using the output current and the termination resistor value (E2-05 for
IM, E5-05 for PM motors) and then adjusts the output voltage to compensate insufficient torque at start or when load is
applied. The effects of this voltage compensation can be increased or decreased using parameter C4-01.
5.3 C: Tuning
Adjustment
Although C4-02 rarely needs to be changed, adjustments may help in the following situations:
If the motor vibrates, increase C4-02.
If the motor responds too slowly to changes in the load, decrease C4-02.
C4-03: Torque Compensation at Forward Start (OLV)
Sets the amount of torque at start in the forward direction in order to improve motor performance during start with a
heavy load. Compensation is applied using the time constant set in parameter C4-05. Enable this function when the load
pulls the motor in reverse when starting with a Forward run command. Setting of 0.0% disables this feature.
No.
Parameter Name
Setting Range
Default
C4-03
0.0 to 200.0%
0.0%
Parameter Name
Setting Range
Default
C4-04
-200.0 to 0.0%
0.0%
Parameter Name
Setting Range
Default
C4-05
0 to 200 ms
10 ms
Parameter Name
Setting Range
Default
C4-06
0 to 10000 ms
150 ms
Note: If C4-06 is set to a relatively large value, be sure to also increase the setting in n2-03 (AFR Time Constant 2) proportionally.
172
No.
Parameter Name
Setting Range
Default
C4-07
0.00 to 2.50
1.00
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
Output frequency
Frequency
reference
Limit
ASR limit
Detected speed
common_TMonly
Change
rate
limiter
P
+
I
C5-01
C5-03
C5-05
C5-02, C5-04
Figure 5.34 Speed Control Block Diagram for V/f Control with PG
Figure 5.35
Torque limits
C5-01, C5-03
Frequency
reference
Detected speed
<1>
I
C5-02, C5-04
I
limit
Torque reference
Primary
filter
P
+
C5-06
(C5-10)
common_TMonly
L7-01 to L7-04
C5-08
Figure 5.35 Speed Control Block Diagram for CLV, AOLV/PM and CLV/PM
<1> Advanced Open Loop Vector Control for PM motors estimates the speed using the motor model and does not require an encoder feedback
signal.
Generally when tuning the ASR, first optimize the ASR gain, then adjust the integral time settings. Always make
adjustments with the load connected to the motor.
Adjusting the ASR Parameters in V/f Control with PG
In V/f Control with PG, the ASR settings change between two sets of parameters depending on the motor speed as
described in C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 175.
Perform the following steps for adjusting ASR parameters:
1. Run the motor at minimum speed and increase ASR gain 2 (C5-03) as much as possible without oscillation.
2. Run the motor at minimum speed and decrease ASR integral time 2 (C5-04) as much as possible without
oscillation.
3. Check the output current monitor to make sure that the output current is less than 50% of the drive rated current.
If the value is higher than 50%, decrease C5-03 and increase C5-04.
4. Run the motor at maximum speed and increase ASR gain 1 (C5-01) as much as possible without oscillations.
5. Run the motor at maximum speed and decrease ASR integral time 1 (C5-02) as much as possible without
oscillations.
6. If higher speed precision and faster response during acceleration or deceleration is required, enable integral
control during accel/decel by setting parameter C5-12 to 1. Change the speed and make sure no over/
undershoot occurs.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
173
5.3 C: Tuning
Adjusting the ASR Parameters in CLV, AOLV/PM, and CLV/PM
In CLV, AOLV/PM, and CLV/PM the drive is pre-set to use ASR settings C5-01/02 over the whole speed range. If
required by the application, a second set of ASR parameters (C5-03/04) can be automatically activated depending on the
motor speed or by using a digital input. Also refer to C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR
Integral Time 1, 2 on page 175.
Perform the following steps for adjusting ASR parameters:
1. Run the motor at zero speed and increase the ASR gain (C5-01) as much as possible without oscillation.
2. Run the motor at zero speed and decrease the ASR integral time (C5-02) as much as possible without
oscillation.
3. Run at the normal operating speed. Check for over/undershoot when changing speed and for any oscillation.
4. Should problems occur in step 3, increase the integral time and reduce the gain.
Alternatively, use different ASR settings for high and low speed. Set the values from step 1 and 2 to parameters
C5-03 and C5-04, then set an ASR switching frequency in parameter C5-07. Run the motor at a speed higher
than C5-07 and repeat step 3 while adjusting C5-01 and C5-02.
Solving Problems During ASR Setup
Use Table 5.14 when making adjustments to ASR. Though the parameters listed below are for motor 1, the same changes
can be made to the corresponding motor 2 parameters when running a second motor.
Table 5.14 ASR Setup Problems and Corrective Actions
Problem
Possible Solutions
Speed reference
Motor Speed
Time
Motor Speed
Speed reference
Time
Speed reference
Motor Speed
Time
Speed reference
Motor Speed
Check the pulse number set to F1-01 and the gear ratio in F1-12 and F1-13.
Make sure the pulse signal from the encoder is set up properly.
Check monitor U6-04 and check if the ASR is working at its output limit
(setting of C5-05). If so, increase C5-05.
Time
174
V/f control: Use C5-01/02 and C5-03/04 to set up different ASR settings at
minimum and maximum speed.
CLV, AOLV/PM, CLV/PM: Use C5-01, C5-02 and C5-03, C5-04 to define
optimal ASR settings for high and low speed. Use C5-07 to define a
switching frequency.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2
These parameters can be used to adjust the responsiveness of the ASR.
Note: C5-01 is automatically set when ASR Tuning is performed (T1-01 = 9 or T2-01 = 9).
No.
Parameter Name
Setting Range
Default
C5-01
0.00 to 300.00
Determined by A1-02
C5-02
0.000 to 10.000 s
Determined by A1-02
C5-03
0.00 to 300.00
Determined by A1-02
C5-04
0.000 to 10.000 s
Determined by A1-02
These parameter settings will function differently depending on the control mode.
V/f Control with PG
Parameters C5-01 and C5-02 determine the ASR characteristics at maximum speed, whereas C5-03 and C5-04 determine
the characteristics at minimum speed.
Figure 5.36
P = C5-01
I = C5-02
P and I setting
common_TMonly
P = C5-03
I = C5-04
E1-09
Min. output frequency
Motor speed
E1-04
Max. output frequency
In these control modes, parameters C5-03 and C5-04 define the ASR gain an integral time at zero speed. The settings in
C5-01 and C5-02 are used at speeds above the setting in C5-07. C5-07 is set to 0 as the default so that C5-01 and C5-02
are used over the entire speed range. Also refer to C5-07: ASR Gain Switching Frequency on page 176.
Figure 5.37
P = C5-01
I = C5-02
P, I
P = C5-03
I = C5-04
C5-07
common_TMonly
(Low speed)
The gain set in C5-03 can also be activated with a digital input programmed to ASR gain switch (H1- = 77). When
the terminal is open, the drive uses the ASR gain level set by the pattern in the figure above. When the terminal closes,
C5-03 is used. The integral time set to C5-02 is used to change linearly between these settings.
The ASR gain switch command from a multi-function input terminal overrides the switching frequency set to C5-07.
Figure 5.38
OFF
ON
Proportional gain
determined
by motor speed.
common_TMonly
C5-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
175
5.3 C: Tuning
ASR Gain Tuning (C5-01, C5-03)
The higher this setting, the faster is the speed response. Too high of a setting can lead to oscillation. In general, this
setting should be increased with larger loads in order to minimize the speed deviation.
ASR Integral Time Tuning (C5-02, C5-04)
Determines how fast a continuous speed deviation problem is eliminated. Too long of an integral time makes the speed
control less responsive, while a too short of an integral time can cause oscillation.
C5-05: ASR Limit
Sets the ASR output limit as a percentage of the maximum output frequency (E1-04). If the motor rated slip is high, the
setting might need to be increased to provide proper motor speed control. Use the ASR output monitor U6-04 to
determine if ASR is working at the limit set in C5-05. If so, make sure the PG pulses (F1-01), PG gear teeth (F1-12, F113), and the PG signal are set correctly before making further changes to C5-05.
No.
Parameter Name
Setting Range
Default
C5-05
ASR Limit
0.0 to 20.0%
5.0%
Parameter Name
Setting Range
Default
C5-06
0.000 to 0.500 s
Determined by A1-02
Parameter Name
Setting Range
Default
C5-07
0.0 to 400.0 Hz
0.0 Hz
Note: A multi-function input set for the ASR gain switch (H1- = 77) takes priority over the ASR gain switching frequency.
Switching the proportional gain and integral time in the low or high speed range can help stabilize operation and avoid
resonance problems. A good switching point is about 80% of the frequency where oscillation occurs, or at 80% of the
target speed. Refer to C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 175.
C5-08: ASR Integral Limit
Sets the upper limit for ASR as a percentage of the rated load.
No.
Parameter Name
Setting Range
Default
C5-08
0 to 400%
400%
Parameter Name
Setting Range
Default
C5-12
0, 1
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
176
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
C5-17, C5-18: Motor Inertia, Load Inertia Ratio
C5-17 and C5-18 determine the ratio of the machine inertia and the inertia of the motor being used.
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed in CLV and CLV/PM control
modes. Refer to Auto-Tuning on page 114 for details on Auto-Tuning or enter the data manually.
No.
Parameter Name
Setting Range
Default
C5-17
Motor Inertia
C5-18
0.0 to 6000.0
1.0
C5-21, C5-23 / C5-22, C5-24: Motor 2 ASR Proportional Gain 1, 2 / Integral Time 1, 2
These parameters function for motor 2 in the same way that C5-01 through C5-04 function for motor 1. For more details,
see C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time 1, 2 on page 175.
No.
Parameter Name
Setting Range
Default
C5-21
0.00 to 300.00
Determined by E3-01
C5-22
0.000 to 10.000 s
Determined by E3-01
C5-23
0.00 to 300.00
Determined by E3-01
C5-24
0.000 to 10.000 s
Determined by E3-01
Parameter Name
Setting Range
Default
C5-25
0.0 to 20.0%
5.0%
No.
Parameter Name
Setting Range
Default
C5-26
0.000 to 0.500 s
0.004 s
Parameter Name
Setting Range
Default
C5-27
0.0 to 400.0 Hz
0.0 Hz
Note: A multi-function input set for the ASR gain switch (H1- = 77) takes priority over the ASR gain switching frequency.
Parameter Name
Setting Range
Default
C5-28
0 to 400%
400%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
177
Parameter Details
5.3 C: Tuning
C5-32: Integral Operation during Accel/Decel for Motor 2
Functions for motor 2 in the same way that C5-12 functions for motor 1.
Enables integral operation during acceleration and deceleration. For more details, see C5-12: Integral Operation during
Accel/Decel (V/f w/PG) on page 176.
No.
Parameter Name
Setting Range
Default
C5-32
0, 1
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Parameter Name
Setting Range
Default
C5-37
Motor 2 Inertia
C5-38
0.0 to 6000.0
1.0
Parameter Name
Setting Range
Default
C6-01
0 or 1
0 (HD)0 (HD)
C6-01
Overload
150%
Overload
120%
Rated Load
100%
Rated Load
100%
Performance
Motor Speed
100%
Motor Speed
100%
Application
Use Normal Duty Rating for applications in which the torque requirements
drop along with the speed. Examples include fans and pumps where a high
overload tolerance is not required.
150%
120%
150%
120%
2 kHz
Note: By changing the Duty Mode selection, the maximum size motor the drive can run changes, and the E2- parameters are
automatically set to appropriate values (E4- for motor 2). Parameters settings determined by motor capacity are recalculated
automatically when the Duty Mode selection is changed. This includes b8-04, L2-03, n5-02, L3-24, C5-17, and C5-37.
178
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
C6-02: Carrier Frequency Selection
Parameter C6-02 sets the switching frequency of the drives output transistors. Changes to the switching frequency helps
lower audible noise and also reduces leakage current.
Note: Increasing the carrier frequency above the default value automatically lowers the drives current rating. Refer to Rated Current
Depending on Carrier Frequency on page 180.
No.
Parameter Name
C6-02
Setting Range
Default
1 to F
Note: The default setting for the carrier frequency differs based on the type of motor and the Duty Mode selection. The default is 2 kHz
when the drive is set for Heavy Duty performance, and defaulted to Swing PWM1 when set for Normal Duty performance.
When using a PM motor, the default carrier frequency is 5.0 Hz.
Settings:
C6-02
Carrier Frequency
C6-02
Carrier Frequency
C6-02
2.0 kHz
Carrier Frequency
Swing PWM 3
Swing PWM 4
Swing PWM 1
Swing PWM 2
Note: 1. Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.
2. The value in parenthesis indicates the carrier frequency for AOLV/PM.
Remedy
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below.
<2> In Normal Duty, the carrier frequency default is for Swing PWM (C6-02 = 7), the same as setting 2 kHz. Increasing the carrier frequency is fine
when the drive is set for Normal Duty, but remember that the drive rated current falls when the carrier frequency is increased.
Wiring Distance
Up to 50 m
Up to 100 m
1 to F (up to 15 kHz)
Use these parameters to set a user defined or a variable carrier frequency. To set the upper and lower limits and the carrier
frequency proportional gain, first set C6-02 to F.
No.
Parameter Name
Setting Range
C6-03
C6-04
0 to 99
C6-05
Default
Determined by C6-02
A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to F. In V/f
Control, parameter C6-04 must also be adjusted to the same value as C6-03.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
C6-03, C6-04, C6-05: Carrier Frequency Upper Limit, Lower Limit, Proportional Gain
179
5.3 C: Tuning
Setting a Variable Carrier Frequency (V/f Control)
In V/f Control, the carrier frequency can be set up to change linearly with the output frequency. To do this, set the upper
and lower limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) as shown in
Figure 5.39.
Figure 5.39
Carrier Frequency
C6-03
common_TMonly
Output
Frequency x C6-05
C6-04
Output Frequency
E1-04
Max Output Frequency
Parameter Name
Setting Range
Default
C6-09
0, 1
Setting 0: 5 kHz
Setting 1: Same value set to C6-03
180
2 kHz
8 kHz
15 kHz
2 kHz
8 kHz
15 kHz
2A0004
3.2
3.2
2.56
3.5
3.2
2.56
2A0006
2A0008
6.9
6.9
5.5
6.9
Model
CIMR-A
2 kHz
8 kHz
15 kHz
2 kHz
8 kHz
15 kHz
4A0002
1.8
1.8
1.1
2.1
1.8
1.1
4A0004
3.4
3.4
4.1
3.4
5.5
4A0005
4.8
4.8
2.9
5.4
4.8
2.9
3.3
2A0010
6.4
9.6
6.4
4A0007
5.5
5.5
3.3
6.9
5.5
2A0012
11
11
8.8
12
11
8.8
4A0009
7.2
7.2
4.3
8.8
7.2
4.3
2A0018
14
14
11.2
17.5
14
11.2
4A0011
9.2
9.2
5.5
11.1
9.2
5.5
2A0021
17.5
17.5
14
21
17.5
14
4A0018
14.8
14.8
8.9
17.5
14.8
8.9
2A0030
25
25
20
30
25
20
4A0023
18
18
10.8
23
18
10.8
2A0040
33
33
26.4
40
33
26.4
4A0031
24
24
14.4
31
24
14.4
2A0056
47
47
37.6
56
47
37.6
4A0038
31
31
18.6
38
31
18.6
2A0069
60
60
48
69
60
48
4A0044
39
39
23.4
44
39
23.4
2A0081
75
75
53
81
75
53
4A0058
45
45
27
58
45
27
2A0110
85
85
60
110
85
60
4A0072
60
60
36
72
60
36
2A0138
115
115
81
138
115
81
4A0088
75
75
45
88
75
45
4A0103
91
91
55
103
91
55
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.3 C: Tuning
2 kHz
5 kHz
10 kHz
2 kHz
5 kHz
10 kHz
2A0169
145
145
116
169
145
116
Model
CIMR-A
2 kHz
5 kHz
10 kHz
2 kHz
5 kHz
10 kHz
4A0139
112
112
78
139
112
78
180
180
144
211
180
144
4A0165
150
150
105
165
150
105
215
215
172
250
215
172
4A0208
180
180
126
208
180
126
2A0312
283
283
226
312
283
226
4A0250
216
216
151
250
216
151
2A0360
346
346
277
360
346
277
4A0296
160
260
182
296
260
182
2A0415
415
415
332
415
415
332
4A0362
304
304
213
362
304
213
4A0414
370
370
414
370
4A0515
450
375
515
397
4A0675
605
504
675
528
Parameter Details
2A0211
2A0250
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
181
5.4
d: Reference Settings
The figure below gives an overview of the reference input, selections, and priorities.
Figure 5.40
b1-01
(Freq. Reference Source 1)
common_TMonly
=4
=3
=2
=1
Digital Input
H1- = 2
=0
0
Remote
MS 1
Local
Set to supply the
auxiliary frequency reference
Terminal A2
b1-15
(Freq. Reference Source 2)
H3-10 = 2
d1-02
=4
Terminal A3
H3-06 = 3
=3
d1-03
=2
=1
=0
MS 2
H3-10 = 2
d1-04
Frequency
Reference
4 through 16
d1-15
d1-16
MS 3
H3-06 = 3
Open
NetRef
1
MS 15
Jog
Multi-Step Speed
Frequency
Reference
Close
MS 4
MS 16
1 ComRef
Parameter Name
Setting Range
Default
d1-01 to d1-16
Frequency Reference 1 to 16
0.00 Hz <2>
d1-17
6.00 Hz <2>
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is Hz (o1-03 = 0) in V/f, V/f w/PG, OLV, CLV, and OLV/PM control modes.
The default for AOLV/PM and CLV/PM control modes expresses the frequency reference as a percentage (o1-03 = 1).
To use several speed references for a multi-step speed sequence, set the H1- parameters to 3, 4, 5, and 32. To assign
the Jog reference to a digital input, set H1- to 6.
Notes on using analog inputs as Multi-Speed 1, 2, and 3:
The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input
terminal to supply the frequency reference, the frequency reference source must be assigned to the control terminals
(b1-01 = 1).
When an analog input is set to Auxiliary frequency 1 (H3-02, H2-06, or H2-10 = 2), then the value set to this input
will be used as the Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for
Auxiliary frequency 1, then d1-02 becomes the reference for Multi-Step Speed 2.
182
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Multi-Step
Speed
H1-=3
Multi-Step
Speed 2
H1-=4
Multi-Step
Speed 3
H1-=5
Multi-Step
Speed 4
H1-=32
Jog Reference
H1-=6
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
<1> The Jog frequency overrides whatever frequency reference is being used.
Figure 5.41
d1-16
Frequency
reference
d1-15
d1-14
d1-13
d1-12
d1-07
d1-06
d1-05
d1-02
(A2)
Parameter Details
d1-01
(A1)
d1-01
(A3)
d1-04
d1-17
Time
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Jog Reference
ON
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
183
Parameter Name
Setting Range
Default
d2-01
0.0 to 110.0%
100.0%
Parameter Name
Setting Range
Default
d2-02
0.0 to 110.0%
0.0%
Figure 5.42
Internal frequency
reference
common_TMonly
d2-01
Operating
range
Parameter Name
Setting Range
Default
d2-03
0.0 to 110.0%
0.0%
184
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
d3-01
Jump Frequency 1
0.0 Hz <1>
d3-02
Jump Frequency 2
0.0 Hz <1>
d3-03
Jump Frequency 3
0.0 Hz <1>
d3-04
1.0 Hz <1>
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent instead of in Hz.
Figure 5.43 shows the relationship between the Jump frequency and the output frequency.
Figure 5.43
Output
frequency
Frequency
reference
decreases
Frequency
reference
increases
Jump
Frequency
Width (d3-04)
common_TMonly
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Jump
Frequency 2
d3-02
Jump
Frequency 1
d3-01
Frequency
reference
Parameter Name
Setting Range
Default
d4-01
0 or 1
Acceleration hold
The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active
frequency reference will be the value the drive uses when it restarts.
Up/Down
The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched
off. The drive will start from 0 Hz when it is turned back on again.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
This parameter is effective when either of the digital input functions listed below is used.
185
Acceleration hold
The last hold value will be saved when the Run command or the drive power is switched off. The drive will use the
value that was saved as the frequency reference when it restarts. The multi-function input terminal set for Accel/decel
ramp hold (H1- = A) must be enabled the entire time, or else the hold value will be cleared when the power is
switched on.
Figure 5.44
ON
Power supply
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
common_TMonly
Frequency reference
Output frequency
d4-01 = 1
d4-01 = 0
Hold
Hold
Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will
use the frequency reference that was saved when it restarts.
Up/Down 2 with frequency reference from digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias
value is added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be
used to restart the drive after the power is cycled.
Figure 5.45
Output
frequency
Frequency
reference
common_TMonly
Bias
5s
5s
Up 2 command
Figure 5.45 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
Up/Down 2 with frequency reference from input sources other than the digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the bias value will be
saved in parameter d4-06. When restarting after the power is switched off, the drive will add the value saved in d4-06
as a bias to the frequency reference.
186
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output
frequency
d4-06 value
common_TMonly
Bias
5s
5s
Up 2 command
Figure 5.46 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note: Make sure to set the limits for Up/Down 2 properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to
d4-08: Frequency Reference Bias Upper Limit (Up/Down 2) on page 189 and Refer to d4-09: Frequency Reference Bias
Lower Limit (Up/Down 2) on page 189 for details on the limit settings.
Depending on which function is used, the frequency reference value that was saved can be cleared by:
Releasing the input programmed for Acceleration hold.
Setting an Up or Down command while no Run command is active.
Parameter d4-06 is reset to zero. Refer to d4-06: Frequency Reference Bias (Up/Down 2) on page 188 for details.
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.
No.
Parameter Name
Setting Range
Default
d4-03
0.00 to 99.99 Hz
0.00 Hz
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel time
determined by parameter d4-04.
Figure 5.47
Parameter Details
Output
frequency
Bias
common_TMonly
Up 2 command
When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The
frequency reference changes with the accel/decel times determined by parameter d4-04.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
187
Output
frequency
Bias
common_TMonly
Up 2 command
Parameter Name
Setting Range
Default
d4-04
0 or 1
The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.
d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)
Determines if the bias value is held or not when the Up/Down 2 inputs are both released or both enabled. The parameter
is effective only when parameter d4-03 is set to 0.00.
No.
Parameter Name
Setting Range
Default
d4-05
0 or 1
The bias is reset to 0% when both inputs Up 2 and Down 2 are either on or off. The drive will use the accel/decel time as
selected in d4-04 to accelerate or decelerate to the frequency reference value.
d4-06: Frequency Reference Bias (Up/Down 2)
This parameter is used to save the frequency reference bias value set by the Up/Down 2 function. It is set as a percentage
of the maximum output frequency. The function of d4-06 depends on how the Up/Down 2 function is configured.
This parameter is normally not used when the frequency reference is set by the digital operator. The user can set d4-06
to a certain value that will be applied during run, but this value will be reset when the frequency reference changes
(including multi-step references) or will be disabled when d4-01 = 0 and the Run command is removed.
When d4-01 = 0 and the frequency reference is set by a source other than the digital operator, the value set in d4-06 is
generally added to or subtracted from the frequency reference.
When d4-01 = 1 and the frequency reference is set by a source other than the digital operator, the bias value adjusted
with the Up/Down 2 inputs is stored in d4-06 once 5 s have passed after the Up 2 or Down 2 command is released. The
frequency reference will then return to what it was without the Up/Down 2 command.
188
No.
Parameter Name
Setting Range
Default
d4-06
-99.9 to 100.0%
0.0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
When the Up/Down 2 function has not been assigned to the multi-function terminals
When the frequency reference source has been changed (including LOCAL/REMOTE or External reference 1/2 switch
over by digital inputs)
If d4-03 = 0 Hz, d4-05 = 1 and the Up/Down 2 commands are both open or both closed
Any changes to the maximum frequency set to E1-04
d4-07: Analog Frequency Reference Fluctuation Limit (Up/Down 2)
This parameter is for handling changes in the frequency reference while the terminal set for Up 2 or Down 2 is enabled.
If the frequency reference changes for more than the level set to d4-07, then the bias value will be held, and the drive will
accelerate or decelerate following the frequency reference. When the frequency reference is reached, the bias hold is
released and the bias follows the Up/Down 2 input commands.
Parameter d4-07 is applicable only if the frequency reference is set by an analog or pulse input.
No.
Parameter Name
Setting Range
Default
d4-07
0.1 to 100.0%
1.0%
Parameter Name
Setting Range
Default
d4-08
0.0 to 100.0%
100.0%
No.
Parameter Name
Setting Range
Default
d4-09
-99.9 to 0.0%
0.0%
Parameter Details
Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the
frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. If the bias is increased using
the Up 2 command, it cannot be reduced with a Down 2 command when the limit set in d4-09 is 0. To allow speed reduction in
this situation, set a negative lower limit in d4-09.
Parameter Name
Setting Range
Default
d4-10
0 or 1
The lower frequency reference limit is determined by the higher value of either parameter d2-02 or an analog input (A1,
A2, A3) that is programmed for Frequency bias.
Note: For example, if the command to switch the external reference (H1- = 2) is used to switch between the Up/Down function and
an analog input as the reference source, then the analog value would become the lower reference limit when the Up/Down
command is active. Change d4-10 to 1 to make the Up/Down function independent of the analog input value.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
189
Torque Compensation
d5-02
Soft
Starter
+
+
1 d5-03
2
L7-
d5-08
C1- , C2-
U1-09
Internal Torque
Reference
Speed Limiter
Compensated torque
reference
Speed Feedback
common_TMonly
The externally input torque reference is used as the target value for the motor output torque. If the motor torque reference
and the load torque are not in balance when in Torque Control, the motor accelerates or decelerates. An operation beyond
the speed limit is prevented by compensating the external torque reference value if the motor speed reaches the limit. The
compensation value is calculated using the speed limit, speed feedback, and the speed limit bias.
If an external torque compensation value is input, it is added to the speed limit compensated torque reference value. The
value calculated is limited by the L7- settings, and is then used as the internal torque reference, which can be
monitored in U1-09. The L7- settings have highest priority, i.e., the motor cannot be operated with a higher torque
than the L7- settings, even if the external torque reference value is increased.
190
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Input values for Torque Control can be set like explained in Table 5.18.
Table 5.18 Torque Control Input Value Selection
Input Value
Signal Source
Settings
F2-01 = 0
H3-02, H3-06, or H3-10 = 13 <1>
The F3- settings become effective for the option board input
terminals. Make sure the signal level settings for the input terminal
selected match the signal used. Refer to H3: Multi-Function
Analog Inputs on page 237 for details on adjusting analog input
signals.
F6-06 = 1
Refer to the option card manual for details about
setting the torque compensation value.
d5-03 = 1
The settings in C1- for accel/decel times and in C2- for SThe speed limit is taken from the input selected as
frequency reference source in parameter b1-01 or b1- curves are applied to the speed limit value.
15. <1>
Parameter d5-04
d5-03 = 2
Torque Reference
Speed Limit
Remarks
Make sure the signal level settings for the input terminal selected
match the signal used. Refer to H3: Multi-Function Analog Inputs
on page 237 for details on adjusting analog input signals.
Make sure the signal level settings for the input terminal selected
match the signal used. Refer to H3: Multi-Function Analog Inputs
on page 237 for details on adjusting analog input signals.
F2-01 = 0
H3-02, H3-06, or H3-10 = 14 <1>
The H3- settings become effective for the option card input
terminals. Make sure the signal level settings for the input terminal
selected match the signal used.
F6-06 = 1
Refer to the option card manual for details about
setting the torque compensation value.
Torque Compensation
<1> Sets analog input terminals A1, A2, and A3 to supply the speed limit, torque reference, or torque compensation. An oPE error will occur if two
analog inputs are set for the same function.
The direction of the input values described above depends on the polarity of the Run command and the input value.
+ (positive)
Forward direction
- (negative)
Reverse direction
+ (positive)
Reverse direction
- (negative)
Forward direction
Example:
With a Forward run command and a positive torque reference signal the internal torque reference will be positive, i.e.,
in the forward direction.
With a Forward run command and a negative torque reference signal the internal torque reference will be negative, i.e.,
in the reverse direction.
When analog inputs are used, negative input values can be generated by
applying negative voltage input signals.
using positive analog input signals but setting the analog input bias to negative values so that the input value can be
negative.
When MEMOBUS communication or a communication option card is used, only positive input values can be set.
Independent of its input source, the polarity of the torque reference signal can be inverted using a digital input that is
programmed for H1- = 78. Use this function to input negative torque reference values when using MEMOBUS or a
communication option card.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
191
Parameter Details
Forward
Forward
Forward
Forward
Torque Reference
Direction
Positive (Forward)
Negative (Reverse)
Negative (Reverse)
Positive (Forward)
Speed Limit
Direction
Positive (Forward)
Negative (Reverse)
Positive (Forward)
Negative (Reverse)
Normal Operation
Direction
Forward
Reverse
Forward
Reverse
Torque
Limit
Generated Torque
(d5-08 = 0)
Torque
Speed Limit
n
Bias d5-05
Speed Limit
Bias d5-05
Speed
Limit
Torque
Torque n
Limit
Generated Torque
(d5-08 = 1)
Torque
Limit
Speed
Limit Bias
d5-05
d5-05
Speed
Internal
Torque
Reference
Internal
Torque
Reference
Torque
Limit
Winder
Speed Torque
Torque
Limit
Speed Torque
Torque n
Limit
Speed
0
Speed
Limit
Torque
Limit
Speed Limit
Speed
Limit Bias
d5-05
Torque
Limit
Speed Limit
Bias d5-05
Speed Limit
Bias d5-05
Speed
Speed
Limit
Torque
Torque
Limit
Speed
<1>
Torque
Limit
Torque
Speed
Limit
Internal
Torque
Reference
Internal
Torque
Reference
n
Internal
Torque
Reference
0
Internal
Torque
Reference
Speed Limit
Bias d5-05
Torque
Speed
Speed Limit
Limit Bias
Speed
d5-05
Torque
Limit
Torque n
Limit
Speed Limit
Bias d5-05
Speed
Speed
Torque
Torque
Limit
Speed Limit
Bias d5-05
Speed
Limit
Internal
Torque
Reference
<1>
Torque
Torque
Limit
Torque
n
Internal
Torque
Reference
Speed
Speed
Limit Bias
d5-05
Speed
Limit
Torque
Limit
Torque
Limit
Unwinder
Torque Speed
Torque Speed
Line Direction
Line Direction
Line Direction
<1> The value of delta n in the drawings depends on the ASR setting in parameters C5-.
192
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
OFF
Speed/Torque control
input (H1- = 71)
Run command
Operation Mode
Frequency refernce
signal or d5-04
Torque reference signal/
Torque limit
OFF
ON
OFF
ON
ON
Speed Control
Torque Control
Speed Control
Torque Control
Speed Ref.
Speed Limit
Speed Ref.
Speed Limit
Torque Limit
Torque Reference
d5-06
Torque Limit
d5-06
Speed Control
Speed Ref.
Torque Reference
Torque Limit
common_TMonly
d5-06
Parameter Name
Setting Range
Default
d5-01
0 or 1
Setting 0: Disabled
Speed Control will be active. Also use this setting when H1- = 71 (Speed/Torque Control Switch).
Setting 1: Enabled
Parameter Name
Setting Range
Default
d5-02
0 to 1000 ms
0 ms
No.
Parameter Name
Setting Range
Default
d5-03
1 or 2
The frequency reference value at the active reference source (digital operator, External reference 1 or External reference
2) will be used as speed limit. Note that in this case all settings for accel/decel times (C1-01 to C1-08) and S-curves (C201 to C2-04) will apply for the speed limit.
Setting 2: Parameter d5-04
Parameter Name
Setting Range
Default
d5-04
Speed Limit
-120 to 120%
0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
193
Parameter Details
Parameter Name
Setting Range
Default
d5-05
0 to 120%
10%
Parameter Name
Setting Range
Default
d5-06
0 to 1000 ms
0 ms
Parameter Name
Setting Range
Default
d5-08
0 or 1
Setting 0: Disabled
The speed limit bias is applied in both directions, the speed limit and the opposite direction.
Setting 1: Enabled
The speed limit bias is applied in the opposite direction of the speed limit only.
Parameter Name
Setting Range
Default
d6-01
0 to 100%
80%
194
No.
Parameter Name
Setting Range
Default
d6-02
0 to 400.0 Hz
0.0 Hz
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
d6-03
0 or 1
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Setting Range
Default
d6-06
100 to 400%
400%
Parameter Name
Setting Range
Default
d7-01
Offset Frequency 1
-100.0 to 100.0%
0%
d7-02
Offset Frequency 2
-100.0 to 100.0%
0%
d7-03
Offset Frequency 3
-100.0 to 100.0%
0%
Frequency
reference
SFS
Frequency
reference after
soft starter
Multi-function
input (44) = on
Parameter Details
Multi-function
input (45) = on
Offset Frequency 2 [d7-02]
(Signed)
Multi-function
input (46) = on
Offset Frequency 3 [d7-03]
(Signed)
common_TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
195
5.5
E: Motor Parameters
Parameter Name
Setting Range
Default
E1-01 <1>
155 to 255 V
200 V
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
The input voltage setting determines the undervoltage detection level as well as DC bus levels used by the KEB function
and the overvoltage suppression function.
(Approximate Values)
Voltage
200 V Class
400 V Class
Setting Value of
E1-01
Uv Detection Level
(L2-05)
ov Suppression /
Stall Prevention Level
(L3-17)
All settings
190 V
260 V
375 V
setting 400 V
380 V
500 V
750 V
350 V
460 V
750 V
Note: The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is
used, refer to the instruction manual of that unit.
Parameter Name
Setting Range
Default
E1-03
0 to F <1>
F <2>
<1> Parameter setting value is not reset to the default value during drive initialization (A1-03).
<2> Settings 0 through E are not available when using any of the vector control modes.
196
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Choose the V/f pattern that best meets the application demands from the table below. These settings are available only in
V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note: 1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Parameter E1-03 is not reset when the drive is initialized.
Specification
50 Hz
60 Hz
60 Hz (with 50 Hz base)
72 Hz (with 60 Hz base)
90 Hz (with 60 Hz base)
Characteristic
Application
Constant torque
Derated torque
For fans, pumps, and other applications that require torque derating
relative to the load.
Constant output
200
Setting = 1
60 Hz
Setting = 2
Voltage (V)
Voltage (V)
15
9
72 Hz
200
15
15
0 1.5 3
60
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
Setting = 3
200
200
15
60 Hz
Voltage (V)
50 Hz
Voltage (V)
Setting = 0
60 72
0 1.5 3
Frequency (Hz)
0 1.5 3
50 60
Frequency (Hz)
Setting = 5
Setting = 6
200
Voltage (V)
200
Voltage (V)
50 Hz
35
8
Setting = 7
200
50
9
8
0 1.5
60 Hz
200
35
0 1.3
25
50
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
60 Hz
Voltage (V)
50 Hz
Voltage (V)
Setting = 4
Parameter Details
50
9
0 1.5
30
60
Frequency (Hz)
30
60
Frequency (Hz)
19
11
0 1.3 2.5
50
Frequency (Hz)
Setting = A
24
60 Hz
200
200
Voltage (V)
Voltage (V)
200
50 Hz
13
0 1.3 2.5
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
19
Setting = B
60 Hz
200
Voltage (V)
50 Hz
Voltage (V)
Setting = 8
24
15
11
0 1.5 3
60
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
197
120 Hz
Setting = E
200
15
15
60 Hz
15
0 1.5 3
60 120
Frequency (Hz)
0 1.5 3
60 90
Frequency (Hz)
Setting = F
200
15
180 Hz
200
Voltage (V)
Voltage (V)
200
Voltage (V)
Setting = D
Voltage (V)
Setting = C
0 1.5 3
60 180
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
Predefined V/f Patterns for Models CIMR-A2A0030 to 0211 and CIMR-A4A0018 to 0103
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Table 5.26 Rated Torque Characteristics, Settings 0 to 3
50 Hz
60 Hz
200
14
Setting = 2
60 Hz
14
Setting = 3
72 Hz
200
200
Voltage (V)
Voltage (V)
200
Voltage (V)
Setting = 1
Voltage (V)
Setting = 0
14
14
0 1.3 2.5
50
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
0 1.5 3
50 60
Frequency (Hz)
0 1.5 3
60 72
Frequency (Hz)
200
Voltage (V)
50 Hz
35
Setting = 7
60 Hz
200
35
50
7
25
50
0 1.3
Frequency (Hz)
0 1.3
25
50
Frequency (Hz)
60 Hz
200
50
Setting = 6
Voltage (V)
50 Hz
Voltage (V)
Setting = 4
0 1.5
30
60
Frequency (Hz)
0 1.5
30
60
Frequency (Hz)
Voltage (V)
18
9
Setting = A
23
11
Setting = B
60 Hz
200
18
23
13
0 1.3 2.5
50
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
60 Hz
200
200
200
Voltage (V)
50 Hz
Voltage (V)
50 Hz
Voltage (V)
Setting = 8
0 1.5 3
60
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
198
14
120 Hz
200
14
Setting = E
180 Hz
Setting = F
200
200
Voltage (V)
Voltage (V)
200
Setting = D
Voltage (V)
90 Hz
Voltage (V)
Setting = C
14
60 Hz
14
0 1.5 3
60 90
Frequency (Hz)
0 1.5 3
60 120
Frequency (Hz)
0 1.5 3
60 180
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Table 5.30 Rated Torque Characteristics, Settings 0 to 3
200
Setting = 1
60 Hz
Voltage (V)
Voltage (V)
200
Setting = 2
60 Hz
Setting = 3
200
200
Voltage (V)
50 Hz
Voltage (V)
Setting = 0
72 Hz
12
12
12
12
0 1.3 2.5
50
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
0 1.5 3
50 60
Frequency (Hz)
0 1.5 3
60 72
Frequency (Hz)
50 Hz
200
Voltage (V)
Voltage (V)
200
35
Setting = 6
50
60 Hz
200
35
50
6
0 1.3
25
50
Frequency (Hz)
25
50
0 1.3
Frequency (Hz)
Setting = 7
200
60 Hz
Voltage (V)
50 Hz
Voltage (V)
Setting = 4
0 1.5
30
60
Frequency (Hz)
0 1.5
30
60
Frequency (Hz)
15
Setting = A
20
9
Setting = B
60 Hz
200
15
20
11
7
0 1.5 3
60
Frequency (Hz)
0 1.3 2.5
50
Frequency (Hz)
50
0 1.3 2.5
Frequency (Hz)
60 Hz
200
200
200
Voltage (V)
50 Hz
Voltage (V)
50 Hz
Voltage (V)
Setting = 8
0 1.5 3
60
Frequency (Hz)
200
12
Setting = E
180 Hz
200
Setting = F
60 Hz
200
12
12
0 1.5 3
60 90
Frequency (Hz)
0 1.5 3
60 120
Frequency (Hz)
0 1.5 3
60 180
Frequency (Hz)
0 1.5 3
60
Frequency (Hz)
Parameter Details
120 Hz
Voltage (V)
Voltage (V)
12
Setting = D
Voltage (V)
90 Hz
200
Voltage (V)
Setting = C
Setting parameter E1-03 to F allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined
patterns.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
199
Parameter Name
Setting Range
Default
E1-04
40.0 to 400.0 Hz
E1-05
Maximum Voltage
<1> <3>
E1-06
Base Frequency
0.0 to [E1-04]
E1-07
0.0 to [E1-04]
<1> <6>
E1-08
<1> <3>
<1> <2> <6>
E1-09
0.0 to [E1-04]
E1-10
<1> <3>
E1-11
0.0 to [E1-04]
0.0 Hz <5>
E1-12
E1-13
Base Voltage
Frequency (Hz)
200
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
E2-01
Note: 1. This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The
value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
Note: If the motor rated current in E2-01 is set lower than the motor no-load current in E2-03, than a parameter setting error will occur
(oPE02). E2-03 must be set correctly to prevent this error.
Parameter Name
Motor Rated Slip
Setting Range
Default
0.00 to 20.00 Hz
If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate
and the formula below:
E2-02 = f - (n p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)
Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor noload current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
No.
Parameter Name
Setting Range
Default
E2-03
0 to [E2-01]
(unit: 0.01 A)
Note: This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01.
The value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer
to Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW
Parameter Name
Setting Range
Default
E2-04
2 to 48
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
201
Parameter Details
Parameter Name
Motor Line-to-Line Resistance
Setting Range
Default
0.000 to 65.000
Parameter Name
Motor Leakage Inductance
Setting Range
Default
0.0 to 40.0%
Parameter Name
Setting Range
Default
E2-07
0.00 to 0.50
0.50
Parameter Name
Setting Range
Default
E2-08
E2-07 to 0.75
0.75
Parameter Name
Setting Range
Default
E2-09
0.0 to 10.0%
0.0%
202
Parameter Name
Motor Iron Loss for Torque Compensation
Setting Range
Default
0 to 65535 W
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
E2-11
0.00 to 650.00 kW
Determined by o2-04
Enter the motor rated current listed on the nameplate of the motor to E2-01.
Setting the Motor Rated Slip
Use the base speed listed on the motor nameplate to calculate the rated slip. Refer to the formula below, then enter that
value to E2-02.
Motor rated slip = rated frequency [Hz] base speed [r/min] (no. of motor poles) / 120
Setting the No-Load Current
Enter the no-load current at rated frequency and rated voltage to E2-03. The no-load current is not usually listed on the
nameplate. Contact the motor manufacturer if the data cannot be found.
The default setting of the no-load current is for performance with a 4-pole Yaskawa motor.
Setting the Number of Motor Poles
Only required in V/f Control with PG and Closed Loop Vector Control. Enter the number of motor poles as indicated on
motor nameplate.
Setting the Line-to-Line Resistance
E2-05 is normally set during Auto-Tuning. If Auto-Tuning cannot be performed, contact the manufacturer of the motor to
find out what the correct resistance is between motor lines. The motor test report can also be used to calculate this value:
E-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75C.
B-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75C.
F-type insulation: Multiply 0.87 times the resistance value () listed on the test report at 115C.
The motor leakage inductance set to E2-06 determines the amount of voltage drop relative to the motor rated voltage.
This value should be entered particularly for motors with a low degree of inductance, such as high-speed motors. As this
information is not listed on the motor nameplate, contact the motor manufacturer to find out the correct value for the
motor leakage inductance.
Setting the Motor Iron-Core Saturation Coefficient 1, 2
The drive only requires this information when using Closed Loop Vector Control. The drive compensates for the degree
of mechanical loss with torque compensation. Although E2-09 rarely needs to be changed, adjustment may benefit the
following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
Setting the Motor Iron Loss for Torque Compensation
This value only needs to be set when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to
improve the precision of torque compensation.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
203
Parameter Name
Setting Range
Default
E3-01
0 to 3
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in Figure 5.53.
Note: Certain E3- parameters might not be visible depending on the control mode. Refer to Parameter Table on page 408.
No.
Parameter Name
Setting Range
Default
E3-04
40.0 to 400.0 Hz
<2> <5>
E3-05
<1> <2>
E3-06
0.0 to [E3-04]
<2> <5>
<2> <5>
E3-07
0.0 to [E3-04]
E3-08
<1> <2>
E3-09
0.0 to [E3-04]
<2> <5>
E3-10
<1> <2>
E3-11
0.0 to [E3-04]
0.0 Hz <4>
E3-12
E3-13
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
<5> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMR-ATA).
For default value of China localized drive (Model code: CIMR-ABB), refer to Default Values of the China Localized Drive: CIMR-ABA
on page 465.
Figure 5.53
Output (V)
E3-05
E3-12
E3-13
E3-08
common_TMonly
E3-10
E3-09
204
The following conditions must be true when setting up the V/f pattern: E3-09 E3-07 < E3-06 E3-11 E3-04
To make the V/f pattern a straight line at a frequency lower than E3-07, set E3-09 = E3-07. With this setting, E3-08 is disregarded.
Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
E3-11, E3-12, and E3-13 rarely need to be changed, and should only be used to fine-tune the V/f pattern in the constant output range.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
E4-01
Setting Range
Default
Note: 1. This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The
value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to
Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW
2. If the motor rated current in E4-01 is set lower than the motor no-load current in E4-03, then a parameter setting error will occur
(oPE02). E4-03 must be set correctly to prevent this error.
Parameter Name
E4-02
Setting Range
Default
0.00 to 20.00 Hz
No.
E4-03
Parameter Name
Motor 2 Rated No-Load Current
Setting Range
Default
0 to [E4-01]
Note: This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01.
The value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer
to Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
Parameter Name
Setting Range
Default
E4-04
2 to 48
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Set the no-load current for motor 2 in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor noload current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
205
Parameter Name
E4-05
Setting Range
Default
0.000 to 65.000
Parameter Name
Setting Range
Default
E4-06
0.0 to 40.0%
Parameter Name
Setting Range
Default
E4-07
0.00 to 0.50
0.50
Parameter Name
Setting Range
Default
E4-08
[E4-07] to 0.75
0.75
Parameter Name
Setting Range
Default
E4-09
0.0 to 10.0%
0.0%
Parameter Name
Setting Range
Default
0 to 65535 W
206
No.
Parameter Name
Setting Range
Default
E4-11
0.00 to 650.00 kW
Determined by o2-04
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
E5-01
Setting Range
Default
0000 to FFFF
Determined by A1-02,
C6-01 and o2-04
Note: 1. If E5-01 was set a value besides FFFF and is then changed to FFFF, the value of parameters E5-02 through E5-24 will not change.
2. If using a different motor other than Yaskawas SMRA, SSR1, or SST4 series, then E5-01 should be set to FFFF.
3. The default setting is below:
OLV/PM, AOLV/PM: Yaskawa SSR1 Series (1750 r/min)
CLV/PM: Yaskawa SSR4 Series (1750 r/min)
0000
Motor Voltage Class
and Capacity
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
YEC_TMonly
Parameter Name
Setting Range
Default
E5-02
0.10 to 650.00 kW
Determined by E5-01
Parameter Name
Setting Range
Default
E5-03
Determined by E5-01
Note: This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01.
The value will have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer
to Table A.2 and Table A.3) and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
207
Parameter Details
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
2: Rated Torque for IPM
Motors
(SST4 Series)
Parameter Name
Setting Range
Default
E5-04
2 to 48
Determined by E5-01
Parameter Name
Setting Range
Default
E5-05
0.000 to 65.000
Determined by E5-01
Parameter Name
Setting Range
Default
E5-06
0.00 to 300.00 mH
Determined by E5-01
Parameter Name
Setting Range
Default
E5-07
0.00 to 600.00 mH
Determined by E5-01
Parameter Name
Setting Range
Default
E5-09
Determined by E5-01
Note: Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or
if neither parameter is set to 0. When E5-01 = FFFF, then E5-09 = 0.0.
Parameter Name
Setting Range
Default
E5-11
0.0 deg
Parameter Name
Setting Range
Default
E5-24
Determined by E5-01
Note: Ensure that E5-09 = 0 when setting parameter E5-24. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or
if neither parameter is set to 0. When E5-01 = FFFF, then E5-09 = 0.0.
208
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.6
F: Option Settings
Parameters
CN5-C only
CN5-B only
F1-31 to F1-37
Parameter Name
Option Port
Setting Range
Default
F1-01
CN5-C
0 to 60000 ppr
Determined by A1-02
F1-31
CN5-B
0 to 60000 ppr
<1>
Parameter Name
Option Port
Setting Range
F1-02
CN5-B, CN5-C
0 to 3
Default
1
F1-14
CN5-B, CN5-C
0.0 to 10.0 s
2.0 s
Parameter Details
F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An overspeed error (oS) is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set
in F1-09. The stopping method when an overspeed fault occurs can be selected in parameter F1-03.
No.
Parameter Name
Option Port
Setting Range
F1-03
CN5-B, CN5-C
0 to 3
Default
1
F1-08
CN5-B, CN5-C
0 to 120%
115%
F1-09
CN5-B, CN5-C
0.0 to 2.0 s
Determined by A1-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
209
Parameter Name
Option Port
Setting Range
F1-04
CN5-B, CN5-C
0 to 3
Default
3
F1-10
CN5-B, CN5-C
0 to 50%
10%
F1-11
CN5-B, CN5-C
0.0 to 10.0 s
0.5 s
Parameter Name
Option Port
Setting Range
Default
F1-05
PG 1 Rotation Selection
CN5-C
0, 1
Determined by A1-02
F1-32
PG 2 Rotation Selection
CN5-B
0, 1
(1 + n)
m
common_TMonly
Example: To have a ratio of 1/32 between the PG card pulse input and output, set F1-06 = 032.
No.
Parameter Name
Option Port
Setting Range
Default
F1-06
CN5-C
1 to 132 (1 to 1 )
F1-35
CN5-B
1 to 132 (1 to 1 )
32
32
common_TMonly
No.
Parameter Name
Option Port
Setting Range
Default
F1-12
PG 1 Gear Teeth 1
CN5-C
0 to 1000
F1-13
PG 1 Gear Teeth 2
CN5-C
0 to 1000
F1-33
PG 2 Gear Teeth 1
CN5-B
0 to 1000
F1-34
PG 2 Gear Teeth 2
CN5-B
0 to 1000
210
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Option Port
Setting Range
Default
F1-18
CN5-B, CN5-C
0 to 10
10
Note: A common cause for a dv3 fault is the incorrect setting of E5-11. Make sure the correct Z pulse offset has been entered to E5-11.
Parameter Name
Option Port
Setting Range
Default
F1-19
CN5-B, CN5-C
0 to 5000
128
Note: 1. A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure the correct Z pulse offset is set to E5-11.
2. Set F1-19 to 0 for applications where the direction of the load is the opposite of the speed reference.
Parameter Name
Option Port
Setting Range
Default
F1-20
CN5-C
0, 1
F1-36
CN5-B
0, 1
Setting 0: Disabled
Setting 1: Enabled
No.
Parameter Name
Option Port
Setting Range
Default
F1-21
PG 1 Signal Selection
CN5-C
0, 1
F1-37
PG 2 Signal Selection
CN5-B
0, 1
Parameter Name
Setting Range
Default
F1-30
0, 1
Setting 0: CN5-C
Setting 1: CN5-B
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
211
Parameter Details
Determines whether the signal to the PG option card is single track or two track.
Parameter Name
Setting Range
Default
F2-01
0, 1
Setting 0: Separate functions for each terminal (V1, V2, V3 replace terminals A1, A2, A3)
Apply this setting to replace the drive terminals A1, A2, and A3 by the option board terminals V1, V2, and V3.
Functions, gain, and bias levels for an analog reference supplied by AI-A3 are set using the H3- parameters as
described in H3-03, H3-04: Terminal A1 Gain and Bias Settings on page 237.
Note: Parameter setting error oPE05 will occur if option card terminals are set for separate input functions (F2-01 = 0) while b1-01 = 3.
With this setting, all three input signals on the AI-A3 option card are added together to create the frequency reference.
When the option card is the source of the frequency reference for the drive, parameter b1-01 must be set to 3. Gain and
bias settings for the frequency reference supplied from AI-A3 can be set using parameters F2-02 and F2-03.
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the
combined input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
Parameter Name
Setting Range
Default
F2-02
-999.9 to 999.9%
100.0%
F2-03
-999.9 to 999.9%
0.0%
Parameter Name
Setting Range
Default
F3-01
0 to 7
212
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
F3-03
0 to 2
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
Parameter Name
Setting Range
Default
F4-01
000 to 999
102
F4-03
000 to 999
103
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set
as a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is
limited to 10 V.
No.
Parameter Name
Setting Range
Default
F4-02
-999.9 to 999.9%
100.0%
F4-04
-999.9 to 999.9%
50.0%
F4-05
-999.9 to 999.9%
0.0%
F4-06
-999.9 to 999.9%
0.0%
When viewing the values set to F4-02 or F4-05 on the digital operator, a voltage equal to 100% of the parameter being
viewed (including current gain and bias settings) will be output from terminal V1 or V2. When viewing the value set to
F4-05 or F4-06, terminal V1 or V2 will output a voltage equal to 0% of the parameter being viewed (including current
gain and bias settings).
Example 1: F4-02 = 0%, F4-02 = 80%. When the parameter setting display for F4-02 is accessed using the digital
operator, terminal V1 will output a voltage of 8 V, even when the drive is stopped.
Example 2: F4-03 = 5%. When the parameter setting display for F4-03 is accessed using the digital operator, terminal V1
will output a voltage of 0.5 V, even when the drive is stopped.
F4-07, F4-08: Terminal V1, V2 Signal Level
Sets the output signal level for terminals V1 and V2.
No.
Parameter Name
Setting Range
Default
F4-07
0, 1
F4-08
0, 1
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
213
Parameter Details
Name
Setting Range
Default
F5-01
0 to 192
2: Speed agree
F5-02
0 to 192
4: Frequency detection 1
F5-03
0 to 192
6: Drive ready
37: During frequency output
F5-04
0 to 192
F5-05
0 to 192
F: Not used
F5-06
0 to 192
F: Not used
0 to 192
0: During run
0 to 192
1: Zero speed
F5-07
F5-08
Parameter Name
Setting Range
Default
F5-09
0 to 2
Communication Protocol
CC-Link
MECHATROLINK-II
PROFIBUS-DP
CANopen
DeviceNet
F6-20 to F6-26
F6-30 to F6-32
F6-35 to F6-36
F6-50 to F6-63
Parameter Name
Setting Range
Default
F6-01
0 to 3
214
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Setting Range
Default
F6-02
0 or 1
Parameter Name
Setting Range
Default
F6-03
0 to 3
Parameter Name
Setting Range
Default
F6-06
0, 1
Setting 0: Enabled
Setting 1: Disabled
Parameter Name
Setting Range
Default
F6-07
0, 1
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option .
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-) are reset when the drive is initialized using parameter
A1-03.
No.
Parameter Name
Setting Range
Default
F6-08
0, 1
Setting 0: Do not reset parameters F6- when the drive is initialized with A1-03
Setting 1: Reset F6- when the drive is initialized with A1-03
Note: F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive with A1-03 resets the other
communication parameters, F6-.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
215
Parameter Details
If the NetRef command is selected, multi-step speed input frequency references are disabled.
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card CC-Link Installation Manual and
Technical Manual.
MECHATROLINK Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card MECHATROLINK-II Installation
Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card PROFIBUS-DP Installation Manual
and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card CANopen Installation Manual and
Technical Manual.
DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card DeviceNet Installation Manual and
Technical Manual.
216
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.7
H: Terminal Functions
Parameter Name
Setting
Range
Default
H1-01
1 to 9F
H1-02
1 to 9F
H1-03
0 to 9F
H1-04
0 to 9F
H1-05
0 to 9F
H1-06
0 to 9F
H1-07
0 to 9F
H1-08
0 to 9F
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Setting
3-wire sequence
Function
218
34
224
Local/remote selection
218
35
224
219
40
41
42
43
219
Function
Page
224
224
219
44
Offset frequency 1
219
45
Offset frequency 2
46
Offset frequency 3
47
Node setup
225
219
60
225
220
61
225
220
62
225
PG encoder disable
220
63
Field Weakening
225
220
65
Through mode
220
66
67
68
225
6A
Drive enabled
226
219
225
225
10
Up command
11
Down command
12
Forward jog
13
Reverse jog
71
226
14
Fault reset
221
72
Zero Servo
226
15
221
75
Up 2 command
16
Motor 2 selection
222
76
Down 2 command
17
221
77
226
18
222
78
227
220
221
225
226
19
PID disable
223
7A
1A
223
7B
1B
Program lockout
223
7C
1E
223
7D
227
227
227
20 to 2F
External fault
223
7E
224
90 to 97
31
224
9F
DriveWorksEZ disabled
32
224
30
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Setting
227
227
217
When one of the digital inputs is programmed for 3-wire control, that input becomes a forward/reverse directional input,
S1 becomes the Run command input, and S2 becomes the Stop command input.
The drive will start the motor when the input S1 set for the Run command is closed for longer than 2 ms. The drive will
stop the operation when the Stop input S2 is released for a brief moment. Whenever the input programmed for 3 wire
sequence is open, the drive will be set for forward direction. If the input is closed, the drive is set for reverse direction.
Note: When 3-wire sequence is selected, the Run and Stop commands must be input via S1 and S2.
Figure 5.55
Stop Switch
(N.C.)
Run Switch
(N.O.)
DRIVE
S1
S2
S5
SC
2 ms min.
Can be either ON or OFF
Run command
Stop command
OFF (stopped)
Forward/reverse
command
OFF (forward)
ON (reverse)
Motor speed
TIME
Stop
Forward
Reverse
Stop
Foward
This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.
Status
Closed
Open
Description
LOCAL: Frequency reference and Run command are input from the digital operator.
REMOTE: Frequency reference and Run command are input from the external reference that has been selected. If a digital input set to H1- = 2 is active, they will
be read from external reference source 2 (b1-15 and b1-16). Otherwise they will be read from external reference source 1 (b1-01 and b1-02).
Note: 1. If one of the multi-function input terminals is set to for LOCAL/REMOTE, then the LO/RE key on the operator will be disabled.
2. When the drive is set to LOCAL, the LO/RE LED will light.
3. The default setting of the drive is not to allow switching between LOCAL and REMOTE during run. To allow the drive to switch
between LOCAL and REMOTE during run, Refer to b1-07: LOCAL/REMOTE Run Selection on page 143.
218
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
This function can be used to switch the Run command and frequency reference source between External reference 1 and
2 if the drive is in the REMOTE mode.
Status
Description
Open
Closed
Note: With default settings the drive is not to allow switching between External reference 1 and 2 during run. Refer to b1-07: LOCAL/
REMOTE Run Selection on page 143 if this feature is required by the application.
Used to switch multi-step speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1: Frequency
Reference on page 182 for details.
Setting 6: Jog reference selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.
Refer to d1: Frequency Reference on page 182 for details.
Setting 7: Accel/decel time selection 1
Used to switch between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04). Refer to C1-01 to C1-08:
Accel, Decel Times 1 to 4 on page 166 for details.
Setting 8, 9: Baseblock command (N.O., N.C.)
When the drive receives a Baseblock command, the output transistor stop switching and the motor coasts to stop. During
this time, the alarm bb will flash on the digital operator to indicate baseblock. When baseblock ends and a Run
command is active, the drive performs Speed Search to get the motor running again.
Drive Operation
Input Open
Input Closed
Setting 8 (N.C.)
Normal operation
Setting 9 (N.O.)
Normal operation
NOTICE: If using baseblock in hoist applications, make sure the brake closes when the drive output is cut off by a Baseblock
command triggered via one of the input terminals. Failure to do so will result in the motor suddenly coasting when the Baseblock
command is entered, causing the load to slip.
Figure 5.57
Baseblock input
OFF
ON
ON
Frequency
reference
Parameter Details
Run command
Baseblock
release
common_
TMonly
Output frequency
Output off, motor coasts
When the digital input programmed for the Accel/decel ramp hold function closes, the drive will lock (hold) the output
frequency. Acceleration or deceleration will resume once the input is opened again.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive will save the output frequency to memory
whenever the Ramp Hold input is closed. When the drive is restarted after stop or after power supply interruption, the
output frequency that was saved will become the frequency reference (provided that the Accel/decel ramp hold input is
still closed). Refer to d4-01: Frequency Reference Hold Function Selection on page 185 for details.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
219
Triggers an oH2 alarm when the contact closes. Because this is an alarm, drive operation is not affected.
Setting C: Analog terminal input selection (terminal A1, A2, A3)
When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog
terminals.
Setting D: PG encoder disable
When closed the drive disregards PG feedback from the motor when using V/f Control with PG. When the terminal is
opened again, the drive resumes using PG feedback to control motor speed.
Setting E: ASR integral reset
Switches between PI control or simply P control by resetting the integral value. As long as the terminal is closed, integral
operation is disabled and the drive uses P control. When the terminal opens, PI control resumes.
Setting F: Through mode
Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function
in the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or
MEMOBUS/Modbus communications.
Setting 10, 11: Up, Down command
Using the Up/Down function allows the frequency reference to be set by two push buttons. One digital input must be
programmed as the Up input (H1-= 10) to increase the frequency reference, and the other one must be programmed
as the Down input (H1-= 11) to decrease the frequency reference.
The Up/Down function has priority over the frequency references from the digital operator, the analog inputs, and the
pulse input (b1-01 = 0, 1, 4). If the Up/Down function is used, then references provided by these sources will be
disregarded.
The inputs operate as shown in the table below.
Status
Up (10)
Down (11)
Drive Operation
Open
Open
Closed
Open
Open
Closed
Closed
Closed
Note: 1. An oPE03 alarm will occur when only one of the functions Up/Down is programmed for a digital input.
2. An oPE03 alarm will occur if the Up/Down function is assigned to the terminals while another input is programmed for the Accel/
decel ramp hold function. For more information on alarms, Refer to Drive Alarms, Faults, and Errors on page 304.
3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference
switching command (H1- = 2).
220
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output frequency
upper limit
Accelerates to
lower limit
Same
frequency
d4-01 = 1
d4-01 = 0
Lower limit
ON
FWD run/stop
common_
TMonly
ON
Up command
Frequency
reference
reset
ON
Down command
ON
ON
Power supply
Digital inputs programmed as Forward Jog (H1- = 12) and Reverse Jog (H1- = 13) will be Jog inputs that do not
require a Run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog frequency
reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The
Forward Jog and Reverse Jog command can be set independently.
Note: The Forward Jog and Reverse Jog commands override all other frequency references. However, if the drive is set to prohibit
reverse rotation (b1-04 = 1), then activating Reverse Jog will have no effect. If both the Forward Jog and Reverse Jog are input
simultaneously for 500 ms or more, an alarm will occur and the drive will ramp to stop.
Figure 5.59
d1-17
Output
Frequency
FJOG
ON
RJOG
ON
common_
TMonly
Whenever the drive detects a fault condition, the fault output contact will close and the drives output will shut off. The
motor then coasts to stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat).
Once the Run command is removed, the fault can be cleared by either the RESET key on the digital operator or by
closing a digital input configured as a Fault Reset (H1- = 14).
Note: Fault Reset commands are ignored as long as the Run command is present. To reset a fault, first remove the Run command.
The Fast Stop function operates much like an emergency stop input to the drive. If a Fast Stop command is input while
the drive is running, the drive will decelerate to a stop by the deceleration time set to C1-09 (Refer to C1-09: Fast Stop
Time on page 167). The drive can only be restarted after is has come to a complete stop, the Fast Stop input is off, and
the Run command has been switched off.
To trigger the Fast Stop function with a N.O. switch, set H1- = 15.
To trigger the Fast Stop function with a N.C. switch, set H1- = 17.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
221
Parameter Details
d1-17
Run/Stop
ON
Fast-Stop
H1= 17
ON
ON
ON
Decelerates at C1-09
Output Frequency
TIME
common_
TMonly
The drive has the capability to control two induction motors independently. A second motor may be selected using a
multi-function digital input as shown in Figure 5.61.
Note: The motor 2 selection function cannot be used when PM motor is used.
Figure 5.61
Drive
Motor 1
Motor 2
common_
TMonly
When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below,
Table 5.36 lists the parameters that correspond to each motor.
Table 5.36 Parameters for Switching Between Two Motors
No.
C1-01 to C1-04
C1-05 to C1-08
C3-21 to C3-25
C4-01
C4-07
E1-, E2-
E3- to E4-
F1-01 to F1-21
Note: 1.
2.
3.
4.
When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger the rUn alarm.
There is a 500 ms delay when switching between motors equipped with a PG encoder for feedback.
The motor 2 selection function cannot be used when PM motor is used.
If a digital output is programmed for Motor 2 selection (H1-01, H1-02, or H1-03 = 1C), motor will be selected when
the output is closed.
Setting 18: Timer function input
This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the
timer function output (H2- = 12). Refer to b4: Delay Timers on page 152 for details.
222
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
When the PID function has been enabled by parameter b5-01, it can be indefinitely disabled by closing a digital input.
When the input is released, the drive resumes PID operation. Also refer to PID Block Diagram on page 155.
Setting 1A: Accel/decel time selection 2
Used to select accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command. Refer to C1-01 to
C1-08: Accel, Decel Times 1 to 4 on page 166 for details.
Setting 1B: Program lockout
When an input is programmed for Program Lockout, parameters values cannot be changed as long as this input is open (it
is still possible to view and monitor parameter settings).
Setting 1E: Reference sample hold
This function allows the user to sample an analog frequency reference signal being input to terminal A1, A2, or A3 and
hold the frequency reference at the sampled level. Once the Analog Frequency Reference Sample/Hold function is held
for at least 100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as
illustrated in Figure 5.62.
When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.
Figure 5.62
Frequency
reference
l
na
g
alo
sig
An
Time
OFF
Referenece
Sample Hold Input
100 ms
ON
common_
TMonly
100 ms
An oPE03 error will occur when one of the following functions is used simultaneously with the Analog frequency
reference sample/hold command.
Hold accel/decel stop (setting: A)
Up command, Down command (setting: 10, 11)
Offset frequency (setting: 44 to 46)
Up or Down functions (setting: 75, 76)
By using the External fault command, the drive can be stopped when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to any value between 20 to 2F. The digital
operator will display EF where is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal S3, EF3 will be displayed.
Select the value to be set in H1- from a combination of any of the following three conditions:
Signal input level from peripheral devices (N.O., N.C.)
External fault detection method
Operation after external fault detection
The following table shows the relationship between the conditions and the value set to H1-:
Terminal Status <1>
Setting
20
N.O.
O
21
22
Always Detected
Stopping Method
Ramp to Stop
(fault)
O
O
O
Detected during
Run only
23
24
N.C.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Coast to Stop
(fault)
Fast Stop
(fault)
Parameter Details
Alarm Only
(continue running)
223
N.O.
25
26
2F
Stopping Method
Ramp to Stop
(fault)
Coast to Stop
(fault)
Fast Stop
(fault)
O
O
O
O
O
O
Alarm Only
(continue running)
O
O
O
O
2D
2E
2B
2C
Detected during
Run only
29
2A
Always Detected
27
28
N.C.
O
O
O
O
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.
By configuring one of the digital inputs for PID integral reset (H1- = 30), the value of the integral component in PID
control will be reset to 0 whenever the terminal is closed. Refer to PID Block Diagram on page 155 for more details.
Setting 31: PID integral hold
By configuring a digital input for Integral Hold (H1-0 = 31), the value of the integral component of the PID control is
locked as long as the input is active. The PID controller resumes integral operation from the hold value as soon as the
integral hold input is released. Refer to PID Block Diagram on page 155 for more information on this function.
Setting 32: Multi-Step Speed Reference 4
Used to select the multi-step speeds d1-09 to d1-16 in combination with the input terminal set for Multi-Step Speed 1, 2
and 3. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference on page 182.
Setting 34: PID soft starter cancel
A digital input configured as a PID soft starter cancel input (H1-0 = 34) can be used to enable or disable the PID soft
starter and thereby canceling the PID accel/decel time (b5-17). Refer to PID Block Diagram on page 155.
Setting 35: PID input level selection
Allows and input terminal to switch the sign of the PID input. Refer to PID Block Diagram on page 155 for details.
Setting 40, 41: Forward run, Reverse run command for 2-wire sequence
Drive
Forward Run
S1
Reverse Run
S2
SC Digital Input Common
common_
TMonly
Setting 42, 43: Run and direction command for 2-wire sequence 2
224
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
These inputs can be used to add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference. Refer to d7-01 to
d7-03: Offset Frequency 1 to 3 on page 195 for details.
Setting 47: Node setup
If the SI-S3 option card is connected, closing this terminal will set a node address for operation on a CANopen network.
Setting 60: DC Injection Braking command
When a DC Injection Braking command is input while the drive is stopped, DC Injection Braking operation is activated.
When a Run command or a Jog command is input, DC Injection Braking is released. Refer to b2: DC Injection Braking
and Short Circuit Braking on page 144 for details on setting up the DC Injection Braking function.
The diagram below illustrates how the DC Injection Braking function works.
Figure 5.64
DC Injection braking
command
OFF
ON
OFF
OFF
OFF
ON
DC Injection
braking
DC Injection Braking
Start Frequency
(b2-01)
Output frequency
DC Injection
braking
common_
TMonly
These input functions can be used to enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start). Refer
to Activating of Speed Search on page 149 for details on how to use the input signals. Refer to b3: Speed Search on
page 147 for more about Speed Search.
Note: Operator error oPE03 will result if both Speed Search 1 and Speed Search 2 are set to the input terminals at the same time.
Enabled in V/f Control. When closed, Field Weakening is performed. For details, Refer to d6: Field Weakening and
Field Forcing on page 194.
Setting 65, 66: KEB Ride-Thru 1 (N.C.), 2 (N.O.)
Parameter Details
Used to enable the KEB Ride-Thru function selected in parameter L2-29. Refer to KEB Ride-Thru Function on
page 252 for more information on this function.
Drive Operation
Input Open
Input Closed
Setting 65 (N.C.)
Normal operation
Setting 66 (N.O.)
Normal operation
Note: Both KEB Ride-Thru 1 and 2 cannot be assigned to the input terminals at the same time. This will trigger setting error oPE03.
The drive has a built-in function for self-diagnosing serial communications operation. The test involves wiring the send
and receive terminals of the RS-485/422 port together. The drive transmits data and then confirms that the
communications are received normally. Refer to Self-Diagnostics on page 515 for details on how to use this function.
Setting 68: High Slip Braking
Closing an input programmed for this function triggers High Slip Braking (available only in V/f and V/f w/PG control
modes). Once HSB is started, the drive has to come to a complete stop and the HSB command must be removed before a
restart can be performed. Refer to n3: High Slip Braking (HSB) and Overexcitation Braking on page 279.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
225
A digital input configured as a Drive enable (H1- = 6A) will prevent the drive from executing a Run command
until the input is closed. When the input is open, the digital operator will display dnE to indicate that the drive is
disabled.
If a Run command is enabled before the terminal set for Drive enable closes, then the drive will not run until the Run
command is cycled (i.e., a new Run command is required). If the input is opened while the drive is running, the drive will
stop according to the stop method set to b1-03 (Refer to b1-03: Stopping Method Selection on page 139).
Setting 71: Speed/Torque Control switch
Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed,
and Speed Control is enabled when the terminal is open. Note that parameter d5-01 must be set to 0 when using this
function. Refer to d5: Torque Control on page 190 and Switching Between Torque and Speed Control on page 192.
Setting 72: Zero Servo
Used to activate the Zero Servo function that can be used to lock the rotor at a certain position. Refer to b9: Zero Servo
on page 165 for details.
Setting 75, 76: Up 2, Down 2 command
The Up 2 and Down 2 function can be used to add a bias to the frequency reference. The input programmed for 75 will
increase the bias and the input programmed for 76 will decrease it. Table 5.37 explains how the Up/Down 2 function
works depending on the frequency reference source and parameters d4-01, d5-03, and d4-05. Refer to d4: Frequency
Reference Hold and Up/Down 2 Function on page 185 for detailed explanations of these and other Up/Down 2 related
parameters.
Note: 1. The Up 2 and Down 2 functions must be set as a pair.
2. When using the Up 2 and Down 2, set appropriate bias limit values to parameters d4-08 and d4-09.
d4-03
d4-05
0
Multi-Step Speed
Reference
4
Multi-Step Speed
Reference
10
--
Value
other than
0
--
0
Other
(analog comm., etc.)
8
9
Operation
d4-01
Other
(analog comm, etc.)
-0
Value other
than 0
--
Frequency Saved
Not saved
If the bias and frequency reference are
constant for 5 s, the bias is added to the
active frequency reference and reset
afterwards.
Not saved
If the bias and frequency reference are
constant for 5 s, the bias is added to the
active frequency reference and reset
afterwards.
Not saved
If the bias is constant for 5 s, it is saved to
parameter d4-06. The frequency reference
cannot be overwritten, so only the bias is
saved.
Not saved
If the bias is constant for 5 s, it is saved to
parameter d4-06. The frequency reference
cannot be overwritten, so only the bias is
saved.
Switches the ASR gain between the values set to C5-01 and C5-03. The gain set to C5-03 is enabled when the terminal is
closed, and C5-01 is enabled when the terminal opens again. See C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain
1, 2 / ASR Integral Time 1, 2 on page 175 for a more detailed description.
226
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Reverses the direction of the torque reference when the terminal closes. Refer to d5: Torque Control on page 190 and
Setting the Torque Reference, Speed Limit, and Torque Compensation Values on page 191 for details.
Setting 7A, 7B: KEB Ride-Thru 2 (N.C., N.O.)
An input terminal set to 7A or 7B can trigger Single Drive KEB Ride-Thru during deceleration. If enabled, L2-29 is
disregarded. Refer to KEB Ride-Thru Function on page 252 for details.
Drive Operation
Input Open
Input Closed
Setting 7A (N.C.)
Normal operation
Setting 7B (N.O.)
Normal operation
Note: KEB Ride-Thru 1 and 2 cannot both be assigned to the input terminals at the same time. Doing so will trigger an oPE3 error.
Setting 7C, 7D: Short Circuit Braking (N.O., N.C.) (OLV/PM, AOLV/PM)
An input programmed for this function can be used to activate Short Circuit Braking in Open Loop Vector control modes
for PM motors. By linking all three phases of a PM motor, Short Circuit Braking creates a braking torque that can be used
to stop a rotating motor or prevent a motor from coasting due to external forces (such as the windmill effect in fan
applications). Parameter b2-18 can be used to limit the current during Short Circuit Braking.
Drive Operation
Input Open
Input Closed
Setting 7C (N.O.)
Normal operation
Setting 7D (N.C.)
Short-Circuit Braking
Normal operation
Setting 7E: Forward/reverse detection (for V/f Control with Simple PG Feedback)
When a digital input is programmed for this function, the input determines the motor rotation direction for V/f Control
with Simple PG feedback (A1-02 = 0 and H6-01 = 3). If the input is open, the speed feedback signal is considered to be
forward. If the input is closed, it is considered to be in reverse. Refer to H6: Pulse Train Input/Output on page 244.
Setting 90 to 97: DriveWorksEZ Digital Input 1 to 8
These settings are for digital inputs functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 9F: DriveWorksEZ Disable
Status
Description
Open
DriveWorksEZ enabled
Closed
DriveWorksEZ disabled
Parameter Details
This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function
is effective only if A1-07 = 2.
The drive has three multi-function output terminals. Table 5.38 lists the functions available for theses terminals using
H2-01, H2-02, and H2-03.
No.
Parameter Name
Setting Range
Default
H2-01
0 to 192
0: During run
H2-02
0 to 192
1: Zero Speed
H2-03
0 to 192
2: Speed agree 1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
227
Page
Setting
During run
Function
228
1D
During regeneration
Function
Page
Zero Speed
228
1E
Restart enabled
234
Speed agree 1
229
1F
234
229
20
234
Frequency detection 1
230
22
234
Frequency detection 2
230
2F
Maintenance period
235
Drive ready
230
30
235
DC bus undervoltage
231
31
235
231
32
235
231
33
235
231
37
235
231
38
Drive enabled
235
231
39
235
231
3C
LOCAL/REMOTE Status
235
236
234
Fault
231
3D
Through mode
232
3E
236
10
Minor fault
232
3F
236
11
232
4A
236
12
Timer output
232
4B
236
13
Speed agree 2
232
4C
236
14
232
4D
236
15
Frequency detection 3
233
4E
236
16
Frequency detection 4
233
4F
236
17
60
236
18
61
236
19
231
90
1A
During reverse
234
91
1B
234
92
1C
Motor 2 selection
234
100 to 192
231
236
236
Description
Drive is stopped.
A Run command is input or the drive is during deceleration or during DC injection.
Figure 5.65
Run command
OFF
Baseblock
command
OFF
ON
ON
Output
frequency
During Run
OFF
common_
TMonly
ON
Terminal closes whenever the output frequency or motor speed (CLV, CLV/PM) falls below the minimum output
frequency set to E1-09 or b2-01.
Status
Open
Closed
Description
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Note: When using CLV or CLV/PM control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed
level is the minimum output frequency set to E1-09.
228
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output frequency
or
motor speed
OFF
Zero Speed
common_
TMonly
ON
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02)
of the current frequency reference regardless of the direction.
Status
Open
Closed
Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-02.
Frequency
reference
Output Frequency
or Motor Speed
L4-02
L4-02
OFF
Speed agree 1
ON
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 265 for more details.
Setting 3: User-set speed agree 1 (fref/fset Agree 1)
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the
speed agree width (L4-02) of the programmed speed agree level (L4-01).
Description
Open
Output frequency or motor speed and frequency reference are not both within the range of L4-01 L4-02.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-01 L4-02.
Parameter Details
Status
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.68
Output Frequency
or Motor Speed
Frequency
reference
L4-01
Output
frequency
+/- L4-02
L4-01
Frequency
reference
User Set
Speed Agree 1
OFF
ON
5
+/- L4-02
OFF
ON
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 265 for more instructions.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
229
Output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus
the detection width set in L4-02. The terminal remains open until the output frequency or motor speed falls below the
level set in L4-01.
Status
Open
Closed
Description
Output frequency or motor speed exceeded L4-01 + L4-02.
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.69
Output Frequency
or Motor Speed
L4-02
L4-01
L4-01
L4-02
Frequency
detection 1
ON
common_
TMonly
OFF
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 265 for more details.
Setting 5: Frequency Detection 2
Output closes whenever the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01.
The terminal remains closed until the output frequency or motor speed falls below L4-01 minus the setting of L4-02.
Status
Open
Closed
Description
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.70
Output Frequency
or Motor Speed
L4-02
L4-01
L4-01
L4-02
Frequency
Detection 2
OFF
ON
common_
TMonly
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 265 for more details.
Setting 6: Drive ready
Output closes whenever the drive is ready to operate the motor. The terminal will not close under the conditions listed
below, and any Run commands will be disregarded.
230
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A
fault in the DC bus circuit will also cause the terminal to set for DC bus undervoltage to close.
Status
Open
Closed
Description
DC bus voltage is above the level set to L2-05
DC bus voltage has fallen below the trip level set to L2-05.
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Closed
Description
Drive is not in a baseblock state.
Baseblock is being executed.
A digital output programmed for this function shows the frequency reference source that is currently selected.
Status
Open
Closed
Description
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15)
Frequency reference is being sourced from the digital operator.
A digital output programmed for this function shows the Run command source that is currently selected.
Status
Open
Closed
Description
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Run command is being sourced from the digital operator.
Setting B, 17, 18, 19: Torque detection 1 (N.O., N.C.), Torque detection 2 (N.O., N.C.)
These digital output functions can be used to signal an overtorque or undertorque situation to an external device.
Setting
Status
Description
Closed
17
Open
18
Closed
19
Open
An output set for this function will be closed if frequency reference loss is detected. Refer to L4-05: Frequency
Reference Loss Detection Selection on page 265 for details.
Setting D: Braking resistor fault
An output programmed for this function will close when the dynamic braking resistor (DB) overheats or the braking
transistor is in a fault condition.
Setting E: Fault
The digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
231
Parameter Details
Set up the torque detection levels and select the output function from the table below. Refer to L6: Torque Detection on
page 267 for details.
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function
in the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or
MEMOBUS/Modbus communications.
Setting 10: Minor fault
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Timer output
This setting configures a digital output terminal as output for the timer function. Refer to b4: Delay Timers on page 152
for details.
Setting 13: Speed agree 2 (fref /fout agree 2)
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04) of
the current frequency reference, regardless of the direction.
Status
Open
Closed
Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-04.
Frequency
reference
L4-04
Output Frequency
or Motor Speed
common_
TMonly
L4-04
Speed Agree 2
OFF
ON
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 265 for more details.
Setting 14: User-set speed agree 2 (fref /fset agree 2)
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the
speed agree width (L4-04) of the programmed speed agree level (L4-03). As the detection level L4-03 is a signed value,
detection works in the specified direction only.
Status
Open
Closed
232
Description
Output frequency or motor speed and frequency reference are both outside the range of L4-03 L4-04
Output frequency or motor speed and the frequency reference are both with in the range of L4-03 L4-04
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output Frequency
or Motor Speed
Frequency
reference
L4-03
+/- L4-04
Output Frequency
or Motor Speed
Frequency
reference
User Set
Speed Agree 2
OFF
common_
TMonly
ON
Figure 5.72 User Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 265 for more details.
Setting 15: Frequency detection 3
Output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level
set in L4-03. As the detection level L4-03 is a signed value, the detection works in the specified direction only.
Status
Open
Closed
Description
Output frequency or motor speed exceeded L4-03 plus L4-04.
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
Figure 5.73
Output Frequency
or Motor Speed
L4-04
L4-03
Frequency
detection 3
ON
common_
TMonly
OFF
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 265 for more details.
Output closes whenever the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-03.
The terminal remains closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04. As
the detection level L4-03 is a signed value, frequency detection works in the specified direction only.
Status
Open
Closed
Description
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
Output frequency or motor speed exceeded L4-03.
Figure 5.74
Output Frequency
or Motor Speed
L4-04
L4-03
Frequency
Detection 4
OFF
Parameter Details
common_
TMonly
ON
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 265 for more details.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
233
A digital output set for During reverse will close whenever the drive is running the motor in the reverse direction.
Status
Open
Closed
Description
Motor is being driven in the forward direction or stopped.
Motor is being driven in reverse.
Figure 5.75
Output frequency
During Reverse
OFF
ON
time
common_
TMonly
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status
Open
Closed
Description
Baseblock is being executed.
Drive is not in a baseblock state.
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1- = 16). Refer to Setting 16: Motor 2 selection on page 222 for details on switching motors.
Status
Description
Open
Motor 1 is selected.
Closed
Motor 2 is selected.
An output set for Restart enabled closes once the drive begins attempting to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has begun attempting to restart. If the drive cannot successfully restart within the number of
attempts permitted by L5-01, then a fault will be triggered and the terminal set to 1E will open. Refer to L5: Fault
Restart on page 266 for details on automatic restart.
Setting 1F: Motor overload alarm (oL1)
An output programmed for this function will close when the motor overload level estimated by the oL1 fault detection
exceeds 90% of the oL1 detection level. Refer to L1-01: Motor Overload Protection Selection on page 247.
Setting 20: Drive overheat pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02:
Overheat Alarm Level on page 272 for details on drive overheat detection.
Setting 22: Mechanical weakening detection
Output closes when a mechanical weakening situation is detected. Refer to Mechanical Weakening Detection on
page 269 for details.
234
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components. Components performance life is displayed as a
percentage on the digital operator screen. Refer to Periodic Maintenance on page 353.
Setting 30: During torque limit
Output closes when the motor is operating at the torque limit specified by the L7- parameters or an analog input.
This setting can only be used in OLV, CLV, AOLV/PM and CLV/PM control modes. Refer to L7-01 to L7-04: Torque
Limits on page 271 for details.
Setting 31: During speed limit
Output closes when the speed limit has been reached. This function can be used in CLV and CLV/PM control modes.
Status
Open
Closed
Description
The conditions described below are not present.
1.
2.
3.
The frequency reference has reached the upper limit set in d2-01.
The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency (E1-09).
The motor torque and load torque are not in balance, causing the motor to accelerate. An output terminal set to 32 closes
when the motor reaches the speed limit. Refer to d5: Torque Control on page 190 and Indicating Operation at the Speed
Limit on page 192 for details.
Setting 33: Zero Servo complete
Output closes when Zero Servo is enabled and the load is locked into position within the allowable deviation (b9-02). For
how Zero Servo operates, see b9: Zero Servo on page 165.
Setting 37: During frequency output
Description
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Drive is outputting frequency.
Figure 5.76
baseblock
command
OFF
ON
OFF
ON
Parameter Details
run command
output
frequency
during run
OFF
during frequency
output
OFF
ON
ON
common_
TMonly
A digital output set for Drive enable will reflect the status of a digital input configured as a Drive enable input (H1 = 6A). If that digital input closes, then the digital output set for Drive enable will also close.
Setting 39: Watt hour pulse output
Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 236 for details.
Setting 3C: LOCAL/REMOTE status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
235
Description
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference and Run command source
LOCAL: The digital operator is used as frequency reference and Run command source
Output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 147 for details.
Setting 3E: PID feedback low
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 157 for details.
Setting 3F: PID feedback high
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the
level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 157 for details.
Setting 4A: During KEB operation
Output terminal closes while KEB is being performed. Refer to KEB Ride-Thru Function on page 252 for a KEB
function description.
Setting 4B: During Short Circuit Braking
Output terminal closes when a Fast Stop is being executed. Setting 15, 17: Fast Stop (N.O., N.C.) on page 221.
Setting 4D: oH pre-alarm time limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after ten frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm
Operation Selection on page 272 for a more detailed description.
Setting 4E: Braking transistor fault (rr)
Output closes if the drives internal braking transistor reaches the overheat level.
Setting 4F: Braking resistor overheat (rH)
The braking resistor may overheat due to motor regeneration or too short of a deceleration time setting. The output
terminal closes when the braking resistor exceeds the overheat level.
Setting 60: Internal cooling fan alarm
Output closes when the drives internal cooling fan has failed.
Setting 61: Rotor position detection complete
After the Run command is given, the output terminal signals that the drive has detected the rotor position (PM motors).
Setting 90 to 92: DriveWorksEZ digital output 1 to 3
These settings are for output functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 100 to 192: Functions 0 to 92 with inverse output
These settings have the same function as settings 0 to 92 but with inverse output. Set as 1, where the 1 indicates
inverse output and the last two digits specify the setting number of the function.
Examples:
For inverse output of 8: During baseblock, set 108.
For inverse output of 4A: During KEB set 14A.
H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01, H2-02, or H2-03 = 39),
parameter H2-06 determines the units for the output signal.
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the
frequency that pulses are issued to keep track of the kWh for the drive.
236
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
H2-06
Parameter Name
Setting Range
Default
Note: 1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
Figure 5.77
H2-06
(Pulse Output Unit)
OFF
ON
OFF
common_TMonly
0.2 s
Name
Setting Range
Default
H3-01
0 to 1
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and
bias settings will be simply read as 0%.
Setting 1: 10 to 10 Vdc
Name
Setting Range
Default
H3-02
0 to 31
Name
Setting Range
Default
H3-03
-999.9 to 999.9%
100.0%
H3-04
-999.9 to 999.9%
0.0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
The input level is 10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then
the motor will rotate in reverse.
237
Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency
reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will
be equal to E1-04 above 5 Vdc.
Figure 5.78
H3-01 = 0
H3-01 = 1
Gain = 200 %
Gain = 200 %
Frequecny
reference
100%
E1-04
-10 V
-5 V
100 %
E1-04
0V 5V
10 V
-100%
E1-04
Bias = 0 %
Gain = -200 %
0V
5V
10 V
Figure 5.78 Frequency Reference Setting by Analog Input with Increased Gain
Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
Figure 5.79
H3-01 = 0
H3-01 = 1
100 %
Frequency
reference
100%
H3-01 = 0
-10 V -6.0 V
2.0 V
-25%
0
2.0 V
-25%
10 V
Analog Input
Voltage
10 V
Analog Input
Voltage
-100%
E1-04
-150%
H3-01 = 1
Figure 5.79 Frequency Reference Setting by Analog Input with Negative Bias
Name
Setting Range
Default
H3-05
0, 1
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 0: 0 to 10 Vdc on page 237.
Setting 1: 10 V to 10 Vdc
The input level is 10 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 1: 10 to 10 Vdc on page 237.
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3. Refer to Multi-Function Analog Input Terminal Settings
on page 240 for a list of functions and descriptions.
238
No.
Name
Setting Range
Default
H3-06
0 to 31
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
H3-07
-999.9 to 999.9%
100.0%
H3-08
-999.9 to 999.9%
0.0%
Name
Setting Range
Default
H3-09
0 to 3
Setting 0: 0 to 10 Vdc
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2. Refer to Multi-Function Analog Input Terminal Settings
on page 240 for a list of functions and descriptions.
No.
Name
Setting Range
Default
H3-10
0 to 31
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Both can be used to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same
way as parameters H3-03 and H3-04 for analog input A1.
No.
Name
Setting Range
Default
H3-11
-999.9 to 999.9%
100.0%
H3-12
-999.9 to 999.9%
0.0%
Name
Setting Range
Default
H3-13
0.00 to 2.00 s
0.03 s
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
239
Name
Setting Range
Default
H3-14
1 to 7
Page
Setting
Frequency bias
Function
240
Function
Page
242
Frequency gain
240
Through mode
242
240
10
240
11
241
12
241
13
242
241
14
Torque compensation
242
241
15
242
241
16
242
241
1F
Through mode
242
PID feedback
242
30
PID setpoint
242
31
Frequency bias
242
32
242
242
The input value of an analog input set to this function will be added to the analog frequency reference value. When the
frequency reference is supplied by a different source other than the analog inputs, this function will have no effect. Use
this setting also when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Using A1 and A2 at the same time increases the frequency
reference by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog
input terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency gain
The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from
analog input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary reference 1
Sets the auxiliary frequency reference 1 when multi-step speed operation is selected. Refer to Multi-Step Speed
Selection on page 182 for details.
Setting 3: Auxiliary reference 2
Sets the auxiliary frequency reference 2 when multi-step speed operation is selected. Refer to Multi-Step Speed
Selection on page 182 for details.
240
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available
only when using V/f Control.
Setting 5: Accel/decel time gain
Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The acceleration time used by the drive is calculated by multiplying the this gain level to C1- as follows:
C1- Accel/decel time gain = Drive accel/decel time
Figure 5.80
100%
50%
20%
10%
0 1V
2V
5V
10 (%)
common_TMonly
10 V
The current level used for DC Injection Braking. Set as a percentage of the maximum output current using.
Figure 5.81
100%
Drive Rated
Current
common_TMonly
0
(4)
10 V
(20 mA)
This setting allows an analog input signal to adjust the Stall Prevention level. Figure 5.82 shows the setting
characteristics. The drive will use either the Stall Prevention level set to L3-06 or the level coming from the analog input
terminal that has been selected, whichever value is lower.
Parameter Details
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog
input. The analog input will replace the level set to L6-02. An analog input of 100% (10 V or 20 mA) will set a torque
detection level equal to 100% drive rated current / motor rated torque. Adjust the analog input gain if higher detection
level settings are required. Refer to L6: Torque Detection on page 267 for details on torque detection.
Figure 5.82
common_TMonly
100%
30%
30%
100%
Figure 5.82 Stall Prevention During Run Using an Analog Input Terminal
The user can adjust the lower limit of the output frequency using an analog input signal.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
241
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input Methods on page 153.
Setting C: PID setpoint
An input set for this function supplies the PID setpoint value, and the frequency reference selected in parameter b1-01 is
no longer the PID setpoint. PID operation to be enabled in b5-01 to use this setting. Refer to PID Setpoint Input
Methods on page 153.
Setting D: Frequency bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used
with any frequency reference source.
Setting E: Motor temperature
In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient)
thermistor for motor insulation protection. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC)
on page 250 for a detailed explanation.
Setting F, 1F: Through mode
When set to F or 1F, an input does not affect any drive function, but the input level can still be read out by a PLC via a
communication option or MEMOBUS/Modbus communications.
Setting 10, 11, 12, 15: Forward, Reverse, Regenerative, General torque limit (OLV, CLV, AOLV/PM, CLV/PM)
These functions can be used to set a torque limit using analog inputs for different operating conditions. Refer to L7:
Torque Limit on page 270 for details.
Setting 13: Torque Limit Using Torque Reference/Speed Limit
When using Torque Control, an analog input programmed to this function can set the torque reference (when in Torque
Control) or the torque limit (when in Speed Control). Refer to Setting the Torque Reference, Speed Limit, and Torque
Compensation Values on page 191 for details.
Setting 14: Torque compensation
Used to set a torque compensation value when using Torque Control. Refer to Setting the Torque Reference, Speed
Limit, and Torque Compensation Values on page 191 for details.
Setting 16: Differential PID Feedback
If an analog value is set for this function, the PID controller is set for differential feedback. The subtraction of the PID
feedback input value and the differential feedback input value builds the feedback value that is used to calculate the PID
input. Refer to PID Feedback Input Methods on page 153.
Setting 30, 31, 32: DriveWorksEZ Analog Input 1, 2, 3
These settings are for functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.
242
Name
Setting Range
Default
H4-01
000 to 999
102
H4-04
000 to 999
103
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter H4-02 and H4-05 set the terminal FM and AM output signal level equal to 100% of the monitor (gain).
Parameter H4-03 and H4-06 set the bias added to the monitor output for terminals FM and AM. Both are set as a
percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc using parameter H4-07 and H4-08.
Figure 5.83 illustrates how gain and bias settings work.
No.
Name
Setting Range
Default
H4-02
-999.9 to 999.9%
100.0%
H4-03
-999.9 to 999.9%
0.0%
H4-05
-999.9 to 999.9%
50.0%
H4-06
-999.9 to 999.9%
0.0%
When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage
signal equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias
setting parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value (including
changes made from bias and gain settings).
Example 1: To have an output signal of 5 V at terminal FM when the monitored value is at 100%, set H4-02 to 50%.
Example 2: To have an output signal of 10 V at terminal FM when the monitored value is at 76.7%, set H4-02 to 150%.
Figure 5.83
H4-07, 08 = 0
H4-07, 08 = 1
15V
Gain = 150%
Bias = 0%
Output Voltage
10V
10 V
Output Voltage
Gain 150%
Bias 0%
5V
Gain 100%
Bias 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
5V
-100%
-5 V
Gain 50%
Bias 0%
100%
Monitor Value
0%
Monitor Value
Parameter Details
-10 V
0V
100%
-15 V
Figure 5.83 Analog Output Gain and Bias Setting Example 1 and 2
Example 3: To have an output signal of 3 V at terminal FM when the monitored value is at 0%, set H4-03 to 30%.
Figure 5.84
H4-07, 08 = 0
H4-07, 08 = 1
15 V
Gain = 100%
Bias = 30%
Output Voltage
10V
Gain = 100%
Bias = 0%
10 V
5V
Bias 30%
Gain 100%
Output Voltage
Bias 0%
Gain 100%
3V
0V
-100%
-5 V
100%
Monitor Value
-10 V
0%
Monitor Value
100%
-15 V
YEC_common
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
243
Name
Setting Range
H4-07
0, 1
0, 1
H4-08
Default
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Name
Setting Range
Default
H6-01
0 to 3
If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01, b1-15 = 4), the
drive reads the frequency value from terminal RP.
Setting 1: PID feedback value
Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 152 for details on PID control.
Setting 2: PID setpoint value
Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 152 for details on PID control.
Setting 3: Speed feedback (V/f Control with Simple Speed Feedback)
This setting can be used in V/f control to increase the speed control precision by using a motor speed feedback signal.
The drive reads the speed feedback from terminal RP, compares it to the frequency reference and compensates the motor
slip using a speed regulator (ASR, setup in the C5- parameters) like shown in Figure 5.82. Because input terminal
RP is incapable of detecting motor direction, a separate way of determining motor direction still needs to be set up:
1. Using a Digital Input
If a digital input programmed for Forward/reverse detection (H1- = 7E) is closed, the drive assumes
reverse rotation. If open, then the drive assumes that the motor is rotating forwards.
2. Using the Frequency Reference Direction
If no digital input is set to Forward/reverse detection (H1- = 7E), the drive uses the direction of the
frequency reference as the direction for the speed feedback detected at the pulse input.
244
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
common_TMonly
Motor speed
Figure 5.85 Speed Control with ASR in V/f with Simple Speed Feedback
Name
Setting Range
Default
H6-02
100 to 32000 Hz
1440 Hz
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
No.
Name
Setting Range
Default
H6-03
0.0 to 1000.0%
100.0%
Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
No.
Name
Setting Range
Default
H6-04
-100.0 to 100.0%
0.0%
Name
Setting Range
Default
H6-05
0.00 to 2.00 s
0.10 s
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
245
Name
Setting Range
Default
102
<1> Set 000 when the terminal is not used, or when using the terminal in the through mode.
Name
Setting Range
Default
H6-07
0 to 32000 Hz
1440 Hz
246
No.
Name
Setting Range
Default
H6-08
0.1 to 1000.0 Hz
0.5 Hz
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
5.8
L: Protection Functions
Name
Setting Range
Default
L1-01
0 to 6
Determined by A1-02
Note: 1. When the motor protection function is enabled (L1-01 0), an oL1 alarm can be output through one of the multi-function outputs by
setting H2-01 to 1F. The output will close when the motor overload level reaches 90% of the oL1 detection level.
2. Select a method to protect the motor from overheat by setting L1-01 between 1 and 5 when running a single motor from the drive. An
external thermal relay is not needed.
This setting should be used if no motor overheat protection is desired or if multiple motors are connected to a single
drive. In this case it is recommended that you install a thermal relay for each motor as shown in Figure 5.86
Figure 5.86
Power
supply
Drive
M1
MC1
L10
MC2
L20
M2
common_TMonly
NOTICE: Close MC1 and MC2 before operating the drive. (MC1 and MC2 cannot be switched off during run.)
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from
overheat throughout the entire speed range.
Overload Tolerance
Cooling Ability
Overload Characteristics
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
NOTICE: Thermal protection cannot be provided when running multi-motors simultaneously with the same drive, or when using
motors with a current rating that is relatively high when compared with other standard motors (such as a submersible motor). Failure to
comply could result in motor damage. Disable the electronic overload protection of the drive (L1-01 = 0: Disabled) and protect each
motor with individual motor thermal overloads.
247
Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will
allow the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger
an overload fault.
Overload Tolerance
Cooling Ability
Overload Characteristics
150
Rated Speed=100% Speed
Torque (%)
60 s
100
55
50
Continuous
B
C
0 110
Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor
type is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an
overload fault.
Overload Tolerance
150
Overload Characteristics
60 s
Torque (%)
Cooling Ability
100
90
50 Continuous
B
C
0 1
This setting is for operating a PM motor. PM motors for derated torque have a self-cooling design, so the overload
tolerance drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload
characteristics, providing overheat protection across the entire speed range.
Overload Tolerance
Cooling Ability
Overload Characteristics
Torque (%)
150
120
100
80
60 s
Continuous
50
0.0
10
33
100
248
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Sets protection characteristics needed when driving a PM with constant torque. These motors allow for a speed control
from 0.2% to 100% when operating with 100% load. Slower speeds with 100% load will trigger overload.
Overload Tolerance
Cooling Ability
Overload Characteristics
Motor is designed to effectively cool itself at ultralow speeds (about 0.2% of base speed).
150
Torque (%)
125
115
Continuous
100
83
77
67
0 0.2
150
Because the motor (50 Hz) is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive
appropriately adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the
motor from overheat throughout the entire speed range.
Overload Tolerance
Torque (%)
150
60 s
Cooling Ability
Overload Characteristics
100
90
50 Continuous
A
B
C
05 33
No.
Name
Setting Range
Default
L1-02
1.0 minutes
Parameter Details
Sets the time it takes the drive to detect motor overheat due to overload. This setting rarely requires adjustment, but
should correlate with the motor overload tolerance protection time for performing a hot start.
Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start.
Figure 5.87 shows an example of the electrothermal protection operation time using a general-purpose motor operating
at 60 Hz with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when
starting a stationary motor.
Hot start: Motor protection operation time in response to an overload situation that occurred during sustained
operation at rated current.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
249
common_TMonly
10
7
3
Cold start
1
0.4
Hot start
0.1
0
100
150
200
Drive
Multi-function input
MA
MB
Fault output
MC
+V
(+10.5V, 20 mA)
M1 Multi-function
M2 digital output
Branch
resistor
12 k
P1
A2 (0-10 V)
PTC
thermistor
P2 Multi-function
photocoupler output
AC
PC
YEC_TMonly
Figure 5.88 Connection of a Motor PTC
The PTC must have the following characteristics for one motor phase. The drives motor overload detection expects 3 of
these PTCs to be connected in series.
Figure 5.89
common_TMonly
Tr
Tr - 5K (oH3 Alarm Level)
Overheat detection using a PTC can be set up by parameters L1-03, L1-04, and L1-05 as explained below.
250
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L1-03
0 to 3
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
Setting 3: Alarm only
The operation is continued and an oH3 alarm is displayed on the digital operator.
L1-04: Motor Overheat Fault Operation Selection (PTC input)
Sets the drive operation when the PTC input signal reaches the motor overheat fault level (oH4).
No.
Name
Setting Range
Default
L1-04
0 to 2
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast Stop time set in parameter C1-09.
L1-05: Motor Temperature Input Filter Time (PTC input)
No.
Name
Setting Range
Default
L1-05
0.00 to 10.00 s
0.20 s
Parameter Details
Used to set a filter on the PTC input signal in order to prevent a motor overheat fault from being mistakenly detected.
Name
Setting Range
Default
L1-13
0 or 1
Setting 0: Disabled
Setting 1: Enabled
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
251
Name
Setting Range
Default
L2-01
0 to 5
If power is not restored within 15 ms, a Uv1 fault will result and the drive will stop the motor. The motor coasts to stop.
Setting 1: Recover within L2-02
When a momentary power loss occurs, the drive output will be shut off. Should the power return within the time set to
parameter L2-02, the drive will perform Speed Search and attempt to resume operation. If power is not restored within
this time (i.e., DC bus voltage level remains below Uv1 detection level L2-05), then a Uv1 fault is triggered.
Setting 2: Recover as long as CPU has power
When a momentary power loss occurs, the drive output will be shut off. Should the power return as long as the drive
control circuit has power, the drive will attempt to perform Speed Search and resume the operation. A Uv1 fault is not
triggered.
Setting 3: KEB Ride-Thru operation within L2-02
The drive decelerates using regenerative energy from the motor until the time set in L2-02 has expired. It then tries to
accelerate back to the frequency reference. If the power does not returned within the time set in L2-02, an Uv1 fault is
triggered and the drive output shuts off. The type of KEB operation is determined by the setting of L2-29.
Setting 4: KEB Ride-Thru as long as CPU has power
The drive decelerates using regenerative energy from the motor until the power returns and then restarts. If the motor has
come to a stop before, the power returns. If the drive control power gets lost, the drive output will shut off. A Uv1 fault is
not triggered. The type of KEB operation is determined by the setting of L2-29.
Setting 5: Ramp to stop with KEB deceleration
The drive ramps to stop using the regenerative energy from the motor. Even if the power is restored, the drive will
continue decelerating until it brings the motor to a complete stop. The type of KEB operation is determined by the setting
of parameter L2-29. Note that if an input terminal set for KEB 1 (H1- = 65, 66) is triggered while the drive is
decelerating, then it will accelerate back up to speed when the input is released.
Notes on Settings 1 through 5
Uv will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is
not output at this time.
A Momentary Power Loss Unit is available to allow for a longer momentary power loss ride through time in the drive
model CIMR-A2A0004 through 2A0056 and CIMR-A4A0002 through 4A0031. This option makes it possible to
continue running after up to two seconds of power loss.
When a magnetic contactor between motor and drive is used, be sure that the magnetic contactor remains closed as
long as the drive performs KEB operation or attempts to restart with Speed Search.
Make sure the Run command is kept active during KEB operation. Otherwise the drive cannot accelerate back to the
frequency reference when the power returns.
When L2-01 is set to 3, 4, or 5, KEB Ride-Thru will be executed as specified in L2-29.
KEB Ride-Thru Function
When power loss is detected, the Kinetic Energy Backup Ride-Thru function (KEB Ride-Thru) decelerates the motor and
uses regenerative energy to keep the main circuit operating. Despite power loss, the drive output is not interrupted.
For applications driven by a single drive, choose between Single Drive KEB Ride-Thru 1 and 2 (L2-29 = 0 or 1).
For applications where multiple drives have to perform KEB operation while keeping a certain speed ratio (such as
textile machinery), select between System KEB Ride-Thru 1 and 2, (L2-29 = 2 or 3).
252
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Once KEB Ride-Thru begins, the drive uses regenerative energy from the motor to keep the DC bus voltage at the level
set to L2-11 while adjusting the rate of deceleration based on the time set to L2-06.
Note: If undervoltage occurs in the DC bus (Uv1), shorten the KEB deceleration time (L2-06). If overvoltage occurs (oV), increase the
KEB deceleration time.
The drive uses information about the inertia of the connected machinery to determine the deceleration rate necessary to
keep the DC bus voltage at the level set in parameter L2-11. The resulting deceleration time is calculated based on the
system inertia and cannot be adjusted.
System KEB Ride-Thru 1 (L2-29 = 2)
Drive decelerates at the KEB deceleration time set to L2-06. L2-06 is the time required decelerate from the current
frequency reference to 0. Using this setting, multiple drives can decelerate while still keeping the speed ratio between
those drives constant. The voltage level in the DC bus is disregarded when using this function. Braking resistor option
required.
System KEB Ride-Thru 2 (L2-29 = 3)
Drive decelerates based on the KEB deceleration time set to L2-06 while monitoring the DC bus voltage. If the voltage
level rises, the drive briefly holds the frequency before continuing to decelerate again.
KEB Ride-Thru Start
KEB operation is always triggered in the same way, independent of the selected KEB operation mode. When the KEB
function is selected as the function to be executed when power loss operation occurs (L2-01 = 3, 4, or 5), then KEB RideThru will be activated if one of the following conditions becomes true:
A digital input programmed for H1- = 65 or 66 is activated. This will start KEB operation using the mode selected
in parameter L2-29.
A digital input programmed for H1- = 7A or 7B is activated. This will automatically select Single KEB Ride-Thru
2, disregarding the setting of L2-29.
The DC bus voltage fell below the level specified in L2-05. The KEB operation will start as specified in L2-29.
Note: KEB Ride-Thru 1 and 2 cannot both be assigned to input terminals at the same time. Attempting this will trigger an oPE3 error.
If a digital input is used for triggering the KEB operation and the device that controls the input acts relatively slow,
parameter L2-10 can be used to set a minimum KEB operation time. In the example below, KEB operation is triggered
by the DC bus voltage and the Hold command is triggered by a digital input.
Figure 5.90
Power loss
L2-10
Parameter Details
0V
KEB digital input is
set with in L2-10
DC bus voltage
Output Frequency
KEB deceleration is
triggered by DC bus voltage
common_TMonly
0 Hz
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
253
Here, L2-01 = 3 and the input terminals have not been set for KEB Ride-Thru (H1- does not equal 65, 66, 7A, 7B).
After decelerating for the time set in parameter L2-02, the drive ends KEB operation and attempts to accelerate back to
the frequency reference. If the power has not returned within L2-02, an Uv1 fault occurs and the drive output shuts off.
Figure 5.91
Power Loss
0V
0V
DC Bus Voltage
L2-11 (Desired DC
Bus Voltage)
0V
L2-02
(Powe Loss
Ride-Thru Time)
common_TMonly
Output Frequency
L2-02
(Powe Loss
Ride-Thru Time)
KEB Deceleration
0 Hz
0 Hz
Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1- = 65, 66, 7A, 7B). After decelerating for
the time set in parameter L2-02, the drive checks the DC bus voltage and the status of the digital input. If the DC bus
voltage is still below the level set in L2-11 or if the KEB digital input is still active, KEB deceleration continues. If the
voltage level has risen above the value set to L2-11, then normal operation is resumed.
Note: The time set in L2-02 has priority over L2-10. Even if L2-10 is set to a longer time than L2-02, once the time in L2-02 passes, the
drive will check the DC bus voltage level and the status of the terminal assigned to KEB Ride-Thru, then try to restart.
Figure 5.92
Power Loss
Power Loss
0V
0V
L2-10
L2-10
DC bus voltage
L2-11 (Desired DC Bus Voltage)
common_TMonly
L2-02
(Powe Loss
Ride-Thur Time)
L2-02
(Powe Loss
Ride-Thur Time)
Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz
KEB deceleration is
triggered by DC bus voltage
0 Hz
254
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Here, L2-01 = 4 and the input terminals have not been set for KEB Ride-Thru (H1- does not equal 65, 66, 7A, 7B).
After decelerating for the time set in parameter L2-10, the drive checks the DC bus voltage level. If the DC bus voltage is
lower than the level set in L2-11, then deceleration continues. Once the DC bus voltage rises above the value of L2-11,
normal operation is resumed.
Figure 5.93
Power Loss
Power Loss
0V
0V
DC Bus Voltage
L2-11 (Desired DC Bus Voltage)
0V
0V
L2-10
(Min. KEB Operation
Time
common_TMonly
Output Frequency
L2-10
(Min. KEB
Op. Time
KEB Deceleration
KEB Deceleration
0 Hz
0 Hz
KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Used
Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1- = 65, 66, 7A, 7B). After decelerating for
the time set in parameter L2-10, the drive checks the DC bus voltage and the status of the digital input. If the DC bus
voltage is still below the level set in L2-11 or if the digital input assigned to KEB Ride-Thru is still active, then the drive
continues to decelerate. If the DC bus voltage has risen above L2-11 and the terminal that initiated KEB Rid-Thru is
released, then operation resumes.
Figure 5.94
Power Loss
Power Loss
0V
0V
DC bus voltage
L2-11 (Desired DC Bus Voltage)
L2-10 (Min.
KEB
Operation
Time)
Parameter Details
common_TMonly
Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz
KEB deceleration is
triggered by DC bus voltage
0 Hz
L2-01 = 5
KEB operation ends when the motor has come to a stop, even if the power returns and the digital input terminal that
initiated KEB Ride-Thru is cleared.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
255
Braking
Resistor
B1
B2
L1
R/L1
U/T1
L2
S/L2
V/T2
L3
T/L3
W/T3
UV Detection
Relay
S6 - KEB command 1 or 2
S1 - Start command
common_TMonly
SC
Name
C1-09
C2-03
L2-05
L2-06
L2-07
L2-08
L2-10
L2-11
L3-20
L3-21
Accel/Decel Rate
Calculation Gain
L3-24
L3-25
256
Setting Instructions
Increase if an overvoltage fault (ov) occur during KEB deceleration.
Decrease if an undervoltage fault (Uv1) occurs during KEB deceleration.
Shorten if undervoltage (Uv1) occurs right after KEB Ride-Thru is triggered.
Lengthen this setting if overvoltage occurs right after KEB operation starts.
Increase if an undervoltage fault (Uv1) fault occurs at KEB operation start in order to
let the drive detect power loss more quickly.
Increase if an overvoltage fault (ov) occur during KEB deceleration
Decrease if an undervoltage fault (Uv1) occurs during KEB deceleration
Adjust to the desired acceleration time. If set to 0, standard acceleration times are used
(C1-01, C1-03, C1-05, C1-07).
Increase if an undervoltage fault occurs right after KEB operation starts.
Decrease if an overvoltage fault occurs right after KEB operation starts.
Increase when a digital input is set for KEB Ride-Thru and an undervoltage fault
occurs after power was lost because the device that controls the input does not react
quickly enough.
If the DC bus voltage overshoots after KEB Ride-Thru begins (and no input terminal
is set to KEB Ride-Thru), increase L2-10 to longer than the overshoot.
Set to around 1.22 times the input voltage for Single Drive KEB Ride-Thru 2.
Set to around 1.4 times the input voltage for Single Drive KEB Ride-Thru 1 and
System KEB Ride-Thru modes.
Increase this setting slowly in steps of 0.1 if overvoltage (ov) or undervoltage (Uv1)
occurs at the beginning of deceleration
Reduce if torque ripple occurs during deceleration while executing KEB Ride-Thru.
Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current ripple.
Decreasing this setting too much can result in a slow DC bus voltage control
response, and may lead to problems with overvoltage or undervoltage.
Set the motor acceleration time as described on page 264.
Set the load/inertia ratio as described on page 264.
YES
NO
NO
NO
YES
NO
YES
YES
YES
YES
YES
YES
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES
NO
NO
NO
YES
NO
NO
NO
NO
YES
YES
NO
NO
NO
NO
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Momentary Power Loss Ride-Thru Time
Setting Range
Default
0.0 to 25.5 s
Name
Setting Range
Default
0.1 to 5.0 s
Determined by C6-01
and o2-04
Name
Momentary Power Loss Voltage Recovery Ramp Time
Setting Range
Default
0.0 to 5.0 s
Name
Setting Range
Default
L2-05 <1>
Note: 1. When setting L2-05 below the default value, an AC reactor option should be installed to the input side of the power supply to prevent
damage to drive circuitry.
2. If using KEB Ride-Thru and L2-05 is set too low, then undervoltage in the DC bus (uv1) will be triggered before KEB Ride-Thru can
be executed. Take caution not to set this value too low.
Name
Setting Range
Default
L2-06
0.00 s
<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes
0.00 to 600.00 s.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
<1> Values are for 200 V class drives and must be doubled for 400 V class drives.
<2> The default setting for 400 V class drives will vary depending on if the drive input voltage is over or under 400 V.
257
Name
Setting Range
Default
L2-07
0.00 s
<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes
0.00 to 600.00 s.
Name
Setting Range
Default
L2-08
0 to 300%
100%
Name
Setting Range
Default
L2-10
0 to 2000 ms
50 ms
Name
Setting Range
Default
L2-11
<2>
<1> Values are for 200 V class drives and must be doubled for 400 V class drives.
<2> Default setting is determined by E1-01.
Name
Setting Range
Default
L2-29
0 to 3
258
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L3-01
0 to 2 <1>
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to
speed fast enough, thus tripping an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration. Operation varies, depending on the control mode.
V/f Control, V/f Control with PG, and Open Loop Vector Control:
If the output current rises above the Stall Prevention level set in L3-02, then the drive stops accelerating. Acceleration
will not resume until the output current falls 15% below the setting in L3-02.
The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention
Limit during Acceleration on page 260.
Figure 5.96
Output current
L3-02
L3-02
Parameter Details
-15%
Time
Output frequency
5
Controls the output frequency
to prevent the motor from stalling
Time
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
259
Output current
L3-02
15 % of L3-02
Time
Output frequency
L3-27
L3-27
Time
Deceleration
using L3-22
Figure 5.97 Stall Prevention During Acceleration for Permanent Magnet Motors
When L3-02 = 2, the drive will disregard the selected acceleration time and try to accelerate in the minimum time. The
acceleration rate is adjusted so that the current does not exceed the value set in parameter L3-02.
L3-02: Stall Prevention Level during Acceleration
Sets the output current level at which the Stall Prevention during acceleration is activated.
No.
Name
Setting Range
Default
L3-02
0 to 150% <1>
<1>
<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).
Stalling may occur when the motor is rated at a smaller capacity than the drive and the Stall Prevention default settings
are used. Set L3-02 as appropriate if stalling occurs.
When operating the motor in the constant power range, also set parameter L3-03.
L3-03: Stall Prevention Limit during Acceleration
The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets
the lower limit for this reduction as a percentage of the drive rated current.
No.
Name
Setting Range
Default
L3-03
0 to 100%
50%
Figure 5.98
L3-02
L3-03
Output frequency
E1-06
Base frequency
260
No.
Name
Setting Range
Default
L3-22
0 to 6000.0 s
0.0 s
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L3-04
0 to 5 <1>
<1> Settings 3 through 5 are not available in OLV/PM. Settings 2 through 5 are not available in AOLV/PM and CLV/PM.
Setting 0: Disabled
When this setting is used, the drive decelerates according to the set deceleration time. With high inertia loads or rapid
deceleration, an overvoltage (ov) fault may occur. In this case use dynamic braking options or switch to another L3-04
selection.
Setting 1: General-purpose Stall Prevention
With this setting the drive tries to decelerate within the set deceleration time. When the DC bus voltage exceeds the Stall
Prevention level, the drive pauses deceleration. Deceleration continues as soon as the DC bus voltage drops below that
level. Stall Prevention may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall
Prevention depends on the input voltage setting E1-01.
Drive Input Voltage
200 V Class
377 Vdc
400 V Class
754 Vdc
Note: 1. This setting should not be used in combination with a Dynamic Braking Resistor or other dynamic braking options. If Stall
Prevention during deceleration is enabled, it will be triggered before the braking resistor option can operate.
2. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider
using a dynamic braking option.
Output Frequency
Deceleration characteristics
when Stall Prevention was
triggered during deceleration
Time
With this setting, the drive adjusts the deceleration rate so that the DC bus voltage is kept at the level set in parameter L317. This way the shortest possible deceleration time is achieved while the motor is protected from stalling. The
deceleration time that has been selected is disregarded, but the achievable deceleration time cannot be smaller than 1/10
of the set deceleration time.
This function uses the following parameters for adjusting the deceleration rate:
Enables the Stall Prevention function while using a dynamic braking resistor. Overvoltage problems in the DC bus can
occur if Stall Prevention during deceleration is disabled (L3-04) in OLV and a dynamic braking option is installed. Set
L3-04 to 3 to remedy this situation.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
261
Parameter Details
Overexcitation Deceleration 1 (increasing the motor flux) is faster than deceleration with no Stall Prevention (L3-04 = 0).
Refer to Overexcitation Deceleration (Induction Motors) on page 280 for details.
Setting 5: Overexcitation Deceleration 2
Overexcitation Deceleration 2 slows down the motor while trying to maintain the DC bus voltage at the level set in
parameter L3-17. By doing this, the achievable deceleration time can even be shorter than with Overexcitation
Deceleration 1. Refer to Overexcitation Deceleration (Induction Motors) on page 280 for details.
L3-05: Stall Prevention Selection during Run
Stall Prevention during run can prevent a motor from stalling by automatically reducing the speed when a transient
overload occurs while the motor is running at constant speed.
This parameter determines how Stall Prevention works during run.
No.
Name
Setting Range
Default
L3-05
0 to 2
Setting 0: Disabled
Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL
fault.
Setting 1: Decelerate using C1-02
If the current exceeds the Stall Prevention level set in parameter L3-06, then the drive will decelerate at decel time 1 (C102). Once the current level drops below the value of L3-06 minus 2% for 100 ms, the drive accelerates back to the
frequency reference at the active acceleration time.
Setting 2: Decelerate using C1-04
Name
Setting Range
Default
L3-06
30 to 150 <1>
<1>
<1> The upper limit and default for this setting is determined by C6-01 and L8-38.
Name
Setting Range
Default
L3-23
0 or 1
Setting 0: Disabled
The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled
The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.
Overvoltage Suppression Function
This function suppresses overvoltage faults by decreasing the regenerative torque limit and slightly increasing the output
frequency when the DC bus voltage rises. It can be used to drive loads with cyclic regenerative operation, such as a
punch press or other applications that involve repetitive crank movements.
262
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L3-11
0 or 1
Setting 0: Disabled
The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an
overvoltage fault. Use this setting if dynamic braking options are installed.
Setting 1: Enabled
When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative
torque limit and increasing the output frequency.
L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
Sets the target DC bus voltage target level used by the overvoltage suppression function (L3-11 = 1), Intelligent Stall
Prevention during deceleration (L3-04 = 2).
No.
Name
Setting Range
Default
L3-17
No.
Name
Setting Range
Default
L3-20
0.00 to 5.00
Determined by A1-02
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
Increase this setting slowly in steps of 0.1 if overvoltage or undervoltage occurs at the beginning of deceleration.
If this setting is too high, then a fair amount of speed or torque ripple can result.
Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a
regenerative load results in an overvoltage (ov) fault.
If this setting is too high, excessive speed or torque ripple can result.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
<1> Values are for 200 V class drives and must be doubled for 400 V class drives.
<2> This value is initialized when E1-01 is changed.
263
Name
Setting Range
Default
L3-21
0.10 to 10.00
<1>
<1> This value is reset to its default value when the control mode is changed (A1-02). The value shown here is for Open Loop Vector Control.
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current ripple.
Small reductions of L3-21can also help solve problems with overvoltage and overcurrent.
Decreasing this setting too much can result in a slow DC bus voltage control response and may also lengthen
deceleration times beyond optimal levels.
Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage
suppression is enabled (L3-11 = 1).
If there is a fairly large speed ripple when overvoltage suppression is enabled, then decrease L3-21 in steps of 0.05.
L3-24: Motor Acceleration Time for Inertia Calculations
Sets the time it takes to accelerate the motor from stop to the maximum speed at motor rated torque. This parameter
should be set when using Single Drive KEB 2 (L2-29 = 1), Intelligent Stall Prevention during deceleration (L2-04 = 2),
or the overvoltage suppression function (L3-11 = 1).
No.
L3-24
Name
Setting Range
0.001 to 10.000 s
Default
Determined by o2-04, C6-01, E2-11, and E5-01
<1>
<1> Parameter L3-24 is defaulted for a Yaskawa standard 4-pole motor. During Auto-Tuning, L3-24 will be initialized to a Yaskawa standard 4-pole
motor if parameter E2-11 is changed. This value also changes based on the motor code set to E5-01 when using the Open Loop Vector Control
Mode for PM motors.
In Closed Loop Vector Control for induction motors or PM motors, the Inertia Auto-Tuning function can be used to let
the drive automatically adjust this parameter. Refer to Auto-Tuning on page 114.
Manual Parameter Setup
common_TMonly
60
2
P Motor[kW] 103
n rated [r/min]
common_TMonly
Name
Setting Range
Default
L3-25
1.0 to 1000.0
1.0
When set incorrectly, a fairly large current ripple can result during Single Drive KEB 2 (L2-29 = 1) and overvoltage
suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC may occur.
Automatic Parameter Setup
In Closed Loop Vector Control for induction motors or PM motors the Inertia Auto-Tuning function can be used to let the
drive automatically adjust this parameter. Refer to Auto-Tuning on page 114.
264
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Machine Inertia
Motor Inertia
common_TMonly
Name
Setting Range
Default
L3-26
0 to 65000 F
0 F
Name
Setting Range
Default
L3-27
0 to 5000 ms
50 ms
Name
Setting Range
L4-01
0.0 to 400.0 Hz
0.0 Hz
0.0 to 20.0 Hz
Determined by A1-02
L4-02
Default
Refer to H2-01 to H2-03: Terminal M1-M2, P1-PC, and P2-PC Function Selection on page 227, Settings 2, 3, 4, and
5.
Parameter Details
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)
Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2,
Frequency detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.
No.
Name
Setting Range
Default
L4-03
-400.0 to 400.0 Hz
0.0 Hz
L4-04
0.0 to 20.0 Hz
Determined by A1-02
Refer to H2-01 to H2-03: Terminal M1-M2, P1-PC, and P2-PC Function Selection on page 227, Settings 13, 14, 15,
and 16.
L4-05: Frequency Reference Loss Detection Selection
The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is
detected when the frequency reference drops below 10% of the reference before or below 5% of the maximum output
frequency within 400 ms.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
265
100%
Analog
frequency
reference
10%
400 ms
Loss of
Reference
output
OFF
ON
time
common_TMonly
To have a digital output trigger when frequency reference loss occurs, set H2-01, H2-02, or H2-03 to C. Refer to Setting
C: Frequency reference loss on page 231 for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
No.
Name
Setting Range
Default
L4-05
0 or 1
Setting 0: Stop
Drive follows the frequency reference (which is no longer present) and simply stops the motor.
Setting 1: Continue operation with reduced frequency reference
The drive will continue operation at the frequency reference value set in parameter L4-06. When the external frequency
reference value is restored, the operation is continued with the frequency reference.
L4-06: Frequency Reference at Reference Loss
Sets the frequency reference level the drive runs with when L4-05 = 1 and a reference loss was detected. The value is set
as a percentage of the frequency reference before the loss was detected.
No.
Name
Setting Range
Default
L4-06
0.0 to 100.0%
80.0%
Name
Setting Range
Default
L4-07
0 or 1
The drive can attempt to restart itself following the faults listed below.
Fault
Name
Fault
Name
GF
Ground Fault
oL4
Overtorque 2
LF
ov
DC Bus Overvoltage
oC
Overcurrent
PF
oH1
Drive Overheat
rH
oL1
Motor Overload
rr
oL2
Drive Overload
Uv1
oL3
Overtorque 1
Sto
Pull-Out Detection
<1> When L2-01 is set to 1 through 4 (continue operation during momentary power loss)
266
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L5-01
0 to 10 Times
0 Time
Name
Setting Range
Default
L5-02
0 or 1
Name
Setting Range
Default
L5-04
0.5 to 600.0 s
10.0 s
No.
Name
Setting Range
Default
L5-05
0 or 1
The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is
repeated each time a fault occurs until the counter reaches the value set in L5-01.
Setting 1: Count restart attempts
The drive will try to restart using the time interval set in parameter L5-04. A record is kept of the number of attempts to
restart to the drive, regardless of whether or not those attempts were successful. When the number of attempted restarts
exceeds the value set to L5-01, the drive gives up trying to restart.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
267
Parameter Details
Description
17
18
19
Figure 5.101 and Figure 5.102 show the function of overtorque and undertorque detection.
Figure 5.101
common_TMonly
10 % hysteresis
L6-02/05
L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)
L6-03/06
ON
ON
common_TMonly
10 % hysteresis
L6-02/05
L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)
L6-03/06
ON
ON
Name
Setting Range
Default
L6-01
0 to 8
L6-04
0 to 8
Setting 0: Disabled
Setting 1: oL3, oL4 at speed agree (alarm)
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detection and an oL3/oL4 alarm is triggered.
Setting 2: oL3, oL4 at run (alarm)
Overtorque detection works as long as the Run command is active. The operation continues after detection and an oL3 or
oL4 alarm is triggered.
Setting 3: oL3, oL4 at speed agree (fault)
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation is stopped and an oL3 or oL4 fault is triggered.
Setting 4: oL3, oL4 at run - (fault)
Overtorque detection works as long as a Run command is active. Operation stops and an oL3 or oL4 fault is triggered.
268
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detection and an oL3 or oL4 alarm is triggered.
Setting 6: UL3, UL4 at Run - Alarm
Undertorque detection works as long as the Run command is active. The operation continues after detection and an oL3
or oL4 alarm is triggered.
Setting 7: UL3, UL4 at Speed Agree - Fault
Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation is stopped and an oL3 or oL4 fault is triggered.
Setting 8: UL3, UL4 at run - fault
Undertorque detection works as long as a Run command is active. Operation stops and an oL3 or oL4 fault is triggered.
L6-02, L6-05: Torque Detection Level 1, 2
These parameters set the detection levels for the torque detection functions 1 and 2. In V/f and OLV/PM control modes
these levels are set as a percentage of the drive rated output current, while in vector control modes these levels are set as
a percentage of the motor rated torque.
No.
Name
Setting Range
Default
L6-02
0 to 300%
150%
L6-05
0 to 300%
150%
Note: The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3- = 7. Here, the analog value
has priority and the setting in L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input.
Name
Setting Range
Default
L6-03
0.0 to 10.0 s
0.1 s
L6-06
0.0 to 10.0 s
0.1 s
The function is activated in the drive when the cumulative operation counter U4-01 exceeds the time set in parameter L611. Mechanical Weakening Detection uses the torque detection 1 settings (L6-01, L6-02, L6-03) and triggers an oL5 fault
when overtorque or undertorque occurs in the speed range determined by parameter L6-08 and L6-09. The oL5 operation
is set by parameter L6-08.
To output a signal for Mechanical Weakening Detection, set H2- to 22.
Name
Setting Range
Default
L6-08
0 to 8
Setting 0: Disabled
Setting 1: Continue running if the speed is greater than L6-09 (signed) (alarm)
Detection when the speed is above L6-09 (signed). Upon detection operation continues, but an oL5 alarm is output.
Setting 2: Continue running if the speed is greater than L6-09 (alarm)
Detection when the speed is above L6-09 (unsigned). Upon detection operation continues, but an oL5 alarm is output.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
This function can be used to detect mechanical weakening of a machine that leads to overtorque or undertorque situations
after a certain machine operation time has elapsed.
269
Detection when the speed is above L6-09 (signed). Upon detection operation is stopped and an oL5 fault is output.
Setting 4: Stop when Motor Speed is Greater than L6-09
Detection when the speed is above L6-09 (unsigned). Upon detection operation is stopped and a fault is output.
Setting 5: Continue running if the speed is less than L6-09 (signed) (alarm)
Detection when the speed is below L6-09 (signed). Upon detection operation continues, but an oL5 alarm is output.
Setting 6: Continue running if the speed is less than L6-09 (alarm)
Detection when the speed is below L6-09 (unsigned). Upon detection operation continues, but an oL5 alarm is output.
Setting 7: Stop when Motor Speed is less than L6-09 (signed)
Detection when the speed is below L6-09 (signed). Upon detection operation is stopped and an oL5 fault is output.
Setting 8: Stop when motor speed is less than L6-09
Detection when the speed is below L6-09 (unsigned). Upon detection the operation is stopped and an oL5 fault is output.
L6-09: Mechanical Weakening Detection Speed Level
Sets the speed level for Mechanical Weakening Detection.
No.
Name
Setting Range
Default
L6-09
-110.0 to 110.0%
110%
The value is set as a percentage of the maximum frequency. If L6-08 is set for unsigned speed detection (L6-08 = 2, 4, 6,
8) then the absolute value of L6-09 is used (negative settings are treated as positive values).
L6-10: Mechanical Weakening Detection Time
Sets the time permitted for the situation selected in parameter L6-08 to arise before mechanical weakening is detected.
No.
Name
Setting Range
Default
L6-10
0.0 to 10.0 s
0.1 s
Name
Setting Range
Default
L6-11
0 to 65535 (Hex)
0 (Hex)
270
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
quadrant 1
quadrant 3
quadrant 4
common_TMonly
Name
Setting Range
Default
0 to 300%
200%
L7-02
0 to 300%
200%
L7-03
0 to 300%
200%
L7-04
0 to 300%
200%
L7-01
Note: If the multi-function analog input is programmed for 10: Forward torque limit, 11: Reverse torque limit, 12: Regenerative
torque limit, or 15: General torque limit, the drive uses the lower value in L7-01 through L7-04, or analog input torque limit.
Name
Setting Range
Default
L7-06
5 to 10000 ms
200 ms
No.
Name
Setting Range
Default
L7-07
0 or 1
Parameter Details
The torque limit function works with P control during accel and decel, and switches to I control at constant speed. Use
this setting when accelerating or decelerating to the desired speed has priority over the torque limit during speed changes.
Setting 1: Integral control
The torque limit function always uses I control. Use this setting when a highly accurate torque limit is required, even
during speed changes. Using this function may increase the acceleration time, or may prevent the motor speed from
reaching the frequency reference if the torque limit is reached first.
L7-16: Torque Limit Process at Start
Assigns a time filter to allow the torque limit to build at start.
No.
Name
Setting Range
Default
L7-16
0 to 1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
271
Toque limit is created at start without a delay time. Disable L7-16 to maximize response time when the application
requires sudden acceleration or deceleration at start.
Setting 1: Enabled
Name
Setting Range
Default
L8-01
0 or 1
Setting 0: Disabled
Disables braking resistor protection. Use this setting for any dynamic braking option other than the Yaskawa ERF type
resistor.
Setting 1: Enabled
Name
Setting Range
Default
L8-02
50 to 150 C
Name
Setting Range
Default
L8-03
0 to 4
If an overheat alarm occurs, the drive decelerates to stop using the deceleration time currently selected. If a digital output
is programmed for fault (H2- = E), this output will be triggered.
Setting 1: Coast to stop
If heatsink overheat (oH) occurs, the drive switches off the output and the motor coasts to stop. If a digital output is
programmed for fault (H2- = E), this output will be triggered.
Setting 2: Fast Stop
If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop time (C1-09). If a digital output is
programmed for fault (H2- = E), this output will be triggered.
Setting 3: Alarm only
If an overheat alarm occurs, an alarm is output and the drive continues operation.
272
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
If an overheat alarm occurs, the operation is continued but the speed is reduced to the level set in parameter L8-19. If
after 10 s the oH alarm is still present, the speed is reduced once more. The amount of reduction depends on how often
the alarm repeats. If the oH alarm disappears while the drive is operating at a reduced speed, then the drive will switch
back to the previous speed it was reduced to before. Figure 5.104 explains the operation with reduced speed during an
oH alarm. A digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.
Figure 5.104
common_TMonly
Output frequency
10 s
10 s
10 s
10 s
10 s
10 s
10 s
fref
fref (L8-19)
fref (L8-19)2
oH
Alarm
Reset oH
Alarm
oH
Alarm
Reset oH
Alarm
oH
Alarm
fref (L8-19)3
etc.
oH
Alarm
fref (L8-19)4
time
oH alarm number
Digital ouput (4D)
Figure 5.104 Output Frequency Reduction During Overheat Alarm
Name
Setting Range
Default
L8-19
0.1 to 0.9
0.8
No.
Name
Setting Range
Default
L8-05
0 or 1
<1>
Parameter Details
Setting 0: Disabled
Setting 1: Enabled
Enables input phase loss detection. As detection is performed by measuring the DC bus ripple, a phase loss fault (PF) can
also be triggered by a power supply voltage imbalance or main circuit capacitor deterioration. Detection is disabled if:
The drive is decelerating.
No Run command is active.
Output current is less than or equal to 30% of the drive rated current.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
273
Name
Setting Range
Default
L8-07
0 to 2
Setting 0: Disabled
Setting 1: Fault when one phase is lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to
stop.
Setting 2: Fault when two phases are lost
An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to
stop.
L8-09: Output Ground Fault Detection Selection
Enables or disables the output ground fault detection.
No.
Name
Setting Range
Default
L8-09
0 or 1
Setting 0: Disabled
A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
L8-10: Heatsink Cooling Fan Operation Selection
Selects the heatsink cooling fan operation.
No.
Name
Setting Range
Default
L8-10
0 or 1
The fan is switched on when a Run command is active. It is switched off with the delay set in parameter L8-11 after the
Run command has been released. Using this setting extends the fan lifetime.
Setting 1: Run always
Name
Setting Range
Default
L8-11
0 to 300 s
60 s
274
No.
Name
Setting Range
Default
L8-12
-10 to 50 C
40 C
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
L8-15
0 or 1
The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can
lead to premature drive faults.
Setting 1: protection enabled at low speed
The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz.
L8-18: Software Current Limit Selection
The Software Current Limit (CLA) is a drive protection function that prevents main circuit transistor failures caused by
high current. Parameter L8-18 enables or disables this function.
Note: This setting should not be changed unless absolutely necessary. For proper drive protection and operation leave the Software
CLA function enabled.
No.
Name
Setting Range
Default
L8-18
0 or 1
The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.
Setting 1: Software CLA enabled
When the soft CLA current level is reached, the drive reduces the output voltage in order to reduce the current. If the
current level drops below the Software CLA level, then normal operation will continue.
L8-27: Overcurrent Detection Gain
Adjusts the overcurrent detection level when running in OLV/PM, AOLV/PM, or CLV/PM. A setting of 100% is equal to
the motor rated current. When the drive rated current is considerably higher than the motor rated current, use this
parameter to decrease the overcurrent level in order to prevent motor demagnetization by too high current.
No.
Name
Setting Range
Default
L8-27
0.0 to 300.0%
300.0%
Parameter Details
Overcurrent detection will use whichever value is the lowest: the overcurrent level for the drive, or the motor rated
current multiplied by L8-27.
Name
Setting Range
Default
L8-29
0 or 1
Setting 0: Disabled
The LF2 fault is triggered if an output current imbalance is detected. Drive output shuts off and the motor coasts to stop.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
275
Name
Setting Range
Default
L8-35
0 to 3
Determined by o2-04
For an IP00 enclosure drive installed with at a minimum of 30 mm space to the next drive or a cabinet wall.
Setting 1: Side-by-Side mounting
For drives mounted according to Yaskawas Side-by-Side specifications (requires 2 mm between drives).
Setting 2: IP20 or NEMA Type 1 enclosure
For finless drives or a standard drive mounted with the heatsink outside the cabinet or enclosure panel.
L8-38: Carrier Frequency Reduction Selection
Lets the drive reduce the carrier frequency when the output current exceeds a certain level. This temporarily increases the
overload capability (oL2 detection), allowing the drive to run through transient load peaks without tripping.
L8-38 selects the operation of the carrier frequency reduction function.
Note: This function cannot be used in Advanced Open Loop Vector for PM motors.
No.
L8-38
Name
Carrier Frequency Reduction Selection
Setting Range
Default
0 to 2
Determined by A1-02,
C6-01 and o2-04
Setting 0: Disabled
The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The
drive returns to its normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for entire frequency range
Name
Setting Range
Default
L8-40
0.00 to 2.00 s
Determined by A1-02
276
No.
Name
Setting Range
Default
L8-41
0 or 1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
No alarm is detected.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm
(H2- = 10) will close.
L8-55: Internal Braking Transistor Protection
Enables or disables protection for the internal braking transistor.
No.
Name
Setting Range
Default
L8-55
0 or 1
Setting 0: Disabled
Braking transistor protection should be disabled whenever the internal braking transistor is not used. This includes,
Enabling this L8-55 under such conditions can incorrectly trigger a braking transistor fault (rF).
Setting 1: Enabled
Parameter Details
Enable L8-55 when connecting a braking resistor or a braking resistor unit to the drive built-in braking transistor.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
277
5.9
n: Special Adjustments
These parameters handle a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control,
High Slip Braking, resistance between motor lines, and PM motor control functions.
Name
Setting Range
Default
n1-01
0 or 1
Setting 0: Disabled
Setting 1: Enabled
Name
Setting Range
Default
n1-02
0.00 to 2.50
1.00
Normally, n1-02 does not need to be changed, but adjustment may help under the following conditions:
If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.
n1-03: Hunting Prevention Time Constant
Determines how responsive the Hunting Prevention function is (affects the primary delay time for Hunting Prevention).
No.
Name
Setting Range
Default
n1-03
0 to 500 ms
Determined by o2-04
Normally, n1-03 does not need to be changed, but adjustment may help under the following conditions:
Increase this value for applications with a large load inertia. A higher setting leads to slower response, though, which
can result in oscillation at lower frequencies.
Lower this setting if oscillation occurs at low speed.
n1-05: Hunting Prevention Gain while in Reverse
This parameter is the same as n1-02, except that it is used when rotating in reverse. See the explanation for n1-02.
Note: When set to 0 ms, n1-02 is enabled even when the drive is operating in reverse.
278
No.
Name
Setting Range
Default
n1-05
0.00 to 2.50
0.00
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
n2-01
0.00 to 10.00
1.00
Normally there is no need to adjust n2-01 from the default setting. Make adjustments in the following cases:
If hunting occurs, increase the setting value in steps of 0.05 while checking the response.
If response is low, decrease the setting value in steps of 0.05 while checking the response.
n2-02, n2-03: Speed Feedback Detection Control (AFR) Time Constant 1, 2
Parameter n2-02 sets the time constant normally used by AFR.
Parameter n2-03 sets the time constant during Speed Search or regenerative operation.
No.
Name
Setting Range
n2-02
0 to 2000 ms
Default
50 ms
n2-03
0 to 2000 ms
750 ms
Note: Parameter n2-02 cannot be set higher than n2-03 or an oPE08 error will result.
These parameters rarely need to be changed. Adjust settings only under the following conditions:
The deceleration time that has been set is ignored during HSB. Use Overexcitation Deceleration 1 (L3-04 = 4) or a
dynamic braking option if the motor has to be stopped in a defined time.
Braking time varies based on the load inertia and motor characteristics.
HSB and KEB Ride-Thru cannot be used simultaneously. If enabled at the same time, an oPE03 will occur.
HSB must be triggered by a digital input set to H1- = 68. Once the HSB command is given, it is not possible to
restart the drive until the motor has stopped completely and the Run command is cycled.
Use parameters n3-01 through n3-04 for adjusting HSB.
Name
Setting Range
Default
n3-01
1 to 20%
5%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
279
Name
High Slip Braking Current Limit
Setting Range
Default
100 to 200%
Name
Setting Range
Default
n3-03
0.0 to 10.0 s
1.0 s
Name
Setting Range
Default
n3-04
30 to 1200 s
40 s
As regenerative energy is mainly dissipated as heat in the motor, the motor temperature will rise if Overexcitation
Deceleration is applied frequently. In such cases, make sure the motor temperature does not exceed the maximum
allowable value or consider using a braking resistor option instead.
During Overexcitation Deceleration 2, Hunting Prevention in V/f Control and torque limits in Open Loop Vector
Control are disabled.
Do not use Overexcitation Deceleration in combination with a braking resistor option.
Overexcitation Deceleration can be used in Open and Closed Loop Vector Control, but it lowers the accuracy of Torque
Control, and thereby the braking efficiency. It can be most efficiently used in a V/f Control.
Overexcitation Deceleration cannot be used with PM motors.
Parameter Adjustments
280
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
n3-13
1.00 to 1.40
1.10
The optimum setting for n3-13 depends on the motor flux saturation characteristics.
Increase the gain gradually by 1.25 to 1.30 to improve the braking power of Overexcitation Deceleration.
If flux saturation characteristics cause overcurrent, try lowering n3-13. A high setting sometimes causes overcurrent
(oC), motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.
n3-14: High Frequency Injection during Overexcitation Deceleration
Enables High Frequency Injection while Overexcitation Deceleration is executed. Injecting high frequency into the
motor increases loss, which in turn shortens deceleration time. This function tends to increase audible noise from the
motor, and might not be desirable in environments where motor noise is a concern.
No.
Name
Setting Range
Default
n3-14
0 or 1
Setting 0: Disabled
Setting 1: Enabled
Name
Setting Range
Default
n3-21
0 to 150%
100%
No.
Name
Setting Range
Default
n3-23
0 to 2
Parameter Details
Limit the Overexcitation Deceleration operation selected in parameter L3-04 to forward only or reverse only.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
281
Overshoot
900
750
Suppresses
overshoot at the
end of acceleration
1050
1050
900
750
0
0
0.5
0.5
Time (s)
Time (s)
common_TMonly
common_TMonly
U6-26
Frequency
reference after
Soft Starter
Feed Forward
Control
n5-02/03
+
U1-20
Frequency
Reference
ASR P and I
C5-01/02/03/04
U6-25
Speed
Feedback
Torque reference
U1-09
ASR Output
Name
Setting Range
Default
n5-01
0 or 1
Setting 0: Disabled
Setting 1: Enabled
Parameter Name
Motor Acceleration Time
Setting Range
Default
0.001 to 10.000 s
Determined by C6-01,
E5-01 and o2-04
This value can be set automatically by Inertia Auto-Tuning. If Inertia Auto-Tuning cannot be performed, use one of the
methods below to determine the setting value for this parameter.
282
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
n5-02 =
Where:
JMotor nrated
30 Trated
or
Where:
n5-02 =
4 JMotor frated
p Trated
Take the following steps when measuring the motor acceleration time.
1.
2.
3.
4.
5.
6.
7.
Parameter Name
Setting Range
Default
n5-03
0.00 or 100.00
1.00
1.
2.
3.
4.
5.
6.
n5-03 =
taccel TLim_Test
n5-02
frated
fref_Test 100
-1
Where:
taccel is the measured acceleration time in s.
frated is the rated frequency of the motor in Hz.
TLim_Test is torque limit setting during the test.
fref_Test is the frequency reference during the test in Nxm.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
This value can be set automatically by Inertia Auto-Tuning. If Inertia Auto Tuning cannot be performed, determine the
value for parameter n5-03 using the following steps.
283
Name
Setting Range
Default
n6-01
0 to 2
Setting 0: Disabled
Setting 1: Line-to-line resistance tuning
This setting enables line-to-line resistance online tuning. This procedure is effective for speed values up to 6 Hz and
improves the overload capacity in the low speed range by adjusting the value set for the motor resistance.
Setting 2: Voltage correction
The drive adjusts the output voltage during run to improve overload tolerance and minimize the effects of high
temperatures on speed accuracy.
Note:
This setting can only be selected if the Energy Saving function is disabled (b8-01 = 0).
Name
Setting Range
Default
n6-05
0.10 to 5.00
1.00
Name
Setting Range
Default
n8-01
0 to 100%
50%
Name
Setting Range
Default
n8-02
0 to 150%
80%
Name
Setting Range
Default
n8-35
0 to 2
Setting 0: Pull in
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
High frequency is injected in order to detect the rotor position. Some noise may be generated from the motor at start.
Setting 2: Pulse injection
A pulse signal is injected into the motor in order to detect the rotor position.
n8-45: Speed Feedback Detection Control Gain (OLV/PM)
Sets the gain for internal speed feedback detection control. Although this setting rarely needs to be changed, adjustment
may be necessary under the following conditions:
Increase this setting if motor oscillation or hunting occurs.
Decrease this setting in increments of 0.05 to decrease drive responsiveness.
No.
Name
Setting Range
Default
n8-45
0.00 to 10.00
0.80
Name
Setting Range
Default
n8-47
0.0 to 100.0 s
5.0 s
Name
Setting Range
Default
n8-48
Pull-In Current
20 to 200%
30%
Parameter Details
Sets the d-axis current reference when running with high load at constant speed. When using an IPM motor, setting this
parameter will increase the efficiency by using the motors reluctance torque and thereby reduce the energy consumption.
This parameter should be set to 0 when using an SPM motor.
Although this setting seldom needs to be changed, please note the following:
If motor operation is unstable when driving heavy loads, try lowering this setting.
If motor parameters (E5-) have been changed, this value will be reset to 0 and will need to be readjusted.
No.
Name
Setting Range
Default
n8-49
-200.0 to 0.0%
Determined by E5-01
Name
Setting Range
Default
n8-51
0 to 200%
50%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
285
Name
Setting Range
Default
n8-54
0.00 to 10.00
1.00
Name
Setting Range
Default
n8-55
Load Inertia
0 to 3
Name
Setting Range
Default
n8-57
0 or 1
Setting 0: Disabled
Disable n8-57 with SPM motors. The speed control range will be limited to approximately 1:20.
Setting 1: Enabled
Enabling n8-57 with IPM motors allows precise speed detection in a speed control range of approximately 1:100.
Note: 1. Be aware that using this function will generate some audible noise in the motor up to a certain speed.
2. Set E1-09 to 0.0 when using zero speed control.
Name
Setting Range
Default
n8-62 <1>
200 Vac
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
286
No.
Name
Setting Range
Default
n8-65
0.00 to 10.00
1.50
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
104 to 813
U1-04 (Control Mode) to U8-13
(DWEZ Version Control Monitor 3) <1>
106 (U1-06)
Name
Setting Range
Default
o1-02
1 to 5
No.
Name
Setting Range
Default
o1-03
0 to 3
Determined by A1-02
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output frequency displayed as 100.00, set the o1-10 = 1000 and o1-11 = 2 (i.e.,
1000 with 2 decimal points).
Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
x U1-01: frequency reference
x U1-02: output frequency
x U1-05: motor speed
x U1-16: output frequency after softstarter (accel/decel ramp generator)
x d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units, then set
parameters o1-10 and o1-11.
287
Name
Setting Range
Default
o1-04
0 or 1
Determined by A1-02
Setting 0: Hertz
Setting 1: r/min
Note: For motor 2, o1-04 can only be set to 0 for Hertz.
Name
Setting Range
Default
o1-10
1 to 60000
Determined by o1-03
Name
Setting Range
Default
o1-11
0 to 3
Determined by o1-03
Name
Setting Range
Default
o2-01
0 or 1
Setting 0: Disabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL
is selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 5.41 lists the setting combinations for o2-01 and b1-07.
288
b1-07
0
Not possible
Not possible
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
o2-02
0 or 1
Setting 0: Disabled
Setting 1: Enabled
The STOP key can be used to terminate drive operation, even if the Run command source is not assigned to the digital
operator. If the drive is stopped by pressing the STOP key, the Run command must be cycled to restart the drive.
o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as user-set default values using parameter o203. Once this has been done, the Initialize Parameters parameter (A1-03) will offer the choice of 1110: User
Initialize. Choosing A1-03 = 1110: User Initialize will reset all parameters to the values saved as user-set defaults.
Refer to A1-03: Initialize Parameters on page 133 for details on drive initialization.
No.
Name
Setting Range
Default
o2-03
0 to 2
The current parameter settings are saved as user-set default for a later User Initialize. Once o2-03 is set to 1 and the
ENTER key is pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for User Initialize are cleared. Once o2-03 is set to 2 and the ENTER key is pressed, the values are
erased and the display returns to 0.
o2-04: Drive Model Selection
This parameter must be set when replacing the control board or the terminal board for any reason. For information on the
drive model selection, see Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) on page 466.
No.
Name
o2-04
Setting Range
Default
Determined by drive
capacity
Name
Setting Range
Default
o2-05
0 or 1
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference is saved for 5 s after it is changed.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
289
Parameter Details
NOTICE: Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate
properly.
Name
Setting Range
Default
o2-06
0 or 1
The operation is stopped and an oPr fault is triggered. The motor coasts to stop.
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the
digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
No.
Name
Setting Range
Default
o2-07
0 or 1
Setting 0: Forward
Setting 1: Reverse
Name
Setting Range
Default
o3-01
0 to 3
All parameters are copied from the drive to the digital operator.
Note: The copy protection for the digital operator is enabled by default. To unlock copy protection, set o3-01 = 1.
All parameters are copied from the digital operator to the drive.
3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
o3-02 Copy Allowed Selection
Restricts or allows the use of the Copy function.
No.
Name
Setting Range
Default
o3-02
0 or 1
0: Disabled
1: Enabled
290
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
o4-01
0 to 9999 H
0H
Name
Setting Range
Default
o4-02
0 or 1
The drive logs the time it is connected to a power supply, regardless if the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Run command is active (even if the motor is
not rotating) and when there is voltage output.
o4-03: Cooling Fan Operation Time Setting
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter
o4-03 also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Be sure to reset this
parameter back to 0 if the cooling fan is replaced.
Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h.
300 will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No.
Name
Setting Range
Default
o4-03
0 to 9999 H
0H
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. This value should be reset to 0 when the DC bus capacitors have been replaced.
Note: The actual maintenance time will depend on the environment where the drive is used.
No.
Name
Setting Range
Default
o4-05
0 to 150%
0%
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. This value should be reset to 0 when the bypass relay has been replaced.
Note: The actual maintenance time will depend on the environment where the drive is used.
No.
Name
Setting Range
Default
o4-07
0 to 150%
0%
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
291
Name
Setting Range
Default
o4-09
0 to 150%
0%
Name
Setting Range
Default
o4-11
U2, U3 Initialization
0 or 1
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2- and U3- monitors. Once o4-11 is set to 1 and the ENTER key is pressed, fault data is
erased and the display returns to 0.
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when power is shut off or the drive is initialized. Use o4-12 to
manually reset them.
No.
Name
Setting Range
Default
o4-12
0 or 1
Setting 0: No Action
Resets the kWh counter. The monitors U4-10 and U4-11 will display 0 after they are initialized. Once o4-12 is set to 1
and the ENTER key is pressed, kWh data is erased and the display returns to 0.
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Use o4-13
to reset U4-02.
No.
Name
Setting Range
Default
o4-13
0 or 1
Setting 0: No Action
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.
q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
292
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Parameter Details
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
293
Runtime data of the drive and cooling fans, and number of Run commands issued
Maintenance data and replacement information for various drive components
kWh data
Highest peak current that has occurred and output frequency at the time the peak current occurred
Motor overload status information
Detailed information about the present Run command and frequency reference source selection
Refer to U4: Maintenance Monitors on page 458 for a complete list of U4- monitors and descriptions.
294
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter Details
A complete description of the U8- monitors can be found in the DriveWorksEZ instruction manual.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
295
296
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
6
Troubleshooting
This chapter provides descriptions of the drive faults, alarms, errors, related displays, and
guidance for troubleshooting. This chapter can also serve as a reference guide for tuning the
drive during a trial run.
6.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 MOTOR PERFORMANCE FINE-TUNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 DRIVE ALARMS, FAULTS, AND ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 ALARM DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 OPERATOR PROGRAMMING ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 AUTO-TUNING FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8 COPY FUNCTION RELATED DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.9 DIAGNOSING AND RESETTING FAULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.10 TROUBLESHOOTING WITHOUT FAULT DISPLAY . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
298
300
304
310
323
329
332
336
338
340
297
6.1
Section Safety
DANGER
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power.
298
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
WARNING
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a dynamic braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user.
Check all the wiring after installing the drive and connecting other devices to ensure that all connections are
correct.
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
299
6.2
This section offers helpful information for counteracting oscillation, hunting, or other problems that occur while
performing a trial run. Refer to the section below that corresponds to the motor control method used.
Note: This section describes parameters that are commonly edited and may be set incorrectly. Consult Yaskawa for more information
on detailed settings and fine-tuning the drive.
Motor noise
Motor hunting and oscillation at
speeds up to 40 Hz
Poor torque or speed response
Motor hunting and oscillation
Poor motor torque at speeds below 10
Hz
Motor hunting and oscillation
Poor motor torque at low speeds
Motor instability at motor start
Parameter No.
Corrective Action
Default
Suggested
Setting
If insufficient motor torque relative to the size of the load causes hunting,
reduce the setting.
When motor hunting and oscillation occur with a light load, increase the
setting.
Lower this setting if hunting occurs when using a motor with a relatively
low inductance, such as a high-frequency motor or a motor with a larger
frame size.
1.00
0.10 to 2.00
1 (2 kHz)
1 to max. setting
200 ms <1>
100 to 1000 ms
1.00
0.50 to 1.50
If motor torque and speed response are too slow, decrease the setting.
If motor hunting and oscillation occur, increase the setting.
If motor torque is insufficient at speeds below 10 Hz, increase the setting.
If motor hunting and oscillation with a relatively light load, decrease the
setting.
After setting the motor-rated current (E2-01), motor-rated slip (E2-02), and
motor no-load current (E2-03), adjust the slip compensation gain (C3-01).
Default setting
5 V
0.0
(no slip
compensation)
0.5 to 1.5
C5-01: 0.20
C5-02: 0.200
Proportional gain
= 0.10 to 1.00
Integral time
= 0.100 to 2.000
<1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03.
<3> ASR in V/f Control with PG only controls the output frequency, and therefore does not allow the high gain settings possible when using Close
Loop Vector control.
<4> Refer to C5: Automatic Speed Regulator (ASR) on page 173 for details on Automatic Speed Regulator (ASR).
300
Parameter No.
Corrective Action
Default
Suggested
Setting
AFR Gain
(n2-01)
If motor torque and speed response are too slow, gradually decrease the
setting by 0.05.
If motor hunting and oscillation occur, gradually increase the setting by
0.05.
1.00
0.50 to 2.00
50 ms
50 to 2000 ms
750 ms
750 to 2000 ms
150 ms
150 to 750 ms
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter No.
Default
Suggested
Setting
20 ms <1>
20 to 100 ms <1>
200 ms <2>
100 to 500 ms
1.0 <2>
0.5 to 1.5
1 (2 kHz)
0 to max. setting
Motor noise
Motor hunting and oscillation occur
at speeds below 10 Hz
Corrective Action
If motor torque and speed response are too slow, increase the setting.
Mid Output Voltage A (E1-08) If the motor exhibits excessive instability at start-up, reduce the setting.
Minimum Output Voltage
Note: The default value is for 200 V class units. Double this value when
(E1-10)
using a 400 V class drive. When working with a relatively light load,
increasing this value too much can result in overtorque.
E1-08: 11.0 V
<2>
E1-10: 2.0 V
Default setting
2 V
<2>
<1> Default setting value is dependent on parameter A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03.
When using OLV, leave the torque compensation gain (C4-01) at its default setting of 1.00.
Default
Suggested
Setting
20.00
10.00 to 50.00
If motor torque and speed response are too slow, decrease the setting.
If motor hunting and oscillation occur, increase the setting.
Parameter C5-04 needs to be adjusted only if C5-05 > 0.
0.500 s
0.300 to 1.000 s
Have the drive switch between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0 Hz
If motor torque and speed response are too slow, gradually decrease the
setting by 0.01.
If the load is less rigid and subject to oscillation, increase this setting.
0.004 s
0.004 to 0.020 s
If there is too much motor noise, the carrier frequency is too low.
If motor hunting and oscillation occur at low speeds, reduce the carrier
frequency.
Note: The default setting for the carrier frequency depends on the drive
capacity (o2-04) and Drive Duty Selection (C6-01).
Parameter No.
ASR Proportional Gain 1
(C5-01)
ASR Proportional Gain 2
(C5-03)
<1>
Motor noise
Control motor hunting and oscillation
occur at speeds below 3 Hz.
Overshoot or undershoot when the
speed changes with high inertia load.
Corrective Action
If motor torque and speed response are too slow, gradually increase the
ASR gain setting by 5.
If motor hunting and oscillation occur, decrease the setting.
Parameter C5-03 needs to be adjusted only if C5-05 > 0.
Perform ASR Auto-Tuning if possible
Troubleshooting
Problem
<1> Refer to C5: Automatic Speed Regulator (ASR) on page 173 for details on Automatic Speed Regulator (ASR).
Parameter No.
Corrective Action
Default
Motor parameters
(E1-, E5-)
Check the settings for base and maximum frequency in the E1-
parameters
Check E5- parameters and make sure all motor data has been set
correctly. Be careful not to enter line to line data where single-phase data
is required, and vice versa.
Perform Auto-Tuning.
Adjust parameter n8-55 to meet the load inertia ratio of the machine.
0.8
Increase in
increments of 0.05
6
Suggested
Setting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
301
Increase in steps
of 5%
b2-02 = 50%
b2-03 = 0.0 s
b2-03 = 0.5 s
Increase b2-02 if
needed
5.0 s
Reduce in
increments of 0.2 s
30%
Increase in
increments of 5%
0.8
Increase in
increments 0.05
dep. on drive
capacity and
motor code
Use DC Injection Braking at start to align the rotor. Be aware that this
operation can cause a short reverse rotation at start.
50%
Suggested
Setting
Corrective Action
Default
Parameter No.
Default
Suggested
Setting
10.00
If motor torque and speed response are too slow, decrease the setting.
If motor hunting and oscillation occur, increase the setting.
Parameter C5-03 needs to be adjusted only if C5-05 > 0
0.500 s
0.300 to
1.000 s <1>
Have the drive switch between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0%
0.010 s
0.016 to
0.035 s <1>
Default
Suggested
Setting
20.00
If motor torque and speed response are too slow, decrease the setting.
If motor hunting and oscillation occur, increase the setting.
0.500 s
0.300 to
1.000 s <1>
Have the drive switch between two different ASR proportional gain and
integral time settings based on the output frequency.
0.0%
0.016 s
0.004 to
0.020 s <1>
Parameter No.
Corrective Action
If motor torque and speed response are too slow, gradually increase the
setting by 5.
If motor hunting and oscillation occur, decrease the setting.
Parameter C5-03 needs to be adjusted only if C5-05 > 0.
If the load is less rigid and subject to oscillation, increase this setting.
Check the motor parameter settings.
<1> Optimal settings will differ between no-load and loaded operation.
Parameter No.
ASR Proportional Gain 1
(C5-01)
ASR Proportional Gain 2
(C5-03)
ASR Integral Time 1 (C5-02)
ASR Integral Time 2 (C5-04)
Corrective Action
If motor torque and speed response are too slow, gradually increase the
setting by 5.
If motor hunting and oscillation occur, decrease the setting.
Perform ASR Gain Auto-Tuning if possible
If the load is less rigid and subject to oscillation, increase this setting.
Check the motor parameter settings.
<1> Optimal settings will differ between no-load and loaded operation.
302
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Application
Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there is powerful
backlash on the machine side.
Used to balance the load between two motors that drive the same load. Can be used when the control method (A1-02) is set to
3 or 7.
Adjusting accel and decel times will affect the torque presented to the motor during acceleration or deceleration.
Prevents motor speed loss and overvoltage. Used when the load is too heavy and also during sudden acceleration/
deceleration.
Adjustment is not normally required because Stall Prevention is enabled as a default. Disable Stall Prevention during
deceleration (L3-04 = 0) when using a braking resistor.
Used to increase response for acceleration/deceleration or to reduce overshooting when there is low machine rigidity and the
gain of the speed controller (ASR) cannot be increased. The inertia ratio between the load and motor and the acceleration time
of the motor running alone must be set.
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
303
6.3
Drive model
Software version
Date of purchase
Description of the problem
Table 6.8 contains descriptions of the various types of alarms, faults, and errors that may occur while operating the drive.
Contact Yaskawa in the event of drive failure.
Table 6.8 Types of Alarms, Faults, and Errors
Type
Drive Response
Faults
Operation Errors
When parameter settings conflict with one another or do not match hardware settings (such as with an option card), it results in an operation error. When the
drive detects an operation error:
The digital operator displays text that indicates the specific error.
Multi-function contact outputs do not operate.
The drive will not operate the motor until the error has been reset. Correct the settings that caused the operation error to clear the error.
Tuning Errors
Tuning errors occur while performing Auto-Tuning. When the drive detects a tuning error:
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Motor coasts to stop.
Remove the cause of the error and repeat the Auto-Tuning process.
These are the types of errors that can occur when using the optional digital operator or the USB Copy Unit to copy, read, or verify parameter settings.
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Pressing any key on the operator will clear the fault. Find out what is causing the problem (such as model incompatibility) and try again.
304
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Page
310
FAn
313
bUS
310
FbH
313
CE
MEMOBUS/Modbus Communication
Error
310
FbL
314
CF
Control Fault
310
GF
Ground Fault
314
LF
314
310
LF2
Current Imbalance
314
CPF00, CPF01
CPF02
310
nSE
314
CPF03
311
oC
Overcurrent
315
CPF06
311
oFA00
315
CPF07,
CPF08
oFA01
315
311
oFA03 to oFA06
315
oFA10, oFA11
315
oFA12 to oFA17
315
oFA30 to oFA43
315
to
,
CPF20, CPF21
311
<1>
to
,
CPF22
Hybrid IC Error
311
CPF23
311
CPF24
311
311
dEv
312
oFb00
316
dv1
312
oFb01
316
dv2
312
oFb02
316
dv3
Inversion Detection
312
oFb03, oFb11
316
dv4
312
CPF26 to CPF34
dWFL
to
Page
boL
<1>
Name
DriveWorksEZ Fault
312
E5
312
EF0
313
313
EF1 to EF8
Err
313
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
to
to
to
oFb12 to oFb17
316
to
oFb30 to oFb43
316
oFC00
316
oFC01
316
oFC02
316
305
Troubleshooting
to
Name
oFC03, oFC11
Page
ov
Overvoltage
319
PF
320
320
320
rF
320
rH
320
320
317
PGoH
to
oFC30 to
oFC43
Page
317
PGo
oFC12 to oFC17
Name
317
oH
Heatsink Overheat
317
rr
oH1
Heatsink Overheat
317
SEr
320
oH3
317
STo
Pull-Out Detection
321
oH4
317
SvE
Zero-Servo Fault
321
oL1
Motor Overload
318
UL3
Undertorque Detection 1
321
oL2
Drive Overload
318
UL4
Undertorque Detection 2
321
oL3
Overtorque Detection 1
318
UL5
321
oL4
Overtorque Detection 2
318
Uv1
Undervoltage
321
oL5
318
Uv2
322
oL7
319
Uv3
322
oPr
319
voF
322
oS
319
<1> Displayed as
display will show
or
or
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the
.
Page
YES
323
No output
323
boL
YES
323
bUS
YES
323
YES
323
YES
324
CrST
Cannot Reset
YES
324
dEv
YES
324
dnE
Drive Disabled
YES
324
DriveWorksEZ Alarm
YES
312
YES
312
CALL
CE
dWAL
E5
306
Name
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
to
Name
Page
EF
YES
324
EF0
YES
324
YES
324
FbH
YES
325
FbL
YES
325
Hbb
YES
325
HbbF
YES
325
HCA
Current Alarm
YES
325
LT-1
No output <1>
325
LT-2
No output <1>
326
LT-3
No output <1>
326
LT-4
No output <1>
326
EF1 to EF8
oH
Heatsink Overheat
YES
326
oH2
Drive Overheat
YES
326
oH3
Motor Overheat
YES
326
oL3
Overtorque 1
YES
326
oL4
Overtorque 2
YES
326
oL5
YES
327
oS
YES
327
ov
Overvoltage
YES
327
PASS
No output
327
PGo
YES
327
YES
327
rUn
YES
327
SE
YES
327
TrPC
YES
327
UL3
Undertorque 1
YES
328
UL4
Undertorque 2
YES
328
UL5
YES
321
Uv
Undervoltage
YES
328
voF
YES
328
PGoH
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
307
Name
Page
Name
Page
oPE01
329
oPE09
330
oPE02
329
oPE10
331
oPE03
329
oPE11
331
oPE04
330
oPE13
331
oPE05
330
oPE15
331
oPE06
330
oPE16
331
oPE07
330
oPE18
331
oPE08
330
Auto-Tuning Errors
Table 6.13 Auto-Tuning Error Displays
Digital Operator Display
Name
Page
Name
Page
End1
332
Er-09
Acceleration Error
333
End2
332
Er-10
333
End3
332
Er-11
334
End4
332
Er-12
334
End5
332
Er-13
334
End6
332
Er-14
334
End7
332
Er-15
334
Er-01
333
Er-16
Inertia ID Error
334
Er-02
Alarm
333
Er-17
334
Er-03
333
Er-18
334
Er-04
333
Er-19
PM Inductance Error
334
Er-05
333
Er-20
334
Er-08
333
Er-21
335
308
Name
Page
CoPy
336
CPEr
336
CPyE
336
CSEr
336
dFPS
336
End
Task completed
336
iFEr
Communication error
336
ndAT
336
rdEr
337
rEAd
337
vAEr
337
vFyE
Parameter settings in the drive and those saved to the copy function are not the same
337
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Comparing parameter settings (flashing)
Page
337
Troubleshooting
vrFy
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
309
6.4
Fault Detection
Fault Name
boL
Cause
Possible Solution
Fault Name
Option Communication Error
bUS
Cause
Possible Solution
Replace the option card if there are no problems with the wiring and the error continues to occur.
The connector pins on the option card are not properly lined up with the connector pins on the drive.
Reinstall the option card.
Fault Name
CE
Cause
Possible Solution
Fault Name
CF
Control Fault
A torque limit was reached continuously for three seconds or longer while ramping to stop in Open Loop Vector Control.
Cause
Possible Solution
Set the torque limit to the most appropriate setting (L7-01 through L7-04).
Fault Name
or
CPF00 or CPF01
<1>
<1>
Cause
Possible Solution
310
Fault Name
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Possible Solution
Cycle power to the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Cause
Possible Solution
Turn the power off and check the connection between the control board and the drive.
If the problem continues, replace either the control board or the entire drive.
Fault Name
EEPROM Memory Data Error
There is an error in the data saved to EEPROM.
Cause
Possible Solution
Turn the power off and check the connection between the control board and the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Fault Name
CPF07
Terminal Board Connection Error
CPF08
Cause
Possible Solution
Turn the power off and reconnect the control circuit terminal board.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
CPF20 or CPF21
Cause
Possible Solution
Cycle power to the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Hardware is damaged.
Digital Operator Display
CPF22
Fault Name
Hybrid IC Error
Cause
Possible Solution
Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 338.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Cause
Possible Solution
Turn the power off and check the connection between the control board and the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Hardware is damaged.
Digital Operator Display
CPF24
Fault Name
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Cause
Possible Solution
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Hardware is damaged.
Digital Operator Display
CPF26 to CPF34
to
Fault Name
Control Circuit Error
CPU error
Cause
Hardware is damaged.
Troubleshooting
or
Fault Name
Possible Solution
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
311
Fault Name
Speed Deviation (for Control Mode with PG)
dEv
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer than the time set to
F1-11.
Cause
Possible Solution
Set H6-02 to the same value as the speed feedback signal frequency when the motor runs at maximum speed.
Adjust the speed feedback signal using parameters H6-03 through H6-05.
Make sure the speed feedback signal frequency does not exceed the maximum input frequency of terminal RP.
Fault Name
dv1
Z Pulse Fault
The motor turned one full rotation without the Z pulse being detected.
Cause
Possible Solution
Make sure the PG encoder is properly connected and all shielded lines are properly grounded.
If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself.
Fault Name
dv2
Cause
Possible Solution
Separate the PG cable lines from the source of the noise (very possibly drive output wiring).
Rewire the PG encoder and make sure all shielded lines are properly grounded.
If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself.
Fault Name
Inversion Detection
dv3
The torque reference and acceleration are in opposite directions from one another (one is in reverse and the other is forward)
while at the same time the speed reference and actual motor speed differ by over 30% for the number of pulses set to F1-18.
Cause
Possible Solution
Set the value for to E5-11 as specified on the motor nameplate. Replacing the PG encoder or changing the application so that
the motor rotates in reverse instead requires readjustment of the Z pulse offset.
An external force on the load side has caused the motor Make sure the motor is rotating in the right direction.
to move.
Look for any problems on the load side that might be causing the motor to rotate in the opposite direction.
Noise interference along the PG cable affecting the A or
B pulse.
PG encoder is disconnected, not wired properly, or the
PG option card or PG itself is damaged.
Rotational direction for the PG encoder set to F1-05 is
the opposite of the order of the motor lines.
Rewire the PG encoder and make sure all lines including shielded line are properly connected.
Make sure motor lines for each phase (U, V, W) are connected properly.
Fault Name
Inversion Prevention Detection
dv4
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number of pulses to trigger
inverse detection to F1-19.
Note: Disable inverse detection in applications where the motor may rotate in the opposite direction of the speed reference.
Setting F1-19 to 0 disables this feature.
Cause
Possible Solution
Noise interference along the PG cable affecting the A or Make sure the motor is rotating in the correct direction.
B pulse.
Look for any problems on the load side that might be causing the motor to rotate in the opposite direction.
PG encoder is disconnected, not wired properly, or the
PG option card or PG itself is damaged.
Rewire the PG encoder and make sure all lines including shielded line are properly connected.
If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself.
Fault Name
dWAL
DriveWorksEZ Fault
dWFL
Cause
Possible Solution
Fault Name
E5
Cause
Data has not been received from the PLC, triggering the
Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and proceed to phase 3.
watchdog timer.
312
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
EF0
Cause
Possible Solution
Fault Name
EF1
EF2
EF3
EF4
EF5
EF6
EF7
EF8
Cause
Possible Solution
Remove the cause of the external fault and reset the fault.
Wiring is incorrect.
Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1- = 20 to 2F).
Reconnect the signal line.
Check if the any unused terminals are set for H1- = 20 to 2F (External Fault).
Change the terminal settings.
Fault Name
Err
Cause
Possible Solution
Press the
button.
Noise has corrupted data while writing to the EEPROM. Correct the parameter setting.
Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 338.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Hardware problem.
Digital Operator Display
FAn
Fault Name
Internal Fan Fault
Fan or magnetic contactor failed.
Possible Solution
Cycle power to the drive and see if the fault is still present.
Check if the fan is operating or not.
Internal cooling fan has malfunctioned (models 2A0360,
Verify the cumulative operation time of the fan using monitor U4-03, and the fan maintenance timer in U4-04.
2A0415, 4A0362 to 4A0675).
If the cooling fan has passed its expected performance life or is damaged in some way, follow the instructions in this manual to
replace it.
Fault detected in the internal cooling fan or magnetic
contactor to the power supply (models 2A0250 to
2A0415, 4A0165 to 4A0675).
Cycle power to the drive and see if the fault is still present.
If the fault still occurs, either replace the control circuit board or the entire unit.
For instructions on replacing the power board, contact the Yaskawa sales office directly or your nearest Yaskawa representative.
Fault Name
Excessive PID Feedback
FbH
PID feedback input is greater than the level set b5-36 for longer than the time set to b5-37. To enable fault detection, set b5-12 =
2 or 5.
Cause
Parameters are not set appropriately.
Possible Solution
Check the settings of parameters b5-36 and b5-37.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
313
Troubleshooting
Cause
Fault Name
PID Feedback Loss
FbL
This fault occurs when PID feedback loss detection is programmed to trigger a fault (b5-12 = 2) and the PID feedback level is
below the detection level set to b5-13 for longer than the time set to b5-14.
Cause
Possible Solution
Check the sensor on the controller side. If damaged, replace the sensor.
Fault Name
Ground Fault
GF
A current short to ground exceeded 50% of rated current on the output side of the drive.
Setting L8-09 to 1 enables ground fault detection in models 2A0030 through 2A0415 and 4A0018 through 4A0675.
Cause
Possible Solution
Check the insulation resistance of the motor.
Replace the motor.
The value set exceeds the allowable setting range while the drive automatically adjusts the current offset (this happens only
when attempting to restart a PM motor that is coasting to stop).
Enable Speed Search at start (b3-01 = 1).
Perform Speed Search 1 or 2 (H1- = 61 or 62) via one of the external terminals.
Note: Speed Search 1 and 2 are the same when using PM OLV.
Hardware problem.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Fault Name
Output Phase Loss
LF
Cause
Possible Solution
Check for wiring errors and ensure the output cable is connected properly.
Correct the wiring.
Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on
page 79.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Fault Name
Output current imbalance (detected when L8-29 = 1)
One or more of the phases in the output current is lost.
Cause
Possible Solution
Check for faulty wiring or poor connections on the output side of the drive.
Correct the wiring.
Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on
page 79.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Measure the line-to-line resistance for each motor phase. Ensure all values are the same.
Replace the motor.
Fault Name
Node Setup Error
A terminal assigned to the node setup function closed during run.
Cause
Possible Solution
314
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
oC
Overcurrent
Drive sensors have detected an output current greater than the specified overcurrent level.
Cause
Possible Solution
Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration time. If the right amount
of torque cannot be set, make the following changes:
Increase the acceleration time (C1-01, -03, -05, -07)
Increase the S-curve characteristics (C2-01 through C2-04)
Increase the capacity of the drive.
The drive is attempting to operate a specialized motor or Check the motor capacity.
a motor larger than the maximum size allowed.
Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the motor nameplate.
Magnetic contactor (MC) on the output side of the drive
Set up the operation sequence so that the MC is not tripped while the drive is outputting current.
has turned on or off.
V/f setting is not operating as expected.
Fault Name
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Cause
Possible Solution
Check if the drive supports the option card that you are attempting to install. Contact Yaskawa for assistance.
PG option boards are supported by option ports CN5-B and CN5-C only. Place the PG option card into the correct option port.
Cause
Possible Solution
Fault Name
oFA03 to oFA06
to
,
oFA10, oFA11
to
oFA12 to oFA17
to
oFA30 to oFA43
Cause
Possible Solution
Cycle power to the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
oFA01
Fault Name
Option Card Fault at Option Port CN5-A
315
Fault Name
Option Card Fault at Option Port CN5-B
Option compatibility error
Cause
Possible Solution
Check if the drive supports the option card that you are attempting to install. Contact Yaskawa for assistance.
Communication option cards are supported by option port CN5-A only. More than one comm. option cannot be installed.
Fault Name
Option Card Fault at Option Port CN5-B
Option not properly connected
Cause
Possible Solution
Fault Name
Option Card Fault at Option Port CN5-B
Same type of option card already connected
Cause
Possible Solution
Except for PG options, each option card type can only be installed once. Make sure only one type of option card is connected.
Make sure that a comm. option, a digital input option, or an analog input option is installed. The same type of card cannot be
installed twice.
oFb03 to oFb11
to
oFb12 to oFb17
Fault Name
oFb30 to oFb43
to
Cause
Possible Solution
Cycle power to the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Fault Name
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Cause
Possible Solution
Check if the drive supports the option card that you are attempting to instal. Contact Yaskawa for assistance.
Communication option cards are supported by option port CN5-A only. More than one comm. option cannot be installed.
Fault Name
Option Card Fault at Option Port CN5-C
Option not properly connected
Cause
Possible Solution
Fault Name
Option Card Fault at Option Port CN5-C
Same type of option card already connected
Possible Solution
Except for PG options, each option card type can only be installed once. Make sure only one type of option card is connected.
Make sure that a comm. option, a digital input option, or an analog input option is installed. The same type of card cannot be
installed twice.
Maximum two PG option boards can be used at the same time. Remove the PG option board installed into option port CN5-A.
316
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
to
oFC03 to oFC11
to
oFC12 to oFC17
oFC30 to oFC43
to
Cause
Possible Solution
Cycle power to the drive.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
Fault Name
Heatsink Overheat
oH
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02. Default value for L8-02 is determined by
drive capacity (o2-04).
Cause
Possible Solution
Check the temperature surrounding the drive. Verify temperature is within drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Replace the cooling fan. Refer to Cooling Fan Component Names on page 356.
After replacing the drive, reset the cooling fan maintenance parameter (o4-03 = 0).
Fault Name
Overheat 1 (Heatsink Overheat)
The temperature of the heatsink exceeded the drive overheat level. The overheat level is determined by drive capacity (o2-04).
Cause
Possible Solution
Fault Name
Motor Overheat Alarm (PTC Input)
oH3
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level.
Detection requires multi-function analog input H3-02, H3-06, or H3-10 be set to E.
Cause
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10.
Be careful not to lower E1-08 and E1-10 too much, as this reduces load tolerance at low speeds.
Fault Name
Motor Overheat Fault (PTC Input)
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the fault detection level.
Detection requires that multi-function analog input H3-02, H3-06, or H3-10 = E.
Cause
Troubleshooting
oH4
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Be careful not to
lower E1-08 and E1-10 too much because this reduces load tolerance at low speeds.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
317
Fault Name
oL1
Motor Overload
The electronic motor overload protection tripped.
Cause
Possible Solution
Adjust the user-set V/f patterns (E1-04 through E1-10). Parameters E1-08 and E1-10 may need to be reduced. Be careful not to
lower E1-08 and E1-10 too much because this reduces load tolerance at low speeds.
Disable the motor protection function (L1-01 = 0) and install a thermal relay to each motor.
Overexcitation increases the motor losses and the motor temperature. If applied too long, motor damage can occur. Prevent
excessive overexcitation operation or apply proper cooling to the motor.
Reduce the excitation deceleration gain (n3-13).
Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Fault Name
oL2
Drive Overload
The thermal sensor of the drive triggered overload protection.
Cause
Possible Solution
Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10.
Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds.
Reduce the torque compensation gain (C4-01) until there is no speed loss but less current.
Fault Name
oL3
Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Cause
Possible Solution
Check the status of the load. Remove the cause of the fault.
Fault Name
oL4
Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06).
Cause
Possible Solution
Fault Name
oL5
Cause
Overtorque triggered mechanical weakening detection
level set to L6-08.
318
Possible Solution
Check for the cause of mechanical weakening.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
oL7
Cause
Possible Solution
Reduce deceleration times in parameters C1-02, C1-04, C1-06, and C1-08 for applications that do not use High Slip Braking.
Use a braking resistor to shorten deceleration time.
Increase parameter n3-04 (High-slip Braking Overload Time).
Install a thermal relay and increase the setting of n3-04 to the maximum value.
Fault Name
External Digital Operator Connection Fault
oPr
Cause
Possible Solution
Fault Name
oS
Cause
Possible Solution
Overshoot is occurring.
Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
If using a Closed Loop Vector mode, enable Feed Forward and perform Inertia Auto-Tuning.
Set H6-02 to the value of the speed feedback signal frequency when the motor runs at the maximum speed.
Adjust the input signal using parameters H6-03 through H6-05.
Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
Fault Name
Overvoltage
ov
Cause
Possible Solution
speed reference.
The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking torque, use a dynamic
braking option, or lengthen decel time.
Install a DC reactor.
Note: Voltage surge can result from a thyristor convertor and phase advancing capacitor using the same input power supply.
PG cable is disconnected.
Separate the wiring from the source of the noise (often the output lines from the drive).
Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention during deceleration.
Adjust the load inertia ratio in L3-25 to better match the load.
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
319
Fault Name
PF
Cause
Possible Solution
Check for wiring errors in the main circuit drive input power.
Correct the wiring.
Check for anything problems with the drive input power. If drive input power appears normal but the alarm continues to occur,
replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Fault Name
PGo
Cause
Possible Solution
PG cable is disconnected.
PG has no power.
Fault Name
PGoH
Cause
Possible Solution
PG cable is disconnected.
Fault Name
rF
Cause
Possible Solution
Select the braking resistor option so that fits to the drives braking transistor specification.
Fault Name
Braking Resistor Overheat
rH
Cause
Possible Solution
Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor settings.
Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors (L8-01 = 1) allows a braking
duty cycle of maximum 3%.
Check the specifications and conditions for the braking resistor device.
Select the optimal braking resistor.
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more frequently than it is rated for trips the alarm
even when the braking resistor surface is not very hot.
Digital Operator Display
Fault Name
rr
Cause
Possible Solution
Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 338.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Fault Name
SEr
Cause
Possible Solution
320
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
STo
Cause
Possible Solution
Enter the correct motor code for the PM being used into E5-01.
For special-purpose motors, enter the correct data to all E5 parameters according to the test report provided for the motor.
Fault Name
Zero Servo Fault
Position deviation during zero servo.
Cause
Possible Solution
Set the torque limit to an appropriate value using parameters L7-01 to L7-04.
Fault Name
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Cause
Possible Solution
Fault Name
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06).
Cause
Possible Solution
Fault Name
Mechanical Weakening Detection 2
The operation conditions matched the conditions set to L6-08.
Cause
Possible Solution
Fault Name
DC Bus Undervoltage
One of the following conditions occurred while the drive was stopped:
Voltage in the DC bus fell below the undervoltage detection level (L2-05)
For 200 V class: approximately 190 V
For 400 V class: approximately 380 V (350 V when E1-01 is less than 400) The fault is output only if L2-01 = 0 or L2-01 = 1
and the DC bus voltage has fallen below the level set to L2-05 for longer than the time set to L2-02.
Cause
Possible Solution
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
Uv1
321
Fault Name
Control Power Supply Voltage Fault
Uv2
Cause
Possible Solution
Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.
Fault Name
Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
Uv3
Cause
Possible Solution
Fault Name
voF
Cause
322
Problem detected with the voltage on the output side of the drive.
Possible Solution
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative.
Hardware is damaged.
<1> Displayed as
display will show
or
or
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the
.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
6.5
Alarm Detection
AEr
Cause
Possible Solutions
Set parameter F6-10 to the proper value if a CC-Link option card is used.
Set parameter F6-35 to the proper value if a CANopen option card is used.
Baseblock
Drive output interrupted as indicated by an external baseblock signal.
Cause
Possible Solutions
Cause
Possible Solutions
bUS
Cause
Possible Solutions
If there are no problems with the wiring and the fault continues to occur, replace the option card.
The connector pins on the option card are not properly lined up with the connector pins on the drive.
Reinstall the option card.
Cause
Communications wiring is faulty, there is a short
circuit, or something is not connected properly.
Troubleshooting
Possible Solutions
Check for wiring errors.
Correct the wiring.
Check for disconnected cables and short circuits. Repair as needed.
A termination resistor must be installed at both ends of a communication line. Slave drives must have the internal termination resistor
switch set correctly. Place DIP switch S2 to the ON position.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
323
CE
Cause
Possible Solutions
Check the H5 parameter settings as well as the protocol setting in the controller.
Ensure settings are compatible.
The CE detection time (H5-09) is set shorter than the Check the PLC.
time required for a communication cycle to take
Change the software settings in the PLC.
place.
Set a longer CE detection time (H5-09).
Incompatible PLC software settings or there is a
hardware problem.
CrST
Cannot Reset
Cause
Possible Solutions
Ensure that a Run command cannot be entered from the external terminals or option card during fault reset.
Turn off the Run command.
dEv
Cause
Possible Solutions
Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08).
The load is locked up.
Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
Adjust the speed feedback signal using parameters H6-03 through H6-05.
Make sure the speed feedback signal frequency does not exceed he maximum input frequency of terminal RP.
dnE
Drive Disabled
Cause
Possible Solutions
Cause
Possible Solutions
Check the forward and reverse command sequence and correct the problem.
Note: When minor fault EF detected, motor ramps to stop.
Sequence error
Digital Operator Display
EF0
Cause
Possible Solutions
324
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Cause
Possible Solutions
Remove the cause of the external fault and reset the multi-function input value.
Wiring is incorrect.
Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1- = 20 to 2F).
Reconnect the signal line.
Check if the unused terminals have been set for H1- = 20 to 2F (External Fault).
Change the terminal settings.
Cause
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
Cause
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
Cause
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
Cause
Possible Solutions
Check signal status at the input terminals H1 and H2. If the Safe Disable function is not utilized, the terminals H1-HC, and H2-HC
must be linked.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
Troubleshooting
HCA
Cause
Possible Solutions
Either reduce the load for applications with repetitive operation (repetitive stops and starts, etc.), or replace the drive.
Calculate the torque required during acceleration and for the inertia moment.
If the torque level is not right for the load, take the following steps:
Increase the acceleration and deceleration times (C1-01 through C1-08).
Increase the capacity of the drive.
LT-1
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.
Cause
The cooling fan has reached 90% of its expected
performance life.
Possible Solutions
Replace the cooling fan and reset the Maintenance Monitor by setting o4-03 to 0.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
325
LT-2
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.
Cause
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
LT-3
The DC bus soft charge relay is nearing the end of its expected performance life.
Note: An alarm output (H2- = 10) will only be triggered if H2- = 2F.
Cause
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
LT-4
Cause
Possible Solutions
oH
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100C). Default value for L8-02 is
determined by drive capacity (o2-04).
Cause
Possible Solutions
Replace the cooling fan. Refer to Cooling Fan Component Names on page 356.
After replacing the drive, reset the cooling fan maintenance parameter to (o4-03 = 0).
Provide proper installation space around the drive as indicated in the manual. Refer to Installation Orientation and Spacing on
page 42.
Allow for the specified space and ensure that there is sufficient circulation around the control panel.
Cause
Possible Solutions
An external device triggered an overheat warning in Search for the device that tripped the overheat warning.
the drive.
Solving the problem will clear the warning.
Digital Operator Display
oH3
Cause
Possible Solutions
Cause
Possible Solutions
Cause
Possible Solutions
326
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
oL5
Cause
Possible Solutions
Cause
Possible Solutions
Overshoot is occurring.
Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
If using a Closed Loop Vector mode enable Feed Forward Control and perform Inertia Auto-Tuning.
Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
Adjust the input signal using parameters H6-03 through H6-05.
Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
Cause
Possible Solutions
PG cable is disconnected.
Separate PG wiring from the source of the noise (often output wiring from the drive).
PASS
Cause
Possible Solutions
PGo
Cause
Possible Solutions
PG cable is disconnected.
Make sure the correct power supply is properly connected to the PG encoder.
PGoH
Troubleshooting
Cause
Possible Solutions
PG cable is disconnected.
rUn
Cause
Possible Solutions
Change the operation pattern so that the motor switch command is entered while the drive is stopped.
Cause
Possible Solutions
Cause
IGBTs have reached 90% of their expected
performance life.
Possible Solutions
Replace the drive.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
327
Cause
Possible Solutions
Cause
Possible Solutions
Uv
One of the following conditions was true when the drive was stopped and a Run command was entered:
DC bus voltage dropped below the level specified in L2-05.
Contactor to suppress inrush current in the drive was opened.
Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05.
Cause
Possible Solutions
Check for wiring errors in the main circuit drive input power. Correct the wiring.
Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
Check the capacity of the drive input power transformer.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest
sales representative.
328
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
6.6
Error Name
oPE01
Cause
Possible Solutions
The drive model selection (o2-04) and the actual capacity of the drive are not the same.
Error Name
oPE02
Cause
Possible Solutions
Note: When multiple errors occur at the same time, other errors are given precedence over oPE02.
Digital Operator Display
Error Name
oPE03
Cause
Possible Solutions
The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11).
Correctly set functions that need to be enabled in combination with other functions.
Run/Stop command for a 2-wire sequence was set (H1- = 42), but Forward/Reverse
command (H1- = 43) was not.
Drive Enable is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A).
Correctly set functions that need to be enabled in combination with other functions.
Check if contradictory settings have been assigned to the multi-function input terminals at
the same time.
Correct setting errors.
The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01).
Settings for N.C. and N.O. input for the following functions were selected at the same time:
External Search Command 1 and External Search Command 2 (61 vs. 62)
Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68)
Check for contradictory settings assigned to the multi-function input terminals at the same
Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A)
time. Correct setting errors.
KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B)
FWD Run Command (or REV) and FWD/REV Run Command (2-wire) (40, 41 vs. 42, 43)
External DB Command and Drive Enable (60 vs. 6A)
Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)
One of the following settings was entered while H1- = 2 (External Reference 1/2):
b1-15 = 4 (Pulse Train Input) but the pulse train input selection is not set for the frequency
reference (H6-01 > 0)
b1-15 or b1-16 set to 3 but no option card is connected
Correct the settings for the multi-function input terminal parameters.
Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias)
Error Name
oPE04
Initialization required.
Cause
The drive, control board, or terminal board has been replaced and the parameter settings
between the control board and the terminal board no longer match.
Possible Solutions
To load the parameter settings to the drive that are stored in the terminal board, set A1-03 to
5550. Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs.
76).
329
Error Name
oPE05
Cause
Possible Solutions
Frequency reference is assigned to an option card (b1-01 = 3) but an input option card is not
connected to the drive.
The Run command is assigned to an option card (b1-02 = 3) but an input option card is not
connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set
Set H6-01 to 0.
for frequency reference input (H6-01 > 0)
Although the digital card input is set for BCD special for a 5 digit input (F3-01 = 6), the data
length is set for 8 bit or 12 bit (F3-03 = 0, 1).
The following values have been set while an AI-A3 option card is installed:
The source of frequency reference setting is assigned to an option card (b1-01 = 3).
The action for the analog card is set for separate terminal input (F2-01 = 0).
Error Name
Control Method Selection Error
oPE06
Cause
Possible Solutions
A control mode has been selected that requires a PG option card to be installed, but no PG
encoder is installed (A1-02 = 1, 3, or 7).
Error Name
Multi-Function Analog Input Selection Error
oPE07
Cause
Possible Solutions
At least two analog input terminals are set to the same function (i.e., at least two of these
parameters has the same setting: H3-02, H3-06, or H3-10).
Change the settings to H3-02, H3-06, and H3-10 so that functions no longer conflict.
Note: Both 0 (frequency reference bias) and F (not used) can be set to H3-02, H3-06, and
H3-10 at the same time.
Error Name
Parameter Selection Error
oPE08
A function has been set that cannot be used in the motor control method selected.
Cause
Possible Solutions
Attempted to use a function that is not valid for the selected control mode.
Set the correct motor code in accordance with the motor being used (E5-01).
When using a special-purpose motor, set E5- in accordance with the test report
provided.
Set E5-09 or E5-24 to the correct value, and set the other to 0.
Set the motor rated current for PM to 0 (E5-03).
b1-14 (Phase Order Selection) is set to 1 (Switch phase order) when in using a PG option card. Correct the parameter settings.
In AOLV/PM High Frequency Injection is disabled (n8-57 = 0) and the minimum frequency
(E1-09) is set lower than 1/20 of the base frequency setting.
Note: Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over oPE08 when multiple errors occur at the same time.
Digital Operator Display
Error Name
PID Control Selection Fault
oPE09
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1
to 4).
Cause
Possible Solutions
PID control is set to b5-01 = 3 or 4, but the lower limit for the frequency reference (d2-01) is
not 0.
330
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Error Name
V/f Data Setting Error
oPE10
Cause
Possible Solutions
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11 (for motor 2, correct E3-04,
E3-06, E3-07, E3-09, and E3-11).
Error Name
oPE11
Cause
Possible Solutions
The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is
greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is
less than or equal to 6, the drive operates at C6-03.
Upper and lower limits between C6-02 and C6-05 contradict each other.
Digital Operator Display
Error Name
oPE13
Cause
Possible Solutions
Scaling for the pulse train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 101, 102,
105, or 116.
Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105, or 116.
Error Name
oPE15
Cause
Possible Solutions
Torque Control in enabled (d5-01 = 1) while the Speed/Torque Control switch function is
assigned to a digital input (H1- = 71).
Either Torque Control is enabled by d5-01 = 1, the or Speed/Torque Control switch is assigned
to a digital input H1- = 71, while at the same time:
Correct the parameter settings.
Feed Forward is enabled (n5-01 = 1), or
Droop Control is enabled (b7-01 0), or
Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled (L3-04 = 2 or 5), or
A digital input is set for the power KEB 1 or KEB 2 (H1- = 7A or 7B)
Digital Operator Display
Error Name
oPE16
Cause
Possible Solutions
In AOLV/PM the automatically calculated energy saving coefficients are out of the allowable
Check and correct the motor data in E5 parameters.
range.
Digital Operator Display
Error Name
oPE18
Cause
Possible Solutions
Troubleshooting
One of the following setting errors has occurred while Online Tuning is enabled in OLV (A102 = 2):
E2-02 has been set below 30% of the original default value
Make sure E2-02, E2-03, and E2-06 are set the correct values.
E2-06 has been set below 50% of the original default value
E2-03 = 0
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
331
6.7
Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator
and the motor coasts to a stop. Auto-Tuning faults do not trigger an multi-function terminal set for fault or alarm output.
An End error indicates that although Auto-Tuning has completely successful, there is some discrepancy in the
calculations the drive made. If an End error occurs, check for what might be causing the error using the table below,
and perform Auto-Tuning again once the problem has been taken care of. If there appears to be no problem despite the
End error being displayed, go ahead and start the application.
Error Name
Excessive V/f Setting (detected only during Rotational Auto-Tuning, and displayed after Auto-Tuning is complete)
Cause
Possible Solutions
Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05.
Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning.
If possible, disconnect the motor from the load and perform Auto-Tuning. If the load cannot be uncoupled, simply use the AutoTuning results as they are.
Error Name
Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete)
Cause
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Error Name
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
Cause
Possible Solutions
Error Name
Adjusted Slip Calculation Error
Cause
Possible Solutions
The slip that was calculated is outside the allowable Make sure the data entered for Auto-Tuning is correct.
range.
Execute Rotational Auto-Tuning instead. If not possible, try Stationary Auto-Tuning 2.
Digital Operator Display
End5
Error Name
Resistance Tuning Error
Cause
Possible Solutions
Double check the data that was entered for the Auto-Tuning process.
Check the motor and motor cable connection for faults.
Error Name
Leakage Inductance Alarm
Cause
Possible Solutions
Double check the data that was entered for the Auto-Tuning process.
Error Name
No-Load Current Alarm
Cause
Possible Solutions
Double check the data that was entered for the Auto-Tuning process.
332
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Error Name
Motor Data Error
Cause
Possible Solutions
Motor data or data entered during Auto-Tuning was Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-Tuning.
incorrect.
Start Auto-Tuning over again and enter the correct information.
Motor output power and motor-rated current settings Check the drive and motor capacities.
(T1-02 and T1-04) do not match.
Correct the settings of parameters T1-02 and T1-04.
Motor rated current and detected no-load current are Check the motor rated current and no-load current.
not consistent with another.
Correct the settings of parameters T1-04 and E2-03.
Base frequency and motor rated speed (T1-05 and
T1-07) do not match.
Error Name
Minor Fault
Cause
Possible Solutions
Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.
Error Name
STOP Button Input
Cause
Possible Solutions
Auto-Tuning did not complete properly and will have to be performed again.
Error Name
Line-to-Line Resistance Error
Cause
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Error Name
No-Load Current Error
Cause
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the parameter Check and correct faulty motor wiring.
setting range or the tuning process took too long.
Perform Rotational Auto-Tuning.
The load during Rotational Auto-tuning was too
high.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make sure the load is lower
than 30%.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Error Name
Rated Slip Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make sure the load is lower
than 30%.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Error Name
Acceleration Error
Cause
Possible Solutions
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make sure the load is lower
than 30%.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Error Name
Motor Direction Error
Cause
Possible Solutions
Check the motor speed monitor U1-05 while turning the motor manually in forward direction. If the sign displayed is negative,
change the setting of parameter F1-05.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
Cause
Motor data entered during Auto-Tuning was
incorrect.
333
Error Name
Motor Speed Fault
Cause
Possible Solutions
Increase the acceleration time (C1-01).
Disconnect the machine from the motor, if possible.
Error Name
Current Detection Error
Cause
Possible Solutions
Error Name
Leakage Inductance Error
Cause
Possible Solutions
Error Name
Motor Speed Error 2
Cause
Possible Solutions
Error Name
Torque Saturation Error
Cause
Possible Solutions
Increase the torque limits in L7-01 through L7-04 (but keep them within reasonable limits).
The output torque reached the torque limit set in L7 First try reducing the test signal amplitude in T3-01 and repeat the tuning. If necessary, then try reducing the test signal frequency
01 through L7-04 during Inertia Tuning.
(T3-02) and repeat the tuning.
Digital Operator Display
Er-16
Error Name
Inertia Detection Error
Cause
Possible Solutions
First try reducing the test signal amplitude in T3-01 and repeat the tuning. If necessary, then try reducing the test signal frequency
(T3-02) and repeat the tuning.
Check the basic motor inertia value entered to T3-03.
Error Name
Reverse Prohibited Error
Cause
Possible Solutions
Inertia Auto-Tuning cannot be performed if the drive is restricted from rotating in reverse.
Assuming it is acceptable for the application to rotate in reverse, set b1-04 to 0 and then execute Inertia Tuning.
Error Name
Induction Voltage Error
Cause
Possible Solutions
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
Error Name
PM Inductance Error
Cause
Possible Solutions
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
334
Error Name
Stator Resistance Error
Possible Solutions
Double check the data that was entered to the T2- parameters, and perform Auto-Tuning again.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Error Name
Z Pulse Correction Error
Cause
Possible Solutions
Check the wiring for the motor and the PG encoder. Repeat Auto-Tuning.
Troubleshooting
PG encoder is damaged.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
335
6.8
Task
CoPy
Cause
Possible Solutions
Not an error.
Task
CPEr
Cause
Possible Solutions
Control mode of the parameters to be loaded onto the drive Check the control mode for the parameters that are to be loaded onto the drive and the control mode set to the drive
and the control mode already set to the drive dont match. those parameters will be written to. Set the same control mode using parameter A1-02 and try again.
Digital Operator Display
Task
CPyE
Cause
Possible Solutions
Task
CSEr
Cause
Possible Solutions
Hardware fault
Task
dFPS
Cause
Possible Solutions
The drive from which the parameter were copied and the
drive you are attempting to write to are not the same model.
The drive the parameters were copied from is a different
model drive.
The drive you attempting to write to is a different model.
Check the model number of the drive that the parameters were copied from and the model of the drive you are
attempting to write those parameters to.
Make sure the drive from which the parameter are copied and the drive to be written to have the same model numbers
and software versions.
Task
End
Task Complete
Cause
Possible Solutions
Not an error.
Task
Communication Error
Cause
Possible Solutions
Use the cable originally packaged with the USB Copy Unit.
Task
Model, Voltage Class, Capacity Mismatch
Possible Solutions
The drive the parameters were copied from and the drive
you are attempting to write to have different electrical
specifications, a different capacity, is set to a different
control mode, or is a different model number.
Make sure model numbers and specifications are the same for both drives.
Making sure all connections are correct, and copy the parameter settings onto the USB Copy Unit or the operator.
336
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Task
Error Reading Data
Cause
Possible Solutions
Failed while attempting to read parameter settings from the Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read parameters from the
drive.
drive.
Digital Operator Display
rEAd
Task
Reading Parameter Settings (flashing)
Cause
Possible Solutions
Not an error.
Task
Voltage Class, Capacity Mismatch
Cause
Possible Solutions
The drive the parameters were copied from and the drive
you performing the Verify mode on have different electrical Make sure electrical specifications and capacities are the same for both drives.
specifications or are a different capacity.
Digital Operator Display
vFyE
Task
Parameter settings in the drive and those saved to the copy function are not the same
Cause
Possible Solutions
Task
Comparing Parameter Settings (flashing)
Cause
Possible Solutions
Troubleshooting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
337
6.9
When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault,
then restart the drive.
Display/Result
DIGITAL OPERATOR JVOP-182
1.
2.
Press
3.
Press
4.
Press
5.
Press
6.
7.
338
REV
ALM
DRV FOUT
DRV
and
Press
Press
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Procedure
Press
YEC_
common
REV
DRV
ESC
LO
RE
RESET
ENTER
RUN
Close then open the fault signal digital input via terminal S4.
S4 is set for Fault Reset as default (H1-04 = 14).
ALM
FOUT
STOP
Drive
Fault Reset Switch
ON
OFF
If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after the digital
operator display is out.
Troubleshooting
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. The Run command must first be removed
before a fault situation can be cleared.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
339
Common Problems
Common Problems
Page
340
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering
External Run Command
341
341
342
342
342
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
342
342
Drive Frequency Reference Differs from the Controller Frequency Reference Command
343
343
343
343
344
344
Unexpected Noise from Connected Machinery
344
Oscillation or Hunting
344
344
344
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
345
345
345
345
345
Possible Solutions
Stop the drive and switch over to the Programming Mode.
Most parameters cannot be edited during run.
The operator is not in the Parameter Setup Mode (the screen will
display PAr).
If the password entered to A1-04 does not match the password saved to A1-05, then drive settings cannot be
changed.
Reset the password.
If you cannot remember the password:
Scroll to A1-04. Press the
340
Check the drive input power voltage by looking at the DC bus voltage (U1-07).
Check all main circuit wiring.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering
External Run Command
Motor Does Not Rotate
Cause
Possible Solutions
The
Push the
button.
When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will not be accepted unless the
drive is in the Drive Mode.
Use the digital operator to enter the Drive Mode. Refer to The Drive and Programming Modes on page 97.
If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If terminal A2 is used, check DIP
switch S1 parameter H3-08. If terminal A3 is used, check parameter H3-08. Refer to Terminal A2 Input Signal Selection on page 85.
Check jumper S3. Refer to Sinking/Sourcing Mode Switch for Digital Inputs on page 81.
When the
Switch off the Run command and then re-enter a new Run command.
The
Enter a value that is above the minimum output frequency determined by E1-09.
If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not set to 0.
If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must be set to 0. Terminal S1
will become the Start, terminal S2 will become the Stop input.
Possible Solutions
Typically, forward is designated as being counterclockwise when looking from the motor shaft (see figure below).
1
The forward direction for the motor is setup incorrectly.
2
1.
2.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Troubleshooting
The
341
Possible Solutions
Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the
manufacturer of the motor.
Possible Solutions
Make sure that one of the input terminals S3 to S8 used for the 3-wire sequence has been set for reverse.
Possible Solutions
If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value for an extended
period of time.
Keep in mind that the motor also has a short-term overload rating in addition to the possible solutions provided below:
Reduce the load.
Increase the acceleration and deceleration times.
Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current (E2-01).
Increase motor capacity.
Perform Auto-Tuning.
The drive is operating in a vector control mode but Auto-Tuning has
Calculate the motor value and reset the motor parameters.
not yet been performed.
Change the motor control method to V/f Control (A1-02 = 0).
When the motor cable is long, high voltage surges occur between the motor coils and drive switching.
Normally, surges can reach up to three times the drive input power supply voltage (600 V for 200 V class, and 1200 V
for 400 V class).
Use a motor with a voltage tolerance higher than the max voltage surge.
Use a motor designed to work specifically with a drive when using a 400 V class unit.
Install an AC reactor on the output side of the drive. The carrier frequency should be set to 2 kHz when installing
an AC reactor.
Possible Solutions
Check if the desired tuning mode is available for the selected control mode. Refer to Auto-Tuning on page 114.
Change the motor control method by setting A1-02.
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Cause
Motor rated current and the motor no-load current setting in the
drive are incorrect.
Possible Solutions
The user is trying to set the motor rated current in E2-01 to a value lower than the no-load current set in E2-03.
Make sure that value set in E2-01 is higher than E2-03.
If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change the setting in E2-01
as needed.
Possible Solutions
Torque limit has been reached or current suppression keeps the drive Take the following steps to resolve the problem:
from accelerating.
Reduce the load.
Increase motor capacity.
Note: Although the drive has a Stall Prevention function and a Torque Compensation Limit function, accelerating too
Load is too heavy.
quickly or trying to drive an excessively large load can exceed the capabilities of the motor.
Torque limit is not set properly.
342
Reduce the load so that the output current remains within the motor rated current.
In extruder and mixer applications, the load will sometimes increase as the temperature drops.
Increase the acceleration time.
Check if the mechanical brake is fully releasing as it should.
Check if the acceleration time parameters have been set too long (C1-01, C1-03, C1-05, C1-07).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Possible Solutions
Set the correct V/f pattern so that it matches the characteristics of the motor being used.
Motor characteristics and drive parameter settings are incompatible
Check the V/f pattern set to E1-03.
with one another.
Execute Rotational Auto-Tuning.
Perform Auto-Tuning.
Although the drive is operating in Open Loop Vector motor control
Calculate motor data and reset motor parameters.
method, Auto-Tuning has not been performed.
Switch to V/f Control (A1-02 = 0).
Incorrect frequency reference setting.
Check the multi-function analog input settings. Multi-function analog input terminal A1, A2, or A3 is set for
frequency gain (H3-02, H3-10, or H3-06 is set to 1), but there is no voltage or current input provided.
Make sure H3-02, H3-10, and H3-06 are set to the proper values.
See if the analog input value is set to the right value (U1-13 to U1-15).
The Stall Prevention level during run has been set too low.
The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance.
Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds.
Consider switching to Open Loop Vector Control.
Possible Solutions
The analog input gain and bias for the frequency reference input
are set to incorrect values.
Check the gain and bias settings for the analog inputs that are used to set the frequency reference. Check parameters
H3-03 and H3-04 for input A1, check parameters H3-11 and H3-12 for input A2, and check parameters H3-07 and
H3-08 for input A3.
Set these parameters to the appropriate values.
If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias (H3-02, H3-10, or H3-06
is set to 0), then the sum of all signals builds the frequency reference.
Make sure that H3-02, H3-10, and H3-06 are set appropriately.
Check the input level set for terminals A1 to A3 (U1-13 to U1-15).
Possible Solutions
Check drive input power voltage to ensure that it provides stable power.
Possible Solutions
Assuming parameter settings are normal and that no overvoltage occurs when there is insufficient torque, it is likely
that the demand on the motor has exceeded the motor capacity.
Use a larger motor.
Check the settings for the torque limit (L7-01 through L7-04).
If the torque limit is enabled, deceleration might take longer than expected because the drive cannot output more
torque than the limit setting. Ensure the torque limit is set to a high enough value.
Increase the torque limit setting.
If multi-function analog input terminal A1, A2, or A3 is set to torque limit (H3-02, H3-10, or H3-06 equals 10, 11, 12,
or 15), ensure that the analog input levels are set to the correct levels.
Ensure H3-02, H3-10, and H3-06 are set to the right levels.
Ensure the analog input is set to the correct value (U1-13 to U1-15).
Possible Solutions
The timing for the brake to close and release is not set properly.
Refer to Notes on Controlling the Brake when Using the Hoist Application Preset on page 111.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
343
Troubleshooting
Possible Solutions
Possible Solutions
Possible Solutions
Adjust the parameters used for the Jump frequency function (d3-01 through d3-04) to skip the problem-causing
bandwidth.
Place the motor on a rubber pad to reduce vibration.
Note: The drive may have trouble assessing the status of the load due to white noise generated from using Swing PWM (C6-02 = 7 to A).
Oscillation or Hunting
Cause
Possible Solutions
Perform Auto-Tuning.
Refer to Motor Performance Fine-Tuning on page 300.
Insufficient tuning.
Gain is too low when using PID control.
Perform Auto-Tuning.
Reduce the length of the cable.
Possible Solutions
The level of detection and the target value do not correspond with
each other.
PID control keeps the difference between target and detection values at 0. Set the input level for the values relative to
one another.
Use analog input gains H3-03 and H3-11 to adjust PID target and feedback signal scaling.
Possible Solutions
Perform Auto-Tuning. Refer to Motor Performance Fine-Tuning on page 300.
344
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)
Cause
Possible Solutions
Possible Solutions
Adjust the parameters used for the Jump frequency function (d3-01, d3-02, d3-03).
Frequency reference is set within the range of the Jump frequency.
Enabling the Jump frequency prevents the drive from outputting the frequencies specified in the Jump range.
Upper limit for the frequency reference has been exceeded.
Set the maximum output frequency and the upper limit for the frequency reference to more appropriate values (E104, d2-01).
The following calculation yields the upper value for the output frequency = E1-04 x d2-01 / 100
Possible Solutions
If the output current rises too high at low speeds, the carrier frequency is automatically reduced and causes a whining
or buzzing sound.
If the sound is coming from the motor, disable carrier frequency derating (L8-38 = 0).
Disabling the automatic carrier frequency derating increases the chances of an overload fault (oL2). Switch to a larger
capacity motor if oL2 faults occur too frequently.
Possible Solutions
Check the speed control range and adjust the speed accordingly.
Enter the correct motor code for the PM motor being used into E5-01.
For special-purpose motors, enter the correct data to all E5 parameters according to the test report provided for the
motor.
Possible Solutions
Troubleshooting
Check the sequence and wiring that has been set up to enter the Run command.
The Run command was not issued again when power was restored.
A relay should be set up to make sure the Run command remains enabled throughout any power loss.
The relay that is supposed to maintain the Run command has been
Check wiring and circuitry for the relay intended to keep the Run command enabled.
switched off.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
345
346
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7
Periodic Inspection & Maintenance
This chapter describes the periodic inspection and maintenance of the drive to ensure that it
receives the proper care to maintain overall performance.
7.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 PERIODIC MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 COOLING FAN AND CIRCULATION FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 DRIVE REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
348
351
353
355
373
347
7.1
Section Safety
DANGER
WARNING
348
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Follow cooling fan replacement instructions. The cooling fan cannot operate properly when it is installed
incorrectly and could seriously damage the drive.
Follow the instructions in this manual to replace the cooling fan, making sure that the label is on top before inserting
the cooling fan into the drive. To ensure maximum useful product life, replace both cooling fans when performing
maintenance.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with
installation, adjustment and maintenance of AC drives.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
Comply with proper wiring practices.
The motor may run in reverse if the phase order is backward.
Connect motor input terminals U, V and W to drive output terminals U/T1,V/T2, and W/T3. The phase order for the
drive and motor should match.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
349
NOTICE
Frequently switching the drive power supply to stop and start the motor can damage the drive.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive
power supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop
and start the motor.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
350
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7.2 Inspection
7.2
Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of
use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and
periodic inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and
relays. The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note: The drive will require more frequent inspection if it is placed in harsh environments, such as:
Perform the first equipment inspection one to two years after installation.
Cooling
Inspection Points
Corrective Action
Inspect for abnormal heat generated from the drive or motor and
visible discoloration.
Checked
Environment
Verify the drive environment complies with the specifications listed Eliminate the source of contaminants or correct poor
in Installation Environment on page 42.
environment.
Load
The drive output current should not be higher than the motor or drive Check for excessive load.
rating for an extended period of time.
Check the motor parameter settings of the drive.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
351
7.2 Inspection
Inspection Points
Corrective Action
Checked
General
Terminals
Inspect contactors and relays for excessive noise during operation. Check coil voltage for over or under voltage conditions.
Inspect coils for signs of overheating such as melted or cracked
Replace damaged removable relays contactors or circuit
insulation.
board.
Braking Resistors
Electrolytic Capacitor
The drive has few serviceable parts and may require complete
drive replacement.
Circuit Boards
Replace as required.
Refer to Cooling Fan and Circulation Fan on page 355 for
information on cleaning or replacing the fan.
Heatsink
Air Duct
Inspect air intake and exhaust openings. They must be free from
obstruction and properly installed.
Digital Operator
352
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7.3
Periodic Maintenance
The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to
check predicted maintenance periods for the components listed below.
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.
Replacement Parts
Table 7.3 contains the estimated performance life of components that require replacement during the life of the drive.
Only use Yaskawa replacement parts for the appropriate drive model and revision.
Table 7.3 Estimated Performance Life
Component
10 years
Electrolytic Capacitors
10 years <1>
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage
conditions for estimated performance life:
Ambient temperature: Yearly average of 40C (IP00 enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
U4-03
U4-04
Contents
Displays the accumulated operation time of the fan, from 0 to 99999 hours. This value is automatically reset to 0 once it
reaches 99999.
Displays the accumulated fan operation time as a percentage of the specified maintenance period.
U4-05
DC Bus Capacitors
Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
U4-06
Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit.
U4-07
IGBT
Function
Corrective Action
<1>
LT-1
The cooling fans have reached 90% of their designated life time.
<1>
LT-2
<1>
LT-3
The DC bus charge circuit has reached 90% of its designated life
time.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
353
Parameter
Function
Corrective Action
<1>
LT-4
<2>
TrPC
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2- = 2F). The alarm
will also trigger a digital output that is programmed for alarm indication (H2- = 10).
<2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2- =
2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2- = 10).
354
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7.4
NOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and could
seriously damage the drive. To ensure maximum useful product life, replace all cooling fans when performing maintenance.
Contact your Yaskawa representative or the nearest Yaskawa sales office to order replacement cooling fans as required.
For drives with multiple cooling fans, replace all the fans when performing maintenance to ensure maximum product
performance life.
Number of Fan
Three-Phase 200 V Class
Model
CIMR-A
Page
Model
CIMR-A
Cooling Fan
Circulation Fan
Cooling Fan
Circulation Fan
Control Board
Cooling Fan
2A0004
Page
4A0002
2A0006
4A0004
2A0008
4A0005
2A0010
4A0007
2A0012
4A0009
2A0018
4A0011
2A0021
4A0018
2A0030
4A0023
2A0040
4A0031
2A0056
4A0038
2A0069
4A0044
2A0081
4A0058
2A0110
4A0072
2A0138
4A0088
2A0169
4A0103
357
359
2A0211
4A0139
2A0250
4A0165
2A0312
4A0208
2A0360
4A0250
2A0415
4A0296
4A0362
4A0414
4A0515
4A0675
359
361
363
367
369
363
357
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
355
2A0018 to 2A0081
4A0007 to 2A0044
A
2A0110 to 2A0138
4A0058 to 4A0103
2A0169 to 2A0415
4A0139 to 4A0362
B
C
D
E
G
YEC_TM
only
4A0414
4A0515, 4A0675
B
D
H
E
G
I
A
B
C
D
E
Fan Cover
Fan Guard
Cable Cover
Cooling Fan
Fan Unit Case
F
G
H
I
356
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_
TMon
ly
Figure 7.2 Removing the Fan Cover: 2A0018 to 2A0081, 4A0007 to 4A0044
2. Remove the cooling fan cartridge. Disconnect the pluggable connector and remove the fan.
Figure 7.3
YEC_
TMonly
Figure 7.3 Removing the Cooling Fan: 2A0018 to 2A0081, 4A0007 to 4A0044
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
357
B
C
YEC_TM
only
Figure 7.4 Installing the Cooling Fan: 2A0018 to 2A0081, 4A0007 to 4A0044
2. Make sure the power lines for the fan are properly connected, then place the cable back into the recess of the
drive.
Figure 7.5
YEC_TMonly
A Back
B Front
Figure 7.5 Cooling Fan Power Supply Connectors: 2A0018 to 2A0081, 4A0007 to 4A0044
3. While pressing in on the hooks on the left and right sides of the fan cover, guide the fan cover until it clicks back
into place.
Figure 7.6
YEC_
TMon
ly
Figure 7.6 Reattach the Fan Cover: 2A0018 to 2A0081, 4A0007 to 4A0044
4. Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting
o4-03 to 0.
358
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_
TMonly
Figure 7.7 Removing the Cooling Fan Cover: 2A0110 and 2A0138, 4A0058 and 4A0072
2. Lift the fan cover out leading with the back end. Unplug the replay connector and free the fan cover from the
drive.
Figure 7.8
YEC_TMonly
Lift the fan cover out of the drive
leading with the back end.
Figure 7.8 Removing the Cooling Fan: 2A0110 and 2A0138, 4A0058 and 4A0072
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
359
YEC_TMonly
Figure 7.9
A Back
B Front
Figure 7.9 Cooling Fan Power Supply Connectors: 2A0110 and 2A0138, 4A0058 and 4A0072
YEC_TM
only
Figure 7.10 Installing the Cooling Fan: 2A0110 and 2A0138, 4A0058 and 4A0072
4. Angle the fan cover so the back end tilts up. Slide the cover into the small opening towards the front of the drive,
and then guide the entire fan cover into place.
Figure 7.11
Insertion area
Front of drive
Back of drive
Cross-Section
Fan cover
Hook
YEC_
TMonly
Back of drive
Hook
Front of drive
Figure 7.11 Reattach the Fan Cover: 2A0110 and 2A0138, 4A0058 and 4A0072
360
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_
TMonly
Figure 7.12 Reattach the Fan Cover: 2A0110 and 2A0138, 4A0058 and 4A0072
6. Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting
o4-03 to 0.
YEC_
TMonly
drive.
Figure 7.14
Figure 7.13 Removing the Cooling Fan Cover: 4A0088 and A0103
2. Lift the cooling fan directly up on the fan as shown below. Unplug the relay connector and free the fan from the
7
YEC_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
361
YEC_TM
only
2. Make sure the power lines for the fan are properly connected, then place the power supply connectors and cable
back into the recess of the drive.
Figure 7.16
YEC_TMonly
A Back
B Front
Figure 7.16 Cooling Fan Power Supply Connectors: 4A0088 and 4A0103
3. Angle the fan cover as shown and insert the connector tabs into the corresponding holes on the drive.
Figure 7.17
Fan cover
Four tabs
Back or Drive
YEC_
TMonly
Hook
Hook
Front of Drive
362
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_
TMonly
Figure 7.18 Reattach the Fan Cover: 4A0088 and 4A0103
5. Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting
o4-03 to 0.
2A0169, 2A0211,
4A0139, 4A0165
A
2A0360, 2A0415,
4A0250, 4A0296, 4A0362
B
B
YEC_
TMonly
D
C
E
A Fan Unit
B Fan Relay Cable
C Fan Connector (CN6)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
363
YEC_
TMonly
Figure 7.20 Removing the Fan Unit: 2A0169 to 2A0415, 4A0139 to 4A0362
4A0250, 4A0296
2A0360, 2A0415,
4A0362
C
C
YEC_
TMonly
A Fan Guard
B Cable Cover
C Cooling Fan
D Circulation Fan
364
YEC_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
4A0165
Fan B2
Fan B1
Connector for fan B1
YEC_
TMonly
Figure 7.22 Cooling Fan Wiring: 2A0169, 2A0211, 4A0139 and 4A0165
3. Make sure that the protective tube does not stick out beyond the fan guard.
Cooling Fan Wiring: 2A0250, 2A0312 and 4A0208
1. Position the protective tube so that the fan connector sits in the center of the protective tube.
Protective tube
YEC_
TMonly
2. Place the connector for fan B2 before the B1 connector and guide the lead wire for fan B2 so that it is held in
place by the cable hook.
Figure 7.23
Fan B1
Fan B2
Cable hook
YEC_
TMonly
Connector for fan B2
3. Make sure that the protective tube does not stick out beyond the fan guard.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
365
YEC_
TMonly
2. The fan connector for fan B2 should be placed in front of the fan B1 connector between fans B1 and B2.
3. The connector for fan B3 should be pressed in between fan B2 and B3.
Figure 7.24
YEC_TMonly
Cable cover
Fan B3
Fan B2
Fan B1
YEC_
TMonly
Figure 7.25 Installing the Cooling Fan Unit: 2A0165 to 2A0415, 4A0139 to 4A0362
366
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_TMonly
B
C
G
A
B
C
D
Fan Unit
Circulation Fan Unit
Circulation Fan
Circulation Fan Relay Cable
E
F
G
H
3. Remove the circulation fan relay cable from the hook. Remove the fan connector (CN7).
4. Remove the screws holding the fan units in place and slide the fan units out of the drive.
Figure 7.27
YEC_TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
367
YEC_TMonly
A
D
C
E
A Fan Guard
B Cooling Fan
C Fan Unit Case
YEC_TMon
ly
Protective tube
2. Place the fan connector covered by the tube as shown in the drawings below.
Figure 7.29
Cooling Fan B1
YEC_TMonly
Connector
for fan B1
Connector
for fan B2
Connector
for fan B3
368
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_TMonly
YEC_TMonly
C
7
E
A
B
C
D
Fan Unit
Fan Relay Connector
Circuit Board Cooling Fan
Circuit Board Cooling Fan Case
E Hook
F Circuit Board Cooling Fan Connector
G Circuit Board Cooling Fan Cable
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
369
Screw
Slide Panel
Screw
YEC_TMonly
4. Remove the slide panel and fan unit along with the cooling fan unit for the circuit boards from the drive.
Note: The fan unit can be removed simply by loosening these screws.
Figure 7.33
YEC_TMonl
y
YEC_TMonly
A
A Cooling Fan
370
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_TMonly
A
A Circulation Fan
Figure 7.35 Fan Unit Disassembly: 4A0515 and 4A0675
YEC_TMonly
Cooling Fan B2
Cooling Fan B1
Cooling Fan B3
Relay Connector
YEC_TMonly
Relay Connector
Relay Connector
Cooling Fan B4
Cooling Fan B5
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
371
Relay Connector
Cooling Fan B3
Cooling Fan B2
Cooling Fan B1
Relay Connector
Cooling Fan B5
YEC_TMonl
y
Cooling Fan B4
3. Position the protective tube so that the fan connector sits in the center of the protective tube. (Only for Circuit
Board Cooling Fans)
Protective tube
YEC_TMon
ly
4. Guide lead wires through the hooks provided so that the wires are held in place.
Figure 7.39
YEC_TMonl
y
YEC_TMonly
Figure 7.40 Installing the Cooling Fan Units: 4A0515 and 4A0675
372
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
7.5
Drive Replacement
Serviceable Parts
The drive contains some serviceable parts. The following parts can be replaced over the life span of the drive:
Terminal board I/O PCBs
Cooling fan(s)
Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing
parts if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa
warranty policy.
Terminal Board
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains onboard memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the
replacement drive. To transfer the terminal board, disconnect the terminal board from the damaged drive then reconnect
it to the replacement drive. Once transferred, there is no need to manually reprogram the replacement drive.
Note: If the damaged drive and the new replacement drive are have different capacities, the data stored in the terminal board cannot be
transferred to the new drive and an oPE01 error will appear on the display. The terminal board can still be used, but parameter
setting from the old drive cannot be transferred. The replacement drive must be initialized and manually programmed.
Figure 7.41
YEC_TMon
ly
A
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
373
The following procedure explains how to replace a drive. This section provides instructions for drive replacement only.
To install option boards or other types of options, then refer to the specific manuals for those options.
NOTICE: When transferring a braking transistor, braking resistor, or other type of option from a damaged drive to a new replacement
drive, make sure they are working properly before reconnecting them to the new drive. Replace broken options to prevent immediate
break down of the replacement drive.
YEC_
comm
on
2. Loosen the screws holding the terminal board in place. Take out the screw securing the bottom cover and
remove the bottom cover from the drive.
Note: Drives set up for compliance with IP00 do not have a bottom cover.
Figure 7.43
YEC_com
mon
Figure 7.43 Drive Replacement: Removing the Terminal Board
3. Slide the terminal board as illustrated by the arrows, and remove it from the drive along with the bottom cover.
Figure 7.44
YEC_
comm
on
374
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YEC_c
ommon
4. Disconnect all option cards and options. Make sure they are intact before reusing them.
5. Replace the drive and wire the main circuit.
Installing the Drive
1. Once the main circuit has been wired, connect the terminal block to the drive as shown in Figure 7.46. Use the
installation screw to fasten the terminal block into place.
Figure 7.46
YEC_
comm
on
2. Reconnect all options to the new drive in the same way they were installed in the old drive. Connect option
boards to the same option ports in the new drive that were used in the old drive.
into the drive memory. Should an oPE04 error occur, load the parameter settings that have been saved on the
terminal board onto the new drive by setting parameter A1-03 to 5550. Reset timers used for the Maintenance
Monitor function by setting parameters o4-01 through o4-12 back to 0, and parameter o4-13 to 1.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
375
376
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
8
Peripheral Devices & Options
This chapter explains the installation of peripheral devices and options available for the drive.
8.1 SECTION SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 DRIVE OPTIONS AND PERIPHERAL DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 CONNECTING PERIPHERAL DEVICES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 OPTION CARD INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.5 INSTALLING PERIPHERAL DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
378
379
382
383
385
377
8.1
Section Safety
DANGER
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
378
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
8.2
The following table of peripheral devices lists the names of the various accessories and options available for Yaskawa
drives. Contact Yaskawa or your Yaskawa agent to order these peripheral devices.
Peripheral Device Selection: Refer to the Yaskawa catalog for selection and part numbers.
Peripheral Device Installation: Refer to the corresponding option manual for installation instructions.
Table 8.1 Available Peripheral Devices
Option
Model Number
Description
DC Reactor
UZDA Series
AC Reactor
UZBA Series
Braking Resistor
ERF-150WJ Series
DF120-B579 Series
LKEB Series
Braking Unit
CDBR Series
NF Series
SC Series
Surge Protector
F6045GB, F11080GB
Fuse
LF-310 Series
Isolator
DGP
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
379
Power Options
Model Number
Description
DCF-6A
RH000850
SDF-12NH
RH000739
CM-3S
Meter Plate
NPJT41561-1
JVOP-180
WV001/WV003
JVOP-181
EZZ020786
Installation kit for mounting the drive with the heatsink outside
of the panel (Side-by-Side mounting possible)
NEMA 1 Kit
EZZ020787
EZZ020642A
EZZ020642B
LOCK
JVOP-181
COM
ERR
YASKAWA
LCD Operator
Re
ad
rify
Ve
Interface Options
Co
py
Attachment
Others
24 V Power Supply
PS-A10L, PS-A10H
DriveWizard Plus
DriveWorksEZ
Communication Options
PG-B3
Line Driver PG
PG-X3
Analog Input
AI-A3
Analog Monitor
AO-A3
Complementary PG
380
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Model Number
Description
DI-A3
Digital Output
DO-A3
PROFIBUS-DP
SI-P3
CC-Link
SI-C3
DeviceNet
SI-N3
CANopen
SI-S3
MECHATROLINK-II
SI-T3
Digital Input
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
381
8.3
Figure 8.1 illustrates how to configure the drive and motor to operate with various peripheral devices.
For more detailed instructions on how to install each device shown below, refer to the specific manual for that device.
Figure 8.1
LOCK
JVOP-181
ERR
COM
ad
Re
rify
Ve
YASKAWA
USB Cable
(Type-AB)
py
Co
PC
USB Cable
(Type-AB, sold separately)
Surge
Absorber
Drive
B1 B2
+3
Magnetic
Contactor
(MC)
+2
+1
DC Reactor
Thermal Relay
AC Reactor
Zero-phase
Reactor
Momentary
Power Loss
Recovery Unit
Braking Resistor
or
Braking Resistor Unit
Braking Unit
Fuse
Ground
Input Side
Noise Filter
24 V control
power supply
unit
Magnetic Zero-phase
Contactor Reactor
(switches to
line power)
Motor
YEC_
TMon
ly
Ground
382
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
8.4
This section provides instructions on installing the option cards listed in Table 8.1.
Port/Connector
CN5-A
PG-B3, PG-X3
CN5-B, C
2 <2>
DO-A3, AO-A3
CN5-A, B, C
<1> If installed to CN5-B or CN5-C, AI-A3 and DI-A3 cannot be used to set the frequency reference, but the input status can still be viewed
using U1-21, U1-22, U1-23 (for AI-A3), and U1-17 (for DI-A3).
<2> If only one PG option card is connected to the drive, use the CN5-C connector. If two PG option cards are connected, use both CN5-B
and CN5-C.
Installation Procedure
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in
death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar
with installation, adjustment and maintenance of AC drives and Option Cards.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option card, drive, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
NOTICE: Damage to Equipment. Tighten all terminal screws to the specified tightening torque. Failure to comply may cause the
application to operate incorrectly or damage the drive.
Use the procedure described below when installing option cards to the drive.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the
operator and front cover. Refer to Digital Operator and Front Cover on page 63
2. Insert the CN5 connector on the option card into the matching CN5 connector on the drive, then fasten it into
place using one of the screws included with the option card.
Figure 8.2
A
E
F
B
C
G
J
L
I
A Connector CN5-C
B Connector CN5-B
C Connector CN5-A
D Drive grounding terminal (FE)
E Insert connector CN5 here
F Option card
YEC_TMonly
G Mounting screw
H Lead line
I Use wire cutters to create an
opening for cable lines
J Front cover
K Digital operator
L Terminal cover
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
383
common_
TMonly
4. Wire the option card to the terminal block on the option card.
For wiring instructions, refer to the manual delivered with the option card.
When installing option cards to drive models CIMR-A2A0004 through 0040 and to models CIMR-A4A0002
through 0023, the cables connected to the option might need to be routed through the front cover to the outside.
In this case, cut out the perforated openings on the left side of the front cover. Make sure no sharp edges are left
that may damage the cable.
Models CIMR-A2A0056 through 2A0415 and 4A0031 through 0675 have enough space to keep all wiring
inside the unit.
Figure 8.4
YEC_TMonly
A Cable through hole
(CIMR-A2A0004 to 0040, 4A0002 to 0023)
5. Place the front cover and digital operator back onto the drive.
Note: 1. Leave enough space when wiring so that the front cover can be easily reattached. Make sure no wires get caught between the front
cover and the drive.
2. Any exposed wiring will void the wall-mount enclosure rating.
384
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
8.5
This section describes the proper steps and precautions to take when installing or connecting various peripheral devices
to the drive.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral
devices could result in drive performance degradation due to improper power supply.
B1
Drive
Braking Resistor
B2
common_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
385
B1
Thermal Relay
Trip Contact
Drive
B2
common_
TMonly
Circuit Breaker
MC
R
S
T
R/L1
S/L2
T/L3
400/200V
ON
MC
Drive
SA
MC
THRX
1 2
Braking Resistor Unit
(Close: Overheat)
SA
YEC_TMonly
386
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Braking Unit
(CDBR type)
+3
+0
Thermal Overload
Protector Trip Contact
Drive
YEC_
TMonly
Thermal Relay
Trip Contact
Figure 8.8 Connecting a Braking Unit (CDBR type) and Braking Resistor Unit (LKEB type)
(CIMR-A2A0169 to 0415, 4A0088 to 0675)
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
2 Braking
Resistor
Unit
B
1
P
+ +0
Level Detector
Drive
2 Braking
Resistor
Unit
B
1
P
MASTER
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
+0
2 Braking
Resistor
Unit
B
1
P
+0
MASTER
MASTER
SLAVE
SLAVE
2
Braking Unit 1
3
SLAVE
+15
5
Braking Unit 3
Braking Unit 2
3
YEC_
TMonly
Installing a Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit
Breaker (ELCB)
Install a MCCB or ELCB for line protection between the power supply and the main circuit power supply input terminals
R/L1, S/L2, and T/L3. This protects the main circuit and devices wired to the main circuit while also providing overload
protection.
Consider the following when selecting and installing an MCCB or ELCB:
The capacity of the MCCB or ELCB should be 1.5 to 2 times the rated output current of the drive. Use an MCCB or
ELCB to keep the drive from faulting out instead of using overheat protection (150% for one minute at the rated output
current).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
387
+3
Braking Resistor
Overheat Contact
(Thermal Relay Trip Contact)
B
A
MCCB
MC
MC
SA
R/L1
S/L2
T/L3
MB
YEC_
TMonly
MC
MC
A Power supply
B Drive
In order to safely protect the drive system, select a breaker that senses all types of current (AC and DC) and high
frequency currents.
388
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Connecting an AC or DC Reactor
AC and DC reactors suppress surges in current and improve the power factor on the input side of the drive.
Use a DC reactor or AC reactor or both:
To suppress harmonic current or improve the power factor of the power supply.
When using a phase advancing capacitor switch.
With a large capacity power supply transformer (over 600 kVA).
Note: Use an AC or DC reactor when also connecting a thyristor converter (such as a DC drive) to the same power supply system,
regardless of the conditions of the power supply.
Connecting an AC Reactor
Figure 8.11
C
A
R/L1
S/L2
T/L3
A Power supply
B MCCB
Common_
TMonly
C AC reactor
D Drive
Connecting a DC Reactor
A DC reactor can be installed to drive models CIMR-A2A0004 to 0081 and 4A0002 to 0044. When installing a DC
reactor, ensure the jumper between terminals +1 and +2 (terminals are jumpered for shipment) is removed. The jumper
must be installed if no DC reactor is used. Refer to Figure 8.12 for an example of DC reactor wiring.
Figure 8.12
C
A
R/L1
S/L2
T/L3
+1
+2
Common_
TMonly
A Power supply
B MCCB
C Drive
D DC reactor
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
389
MCCB
R/L1
S/L2
T/L3
YEC_
TMon
ly
MCCB
A Power supply
B Input-side noise filter
(model LNFD-)
C Drive
D Other control device
B
A
MCCB
A Power supply
B Drive
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
D
M
YEC_
TMon
ly
Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise throughout the radio
bandwidth that can affect surrounding devices.
Induced Noise: Noise generated by electromagnetic induction can affect the signal line and may cause the controller to
malfunction.
390
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away from the signal line to
prevent induced noise.
Figure 8.15
B
A
MCCB
C
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
YEC_
TMon
ly
E
G
F
A
B
C
D
Power supply
Drive
Shielded motor cable
Motor
E Separate at least 30 cm
F Controller
G Signal line
The drive, input lines, and output lines generate radio frequency noise. Use noise filters on input and output sides and
install the drive in a metal enclosure panel to reduce radio frequency noise.
Note: The cable running between the drive and motor should be as short as possible.
Figure 8.16
A
C
B
A
B
C
D
MCCB
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
Metal enclosure
Power supply
Noise filter
Drive
G
M
YEC_
TMon
ly
E Noise filter
F Shielded motor cable
G Motor
Fuse/Fuse Holder
Peripheral Devices &
Options
Yaskawa recommends installing a fuse to the input side of the drive to prevent damage to the drive if a short circuit
occurs.
Select the appropriate fuse from the table below.
Table 8.3 Input Fuses
Model
CIMR-A
Fuse Type
Fuse Holder
Fuse Type
Manufacturer: Bussmann
Model
Quantity
Model
CR2LS-30
30
CM-1A
FWH-70B
70
2A0006
CR2LS-30
30
CM-1A
FWH-70B
70
2A0008
CR2LS-30
30
CM-1A
FWH-70B
70
2A0010
CR2LS-50
50
CM-1A
FWH-70B
70
2A0012
CR2LS-50
50
CM-1A
FWH-70B
70
2A0018
CR2LS-75
75
CM-1A
FWH-90B
90
2A0021
CR2LS-100
100
CM-1A
FWH-90B
90
2A0030
CR2L-125
125
CM-2A
FWH-100B
100
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
391
Fuse Type
Fuse Holder
Fuse Type
Manufacturer: Bussmann
Model
Model
Quantity
Model
2A0040
CR2L-150
150
CM-2A
FWH-200B
200
2A0056
CR2L-175
175
CM-2A
FWH-200B
200
2A0069
CR2L-225
225
FWH-200B
200
2A0081
CR2L-260
260
FWH-300A
300
2A0110
CR2L-300
300
FWH-300A
300
2A0138
CR2L-350
350
FWH-350A
350
2A0169
CR2L-400
400
FWH-400A
400
2A0211
CR2L-450
450
FWH-400A
400
2A0250
CR2L-600
600
FWH-600A
600
2A0312
CR2L-600
600
FWH-700A
700
2A0360
CR2L-600
600
FWH-800A
800
2A0415
CS5F-800
800
FWH-1000A
1000
4A0002
CR6L-20
20
CMS-4
FWH-40B
40
4A0004
CR6L-30
30
CMS-4
FWH-50B
50
4A0005
CR6L-50
50
CMS-4
FWH-70B
70
4A0007
CR6L-50
50
CMS-4
FWH-70B
70
4A0009
CR6L-50
50
CMS-4
FWH-90B
90
4A0011
CR6L-50
50
CMS-4
FWH-90B
90
4A0018
CR6L-75
75
CMS-5
FWH-80B
80
4A0023
CR6L-75
75
CMS-5
FWH-100B
100
4A0031
CR6L-100
100
CMS-5
FWH-125B
125
4A0038
CR6L-150
150
CMS-5
FWH-200B
200
4A0044
CR6L-150
150
CMS-5
FWH-250A
250
4A0058
CR6L-200
200
FWH-250A
250
4A0072
CR6L-250
250
FWH-250A
250
4A0088
CR6L-250
250
FWH-250A
250
4A0103
CR6L-300
300
FWH-250A
250
4A0139
CR6L-350
350
FWH-350A
350
4A0165
CR6L-400
400
FWH-400A
400
4A0208
CS5F-600
600
FWH-500A
500
4A0250
CS5F-600
600
FWH-600A
600
4A0296
CS5F-600
600
FWH-700A
700
4A0362
CS5F-800
800
FWH-800A
800
4A0414
CS5F-800
800
FWH-800A
800
4A0515
CS5F-800
800
FWH-1000A
1000
4A0675
CS5F-1000
1000
FWH-1200A
1200
392
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Generally, thermal relays are applied on general-purpose motors. When general-purpose motors are driven by AC drives,
the motor current is approximately 5% to 10% greater than if driven by a commercial power supply. In addition, the
cooling capacity of a motor with a shaft-driven fan decreases when operating at low speeds. Even if the load current is
within the motor rated value, motor overheating may occur. A thermal relay cannot effectively protect the motor due to
the reduction of cooling at low speeds. For this reason, apply the UL recognized electronic thermal overload protection
function built into the drive whenever possible.
UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated
using data from standard motors and force-ventilated motors. The motor is protected from overload using this function.
Using a Single Drive to Operate Multiple Motors
Turn off the electronic thermal overload function. Please refer to the appropriate product instruction manual to determine
which parameter disables this function.
Note: The UL recognized electronic thermal overload function cannot be applied when operating multiple motors with a single drive.
When a high carrier frequency and long motor cables are used, nuisance tripping of the thermal relay may occur due to
increased leakage current. To avoid this, reduce the carrier frequency or increase the tripping level of the thermal
overload relay.
Nuisance Tripping Due to a High AC Drive Carrier Frequency
Current waveforms generated by high carrier frequency PWM drives tend to increase the temperature in overload relays.
It may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.
WARNING! Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting.
Check local electrical codes before making adjustments to motor thermal overload settings.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
393
394
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Appendix: A
Specifications
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
396
397
398
399
401
402
395
Overload Tolerance
2 kHz
1: Normal Duty
<1> Refer to Three-Phase 200 V Class Drives on page 397 and Three-Phase 400 V Class Drives on page 398 for information on rating changes
based on drive model.
TERMS
HD and ND: HD refers to applications requiring constant torque output, while ND refers to applications with variable torque
needs. The drive allows the user to select HD or ND torque depending on the application. Fans, pumps, and blowers should use
ND (C6-01 = 1), and other applications generally use HD (C6-01 = 0).
Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a less obtrusive white
noise.
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier
frequency, and current limit. The default setting is for HD (C6-01 = 0).
396
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Specification
CIMR-A2A
0004 0006 0008 0010 0012 0018 0021 0030 0040 0056 0069 0081 0110 0138 0169 0211 0250 0312 0360 0415
Input
0.4
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
0.7
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
110
7.5
11
15.6 18.9
HD Rating
2.9
5.8
ND Rating
3.9
7.3
8.8
24
28
37
52
68
80
82
111
136
164
200
271
324
394
37
52
68
80
96
111
136
164
200
271
324
394
471
180
Rated Voltage
Rated Frequency
-15 to 10%
5%
HD Rating
1.3
2.2
3.1
4.1
5.8
7.8
9.5
14
18
27
36
44
37
51
62
75
91
124
148
ND Rating
2.2
3.1
4.1
5.8
7.8
9.5
14
18
27
36
44
52
51
62
75
91
124
148
180
215
HD Rating
1.2
1.9
2.6
4.2
5.3
6.7
9.5
23
29
32
44
55
69
82
108
132
158
ND Rating
1.3
2.3
3.7
4.6
6.7
21
26
31
42
53
64
80
95
119
137
158
3.2
6.9
11
14
17.5
25
33
47
60
75
85
115
145
180
215
283
346
415
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<6>
<6>
<6>
<6>
<6>
<4>
3.5
9.6
12
17.5
21
30
40
56
69
81
110
138
169
211
250
312
360
415
HD Rating
ND Rating
<4>
Output
Overload Tolerance
Carrier Frequency
12.6 17.9
11.4 15.2
400 Hz (user-set)
Specifications
<1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 220 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased up the 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased up the 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
397
Specification
CIMR-A4A
Maximum Applicable Motor
Capacity (kW) <1>
Input Current (A) <2>
Input
0002
0004
0005
0007
0009
0011
0018
0023
0031
0038
0044
0058
0072
0088
HD Rating
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
ND Rating
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
HD Rating
1.8
3.2
4.4
8.2
10.4
15
20
29
39
44
43
58
71
86
ND Rating
2.1
4.3
5.9
8.1
9.4
14
20
24
38
44
52
58
71
86
105
Rated Voltage
Rated Frequency
15 to 10%
5%
HD Rating
1.4
2.3
4.3
6.1
8.1
10.0
14.6
19.2
28.4
37.5
46.6
39.3
53.0
64.9
78.6
ND Rating
2.3
4.3
6.1
8.1
10.0
14.5
19.4
28.4
37.5
46.6
54.9
53.0
64.9
78.6
96.0
69
HD Rating
Rated Output Capacity
(kVA) <3>
ND Rating <4>
Rated Output Current
(A)
HD Rating
ND Rating <4>
1.4
2.6
3.7
4.2
5.5
11.3
13.7
18.3
24
30
34
48
57
1.6
3.1
4.1
5.3
6.7
8.5
13.3
17.5
24
29
34
44
55
67
78
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18
24
31
39
45
60
75
91
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
<5>
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23
31
38
44
58
72
88
103
Output
Overload Tolerance
Carrier Frequency
400 Hz (user-adjustable)
Item
Specification
CIMR-A4A
Maximum Applicable Motor
Capacity (kW) <1>
Input Current (A) <2>
Input
0139
0165
0208
0250
0296
0362
0414
0515
HD Rating
55
75
90
110
132
160
185
220
315
ND Rating
75
90
110
132
160
185
220
250
355
105
142
170
207
248
300
346
410
584
ND Rating
142
170
207
248
300
346
410
465
657
508
15 to 10%
5%
96.0
129.9
155
189
227
274
316
375
ND Rating
129.9
155.5
189
227
274
316
375
416
601
85
114
137
165
198
232
282
343
461
HD Rating
Rated Output Capacity
(kVA) <3>
ND Rating <4>
Rated Output Current
(A)
0675
HD Rating
Rated Voltage
Rated Frequency
0103
HD Rating
ND Rating <4>
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
106
126
159
191
226
276
316
392
514
112
150
180
216
260
304
370
450
605
<6>
<6>
<6>
<6>
<6>
<4>
<6>
<4>
<4>
139
165
208
250
296
362
414
515
675
150 Hz (user-adjustable)
<1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased up the 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased up the 5 kHz while keeping this current rating. Higher carrier frequency settings require derating
398
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Specification
Control Method
0.01 to 400 Hz
Frequency Accuracy
(Temperature Fluctuation)
Digital input: within 0.01% of the max output frequency (-10 to +40C)
Analog input: within 0.1% of the max output frequency (25C 10C)
0.001 Hz
Control
Characteristics
Accel/Decel Time
Braking Torque
Braking Transistor
V/f Characteristics
Motor Protection
Momentary Overcurrent Protection
Overload Protection
Protection
Functions
Torque Control, Droop Control, Speed/torque Control Switching, Feed Forward Control, Zero Servo Function, Momentary
Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection, Torque Limit, 17 Step Speed (max), Accel/decel
Switch, S-curve Accel/decel, 3-wire Sequence, Auto-tuning (rotational, stationary tuning), Dwell, Cooling Fan on/off Switch,
Slip Compensation, Torque Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection
Braking at Start and Stop, Overexcitation Braking, High Slip Braking, PID Control (with sleep function), Energy Saving Control,
MEMOBUS/Modbus Comm. (RS-422/485 max, 115.2 kbps), Fault Restart, Application Presets, DriveWorksEZ (customized
function), Removable Terminal Block with Parameter Backup Function, Online Tuning, KEB, Overexcitation Deceleration,
Inertia (ASR) Tuning, Overvoltage Suppression, High Frequency Injection, etc.
Electronic thermal overload relay
Drive stops when output current exceeds 200% of Heavy Duty Rating
Drive stops after 60 s at 150% of rated Heavy Duty output current <5>
Overvoltage Protection
Undervoltage Protection
200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class: Stops when DC bus voltage falls below approx. 380 V
Immediately stop after 15 ms or longer power loss. <6> Continuous operation during power loss than 2 s (standard) <7>
Thermistor
Braking Resistor Overheat Protection Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Storage Temperature
Altitude
Vibration / Shock
Safety Standard
Protection Design
Specifications
Stall Prevention
Ground Protection
Indoors
-10 to 40C (NEMA Type 1 enclosure), -10 to 50C (IP00 enclosure), up to 60C with output current derating
95 RH% or less (no condensation)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
399
400
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Normal Duty
Model Number
CIMR-A
Heatsink Loss
(W)
2A0004
3.2 <1>
14.8
44
2A0006
5.0 <1>
24
48
2A0008
6.9 <1>
35
49
2A0010
8.0 <1>
43
52
2A0012
11.0 <1>
64
58
122
12.0
77
64
141
2A0018
14.0 <1>
77
60
137
17.5
101
67
168
2A0021
17.5 <1>
101
67
168
21
138
83
222
2A0030
25 <1>
194
92
287
30
262
117
379
2A0040
33 <1>
214
105
319
40
293
145
437
2A0056
47 <1>
280
130
410
56
371
175
546
2A0069
60 <1>
395
163
558
69
491
205
696
2A0081
75 <1>
460
221
681
81
527
257
785
2A0110
85 <1>
510
211
721
110
719
286
1005
2A0138
115 <1>
662
250
912
138
842
312
1154
2A0169
145 <1>
816
306
1122
169
1014
380
1394
Interior Unit
Loss (W)
<3>
Heatsink Loss
(W)
Interior Unit
Loss (W)
59
3.5
18.4
47
66
72
6.0
31
51
82
84
8.0
43
52
95
95
9.6
57
58
115
2A0211
180 <2>
976
378
1354
211
1218
473
1691
2A0250
215 <2>
1514
466
1980
250
1764
594
2358
2A0312
283 <2>
1936
588
2524
312
2020
665
2686
2A0360
346 <2>
2564
783
3347
360
2698
894
3591
2A0415
415 <3>
2672
954
3626
415
2672
954
3626
Interior Unit
Loss (W)
Heatsink Loss
(W)
Interior Unit
Loss (W)
4A0002
1.8 <1>
15.9
45
61
2.1
20
48
68
4A0004
3.4 <1>
25
46
70
4.1
32
49
81
4A0005
4.8 <1>
37
49
87
5.4
45
53
97
4A0007
5.5 <1>
48
53
101
6.9
62
59
121
4A0009
7.2 <1>
53
55
108
8.8
66
60
126
4A0011
9.2 <1>
69
61
130
11.1
89
73
162
4A0018
14.8 <1>
135
86
221
17.5
177
108
285
4A0023
18.0 <1>
150
97
247
23
216
138
354
4A0031
24 <1>
208
115
323
31
295
161
455
4A0038
31 <1>
263
141
403
38
340
182
521
4A0044
39 <1>
330
179
509
44
390
209
599
4A0058
45 <1>
349
170
518
58
471
215
686
4A0072
60 <1>
484
217
701
72
605
265
870
4A0088
75 <1>
563
254
817
88
684
308
993
4A0103
91 <1>
723
299
1022
103
848
357
1205
Heatsink Loss
(W)
4A0139
112 <1>
908
416
1325
139
1215
534
1749
4A0165
150 <2>
1340
580
1920
165
1557
668
2224
4A0208
180 <2>
1771
541
2313
208
1800
607
2408
4A0250
216 <2>
2360
715
3075
250
2379
803
3182
4A0296
260 <2>
2391
787
3178
296
2448
905
3353
4A0362
304 <2>
3075
985
4060
362
3168
1130
4298
4A0414
370 <2>
3578
1164
4742
414
3443
1295
4738
4A0515
450 <3>
3972
1386
5358
515
4850
1668
6518
4A0675
605 <3>
4191
1685
5875
675
4861
2037
6898
Specifications
Heavy Duty
Model Number
CIMR-A
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
401
Normal Duty
2A0004 to 2A0069
Heavy Duty
2A0081 to 2A0138
80% of HD
70% of HD
YEC_
TMonly
0
2 kHz
8 kHz
15 kHz
Normal Duty
2A0169 to 2A0415
Heavy Duty
80% of HD
YEC_
TMonly
0
2 kHz
5 kHz
10 kHz
Normal Duty
4A0002 to
4A0103
Heavy Duty
YEC_
TMonly
60% of HD
2 kHz
8 kHz
15 kHz
402
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Normal Duty
4A0139 to 4A0362
Heavy Duty
70% of HD
YEC_
TMonly
0
2 kHz
5 kHz
10 kHz
4A0414
Normal Duty
YEC_TMon
ly
Heavy Duty
2 kHz
5 kHz
4A05154A0675
Normal Duty
YEC_TMonl
y
Heavy Duty
83% of HD
2 kHz
5 kHz
Temperature Derating
Specifications
To ensure the maximum performance life, the drives output current must be derated like shown in Figure A.7 when the
drive is installed in areas with high ambient temperature or if drives are Side-by-Side mounted in a cabinet. In order to
ensure reliable drive overload protection, the parameters L8-12 and L8-35 must also be set according to the installation
conditions.
Parameter Settings
Description
Range
Def.
L8-12
No.
Ambient Temperature
Setting
Name
Adjust the drive overload (oL2) protection level when the drive is installed in an environment
that exceeds its ambient temperature rating.
-10 to 50
40C
L8-35
Installation Method
Selection
0: IP00 Enclosure
1: Side-by-Side Mounting
2: NEMA Type 1 Enclosure
3: Finless Drive or External Heatsink Installation
0 to 3
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
403
Drive operation between -10C and 50C allows 100% continuous current without derating.
Side-by-Side Mounting
Drive operation between -10C and 30C allows 100% continuous current without derating. Operation between 30C
and 50C requires output current derating.
NEMA Type 1 Enclosure
Drive operation between -10C and 40C allows 100% continuous current without derating. Operation between 40C
and 50C requires output current derating.
External Heatsink Installation, Finless Drive
Drive operation between -10C and 40C allows 100% continuous current without derating. Operation between 40C
and 50C requires output current derating.
Figure A.7
Drive Rating
(%)
100
85
70
55
0
-10
30
40
50
L8-12
(Ambient temp: C)
common_
TMonly
Altitude Derating
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m both the drive
rated voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m.
404
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Appendix: B
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.
B.1 UNDERSTANDING THE PARAMETER TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . .
B.2 PARAMETER GROUPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.3 PARAMETER TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.4 CONTROL MODE DEPENDENT PARAMETER DEFAULT VALUES . . . . . . . . . .
B.5 V/F PATTERN DEFAULT VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.6 DEFAULTS BY DRIVE MODEL SELECTION (O2-04) AND ND/HD (C6-01). . . . .
B.7 PARAMETERS THAT CHANGE WITH THE MOTOR CODE SELECTION . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
406
407
408
462
464
466
472
405
All Modes
V/f
V/f w/PG
Description
Indicates the parameter is accessible in all control modes.
Parameter is available when operating the drive with V/f Control.
Parameter is available when operating the drive with V/f with PG Control.
OLV
Parameter is available when operating the drive with Open Loop Vector.
CLV
Parameter is available when operating the drive with Closed Loop Vector.
OLV/PM
AOLV/PM
CLV/PM
Parameter is available when operating the drive with Open Loop Vector for PM motors.
Parameter is available when operating the drive with Advanced Open Loop Vector for PM motors.
Parameter is available when operating the drive with Closed Loop Vector for PM motors.
Indicates this parameter can be changed during run.
Motor 2
Refers to a second motor when the drive is operating two motors. Switch between these motors using the multi-function input terminals.
Note: If a parameter is not available in a certain control mode, the symbol for that control mode is grayed out.
406
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Page
Parameter Group
Name
Page
A1
Initialization Parameters
Name
408
H2
435
A2
User Parameters
409
H3
438
b1
409
H4
440
b2
410
H5
440
b3
Speed Search
410
H6
441
b4
Timer Function
411
L1
Motor Protection
442
PID Control
411
L2
442
b6
Dwell Function
413
L3
Stall Prevention
443
b7
Droop Control
413
L4
Speed Detection
444
b8
Energy Saving
413
L5
Fault Restart
445
b9
Zero Servo
414
L6
Torque Detection
445
C1
414
L7
Torque Limit
446
C2
S-Curve Characteristics
415
L8
Drive Protection
446
C3
Slip Compensation
415
n1
Hunting Prevention
447
C4
Torque Compensation
416
n2
448
C5
416
n3
448
C6
Carrier Frequency
418
n5
449
d1
Frequency Reference
419
n6
Online Tuning
449
d2
420
n8
449
d3
Jump Frequency
420
o1
450
d4
420
o2
451
d5
Torque Control
421
o3
Copy Function
451
d6
421
o4
451
d7
Offset Frequency
421
DriveWorksEZ Parameters
452
E1
422
452
E2
Motor 1 Parameters
423
T1
452
E3
423
T2
PM Motor Auto-Tuning
453
E4
Motor 2 Parameters
424
T3
454
E5
PM Motor Settings
425
U1
455
F1
426
U2
Fault Trace
457
F2
428
U3
Fault History
458
F3
428
U4
Maintenance Monitors
458
F4
428
U5
PID Monitors
460
F5
429
U6
460
F6
429
U8
DriveWorksEZ Monitors
461
H1
431
Parameter List
b5
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
407
Name
Description
All Modes
A1-00
(100H)
Language Selection
<3>
A1-01
(101H)
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
common_
TMonly
All Modes
Access Level Selection
<2>
0: View and set A1-01 and A1-04. U- parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
<3>
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Initialize Parameters
A1-04
(104H)
Password
A1-05
(105H)
Password Setting
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
3330: 3-wire initialization
5550: oPE04 error reset
common_
TMonly
All Modes
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, A1-06, and A2-01 through A2-33 cannot be changed.
Application Preset
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
common_
TMonly
All Modes
A1-07
(128H)
132
Default: 2
Min: 0
Max: 2
132
Default: <49>
Default: 2
Min: 0
Max: 7
132
Default: 0
Min: 0
Max: 5550
133
Default: 0000
Min: 0000
Max: 9999
134
Default: 0
Min: 0
Max: 7
135
Default: 0
Min: 0
Max: 2
135
common_
TMonly
All Modes
A1-06
(127H)
Default: <48>
Min: 0
Max: 7
common_
TMonly
All Modes
A1-03
(103H)
Page
common_
TMonly
All Modes
A1-02
(102H)
Setting
common_
TMonly
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<3> Parameter setting value is not reset to the default value when the drive is initialized.
<48> Regional default settings
Setting 0: Asia (Model code: CIMR-ATA)
Setting 1: Japan (Model code: CIMR-AAA)
Setting 7: China (Model code: CIMR-ABA)
<49> Regional default settings
Setting 2: Japan (Model code: CIMR-AAA) and Asia (Model code: CIMR-ATA)
Setting 0: China (Model code: CIMR-ABA)
408
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
A2-01 to
User Parameters 1 to 32
A2-32
(106 to 125H)
A2-33
(126H)
Description
Setting
common_
TMonly
All Modes
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
Default: <2>
Min: b1-01
Max: o2-08
Page
136
common_
TMonly
All Modes
Default: 1 <1>
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. Min: 0
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2- Max: 1
17 through A2-32 for quick access.
136
<1> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not equal 0.
<2> Default setting value is determined by the Application Preset selected with parameter A1-06.
b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
Name
Description
Setting
b1-01
(180H)
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
common_
TMonly
All Modes
b1-02
(181H)
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
common_
TMonly
All Modes
b1-03
(182H)
b1-04
(183H)
b1-05
(184H)
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
common_
TMonly
All Modes
0: Reverse enabled.
1: Reverse disabled.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
b1-07
(186H)
b1-08
(187H)
b1-14
(1C3H)
common_
TMonly
0: Input status is read once and processed immediately (for quick response)
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals)
common_
TMonly
All Modes
0: An external Run command has to be cycled at the new source to be activated.
1: An external Run command at new source is accepted immediately.
common_
TMonly
All Modes
0: Run command not accepted while in the Programming Mode.
1: Run command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Standard
1: Switch phase order (reverses the direction of the motor)
All Modes
b1-15
(1C4H)
common_
TMonly
All Modes
b1-06
(185H)
Page
common_
TMonly
All Modes
Enabled when an input terminal set for External reference (H1- = 2) closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Default: 1
Min: 0
Max: 4
137
Default: 1
Min: 0
Max: 3
138
Default: 0
Min: 0
Max: 3 <11>
139
Default: 0
Min: 0
Max: 1
141
Default: 0
Min: 0
Max: 3
141
Default: 1
Min: 0
Max: 1
142
Default: 0
Min: 0
Max: 1
143
Default: 0
Min: 0
Max: 2
143
Default: 0
Min: 0
Max: 1
143
Default: 0
Min: 0
Max: 4
144
Parameter List
No.(Addr.)
common_
TMonly
409
Name
Description
Setting
b1-16
(1C5H)
b1-17
(1C6H)
Page
common_
TMonly
All Modes
Enabled when a terminal set for External reference (H1- = 2) closes.
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 0
Min: 0
Max: 3
144
Default: 0
Min: 0
0: Disregarded. A new Run command needs to be issued after power up.
Max: 1
1: Allowed. Motor will start immediately after power up if a Run command is already enabled.
144
common_
TMonly
All Modes
Name
b2-01
(189H)
b2-02
(18AH)
Description
Setting
common_
TMonly
All Modes
Sets the frequency at which DC Injection Braking starts when Ramp to stop (b1-03 = 0) is
selected.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the DC Injection Braking current as a percentage of the drive rated current.
Page
Default: <10>
Min: 0.0 Hz
Max: 10.0 Hz
144
Default: 50%
Min: 0%
Max: 100%
145
common_
TMonly
b2-03
(18BH)
Default: 0.00 s
Min: 0.00 s
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) time at
Max: 10.00 s
start. Disabled when set to 0.00 s.
145
b2-04
(18CH)
Default: <10>
Min: 0.00 s
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) at stop. Max: 10.00 s
145
b2-08
(190H)
All Modes
common_
TMonly
All Modes
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03).
b2-12
(1BAH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time for Short Circuit Braking operation at start. <7>
b2-13
(1BBH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
b2-18
(177H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Determines the current level for Short Circuit Braking. Set as a percentage of the motor rated
current.
Default: 0%
Min: 0%
Max: 1000%
146
Default: 0.00 s
Min: 0.00 s
Max: 25.50 s
146
Default: 0.50 s
Min: 0.00 s
Max: 25.50 s
146
Default: 100.0%
Min: 0.0%
Max: 200.0%
146
<7> A coasting motor may require a braking resistor circuit to bring the motor to a stop in the required time.
<10> Default setting is determined by the control mode (A1-02).
Name
b3-01
(191H)
b3-02
(192H)
b3-03
(193H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the current level at which the speed is assumed to be detected and Speed Search is ended.
Set as a percentage of the drive rated current.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
b3-04
(194H)
410
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Determines how much to lower the V/f ratio during Speed Search.
Output voltage during Speed Search equals the V/f setting multiplied by b3-04.
common_
TMonly
Page
Default: <10>
Min: 0
Max: 1
150
Default: <10>
Min: 0%
Max: 200%
150
Default: 2.0 s
Min: 0.1 s
Max: 10.0 s
150
Default: <9>
Min: 10%
Max: 100%
150
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
b3-05
(195H)
b3-06
(196H)
b3-10
(19AH)
b3-14
(19EH)
b3-17
(1F0H)
Description
Setting
common_
TMonly
Default: 0.2 s
Min: 0.0 s
When using an external contactor on the output side, b3-05 delays executing Speed Search after
Max: 100.0 s
a momentary power loss to allow time for the contactor to close.
All Modes
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
151
Default: <10>
Min: 0
Max: 1
151
common_
TMonly
Default: 150%
Min: 0%
Max: 200%
151
common_
TMonly
Default: 0.10 s
Min: 0.00 s
Max: 1.00 s
151
Default: 3
Min: 0
Max: 10
151
Default: 0
Min: 0
Max: 1
151
Default: 0.5 s
Min: 0.0 s
Max: 30.0 s
151
common_
common_
TMonly
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the Speed Search restart current level as a percentage of the drive rated current.
b3-18
(1F1H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the number of times the drive can attempt to restart when performing Speed Search.
b3-24
(1C0H)
b3-25
(1C8H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Current Detection
1: Speed Estimation
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
150
Default: 1.05
Min: 1.00
Max: 1.20
Sets the gain which is applied to the speed detected by Speed Estimation Speed Search before
the motor is reaccelerated. Increase this setting if ov occurs when performing Speed Search
after a relatively long period of baseblock.
OLV/PM
150
common_
TMonly
Default: <9>
Min: 0.0
Sets the current injected to the motor at the beginning of Speed Estimation Speed Search. Set as Max: 2.0
a coefficient for the motor rated current.
OLV/PM
Page
common_
TMonly
Sets the time the must wait between each Speed Search restart attempt.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
Name
b4-01
(1A3H)
b4-02
(1A4H)
Description
Setting
Page
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
152
Used to set the on-delay and off-delay times for a digital timer output (H2-=12). The output Default: 0.0 s
is triggered by a digital input programmed to H1-=18)
Min: 0.0 s
Max: 3000.0 s
152
common_
TMonly
All Modes
Description
All Modes
b5-01
(1A5H)
b5-02
(1A6H)
Setting
0: Disabled
1: Enabled (PID output becomes output frequency reference, deviation D controlled)
2: Enabled (PID output becomes output frequency reference, feedback D controlled)
3: Enabled (PID output added to frequency reference, deviation D controlled)
4: Enabled (PID output added to frequency reference, feedback D controlled)
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
Integral Limit Setting
common_
TMonly
Sets the maximum output possible from the integrator as a percentage of the maximum output
frequency.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Page
common_
TMonly
Default: 0
Min: 0
Max: 4
156
Default: 1.00
Min: 0.00
Max: 25.00
156
Default: 1.0 s
Min: 0.0 s
Max: 360.0 s
156
Default: 100.0%
Min: 0.0%
Max: 100.0%
156
Parameter List
No.(Addr.)
411
Name
Derivative Time (D)
Description
Setting
156
Default: 100.0%
Min: 0.0%
Max: 100.0%
156
Default: 0.0%
Min: -100.0%
Max: 100.0%
157
common_
TMonly
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
157
common_
TMonly
Default: 0
Min: 0
Max: 1
157
common_
TMonly
Default: 1.00
Min: 0.00
Max: 25.00
157
Default: 0
Min: 0
Max: 1
157
All Modes
Sets D control derivative time.
b5-06
(1AAH)
b5-07
(1ABH)
b5-08
(1ACH)
common_
TMonly
All Modes
PID Output Limit
Sets the maximum output possible from the entire PID controller as a percentage of the
maximum output frequency.
common_
TMonly
All Modes
PID Offset Adjustment
Applies an offset to the PID controller output. Set as a percentage of the maximum output
frequency.
All Modes
Sets a low pass filter time constant on the output of the PID controller.
All Modes
b5-09
(1ADH)
b5-10
(1AEH)
b5-11
(1AFH)
All Modes
Sets the gain applied to the PID output.
common_
TMonly
All Modes
PID Output Reverse Selection
All Modes
b5-12
(1B0H)
b5-13
(1B1H)
b5-14
(1B2H)
b5-15
(1B3H)
b5-16
(1B4H)
b5-17
(1B5H)
b5-18
(1DCH)
b5-19
(1DDH)
b5-34
(19FH)
b5-35
(1A0H)
Default: 1.0 s
Min: 0.0 s
Max: 25.5 s
159
All Modes
common_
TMonly
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
159
All Modes
common_
TMonly
Default: 0.0 s
Min: 0.0 s
Max: 25.5 s
160
common_
TMonly
Default: 0.0 s
Min: 0.0 s
Max: 6000.0 s
160
Default: 0
Min: 0
Max: 1
160
Default: 0.00%
Min: 0.00%
Max: 100.00%
160
Default: 1
Min: 0
Max: 3
160
Default: 0.00%
Min: -100.0%
Max: 100.0%
161
Default: 1000.0%
Min: 0%
Max: 1000.0%
161
Default: 100%
Min: 0%
Max: 100%
159
Default: 1.0 s
Min: 0.0 s
Max: 25.5 s
159
All Modes
Sets the acceleration and deceleration time to PID setpoint.
common_
TMonly
All Modes
0: Disabled
1: Enabled
common_
TMonly
All Modes
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum output
frequency.
common_
TMonly
0: 0.01Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
common_
TMonly
All Modes
PID Output Lower Limit
Sets the minimum output possible from the PID controller as a percentage of the maximum
output frequency.
common_
TMonly
All Modes
PID Input Limit
b5-36
(1A1H)
b5-37
(1A2H)
412
common_
TMonly
All Modes
b5-20
(1E2H)
159
Sets the PID feedback loss detection level as a percentage of the maximum output frequency.
All Modes
Limits the PID control input (deviation signal) as a percentage of the maximum output
frequency. Acts as a bipolar limit.
common_
TMonly
All Modes
Sets the PID feedback high detection level as a percentage of the maximum output frequency.
common_
TMonly
All Modes
Sets the PID feedback high level detection delay time.
158
Default: 0%
Min: 0%
Max: 100%
common_
TMonly
All Modes
Page
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
common_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
PID Setpoint User Display
Description
Setting
common_
TMonly
All Modes
Sets the display value of U5-01 and U5-04 when the maximum frequency is output.
common_
TMonly
All Modes
b5-39
(1FFH)
b5-40
(17FH)
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
common_
TMonly
All Modes
0: Display the frequency reference (U1-01) after PID compensation has been added.
1: Display the frequency reference (U1-01) before PID compensation has been added.
Page
Default: <5>
Min: 1
Max: 60000
161
Default: <5>
Min: 0
Max: 3
161
Default: 0
Min: 0
Max: 1
161
Name
b6-01
(1B6H)
b6-02
(1B7H)
b6-03
(1B8H)
b6-04
(1B9H)
Description
Setting
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
Default: 0.0 s
Min: 0.0 s
Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at Max: 10.0 s
start.
Default: 0.0 Hz
Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at Min: 0.0 Hz
stop.
Max: 400.0 Hz
common_
TMonly
All Modes
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
Page
162
162
162
162
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Sets the speed reduction gain applied at a torque reference of 100%. Set as a percentage of
motor base speed.
b7-02
(1CBH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Page
Default: 0.0%
Min: 0.0%
Max: 100.0%
163
Default: 0.05 s
Min: 0.03 s
Max: 2.00 s
163
b8-01
(1CCH)
b8-02
(1CDH)
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
0: Disabled
1: Enabled
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
b8-04
(1CFH)
b8-05
(1D0H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
164
Default: <10>
Min: 0.0
Max: 10.0
164
Default: <4>
Min: 0.00 s
Max: 10.00 s
164
common_
TMonly
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
common_
TMonly
Default: <10>
Min: 0
Max: 1
OLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the limit for the voltage search operation as a percentage of the motor rated voltage.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Page
Default: 20 ms
Min: 0 ms
Max: 2000 ms
Default: 0%
Min: 0%
Max: 100%
164
Parameter List
No.(Addr.)
164
B
165
413
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 5
Min: 0
Max: 100
165
common_
TMonly
Default: 10
Min: 0
Max: 16383
165
Sets the position loop gain for the Zero Servo function.
b9-02
(1DBH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
Sets the range to trigger an output terminal set for Zero Servo Complete during Zero Servo
operation.
C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip compensation, torque
compensation, and carrier frequency selections.
C1: Acceleration and Deceleration Times
No.(Addr.)
C1-01
(200H)
Name
Acceleration Time 1
Description
Setting
common_
TMonly
All Modes
Page
166
Deceleration Time 1
common_
TMonly
All Modes
166
Acceleration Time 2
common_
TMonly
All Modes
166
Deceleration Time 2
common_
TMonly
All Modes
166
C1-06
(205H)
C1-07
(206H)
C1-08
(207H)
C1-09
(208H)
C1-10
(209H)
C1-11
(20AH)
common_
TMonly
All Modes
Sets the time to accelerate from 0 to maximum frequency.
Default: 10.0 s
Min: 0.0 s
Max: 6000.0 s <12>
common_
TMonly
All Modes
166
166
All Modes
166
All Modes
166
All Modes
167
All Modes
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
common_
TMonly
All Modes
Sets the frequency to switch between accel/decel time settings
Default: 1
Min: 0
Max: 1
168
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
167
<12> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting
range becomes 0.00 to 600.00 seconds.
414
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
C2-01
(20BH)
C2-02
(20CH)
C2-03
(20DH)
Description
Setting
common_
TMonly
All Modes
The S-curve can be controlled at the four points shown below.
ON
Run Command
Output Frequency
C2-02
OFF
C2-03
C2-01
C2-04
(20EH)
C2-04
Time
Page
168
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
168
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
168
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
168
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: <10>
Min: 0.0
Max: 2.5
169
common_
TMonly
Default: <10>
Min: 0 ms
Max: 10000 ms
169
Default: 200%
Min: 0%
Max: 250%
169
Default: 0
Min: 0
Max: 2
169
Default: 0
Min: 0
Max: 1
170
common_
TMonly
Default: <15>
Min: 0.0
Max: 2.5
170
common_
TMonly
Default: <15>
Min: 0 ms
Max: 10000 ms
170
common_
TMonly
Default: 200%
Min: 0%
Max: 250%
170
Default: 0
Min: 0
Max: 2
171
Sets the gain for the motor slip compensation function used for motor 1.
C3-02
(210H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Adjusts the slip compensation function delay time used for motor 1.
C3-03
(211H)
C3-04
(212H)
C3-05
(213H)
C3-21
(33EH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets an upper limit for the slip compensation function as a percentage of motor rated slip for
motor 1 (E2-02).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled.
1: Enabled. Automatically decreases motor flux when output voltage saturation is reached.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C3-23
(242H)
C3-24
(243H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the upper limit for the slip compensation function for motor 2. Set as a percentage of the
motor rated slip (E4-02).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
CLV
Page
common_
TMonly
Parameter List
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
415
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: <10>
Min: 0.00
Max: 2.50
171
common_
TMonly
Default: <16>
Min: 0 ms
Max: 60000 ms
171
common_
TMonly
Default: 0.0%
Min: 0.0%
Max: 200.0%
172
common_
TMonly
Default: 0.0%
Min: -200.0%
Max: 0.0%
172
Sets the gain for the automatic torque (voltage) boost function and helps to produce better
starting torque. Used for motor 1.
C4-02
(216H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C4-05
(219H)
C4-06
(21AH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Default: 10 ms
Min: 0 ms
Sets the time constant for torque compensation at forward start and reverse start (C4-03 and C4- Max: 200 ms
04).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
172
common_
TMonly
Default: 150 ms
Min: 0 ms
Max: 10000 ms
172
common_
TMonly
Default: 1.00
Min: 0.00
Max: 2.50
172
Page
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: <10>
Min: 0.00
Max: 300.00 <17>
175
common_
TMonly
Default: <10>
Min: 0.000 s
Max: 10.000 s
175
common_
TMonly
Default: <10>
Min: 0.00
Max: 300.00 <17>
175
common_
TMonly
Default: <10>
Min: 0.000 s
Max: 10.000 s
175
common_
TMonly
Default: 5.0%
Min: 0.0%
Max: 20.0%
176
Default: <10>
Min: 0.000 s
Max: 0.500 s
176
common_
TMonly
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
176
common_
TMonly
Default: 400%
Min: 0%
Max: 400%
176
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the speed control gain 2 of the speed control loop (ASR).
C5-04
(21EH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C5-05
(21FH)
ASR Limit
C5-06
(220H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the upper limit for the speed control loop (ASR) as a percentage of the maximum output
frequency (E1-04).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the filter time constant for the time from the speed loop to the torque command output.
C5-07
(221H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the frequency for switching between proportional gain 1, 2 and integral time 1, 2.
C5-08
(222H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the ASR integral upper limit as a percentage of rated load torque.
416
Page
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
C5-12
(386H)
C5-17
(276H)
Motor Inertia
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the motor inertia. This value is automatically set during ASR or Inertia Auto-Tuning.
C5-18
(277H)
C5-21
(356H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
C5-26
(35BH)
C5-27
(35CH)
C5-28
(35DH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
common_
TMonly
Default: <15>
Min: 0.000 s
Max: 10.000 s
177
common_
TMonly
Default: <15>
Min: 0.00
Max: 300.00 <17>
177
common_
TMonly
Default: <15>
Min: 0.000 s
Max: 10.000 s
177
Default: 5.0%
Min: 0.0%
Max: 20.0%
177
CLV
common_
TMonly
Sets the upper limit for the speed control loop (ASR) for motor 2 as a percentage of the
maximum output frequency (E3-04).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Default: <15>
Min: 0.000 s
Sets the filter time constant for the time from the speed loop to the torque command output used Max: 0.500 s
for motor 2.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the frequency for motor 2 used to switch between proportional gain 1 and 2, and between
the integral time 1 and 2.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the ASR integral upper limit for motor 2 as a percentage of rated load torque.
C5-32
(361H)
C5-37
(278H)
C5-38
(279H)
Motor 2 Inertia
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled. Integral functions for motor 2 are enabled only during constant speed.
1: Enabled. Integral functions are always enabled for motor 2, during accel/decel and during
constant speed.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
177
Default: 400%
Min: 0%
Max: 400%
177
Default: 0
Min: 0
Max: 1
178
common_
TMonly
common_
TMonly
Sets the ratio between the motor 2 and machine inertia. This value is automatically set during
ASR or Inertia Auto-Tuning.
177
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
Default: <9>
Min: 0.0001 kgm2
2
Sets the inertia of motor 2 alone without the load. This value is automatically set during ASR or Max: 600.00 kgm
Inertia Auto-Tuning.
OLV/PM
177
177
Sets the integral time 2 of the speed control loop (ASR) for motor 2.
C5-25
(35AH)
177
Default: <15>
Min: 0.00
Max: 300.00 <17>
Sets the speed control gain 2 of the speed control loop (ASR) for motor 2.
C5-24
(359H)
common_
TMonly
Sets the integral time of the speed control loop (ASR) for motor 2.
C5-23
(358H)
176
common_
TMonly
Sets the proportional gain of the speed control loop (ASR) for motor 2.
C5-22
(357H)
Default: 0
Min: 0
Max: 1
Default: 1.0
Min: 0.0
Sets the ratio between the motor and load inertia. This value is automatically set during ASR or Max: 6000.0
Inertia Auto-Tuning.
OLV/PM
Page
Default: 1.0
Min: 0.0
Max: 6000.0
178
178
Parameter List
No.(Addr.)
<9> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
<14> Default setting value is dependent on the motor code set to E5-01.
<15> Default setting is determined by the control mode for motor 2 (E3-01).
<17> The setting range is 1.00 to 300.0 in CLV and AOLV/PM.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
417
Name
Description
Setting
common_
TMonly
All Modes
Drive Duty Selection
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User defined (determined by C6-03 through C6-05)
common_
TMonly
All Modes
C6-03
(225H)
C6-04
(226H)
Note: C6-04 and C6-05 are available only in V/f and V/f w/PG control modes.
Determines the upper and lower limits for the carrier frequency.
In OLV, C6-03 determines the upper limit of the carrier frequency.
Carrier Frequency
C6-03
C6-04
C6-05
(227H)
C6-09
(22BH)
Default: 0
Min: 0
Max: 1
178
Default: <4>
Min: 1
Max: F
179
Default: <13>
Min: 1.0 kHz
Max: 15.0 kHz
179
Default: <13>
Min: 1.0 kHz
Max: 15.0 kHz
179
Default: <13>
Min: 0
Max: 99
179
Default: 0
Min: 0
Max: 1
180
common_
TMonly
All Modes
C6-02
(224H)
Page
Output Frequency
(C6-05) K
Output
Frequency
E1-04
Max Output
Frequency
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<13> Default setting value is dependent on the carrier frequency selection (C6-02).
418
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
d: References
Reference parameters are used to set the various frequency reference values during operation.
d1: Frequency Reference
d1-01
(280H)
d1-02
(281H)
d1-03
(282H)
d1-04
(283H)
d1-05
(284H)
d1-06
(285H)
d1-07
(286H)
d1-08
(287H)
Name
Description
d1-10
(28BH)
d1-11
(28CH)
d1-12
(28DH)
d1-13
(28EH)
d1-14
(28FH)
d1-15
(290H)
d1-16
(291H)
d1-17
(292H)
Page
Frequency Reference 1
182
Frequency Reference 2
182
Frequency Reference 3
182
Frequency Reference 4
182
Frequency Reference 5
182
Frequency Reference 6
182
Frequency Reference 7
182
Frequency Reference 8
All Modes
d1-09
(288H)
Setting
common_
TMonly
Sets the frequency reference for the drive. Setting units are determined by parameter o1-03.
Frequency Reference 9
Default: 0.00 Hz
Min: 0.00 Hz
Max: 400.00 Hz
<20> <26>
182
182
Frequency Reference 10
182
Frequency Reference 11
182
Frequency Reference 12
182
Frequency Reference 13
182
Frequency Reference 14
182
Frequency Reference 15
182
Frequency Reference 16
182
All Modes
Sets the jog frequency reference. Setting units are determined by parameter o1-03.
common_
TMonly
Default: 6.00 Hz
Min: 0.00 Hz
Max: 400.00 Hz
Parameter List
No.(Addr.)
182
<20> <26>
<20> Range upper limit is determined by the maximum output frequency (E1-04) and the upper limit of the frequency reference (d2-01).
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
419
Name
d2-01
(289H)
d2-02
(28AH)
d2-03
(293H)
Description
Setting
common_
TMonly
All Modes
Sets the frequency reference upper limit as a percentage of the maximum output frequency.
common_
TMonly
All Modes
Sets the frequency reference lower limit as a percentage of the maximum output frequency.
common_
TMonly
All Modes
Sets the lower limit for frequency references from analog inputs as a percentage of the
maximum output frequency.
Page
Default: 100.0%
Min: 0.0%
Max: 110.0%
184
Default: 0.0%
Min: 0.0%
Max: 110.0%
184
Default: 0.0%
Min: 0.0
Max: 110.0%
184
Name
Jump Frequency 1
d3-02
(295H)
Jump Frequency 2
d3-03
(296H)
Jump Frequency 3
d3-04
(297H)
Description
Setting
common_
TMonly
All Modes
All Modes
Sets the dead-band width around each selected prohibited frequency reference point.
Page
184
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
184
184
Default: <10>
Min: 0.0 Hz
Max: 20.0 Hz
184
d4-04
(2ABH)
d4-05
(2ACH)
d4-06
(2ADH)
d4-07
(2AEH)
d4-08
(2AFH)
d4-09
(2B0H)
d4-10
(2B6H)
420
Name
Frequency Reference Hold
Function Selection
Description
All Modes
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that was saved.
common_
TMonly
All Modes
Sets the bias added to the frequency reference when the Up 2 and Down 2 digital inputs are
enabled (H1- = 75, 76).
common_
TMonly
All Modes
0: Use selected accel/decel time.
1: Use accel/decel time 4 (C1-07 and C1-08).
common_
TMonly
All Modes
All Modes
The Up/Down 2 bias value is saved in d4-06 when the frequency reference is not input by the
digital operator. Set as a percentage of the maximum output frequency.
Default: 0
Min: 0
Max: 1
185
Default: 0.00 Hz
Min: 0.00 Hz
Max: 99.99 Hz
187
Default: 0
Min: 0
Max: 1
188
Default: 0
Min: 0
Max: 1
188
Default: 0.0%
Min: -99.9%
Max: 100.0%
188
Default: 1.0%
Limits how much the frequency reference is allowed to change while an input terminal set for
Min: 0.1%
Up 2 or Down 2 is enabled. If the frequency reference changes for more than the set value, then
Max: 100.0%
the bias value is held and the drive accelerates or decelerates to the frequency reference. Set as a
percentage of the maximum output frequency.
common_
TMonly
Default: 0.0%
Min: 0.0%
Sets the upper limit for the bias and the value that can be saved in d4-06. Set as a percentage of
Max: 100.0%
the maximum output frequency.
Default: 0.0%
Min: -99.9%
Sets the lower limit for the bias and the value that can be saved in d4-06. Set as a percentage of
Max: 0.0%
the maximum output frequency.
Page
common_
TMonly
All Modes
Analog Frequency Reference
Fluctuation Limit (Up/Down 2)
Setting
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
0: The lower limit is determined by d2-02 or an analog input.
1: The lower limit is determined by d2-02.
Default: 0
Min: 0
Max: 1
189
189
189
189
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
V/f
d5-01
(29AH)
d5-02
(29BH)
d5-03
(29CH)
d5-04
(29DH)
OLV
CLV
AOLV/PM
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Default: 0 ms
Min: 0 ms
Sets a delay time for the torque reference signal. Used to suppress effects by noisy or fluctuating Max: 1000 ms
torque reference signals.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Speed Limit
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
common_
TMonly
Sets the speed limit during Torque Control as a percentage of the maximum output frequency.
Enabled when d5-03 = 2. A negative setting set a limit in the opposite direction of the Run
command.
d5-06
(29FH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the speed limit bias as a percentage of the maximum output frequency.
The bias is applied to the specified speed limit and can adjust the margin for the speed limit.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the delay time for switching between Speed and Torque Control using an input terminal
(H1- = 71). Reference values are held during this switch delay time.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
common_
TMonly
Default: 0
Min: 0
0: Speed Control
Max: 1
1: Torque Control
Set to 0 when using a digital input to switch between Speed and Torque Control (H1- = 71).
OLV/PM
d5-05
(29EH)
d5-08
(2B5H)
V/f w/PG
Setting
common_
TMonly
0: Disabled
1: Enabled
193
193
Default: 1
Min: 1
Max: 2
193
Default: 0%
Min: -120%
Max: 120%
193
Default: 10%
Min: 0%
Max: 120%
194
Default: 0 ms
Min: 0 ms
Max: 1000 ms
194
Default: 1
Min: 0
Max: 1
194
Description
V/f
d6-01
(2A0H)
d6-02
(2A1H)
d6-03
(2A2H)
d6-06
(2A5H)
V/f w/PG
OLV
Setting
CLV
common_
TMonly
Default: 80%
Min: 0%
Sets the drive output voltage for the Field Weakening function as a percentage of the maximum Max: 100%
output voltage.
Enabled when a multi-function input is set for Field Weakening (H1- = 63).
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the lower limit of the frequency range where Field Weakening control is valid.
The Field Weakening command is valid only at frequencies above this setting and only when
the output frequency matches the frequency reference (speed agree).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
194
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
194
Default: 0
Min: 0
Max: 1
195
common_
TMonly
Default: 400%
Min: 100%
Sets the upper limit of the excitation current command during magnetic field forcing. A setting Max: 400%
of 100% is equal to motor no-load current. Disabled only during DC Injection Braking.
195
Name
Offset Frequency 1
Description
Setting
common_
TMonly
Default: 0.0%
All Modes
Min: -100.0%
Added to the frequency reference when the digital input Frequency offset 1 (H1- = 44) is
Max: 100.0%
switched on.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Page
Parameter List
No.(Addr.)
195
421
d7-03
(2B4H)
Name
Description
Setting
common_
TMonly
Offset Frequency 2
Default: 0.0%
Min: -100.0%
Added to the frequency reference when the digital input Frequency offset 2 (H1- = 45) is
Max: 100.0%
switched on.
Offset Frequency 3
Default: 0.0%
Min: -100.0%
Added to the frequency reference when the digital input Frequency offset 3 (H1- = 46) is
Max: 100%
switched on.
All Modes
common_
TMonly
All Modes
Page
195
195
E: Motor Parameters
E1: V/f Pattern for Motor 1
No.(Addr.)
Name
Description
Setting
E1-01
(300H)
E1-03
(302H)
E1-04
(303H)
E1-05
(304H)
Maximum Voltage
E1-06
(305H)
Base Frequency
E1-07
(306H)
E1-08
(307H)
E1-09
(308H)
E1-10
(309H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
All Modes
E1-08
<21>
E1-12
(30BH)
<21>
E1-13
(30CH)
Base Voltage
E1-09
196
common_
TMonly
E1-10
E1-11
(30AH)
Page
common_
TMonly
All Modes
Note: Some parameters may not be available depending on the control mode.
E1-07, E1-08 and E-10 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector.
E1-11, E1-12 and E-13 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector, Closed Loop Vector.
Default: F <3>
Min: 0
Max: F <30>
196
200
200
200
200
200
200
200
Default: 0.0 Hz
Min: 0.0
Max: E1-04 <26>
200
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V <18>
200
Default: 0.0 V
<18> <27>
Min: 0.0 V
Max: 255.0 V <18>
200
<3> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<21> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<29> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
<30> The setting value is F in OLV.
422
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Setting
Page
Default: <9>
Min: 10% of drive rated
current
Max: 200% of drive
rated current <19>
201
common_
TMonly
Default: <9>
Min: 0.00 Hz
Max: 20.00 Hz
201
common_
TMonly
Default: <9>
Min: 0 A
Max: E2-01 <19>
201
common_
TMonly
Default: 4
Min: 2
Max: 48
201
common_
TMonly
Default: <9>
Min: 0.000
Max: 65.000
202
common_
TMonly
Default: <9>
Min: 0.0%
Max: 40.0%
202
Default: 0.50
Min: E2-07
Max: 0.50
202
Default: 0.75
Min: E2-07
Max: 0.75
202
common_
TMonly
Default: 0.0%
Min: 0.0%
Max: 10.0%
202
common_
TMonly
Default: <9>
Min: 0 W
Max: 65535 W
202
Default: <9>
Min: 0.00 kW
Max: 650.00 kW
203
common_
TMonly
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
E2-02
(30FH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
E2-04
(311H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
E2-06
(313H)
E2-07
(314H)
E2-08
(315H)
E2-09
(316H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the motor mechanical loss as a percentage of motor rated power (kW).
E2-10
(317H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
E2-11
(318H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 and Table A.3)
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
No.(Addr.)
E3-01
(319H)
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Setting
CLV
common_
TMonly
Default: 0
Min: 0
Max: 3
Page
204
Parameter List
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
423
Name
Description
Setting
Page
E3-04
(31AH)
204
E3-05
(31BH)
Default: <18>
Min: 0.0 V
Max: 255.0 V <18>
204
E3-06
(31CH)
204
E3-07
(31DH)
204
E3-08
(31EH)
204
E3-09
(31FH)
E3-13
204
E3-10
(320H)
E3-08
204
E3-11
(345H)
204
204
E3-12
(346H)
<24>
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
E3-10
E3-09
Note: E3-07 and E3-08 are only available in the following control modes: V/f, V/f w/PG and
OLV.
Default: 0.0 V
E3-13
(347H)
<18> <27>
Min: 0.0 V
Max: 255.0 V <18>
204
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<26> The setting range is 0.0 to 66.0 in AOLV/PM.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMR-ATA).
For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized Drive: CIMR-ABA
on page 465.
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Setting
Page
Default: <9>
Min: 10% of drive rated
current
Max: 200% of drive
rated current <19>
205
common_
TMonly
Default: <9>
Min: 0.00 Hz
Max: 20.00 Hz <19>
205
common_
TMonly
Default: <9>
Min: 0 A
Max: E4-01 <19>
205
common_
TMonly
Default: 4
Min: 2
Max: 48
205
common_
TMonly
Default: <9>
Min: 0.000
Max: 65.000
206
common_
TMonly
Default: <9>
Min: 0.0%
Max: 40.0%
206
Default: 0.50
Min: 0.00
Max: 0.50
206
common_
TMonly
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
E4-02
(322H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
E4-03
(323H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
E4-04
(324H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
E4-06
(326H)
E4-07
(343H)
424
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of rated
voltage. Automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Set to the motor iron saturation coefficient at 50% of magnetic flux for motor 2. Automatically
set during Auto-Tuning.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
E4-08
(344H)
E4-09
(33FH)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 0.75
Min: E4-07
Max: 0.75
206
Default: 0.0%
Min: 0.0%
Max: 10.0%
206
common_
TMonly
Default: <9>
Min: 0 W
Max: 65535 W
206
common_
TMonly
Default: <9>
Min: 0.00 kW
Max: 650.00 kW
206
Set to the motor iron saturation coefficient at 75% of magnetic flux for motor 2. This value is
automatically set during Auto-Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the motor mechanical loss for motor 2 as a percentage of motor rated power (kW).
E4-10
(340H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 and Table A.3)
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
E5-01
(329H)
Name
<3>
E5-02
(32AH)
<3>
E5-03
(32BH)
<3>
E5-11
(333H)
E5-24
(353H)
<3>
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
207
Default: <14>
Min: 10% of drive rated
current
Max: 200% of drive
rated current <19>
207
common_
TMonly
Default: <14>
Min: 2
Max: 48
208
common_
TMonly
Default: <14>
Min: 0.000
Max: 65.000
208
common_
TMonly
Default: <14>
Min: 0.00 mH
Max: 300.00 mH
208
common_
TMonly
Default: <14>
Min: 0.00 mH
Max: 600.00 mH
208
Default: <14>
Min: 0.0 mV/(rad/s)
Max:
2000.0 mV/(rad/s)
208
208
Default: <14>
Min: 0.0 mV/(r/min)
Max: 2000.0 mV/(r/
min)
208
common_
TMonly
common_
TMonly
Set the induced phase peak voltage in units of 0.1 mV (rad/s) [electrical angle]. Set this
parameter when using a Yaskawa SSR1 Series PM motor with derated torque, or a Yaskawa
SST4 Series motor with constant torque.
When setting this parameter, E5-24 should be set to 0.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the offset between the rotor magnetic axis and the Z pulse of an incremental encoder. Set
during Z Pulse Offset Tuning.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set
this parameter when using a Yaskawa SMRA Series SPM motor.
When setting this parameter, E5-09 should be set to 0.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
207
Default: <14>
Min: 0.10 kW
Max: 650.00 kW
common_
TMonly
OLV/PM
Page
common_
TMonly
<3>
E5-09
(331H)
AOLV/PM
<3>
E5-07
(32FH)
OLV/PM
Setting
CLV
<3>
E5-06
(32EH)
OLV
<3>
E5-05
(32DH)
V/f w/PG
<3>
E5-04
(32CH)
Description
V/f
Parameter List
No.(Addr.)
425
F: Options
F parameters are used to program the drive for PG feedback from the motor and to function with option cards.
F1: PG Speed Control Card (PG-B3 / PG-X3)
Parameters F1-01, F1-05, F1-06, F1-12, F1-13, and F1-18 through F1-21 are used to set up a PG option card plugged into
option connector CN5-C of the drive. They include PG 1 in the parameter name.
Parameters F1-21 through F1-37 are used to set up a PG option card plugged into option connector CN5-B of the drive.
They include PG 2 in the parameter name.
Other parameters in the F1 group are used to set operation for PG options plugged into connector CN5-C and CN5-B.
No.(Addr.)
F1-01
(380H)
F1-02
(381H)
F1-03
(382H)
F1-04
(383H)
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: <10>
Min: 0 ppr
Max: 60000 ppr
209
Default: 1
Min: 0
Max: 4
209
Default: 1
Min: 0
Max: 3
209
Default: 3
Min: 0
Max: 3
210
Default: <10>
Min: 0
Max: 1
210
Default: 1
Min: 1
Max: 132
210
common_
TMonly
Default: 115%
Min: 0%
Max: 120%
209
common_
TMonly
Default: <10>
Min: 0.0 s
Max: 2.0 s
209
F1-05
(384H)
PG 1 Rotation Selection
F1-06
(385H)
F1-08
(387H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Pulse A leads
1: Pulse B leads
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the division ratio for the pulse monitor used of the PG option card installed to connector
CN5-C. By setting xyz, the division ratio becomes = [(1 + x) / yz]. If only using the A pulse
for one track input, then the input ratio will be 1:1, regardless of what F1-06 is set to.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the overspeed detection level as a percentage of the maximum output frequency.
F1-09
(388H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
426
Page
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
F1-10
(389H)
Name
Excessive Speed Deviation
Detection Level
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
Default: 10%
Min: 0%
Max: 50%
210
Default: 0.5 s
Min: 0.0 s
Max: 10.0 s
210
Default: 0
Min: 0
Max: 1000
210
Default: 0
Min: 0
Max: 1000
210
common_
TMonly
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
209
common_
TMonly
Default: 10
Min: 0
Max: 10
211
common_
TMonly
Default: 128
Min: 0
Max: 5000
211
common_
TMonly
Default: 1
Min: 0
Max: 1
211
common_
TMonly
Default: 0
Min: 0
Max: 1
211
Default: 1
Min: 0
Max: 1
211
common_
TMonly
Default: <45>
Min: 0 ppr
Max: 60000 ppr
209
common_
TMonly
Default: 0
Min: 0
Max: 1
210
Default: 0
Min: 0
Max: 1000
210
Default: 0
Min: 0
Max: 1000
210
Default: 1
Min: 1
Max: 132
210
common_
TMonly
Default: 1
Min: 0
Max: 1
211
common_
TMonly
Default: 0
Min: 0
Max: 1
211
common_
TMonly
Sets the speed deviation detection level as a percentage of the maximum output frequency.
F1-11
(38AH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).
F1-12
(38BH)
PG 1 Gear Teeth 1
F1-13
(38CH)
PG 1 Gear Teeth 2
F1-14
(38DH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if either of these parameters is set to 0.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
F1-18
(3ADH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
1: Enabled
F1-19
(3AEH)
F1-20
(3B4H)
F1-21
(3BCH)
PG 1 Signal Selection
F1-30
(3AAH)
F1-31
(3B0H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
V/f w/PG
OLV
CLV
0: A pulse detection
1: AB pulse detection
V/f
CLV
OLV/PM
AOLV/PM
CLV/PM
Sets the port for the PG option card used by motor 2.
0: CN5-C
1: CN5-B
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the number of pulses for a PG option card connected to port CN5-B.
F1-32
(3B1H)
PG 2 Rotation Selection
F1-33
(3B2H)
PG 2 Gear Teeth 1
V/f w/PG
OLV
AOLV/PM
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Pulse A leads
1: Pulse B leads
F1-34
(3B3H)
PG 2 Gear Teeth 2
F1-35
(3BEH)
F1-36
(3B5H)
F1-37
(3BDH)
V/f
OLV/PM
PG 2 Signal Selection
CLV
common_
TMonly
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if either of these parameters is set to 0.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the division ratio for the pulse monitor used of the PG option card 2 installed to connector
CN5-B. By setting xyz, the division ratio becomes = [(1 + x) / yz].
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: A pulse detection
1: AB pulse detection
CLV
Page
Parameter List
No.(Addr.)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
427
Name
Description
All Modes
F2-01
(38FH)
F2-02
(368H)
Setting
common_
TMonly
Default: 0
Min: 0
Max: 1
212
common_
TMonly
Default: 100.0%
Min: -999.9%
Max: 999.9%
212
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
212
0: Option card input terminals V1, V2, and V3 replace drive input terminals A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together to create the frequency
reference.
All Modes
Sets the gain for the input signal to the analog card.
F2-03
(369H)
All Modes
Page
Sets the bias for the input signal to the analog card.
Name
Description
All Modes
F3-01
(390H)
F3-03
(3B9H)
Setting
Page
common_
TMonly
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
Default: 0
3: BCD, 1 Hz units
Min: 0
4: BCD, 0.1 Hz units
Max: 7
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
common_
TMonly
All Modes
0: 8 bit
1: 12 bit
2: 16 bit
Default: 2
Min: 0
Max: 2
212
213
Name
Description
Setting
common_
TMonly
Default: 102
Min: 000
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of
Max: 999
the desired U- monitor. Some U parameters are available only in certain control modes.
All Modes
common_
TMonly
All Modes
Sets the gain for voltage output via terminal V1.
F4-03
(393H)
F4-04
(394H)
common_
TMonly
Default: 103
Min: 000
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
Max: 999
the desired U- monitor. Some U parameters are available only in certain control modes.
All Modes
All Modes
All Modes
All Modes
F4-08
(398H)
428
All Modes
0: 0 to 10 V
1: -10 to 10 V
213
213
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
213
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
213
Default: 0
Min: 0
Max: 1
213
Default: 0
Min: 0
Max: 1
213
Sets the amount of bias added to the voltage output via terminal V2.
F4-07
(397H)
213
Default: 50.0%
Min: -999.9%
Max: 999.9%
Sets the amount of bias added to the voltage output via terminal V1.
F4-06
(396H)
213
common_
TMonly
Default: 100.0%
Min: -999.9%
Max: 999.9%
Page
common_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
Setting
Page
F5-01
(399H)
Default: 2
Min: 0
Max: 192
F5-02
(39AH)
Default: 4
Min: 0
Max: 192
214
F5-03
(39BH)
Default: 6
Min: 0
Max: 192
214
F5-04
(39CH)
Default: 37
Min: 0
Max: 192
214
F5-05
(39DH)
Default: F
Min: 0
Max: 192
214
F5-06
(39EH)
Default: F
Min: 0
Max: 192
214
F5-07
(39FH)
Default: 0
Min: 0
Max: 192
214
F5-08
(3A0H)
Default: 1
Min: 0
Max: 192
214
Default: 0
Min: 0
Max: 2
214
common_
TMonly
All Modes
Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
common_
TMonly
All Modes
F5-09
(3A1H)
214
Description
Setting
common_
TMonly
All Modes
F6-01
(3A2H)
F6-02
(3A3H)
All Modes
External Fault from Comm. Option
Detection Selection
0: Always detected
1: Detection during run only
common_
TMonly
All Modes
F6-03
(3A4H)
External Fault from Comm. Option 0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
Operation Selection
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
F6-04
(3A5H)
F6-06
(3A7H)
F6-07
(3A8H)
F6-08
(36AH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
214
Default: 0
Min: 0
Max: 1
215
Default: 1
Min: 0
Max: 3
215
Default: 2.0 s
Min: 0.0 s
Max: 5.0 s
common_
TMonly
Default: 0
Min: 0
Max: 1
215
common_
TMonly
Default: 0
Min: 0
Max: 1
215
All Modes
CLV
Default: 1
Min: 0
Max: 3
common_
TMonly
Set the delay time for error detection if a bus error occurs.
<3>
F6-10
(3B6H)
All Modes
All Modes
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
common_
TMonly
Default: 0
0: Communication-related parameters (F6-) are not reset when the drive is initialized using
Min: 0
A1-03.
Max: 1
1: Reset all communication-related parameters (F6-) when the drive is initialized using
A1-03.
Page
Parameter List
No.(Addr.)
common_
TMonly
Default: 0
Min: 0
Max: 64
215
429
Name
Description
All Modes
F6-11
(3B7H)
F6-14
(3BBH)
F6-20
(36BH)
MECHATROLINK Station
Address
F6-21
(36CH)
F6-22
(36DH)
F6-23
(36EH)
MECHATROLINK Monitor
Selection (E)
F6-24
(36FH)
MECHATROLINK Monitor
Selection (F)
All Modes
All Modes
F6-30
(3CBH)
F6-31
(3CCH)
F6-32
(3CDH)
F6-35
(3D0H)
Default: 0
Min: 0
Max: 1
common_
TMonly
Default: 21
Min: 20
Max: 3FH
common_
TMonly
Default: 0
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: FFFFH
common_
TMonly
Default: 0
Min: 0
Max: FFFFH
Default: 1
Min: 0
Max: 3
common_
TMonly
Default: 2
Min: 2
Max: 10
common_
TMonly
Default: 0
Min: 0
Max: 125
common_
TMonly
Default: 0
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 1
common_
TMonly
Default: 0
Min: 0
Max: 126
Default: 6
Min: 0
Max: 8
Default: 0
Min: 0
Max: 64
Default: 0
Min: 0
Max: 4
common_
TMonly
Default: 21
Min: 0
Max: 255
common_
TMonly
Default: 71
Min: 0
Max: 255
common_
TMonly
Default: 0
Min: 0
Max: 1
0: 32 byte
1: 17 byte
0: 10 Mbps
1: 4 Mbps
All Modes
Sets the MECHATROLINK-II monitor (E).
All Modes
Sets the MECHATROLINK-II monitor (F).
common_
TMonly
All Modes
Sets the number of option communication errors (bUS).
All Modes
Sets the node address.
All Modes
0: Resets drive operation with a Clear mode command.
1: Maintains the previous operation state when Clear mode command is given.
All Modes
0: PPO Type
1: Conventional
All Modes
Sets the node address.
common_
TMonly
All Modes
F6-36
(3D1H)
F6-50
(3C1H)
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
common_
TMonly
All Modes
Selects the drives MAC address.
common_
TMonly
All Modes
F6-51
(3C2H)
F6-52
(3C3H)
F6-53
(3C4H)
F6-54
(3C5H)
430
common_
TMonly
Sets the station address when the MECHATROLINK-II option has been installed.
All Modes
F6-26
(3CAH)
0: Disabled
1: Enabled
All Modes
Page
Default: 0
Min: 0
Max: 4
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
All Modes
F6-25
(3C9H)
Setting
common_
TMonly
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
All Modes
Sets the format of the data set from the DeviceNet master to the drive.
All Modes
Sets the format of the data set from the drive to the DeviceNet master.
All Modes
0: Enabled
1: Disabled, no fault detection
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
F6-55
(3C6H)
F6-56
(3D7H)
F6-57
(3D8H)
F6-58
(3D9H)
F6-59
(3DAH)
F6-60
(3DBH)
F6-61
(3DCH)
F6-62
(3DDH)
F6-63
(3DEH)
F6-64 to
F6-71
(3DFH to
3C8H)
Setting
common_
TMonly
Default: 0
Min: 0
Max: 2
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: -15
Max: 15
common_
TMonly
Default: 0
Min: 0
Max: 10
common_
TMonly
Default: 0
Min: 0
Max: 63
All Modes
Sets the scaling factor for the speed monitor in DeviceNet.
All Modes
Sets the scaling factor for the output current monitor in DeviceNet.
All Modes
Sets the scaling factor for the torque monitor in DeviceNet.
All Modes
Sets the scaling factor for the power monitor in DeviceNet.
All Modes
Sets the scaling factor for the voltage monitor in DeviceNet.
All Modes
Sets the scaling factor for the time monitor in DeviceNet.
All Modes
Sets the heartbeat interval for DeviceNet communications.
All Modes
Used to verify the MAC ID the drive has been assigned.
common_
TMonly
All Modes
Reserved
Page
Setting
Page
<3> Parameter setting value is not reset to the default value when the drive is initialized.
No.(Addr.)
Name
Description
H1-01
(438H)
H1-02
(439H)
217
H1-03
(400H)
Default: 24
Min: 0
Max: 9F
217
H1-04
(401H)
Default: 14
Min: 0
Max: 9F
217
H1-05
(402H)
217
H1-06
(403H)
217
H1-07
(404H)
217
H1-08
(405H)
Default: 8
Min: 0
Max: 9F
217
All Modes
Assigns a function to the multi-function digital inputs.
Refer to H1 Multi-Function Digital Input Selections on page 432 for a description of setting
values.
Note: Unused terminals should be set to F.
217
Parameter List
<31> Value in parenthesis is the default setting when a 3-wire initialization is performed (A1-03 = 3330).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
431
Function
3-wire Sequence
Description
Page
common_
TMonly
All Modes
Closed: Reverse rotation (only if the drive is set up for 3-wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop command.
common_
TMonly
All Modes
1
LOCAL/REMOTE Selection
Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2 (b1-01, b1-02 or b115, b1-16)
Closed: LOCAL, digital operator is run and reference source
common_
TMonly
All Modes
218
Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)
common_
TMonly
All Modes
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the frequency references set in d1-01 through d1-08.
common_
TMonly
All Modes
218
219
219
219
219
219
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference sources.
7
common_
TMonly
All Modes
219
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set in C1-03, C1-04).
8
common_
TMonly
All Modes
219
common_
TMonly
All Modes
219
common_
TMonly
All Modes
All Modes
219
220
All Modes
C
PG Encoder Disable
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
220
220
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
220
Open: PI control
Closed: Integral reset
common_
TMonly
All Modes
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
common_
TMonly
All Modes
The drive accelerates when the Up command terminal closes, and decelerates when the Down command closes.
When both terminals are closed or both are open, the drive holds the frequency reference. The Up and Down
commands must always be used in conjunction with one another.
common_
TMonly
All Modes
220
220
220
221
Reverse Jog
common_
TMonly
All Modes
221
Fault Reset
common_
TMonly
All Modes
221
Closed: Resets faults if the cause is cleared and the Run command is removed.
15
common_
TMonly
All Modes
221
432
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
16
Function
Motor 2 Selection
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Page
CLV
common_
TMonly
222
All Modes
common_
TMonly
221
19
PID Disable
1A
1B
Program Lockout
1E
All Modes
common_
TMonly
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2- = 12).
All Modes
common_
TMonly
All Modes
common_
TMonly
Used in conjunction with an input terminal set for Accel/decel time selection 1 (H1- = 7), and allows the
drive to switch between accel/decel times 3 and 4.
All Modes
common_
TMonly
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
All Modes
common_
TMonly
222
223
223
223
223
Closed: Samples the analog frequency reference and operates the drive at that speed.
All Modes
20 to 2F
30
External Fault
common_
TMonly
All Modes
223
common_
TMonly
224
All Modes
31
32
34
35
common_
TMonly
All Modes
common_
TMonly
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use parameters d1-09 to
d1-16 to set reference values.
All Modes
common_
TMonly
All Modes
common_
TMonly
224
224
224
224
40
41
common_
TMonly
224
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
All Modes
Run Command (2-wire Sequence 2)
224
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
All Modes
42
common_
TMonly
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter List
All Modes
Forward Run Command (2-wire
Sequence)
common_
TMonly
224
433
Function
Description
Page
common_
TMonly
All Modes
43
44
Offset Frequency 1
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command. Cannot be set together with settings 40 or
41.
common_
TMonly
All Modes
224
225
Offset Frequency 2
common_
TMonly
All Modes
225
Offset Frequency 3
common_
TMonly
All Modes
225
Node Setup
common_
TMonly
All Modes
225
60
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
225
61
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
225
Closed: Activates Current Detection Speed Search from the maximum output frequency (E1-04).
62
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
225
Closed: Activates Current Detection Speed Search from the frequency reference.
63
Field Weakening
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
225
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
65
common_
TMonly
All Modes
225
common_
TMonly
All Modes
225
common_
TMonly
All Modes
225
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays PASS if the test completes successfully.
68
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
225
71
Drive Enable
common_
TMonly
All Modes
Open: Drive disabled. If this input is opened during run, then the drive will stop as specified by b1-03.
Closed: Ready for operation.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
226
226
72
Zero Servo
75
Up 2 Command
76
Down 2 Command
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
226
77
common_
TMonly
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2 function. The Up 2 and Down 2
commands must always be used in conjunction with one another.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
226
226
226
78
434
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
227
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Function
Description
Page
common_
TMonly
All Modes
227
Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB Ride-Thru 2.
7B
common_
TMonly
All Modes
227
Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB Ride-Thru 2.
7C
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
227
7D
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
227
7E
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
227
common_
TMonly
All Modes
227
DriveWorksEZ Disable
common_
TMonly
All Modes
227
Name
Description
Setting
H2-01
(40BH)
H2-02
(40CH)
All Modes
TMonly
Terminal P1-PC function selection
(photocoupler)
Refer to H2 Multi-Function Digital Output Settings on page 435 for a description of setting
values.
H2-03
(40DH)
common_
227
Default: 1
Min: 0
Max: 192
227
Default: 2
Min: 0
Max: 192
227
Default: 0
Min: 0
Max: 4
236
common_
TMonly
All Modes
H2-06
(437H)
Page
Default: 0
Min: 0
Max: 192
Outputs a 200 ms pulse signal when the watt-hour counter increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Function
During Run
Description
All Modes
Page
common_
TMonly
228
All Modes
1
Zero Speed
Speed Agree 1
common_
TMonly
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
All Modes
common_
TMonly
228
229
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).
3
All Modes
common_
TMonly
229
Frequency Detection 1
All Modes
common_
TMonly
Parameter List
Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
230
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
5
Frequency Detection 2
All Modes
common_
TMonly
230
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
6
Drive Ready
All Modes
common_
TMonly
230
Closed: Power up is complete and the drive is ready to accept a Run command.
7
DC bus Undervoltage
All Modes
common_
TMonly
231
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
435
Function
During Baseblock (N.O.)
Description
Page
common_
TMonly
All Modes
231
Closed: Drive has entered the baseblock state (no output voltage).
common_
TMonly
All Modes
9
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.
common_
TMonly
All Modes
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
All Modes
Closed: An overtorque or undertorque situation has been detected.
common_
TMonly
common_
TMonly
All Modes
231
231
231
231
common_
TMonly
All Modes
231
Fault
common_
TMonly
All Modes
231
Through Mode
common_
TMonly
All Modes
232
Set this value when using the terminal in the pass-through mode.
10
Minor Fault
common_
TMonly
All Modes
232
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
11
common_
TMonly
All Modes
232
Closed: A command has been entered to clear a fault via the input terminals or from the serial network.
12
Timer Output
common_
TMonly
All Modes
232
Speed Agree 2
common_
TMonly
All Modes
232
Closed: When drive output frequency equals the frequency reference L4-04.
14
common_
TMonly
All Modes
232
Closed: When the drive output frequency is equal to the value in L4-03 L4-04.
15
Frequency Detection 3
common_
TMonly
All Modes
233
Closed: When the drive output frequency is less than or equal to the value in L4-03 L4-04.
16
Frequency Detection 4
common_
TMonly
All Modes
233
Closed: When the output frequency is greater than or equal to the value in L4-03 L4-04.
17
common_
TMonly
All Modes
231
common_
TMonly
All Modes
231
common_
TMonly
All Modes
231
During Reverse
common_
TMonly
All Modes
234
common_
TMonly
All Modes
234
Open: Drive has entered the baseblock state (no output voltage).
1C
Motor 2 Selection
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
234
1D
During Regeneration
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
234
Restart Enabled
common_
TMonly
All Modes
234
All Modes
common_
TMonly
234
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
436
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Function
Drive Overheat Pre-alarm (oH)
Description
Page
common_
TMonly
All Modes
234
common_
TMonly
All Modes
234
Maintenance Period
common_
TMonly
All Modes
235
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance.
30
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
235
31
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
235
32
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
235
Closed: Speed limit has been reached while using Torque Control.
33
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
235
All Modes
37
38
Drive Enabled
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being performed).
common_
TMonly
All Modes
235
235
Closed: Multi-function input set for Drive enable is closed (H1- = 6A)
39
common_
TMonly
All Modes
235
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
common_
TMonly
All Modes
3C
LOCAL/REMOTE Status
3D
Open: REMOTE
Closed: LOCAL
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
235
236
common_
TMonly
All Modes
236
common_
TMonly
All Modes
236
common_
TMonly
All Modes
236
4B
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
236
common_
TMonly
All Modes
236
Closed: A Fast Stop command has been entered from the operator or input terminals.
4D
common_
TMonly
All Modes
236
common_
TMonly
All Modes
236
Parameter List
4E
common_
TMonly
All Modes
236
common_
TMonly
All Modes
236
61
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
236
Closed: Drive has successfully detected the rotor position of the PM motor.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
437
Function
90 to 92
Description
Page
common_
TMonly
All Modes
236
All Modes
100 to 192
236
Name
H3-01
(410H)
H3-02
(434H)
H3-03
(411H)
Description
All Modes
Setting
Default: 0
Min: 0
Max: 1
237
common_
TMonly
Default: 0
Min: 0
Max: 31
237
common_
TMonly
Default: 100.0%
Min: -999.9%
Max: 999.9%
237
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
237
common_
TMonly
Default: 0
Min: 0
Max: 1
238
common_
TMonly
Default: 2
Min: 0
Max: 31
238
common_
TMonly
Default: 100.0%
Min: -999.9%
Max: 999.9%
239
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
239
Default: 2
Min: 0
Max: 3
239
common_
TMonly
Default: 0
Min: 0
Max: 31
239
common_
TMonly
Default: 100.0%
Min: -999.9%
Max: 999.9%
239
0: 0 to 10 V
1: 10 to 10 V
All Modes
Sets the function of terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
H3-04
(412H)
All Modes
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
H3-05
(413H)
H3-06
(414H)
H3-07
(415H)
All Modes
0: 0 to 10 V
1: 10 to 10 V
All Modes
Sets the function of terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3.
H3-08
(416H)
All Modes
Sets the level of the input value selected in H3-06 when 0 V is input at terminal A3.
common_
TMonly
All Modes
H3-09
(417H)
H3-10
(418H)
H3-11
(419H)
0: 0 to 10 V
1: 10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
All Modes
Sets the function of terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at terminal A2.
H3-12
(41AH)
H3-13
(41BH)
H3-14
(41CH)
438
Page
common_
TMonly
Default: 0.0%
Min: -999.9%
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2. Max: 999.9%
239
Default: 0.03 s
Min: 0.00 s
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used for noise filtering. Max: 2.00 s
239
common_
TMonly
All Modes
All Modes
common_
TMonly
All Modes
common_
TMonly
Determines which of the analog input terminals will be enabled when a digital input
programmed for Analog input enable (H1- = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 7
Min: 1
Max: 7
240
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Function
Frequency Bias
Description
Page
common_
TMonly
All Modes
240
Frequency Gain
common_
TMonly
All Modes
240
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100 to 0%.
2
common_
TMonly
All Modes
240
All Modes
240
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
241
common_
TMonly
All Modes
241
10 V = 100%
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
241
All Modes
7
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
241
241
common_
TMonly
All Modes
241
PID Feedback
common_
TMonly
All Modes
242
10 V = 100%
C
PID Setpoint
common_
TMonly
All Modes
242
10 V = 100%
D
Frequency Bias
common_
TMonly
All Modes
242
common_
TMonly
All Modes
242
10 V = 100%
F
Through Mode
common_
TMonly
All Modes
242
Set this value when using the terminal in the pass-through mode.
10
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
242
11
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
242
12
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
242
13
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Parameter List
242
14
Torque Compensation
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
242
15
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
B
common_
TMonly
242
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
439
Function
Description
Page
common_
TMonly
All Modes
242
10 V = 100%
1F
common_
TMonly
All Modes
Through Mode
242
Set this value when using the terminal in the pass-through mode.
30 to 32
common_
TMonly
All Modes
242
H4-03
(41FH)
Name
Multi-Function Analog Output
Terminal FM Monitor Selection
Description
All Modes
Default: 102
Min: 000
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U-. For example, enter 103 Max: 999
for U1-03.
common_
TMonly
All Modes
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
common_
TMonly
All Modes
Sets the bias value added to the terminal FM output signal.
H4-05
(421H)
H4-06
(422H)
H4-07
(423H)
H4-08
(424H)
Page
242
Default: 100.0%
Min: -999.9%
Max: 999.9%
243
Default: 0.0%
Min: -999.9%
Max: 999.9%
243
common_
TMonly
All Modes
H4-04
(420H)
Setting
common_
TMonly
Default: 103
Min: 000
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U-. For example, enter 103 Max: 999
for U1-03.
Default: 50.0%
Min: -999.9%
Max: 999.9%
243
common_
TMonly
Default: 0.0%
Min: -999.9%
Max: 999.9%
243
common_
TMonly
Default: 0
Min: 0
Max: 1
244
common_
TMonly
Default: 0
Min: 0
Max: 1
244
common_
TMonly
All Modes
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
All Modes
Sets the bias value added to the terminal AM output signal.
All Modes
0: 0 to 10 V
1: 10 to 10 V
All Modes
242
0: 0 to 10 V
1: 10 to 10 V
Name
Drive Node Address
<32>
Description
Default: 1F
All Modes
Min: 0
Selects drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-.
Max: FFH
Cycle power for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
common_
TMonly
All Modes
H5-03
(427H)
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
All Modes
H5-04
(428H)
440
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
Page
492
common_
TMonly
All Modes
H5-02
(426H)
Setting
common_
TMonly
common_
TMonly
Default: 3
Min: 0
Max: 8
492
Default: 0
Min: 0
Max: 2
492
Default: 0
Min: 0
Max: 3
492
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
Setting
Default: 0
Min: 0
Max: 1
493
common_
TMonly
Default: 5 ms
Min: 5 ms
Max: 65 ms
493
common_
TMonly
Default: 1
Min: 0
Max: 1
493
common_
TMonly
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
493
common_
TMonly
Default: 0
Min: 0
Max: 1
493
common_
Default: 1
Min: 0
Max: 1
494
Default: 0
Min: 0
Max: 1
494
H5-05
(429H)
H5-06
(42AH)
H5-07
(42BH)
H5-09
(435H)
CE Detection Time
H5-10
(436H)
H5-11
(43CH)
All Modes
TMonly
Communications ENTER Function
Selection
0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command (same as V7).
H5-12
(43DH)
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
All Modes
Set the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Sets the time required to detect a communications error. Adjustment may be needed when
networking several drives.
All Modes
0: 0.1 V units
1: 1 V units
common_
TMonly
All Modes
Page
common_
TMonly
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
<32> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
Name
Description
All Modes
H6-01
(42CH)
H6-02
(42DH)
H6-03
(42EH)
H6-04
(42FH)
Setting
common_
TMonly
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1 in V/f Control)
Default: 1440 Hz
Min: 1000 Hz
Sets the terminal RP input signal frequency that is equal to 100% of the value selected in H6-01. Max: 32000 Hz
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
All Modes
H6-07
(432H)
common_
TMonly
Default: 0.0%
Min: -100.0%
Max: 100.0%
245
common_
TMonly
Default: 0.10 s
Min: 0.00 s
Max: 2.00 s
245
All Modes
common_
TMonly
Default: 102
Min: 000
Max: 809
246
common_
TMonly
Default: 1440 Hz
Min: 0 Hz
Max: 32000 Hz
246
Default: 0.5 Hz
Min: 0.1 Hz
Max: 1000.0 Hz
246
Select the pulse train monitor output function (value of the - part of U-).
Example: To select U5-01, set 501.
All Modes
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the monitor value is 100%. To have the
pulse train monitor output equal the output frequency, set H6-06 to 2 and H6-07 to 0.
All Modes
common_
TMonly
Sets the minimum frequency for the pulse train input to be detected. Enabled when H6-01 = 0,
1, or 2.
Parameter List
H6-08
(43FH)
245
245
244
Default: 100.0%
Min: 0.0%
Max: 1000.0%
Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is
input.
Default: 0
Min: 0
Max: 3
Page
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
441
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, torque limits, and other types of hardware protection.
L1: Motor Protection
No. (Addr.)
Name
Description
Setting
All Modes
L1-01
(480H)
L1-02
(481H)
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
4: PM motor with variable torque
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when multiple motors are used, even if
overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
common_
TMonly
All Modes
Sets the motor thermal overload protection (oL1) time.
L1-05
(484H)
L1-13
(46DH)
Continuous Electrothermal
Operation Selection
247
249
Sets operation when the motor temperature analog input (H3-02, H3-06, or H3-10 = E) exceeds
Default: 3
the oH3 alarm level.
Min: 0
0: Ramp to stop
Max: 3
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (oH3 will flash)
251
common_
TMonly
All Modes
L1-04
(483H)
Default: <10>
Min: 0
Max: 6
common_
TMonly
All Modes
L1-03
(482H)
Page
common_
TMonly
Sets stopping method when the motor temperature analog input (H3-02, H3-06, or H3-10 = E)
exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
common_
TMonly
All Modes
Adjusts the filter for the motor temperature analog input (H3-02, H3-06, or H3-10 = E).
common_
TMonly
All Modes
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 2
251
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
251
Default: 1
Min: 0
Max: 1
251
Name
Description
Setting
All Modes
L2-01
(485H)
L2-02
(486H)
257
Default: <9>
Min: 0.1 s
Max: 5.0 s
257
Default: <9>
Min: 0.0 s
Max: 5.0 s
257
common_
TMonly
257
common_
TMonly
Default: 0.00 s
Min: 0.00 s
Max: 6000.0 s <12>
257
Default: 0.00 s
Min: 0.00 s
Sets the time to accelerate to the frequency reference when momentary power loss is over. If set
Max: 6000.0 s <12>
to 0.0, the active acceleration time is used.
258
Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.
common_
TMonly
L2-03
(487H)
Momentary Power Loss Minimum Sets the minimum wait time for residual motor voltage decay before the drive output
Baseblock Time
reenergizes after performing Power Loss Ride-Thru.
Increasing the time set to L2-03 may help if overcurrent or overvoltage occur during Speed
Search or during DC Injection Braking.
L2-04
(488H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time for the output voltage to return to the preset V/f pattern during Speed Search.
Undervoltage Detection Level
(Uv)
L2-06
(48AH)
L2-07
(48BH)
442
252
Default: <9>
Min: 0.0 s
Max: 25.5 s
common_
TMonly
All Modes
All Modes
L2-05
(489H)
Page
common_
TMonly
All Modes
Sets the DC bus undervoltage trip level.
All Modes
Sets the time required to decelerate from the speed when KEB was activated to zero speed.
All Modes
common_
TMonly
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
L2-08
(48CH)
L2-10
(48EH)
L2-11
(461H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
Sets the percentage of output frequency reduction at the beginning of deceleration when the
KEB Ride-Thru function is started.
Reduction = (slip frequency before KEB) L2-08 2
common_
TMonly
All Modes
Sets the time to perform KEB Ride-Thru.
common_
TMonly
All Modes
Sets the desired value of the DC bus voltage during KEB Ride-Thru.
common_
TMonly
All Modes
L2-29
(475H)
common_
TMonly
Page
Default: 100%
Min: 0%
Max: 300%
258
Default: 50 ms
Min: 0 ms
Max: 2000 ms
258
258
Default: 0
Min: 0
Max: 3
258
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
<12> Setting range value is dependent on the units selected for the accel/decel time (C1-10). When C1-10 = 0 (units of 0.01 s), the setting range
becomes 0.00 to 600.00 s.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<33> Default setting value is dependent on the setting for the input voltage (E1-01).
L3-01
(48FH)
L3-02
(490H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 1
Min: 0
Max: 2
259
common_
TMonly
Default: <35>
Min: 0%
Max: 150% <35>
260
common_
TMonly
Default: 50%
Min: 0%
Max: 100%
260
0: Disabled.
1: General purpose. Acceleration is paused as long as the current is above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the L3-02 level.
Note: Setting 2 is not available when using OLV/PM.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
L3-03
(491H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets Stall Prevention lower limit during acceleration when operating in the constant power
range. Set as a percentage of the drives rated current.
common_
TMonly
All Modes
L3-04
(492H)
L3-05
(493H)
L3-06
(494H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
262
Default: <35>
Min: 30%
Max: 150% <35>
262
Default: 0
Min: 0
Max: 1
263
common_
TMonly
263
common_
TMonly
Default: <10>
Min: 0.00
Max: 5.00
263
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss.
1: Decel time 1. Uses the deceleration time set to C1-02 while Stall Prevention is performed.
2: Decel time 2. Uses the deceleration time set to C1-04 while Stall Prevention is performed.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
All Modes
common_
TMonly
common_
TMonly
L3-11
(4C7H)
Overvoltage Suppression Function Enables or disables the ov suppression function, which allows the drive to change the output
Selection
frequency as the load changes to prevent an ov fault.
0: Disabled
1: Enabled
L3-17
(462H)
L3-20
(465H)
All Modes
Sets the proportional gain for KEB Ride-Thru, Stall Prevention, and overvoltage suppression.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
261
Default: 1
Min: 0
Max: 2
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current.
<18>
Page
Parameter List
No. (Addr.)
443
Name
Description
Setting
common_
TMonly
All Modes
L3-21
(466H)
L3-22
(4F9H)
Sets the proportional gain used to calculate the deceleration rate during KEB Ride-Thru, ov
suppression function, and Stall Prevention during deceleration (L3-04 = 2).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the deceleration time used for Stall Prevention during acceleration in OLV/PM.
264
Default: 0.0 s
Min: 0.0 s
Max: 6000 s
260
L3-23
(4FDH)
V/f w/PG
V/f
OLV
CLV
common_
TMonly
Default: 0
OLV/PM
AOLV/PM
CLV/PM
Automatic Reduction Selection for
Min: 0
Stall Prevention during Run
0: Sets the Stall Prevention level set in L3-06 that is used throughout the entire frequency range. Max: 1
1: Automatic Stall Prevention level reduction in the constant output range. The lower limit
value is 40% of L3-06.
L3-24
(46EH)
L3-25
(46FH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
264
common_
TMonly
Default: 1.0
Min: 1.0
Max: 1000.0
264
Default: 0 F
Min: 0 F
When DC bus capacitors have been added externally, be sure to add those values to the internal
Max: 65000 F
capacitor table for proper DC bus calculations.
All Modes
L3-26
(455H)
L3-27
(456H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
262
common_
TMonly
Sets the time needed to accelerate the uncoupled motor at rated torque from stop to the
maximum frequency.
OLV/PM
Page
Default: 1.00
Min: 0.10
Max: 10.00
common_
TMonly
Sets the time the current must exceed the Stall Prevention level to activate Stall Prevention.
Default: 50 ms
Min: 0 ms
Max: 5000 ms
265
265
Name
Speed Agreement Detection Level
Description
Setting
265
Default: <10>
Min: 0.0 Hz
Max: 20.0 Hz
265
Default: 0.0 Hz
Min: -400.0 Hz
Max: 400.0 Hz
265
Default: <10>
Min: 0.0 Hz
Max: 20.0 Hz
265
common_
TMonly
Default: 0
Min: 0
Max: 1
265
common_
TMonly
Default: 80%
Min: 0.0%
Max: 100.0%
266
common_
TMonly
Default: 0
Min: 0
Max: 1
266
common_
TMonly
All Modes
L4-01 sets the frequency detection level for digital output functions H2- = 2, 3, 4, 5.
Speed Agreement Detection Width L4-02 sets the hysteresis or allowable margin for speed detection.
L4-03
(49BH)
L4-04
(49CH)
L4-03 sets the frequency detection level for digital output functions H2- = 13, 14, 15, 16.
Speed Agreement Detection Width L4-04 sets the hysteresis or allowable margin for speed detection.
(+/-)
L4-05
(49DH)
L4-06
(4C2H)
L4-07
(470H)
common_
TMonly
All Modes
All Modes
0: Stop. Drive stops when the frequency reference is lost.
1: Run. Drive runs at a reduced speed when the frequency reference is lost.
All Modes
Sets the percentage of the frequency reference that the drive should run with when the
frequency reference is lost.
All Modes
0: No detection during baseblock.
1: Detection always enabled.
Page
Default: 0.0 Hz
Min: 0.0 Hz
Max: 400.0 Hz
444
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
L5-01
(49EH)
L5-02
(49FH)
L5-04
(46CH)
Description
All Modes
All Modes
267
common_
TMonly
Default: 0
Min: 0
Max: 1
267
common_
TMonly
Default: 10.0 s
Min: 0.5 s
Max: 600.0 s
267
Default: 0
Min: 0
Max: 1
267
All Modes
Sets the amount of time to wait between performing fault restarts.
Page
Default: 0
Min: 0
Max: 10
Sets the number of times the drive may attempt to restart after the following faults occur: GF,
LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1.
common_
TMonly
All Modes
L5-05
(467H)
Setting
common_
TMonly
Description
All Modes
L6-01
(4A1H)
L6-02
(4A2H)
L6-03
(4A3H)
0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
All Modes
All Modes
268
common_
TMonly
Default: 150%
Min: 0%
Max: 300%
269
common_
TMonly
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
269
Default: 0
Min: 0
Max: 8
268
common_
TMonly
Default: 150%
Min: 0%
Max: 300%
269
common_
TMonly
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
269
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 1.
L6-04
(4A4H)
L6-05
(4A5H)
L6-06
(4A6H)
common_
TMonly
0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4 fault
4: oL4 detection always active during run, output shuts down on an oL4 fault
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
All Modes
Sets the overtorque and undertorque detection level.
All Modes
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 2.
All Modes
L6-08
(468H)
L6-09
(469H)
L6-10
(46AH)
common_
TMonly
This function can detect an overtorque or undertorque in a certain speed range as a result of
machine fatigue. It is triggered by a specified operation time and uses the oL1 detection settings
(L6-01 and L6-03)
0: Mechanical Weakening Detection disabled.
Default: 0
1: Continue running (alarm only). Detected when the speed (signed) is greater than L6-09.
Min: 0
2: Continue running (alarm only). Detected when the speed (not signed) is greater than L6-09.
Max: 8
3: Interrupt drive output (fault). Detected when the speed (signed) is greater than L6-09.
4: Interrupt drive output (fault). Detected when the speed (not signed) is greater than L6-09.
5: Continue running (alarm only). Detected when the speed (signed) is less than L6-09.
6: Continue running (alarm only). Detected when the speed (not signed) is less than L6-09.
7: Interrupt drive output (fault). Detected when the speed (signed) is less than L6-09.
8: Interrupt drive output (fault). Detected when the speed (not signed) is less than L6-09.
All Modes
Default: 110.0%
Min: -110.0%
Max: 110.0%
270
common_
TMonly
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
270
Default: 0
Min: 0
Max: 65535
270
Sets the time mechanical weakening has to be detected before an alarm or fault is triggered.
All Modes
common_
TMonly
Sets the operation time (U1-04) required before Mechanical Weakening Detection is active.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
269
common_
TMonly
Sets the speed that triggers Mechanical Weakening Detection. When L6-08 is set for an
unsigned value, the absolute value is used if the setting is negative.
All Modes
Page
Default: 0
Min: 0
Max: 8
All Modes
L6-11
(46BH)
Setting
common_
TMonly
Parameter List
No. (Addr.)
445
Name
Forward Torque Limit
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants
can be set.
L7-02
(4A8H)
L7-03
(4A9H)
Output Torque
Positive Torque
L7-01
L7-04
Motor
r/min
Regeneration
REV
FWD
Page
Default: 200%
Min: 0%
Max: 300%
271
Default: 200%
Min: 0%
Max: 300%
271
Default: 200%
Min: 0%
Max: 300%
271
Default: 200%
Min: 0%
Max: 300%
271
Default: 200 ms
Min: 5 ms
Max: 10000 ms
271
Default: 0
Min: 0
Max: 1
271
Regeneration
L7-04
(4AAH)
L7-06
(4ACH)
L7-03
L7-02
Negative Torque
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
L7-07
(4C9H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Proportional control (changes to integral control at constant speed). Use this setting when
acceleration to the desired speed should take precedence over the torque limit.
1: Integral control. Set L7-07 to 1 if the torque limit should take precedence.
Name
Description
All Modes
All Modes
L8-07
(4B3H)
L8-09
(4B5H)
L8-10
(4B6H)
L8-11
(4B7H)
L8-12
(4B8H)
L8-15
(4BBH)
446
272
common_
TMonly
Default: <9>
Min: 50C
Max: 130C
272
Default: 3
Min: 0
Max: 4
272
Default: <43>
Min: 0
Max: 1
273
Default: 0
Min: 0
Max: 2
274
common_
TMonly
Default: <9>
Min: 0
Max: 1
274
common_
TMonly
Default: 0
Min: 0
Max: 1
274
common_
TMonly
All Modes
L8-05
(4B1H)
Page
Default: 0
Min: 0
Max: 1
An overheat alarm will occur if the heatsink temperature exceeds the level set in L8-02.
All Modes
L8-03
(4AFH)
Setting
common_
TMonly
Selects the detection of input current phase loss, power supply voltage imbalance, or main
circuit electrolytic capacitor deterioration.
0: Disabled
1: Enabled
common_
TMonly
All Modes
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
All Modes
0: Disabled
1: Enabled
All Modes
0: During run only. Fan operates only during run and for L8-11 seconds after stop.
1: Fan always on. Cooling fan operates whenever the drive is powered up.
Default: 60 s
Min: 0 s
Sets a delay time to shut off the cooling fan after the Run command is removed when L8-10 = 0. Max: 300 s
All Modes
common_
TMonly
All Modes
common_
TMonly
Default: 40C
Min: -10C
Max: 50C
274
common_
TMonly
Default: 1
Min: 0
Max: 1
275
Enter the ambient temperature. This value adjusts the oL2 detection level.
All Modes
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.
274
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
L8-18
(4BEH)
L8-19
(4BFH)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
L8-27
(4DDH)
L8-29
(4DFH)
Default: 0
Min: 0
Max: 1
275
common_
TMonly
Default: 0.8
Min: 0.1
Max: 0.9
273
Specifies the frequency reference reduction gain at overheat pre-alarm when L8-03 = 4.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
L8-38
(4EFH)
L8-40
(4F1H)
L8-41
(4F2H)
L8-55
(45FH)
common_
TMonly
Default: 300.0%
Min: 0.0%
Sets the gain for overcurrent detection as a percentage of the motor rated current. Overcurrent is Max: 300.0%
detected using the drives overcurrent level or the value set to L8-27, whichever is lower.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
275
Default: 1
Min: 0
Max: 1
275
276
Default: <16>
Min: 0
Max: 2
276
Default: <10>
Min: 0.00 s
Max: 2.00 s
276
Default: 0
Min: 0
Max: 1
276
Default: 1
Min: 0
0: Disabled. L8-55 should be disabled when using a regen converter or an optional braking unit.
Max: 1
1: Protection enabled.
277
0: Disabled
1: Enabled
common_
TMonly
All Modes
L8-35
(4ECH)
common_
TMonly
0: Disabled
1: Enabled
All Modes
Page
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time that the drive continues running with reduced carrier frequency after the carrier
reduction condition is gone. Setting 0.00 s disables the carrier frequency reduction time.
common_
TMonly
All Modes
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150% of the drives rated current.
common_
TMonly
All Modes
<3> Parameter setting value is not reset to the default value when the drive is initialized.
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
<10> Default setting is determined by the control mode (A1-02).
<16> Default setting is determined by the control mode (A1-02) and the drive model (o2-04).
<43> Regional default settings
Setting 0: Japan (Model code: CIMR-AAA) and Asia (Model code: CIMR-ATA)
Setting 1: China (Model code: CIMR-ABA)
n: Special Adjustment
The n parameters are used to adjust more advanced performance characteristics such as Hunting Prevention, speed
feedback detection, High Slip Braking, and Online Tuning for motor line-to-line resistance.
n1: Hunting Prevention
Name
n1-01
(580H)
n1-02
(581H)
n1-03
(582H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 1
Min: 0
Max: 1
278
common_
TMonly
Default: 1.00
Min: 0.00
Max: 2.50
278
Default: <6>
Min: 0 ms
Max: 500 ms
278
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
If the motor vibrates while lightly loaded, increase the gain by 0.1 until vibration ceases. If the
motor stalls, decrease the gain by 0.1 until the stalling ceases.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
CLV
Page
common_
TMonly
Parameter List
No. (Addr.)
447
n1-05
(530H)
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 0.00
Min: 0.00
Sets the gain used for Hunting Prevention. If set to 0, the gain set to n1-02 is used for operation Max: 2.50
in reverse.
Page
278
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 1.00
Min: 0.00
Max: 10.00
279
common_
TMonly
Default: 50 ms
Min: 0 ms
Max: 2000 ms
279
common_
TMonly
Default: 750 ms
Min: 0 ms
Max: 2000 ms
279
n2-01
(584H)
n2-02
(585H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the time constant used for speed feedback detection control (AFR).
n2-03
(586H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
Sets the AFR time constant to be used during Speed Search and during regen.
Name
n3-01
(588H)
n3-02
(589H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 5%
Min: 1%
Max: 20%
279
common_
TMonly
Default: <35>
Min: 100%
Max: 200%
280
common_
TMonly
Default: 1.0 s
Min: 0.0 s
Max: 10.0 s
280
Default: 40 s
Min: 30 s
Max: 1200 s
280
Default: 1.10
Min: 1.00
Max: 1.40
281
Default: 0
Min: 0
Max: 1
281
Sets the output frequency reduction step width for when the drive stops the motor using HSB.
Set as a percentage of the maximum output frequency. Increase this setting if overvoltage
occurs during HSB.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the current limit during HSB as a percentage of the motor rated current.
n3-03
(58AH)
n3-04
(58BH)
n3-13
(531H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the time the drive will run with minimum frequency (E1-09) at the end of deceleration.
If this time is set too low, the machine inertia can cause the motor to rotate slightly after HSB.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time required for an HSB overload fault (oL7) to occur when the drive output
frequency does not change during an HSB stop. This parameter does not typically require
adjustment.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the gain applied to the V/f pattern during Overexcitation Deceleration (L3-04 = 4).
n3-14
(532H)
n3-21
(579H)
n3-23
(57BH)
Overexcitation Operation
Selection
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
CLV
common_
TMonly
Default: 100%
Min: 0%
Sets output current level at which the drive will start reducing the overexcitation gain in order to Max: 150%
prevent a too high motor slip during Overexcitation Deceleration. Set as a percentage of the
drive rated current.
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
common_
TMonly
Default: 0
Min: 0
Max: 2
281
281
<35> The upper limit of the setting range is determined by the values set to duty selection (C6-01) and the carrier frequency reduction selection (L8-38).
448
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
n5-01
(5B0H)
n5-02
(5B1H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Default: 0
Min: 0
Max: 1
282
common_
TMonly
282
Default: 1.00
Min: 0.00
Max: 100.00
283
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the time required to accelerate the motor at the rated torque from stop to rated speed.
n5-03
(5B2H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
common_
TMonly
Sets the ratio between motor and load inertia. Lower this setting if overshoot occurs at the end
of acceleration.
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
Name
n6-01
(570H)
n6-05
(5C7H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
0: Disabled
1: Line-to-line resistance tuning
2: Voltage correction. Setting not possible when Energy Saving is enabled (b8-01).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Decrease this setting for motors with a relatively large rotor time constant.
If overload occurs, increase this setting slowly in increments of 0.10.
Page
Default: 2
Min: 0
Max: 2
284
Default: 1.00
Min: 0.10
Max: 5.00
284
n8-01
(540H)
n8-02
(541H)
Name
n8-35
(562H)
n8-45
(538H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Sets the current used for initial rotor position estimation as a percentage of the motor rated
current (E5-03). If the motor nameplate lists an Si value, that value should be entered here.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Default: 80%
Min: 0%
Sets the current during initial polar attraction as a percentage of the motor rated current. Enter a Max: 150%
high value when attempting to increase starting torque.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Pull-in
1: High frequency injection
2: Pulse injection
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
n8-47
(53AH)
n8-48
(53BH)
Pull-In Current
n8-49
(53CH)
Default: 50%
Min: 0%
Max: 100%
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the time constant to make the pull-in current reference and actual current value agree.
Decrease the value if the motor begins to oscillate, and increase the value if it takes too long for
the current reference to equal the output current.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Defines the d-axis current reference during no-load operation at a constant speed. Set as a
percentage of the motor rated current. Increase this setting if hunting occurs while running at
constant speed.
V/f
V/f w/PG
OLV
CLV
common_
TMonly
284
284
Default: 1
Min: 0
Max: 2
284
Default: 0.80
Min: 0.00
Max: 10.00
285
Default: 5.0 s
Min: 0.0 s
Max: 100.0 s
285
Default: 30%
Min: 20%
Max: 200%
285
Default: <14>
OLV/PM
AOLV/PM
CLV/PM
Min: -200.0%
Sets the d-axis current reference when running a high load at constant speed. Set as a percentage Max: 0.0%
of the motor rated current.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Page
Parameter List
No. (Addr.)
B
285
449
Name
n8-51
(53EH)
Acceleration/Deceleration Pull-In
Current
n8-54
(56DH)
n8-55
(56EH)
Load Inertia
n8-57
(574H)
n8-62
(57DH)
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
285
Default: 1.00 s
Min: 0.00 s
Max: 10.00 s
286
Default: 0
Min: 0
Max: 3
286
Default: 0
Min: 0
Max: 1
286
Default: 200.0 V
Min: 0.0 V
Max: 230.0 V
286
common_
TMonly
Default: 1.50
Min: 0.00
Max: 10.00
286
Setting
Page
common_
TMonly
287
Default: 1
Min: 1
Max: 5
287
Sets the d-axis current reference during acceleration/deceleration as a percentage of the motor
rated current. Set to a high value when more starting torque is needed.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Adjusts the value when hunting occurs at low speed. If hunting occurs with sudden load
changes, increase n8-54 in increments of 0.1. Reduce this setting if oscillation occurs at start.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Prevents output voltage saturation. Should be set just below the voltage provided by the input
power supply.
Speed Feedback Detection Control
Gain during ov Suppression
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
Default: 50%
Min: 0%
Max: 200%
For large inertia loads or to increase the speed control response, increase this setting. Too high
of a setting when driving a very light load or load with very low inertia can result in oscillation.
<18>
n8-65
(65CH)
Description
V/f
Sets the gain used for internal speed feedback detection during ov suppression
<14> Default setting value is dependent on the motor code set to E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Name
Drive Mode Unit Monitor
Selection
Description
All Modes
Selects the content of the last monitor that is shown when scrolling through Drive Mode
display. Enter the last three digits of the monitor parameter number to be displayed: U-.
common_
TMonly
All Modes
o1-02
(501H)
All Modes
o1-03
(502H)
Sets the units the drive should use to display the frequency reference and motor speed monitors. Default: <10>
Min: 0
Digital Operator Display Selection 0: 0.01 Hz
Max: 3
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
o1-04
(503H)
o1-10
(520H)
o1-11
(521H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0: Hz
1: r/min
common_
TMonly
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
287
Default: <10>
Min: 0
Max: 1
288
Default: <36>
Min: 1
Max: 60000
288
Default: <36>
Min: 0
Max: 3
288
450
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Description
All Modes
o2-01
(505H)
o2-02
(506H)
Setting
Default: 1
Min: 0
Max: 1
288
common_
TMonly
Default: 1
Min: 0
Max: 1
289
Default: 0
Min: 0
Max: 2
289
Default: Determined by
drive capacity
Min:
Max:
289
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
common_
TMonly
All Modes
o2-03
(507H)
o2-04
(508H)
o2-05
(509H)
o2-06
(50AH)
o2-07
(527H)
All Modes
Motor Direction at Power Up when
0: Forward
Using Operator
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
o2-09
(50DH)
Reserved
0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
common_
TMonly
All Modes
Page
common_
TMonly
Enter the drive model. Setting required only if installing a new control board.
common_
TMonly
All Modes
Default: 0
0: ENTER key must be pressed to enter a frequency reference.
Min: 0
1: ENTER key is not required. The frequency reference can be adjusted using the up and down Max: 1
arrow keys only.
common_
TMonly
All Modes
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
common_
TMonly
289
Default: 0
Min: 0
Max: 1
290
Default: 0
Min: 0
Max: 1
290
Setting
Page
Name
Description
common_
TMonly
All Modes
o3-01
(515H)
o3-02
(516H)
Default: 0
Min: 0
Max: 3
290
common_
TMonly
Default: 0
Min: 0
Max: 1
290
common_
TMonly
Default: 0 h
Min: 0 h
Max: 9999 h
291
common_
TMonly
Default: 0
Min: 0
Max: 1
291
common_
TMonly
Default: 0 h
Min: 0 h
Max: 9999 h
291
common_
TMonly
Default: 0%
Min: 0%
Max: 150%
291
291
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved on the operator.
All Modes
0: Read operation prohibited
1: Read operation allowed
Name
Description
Setting
o4-01
(50BH)
o4-02
(50CH)
o4-03
(50EH)
o4-05
(51DH)
o4-07
(523H)
All Modes
Default: 0%
TMonly
Sets the value of the Maintenance Monitor for the soft charge bypass relay. See U4-06 to check Min: 0%
Max: 150%
when the bypass relay may need to be replaced.
o4-09
(525H)
Default: 0%
Min: 0%
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 to check when the IGBTs
Max: 150%
may need to be replaced.
All Modes
Sets the value for the cumulative operation time of the drive in units of 10 h.
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
All Modes
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
All Modes
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to check when the
capacitors may need to be replaced.
Page
o4-11
(510H)
All Modes
All Modes
U2, U3 Initialization
0: U2- and U3- monitor data is not reset when the drive is initialized (A1-03).
1: U2- and U3- monitor data is reset when the drive is initialized (A1-03).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
common_
TMonly
common_
TMonly
Default: 0
Min: 0
Max: 1
Parameter List
common_
292
B
292
451
Name
Description
Setting
All Modes
o4-12
(512H)
o4-13
(528H)
Default: 0
Min: 0
Max: 1
292
common_
TMonly
Default: 0
Min: 0
Max: 1
292
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
All Modes
Page
common_
TMonly
0: Number of Run commands counter is not reset when the drive is initialized (A1-03).
1: Number of Run commands counter is reset when the drive is initialized (A1-03).
q: DriveWorksEZ Parameters
No. (Addr.)
Name
q1-01 to q6-07
(1600H to
DriveWorksEZ Parameters
1746H)
Description
Setting
common_
TMonly
All Modes
Reserved for DriveWorksEZ
Page
292
Name
r1-01 to
r1-40
(1840H to
1867H)
DriveWorksEZ Connection
Parameters 1 to 20 (upper/lower)
Description
Setting
common_
TMonly
All Modes
DriveWorksEZ Connection Parameters 1 to 20 (upper/lower)
Default: 0
Min: 0
Max: FFFFH
Page
292
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
T1: Induction Motor Auto-Tuning
No. (Addr.)
T1-00
(700H)
T1-01
(701H)
Name
T1-03
(703H)
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: Rotational Auto-Tuning
Default: 0
1: Stationary Auto-Tuning 1
Min: 0
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation Max: 4, 8, 9 <10>
Speed Search)
4: Stationary Auto-Tuning 2
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-Tuning)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Default: 200.0 V
Min: 0.0 V
Max: 255.0 V
119
Default: <6>
Min: 10% of drive rated
current
Max: 200% of drive
rated current
120
common_
TMonly
Default: <46>
Min: 0.0 Hz
Max: 400.0 Hz
120
common_
TMonly
Default: 4
Min: 2
Max: 48
120
common_
TMonly
Default: <47>
Min: 0 r/min
Max: 24000 r/min
120
common_
TMonly
common_
TMonly
Sets the rated frequency of the motor as specified on the motor nameplate.
T1-06
(706H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the rated speed of the motor as specified on the motor nameplate.
452
119
119
119
Default: <6>
Min: 0.00 kW
Max: 650.00 kW
Default: 1
Min: 1
Max: 2
Page
common_
TMonly
<18>
T1-04
(704H)
V/f
OLV/PM
Setting
<37>
T1-02
(702H)
Description
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
PG Number of Pulses Per
Revolution
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
T1-09
(709H)
T1-10
(70AH)
T1-11
(70BH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is cycled. If T1-02 is changed, a
default value appropriate for the motor capacity that was entered will appear.
Page
Default: <45>
Min: 0 ppr
Max: 60000 ppr
120
Default:
Min: 0 A
Max: T1-04
120
Default:
Min: 0.00 Hz
Max: 20.00 Hz
121
Default: 14 W <38>
Min: 0 W
Max: 65535 W
121
T2-01
(750H)
Name
T2-02
(751H)
T2-03
(752H)
PM Motor Type
T2-04
(730H)
T2-05
(732H)
<18>
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
AOLV/PM
CLV/PM
CLV
121
common_
TMonly
Default: 1
Min: 0
Max: 1
121
common_
TMonly
Default: <6>
Min: 0.00 kW
Max: 650.00 kW
122
Default: 200.0 V
Min: 0.0 V
Max: 255.0 V
122
0: IPM motor
1: SPM motor. Parameter T2-17 will not be displayed with this setting.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
121
Default: <16>
Min: 0000
Max: FFFF
Enter the motor code when using a Yaskawa PM motor. Once the motor code is entered, the
drive automatically sets parameters T2-03 through T2-14. When using a motor that is not
supported motor code or a non-Yaskawa motor, set FFFF here and then adjust the other T2
parameters according the motor nameplate or the motor test report.
OLV/PM
Page
common_
TMonly
Parameter List
No. (Addr.)
453
Name
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Setting
Page
Default: <6>
Min: 10% of drive rated
current
Max: 200% of drive
rated current
122
common_
TMonly
Default: 87.5 Hz
Min: 0.0 Hz
Max: 400.0 Hz
122
common_
TMonly
Default: 6
Min: 2
Max: 48
122
common_
TMonly
122
common_
TMonly
Default: <39>
Min: 0.000
Max: 65.000
122
common_
TMonly
Default: <39>
Min: 0.00 mH
Max: 600.00 mH
122
common_
TMonly
Default: <39>
Min: 0.00 mH
Max: 600.00 mH
123
common_
TMonly
Default: 1
Min: 0
Max: 1
123
common_
TMonly
Default: <39>
Min: 0.1
Max: 2000.0
123
Default: 30%
Min: 0%
Max: 120%
123
123
123
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the number of motor poles for the PM motor as indicated on the motor nameplate.
T2-09
(731H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the base speed for the PM motor as indicated on the motor nameplate.
T2-10
(754H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the rotor resistance for the PM motor as indicated on the motor nameplate.
T2-11
(735H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the d-axis inductance for the PM motor as indicated on the motor nameplate.
T2-12
(736H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the q-axis inductance for the PM motor as indicated on the motor nameplate.
T2-13
(755H)
T2-14
(737H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
0: mV/(r/min). E5-09 will automatically be set to 0.0, and E5-24 will be used.
1: mV/(rad/sec). E5-24 will automatically be set to 0.0, and E5-09 will be used
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Enter the induced voltage coefficient for the PM motor as indicated on the motor nameplate.
T2-15
(756H)
T2-16
(738H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the amount of pull-in current to use for Auto-Tuning as a percentage of the motor rated
current. Increase this setting for high inertia loads.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the number of pulses per revolution for the PG being used (pulse generator or encoder).
T2-17
(757H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the offset between encoder offset and the rotor magnetic axis.
Name
<40>
T3-02
(761H)
<40>
454
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
common_
TMonly
Sets the frequency of the test signal used during Inertia Tuning and ASR Gain Auto-Tuning.
Reduce this value if the inertia is large or if a fault occurs.
<40>
T3-03
(762H)
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Sets the amplitude of the test signal used during Inertia and ASR Gain Auto-Tuning. Reduce
this value if the inertia is too large or if a fault occurs.
Motor Inertia
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Sets the motor inertia. Default setting is the inertia of a Yaskawa motor.
common_
TMonly
Page
Default: 3.0 Hz
Min: 0.1 Hz
Max: 20.0 Hz
124
124
124
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
<40>
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Setting
CLV
Page
common_
TMonly
Default: 10.0 Hz
Min: 0.1 Hz
Sets the response frequency of the mechanical system connected to the motor. Oscillation may Max: 50.0 Hz
result if set too high.
124
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
<40> Displayed only when performing Inertia Tuning or ASR Gain Auto-Tuning (T1-01 = 9 or T2-01 = 9).
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
U1: Operation Status Monitors
No. (Addr.)
Name
U1-01
(40H)
Frequency Reference
U1-02
(41H)
Output Frequency
U1-03
(42H)
Output Current
Description
common_
TMonly
All Modes
Analog Output
Level
Unit
Page
10 V: Max frequency
0.01 Hz
10 V: Max frequency
0.01 Hz
10 V: Drive rated
current
<19> <50>
No signal output
available
All Modes
Displays the output frequency. Display units are determined by o1-03.
common_
TMonly
All Modes
Displays the output current.
common_
TMonly
All Modes
U1-04
(43H)
Control Method
U1-05
(44H)
Motor Speed
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
0.1 Vac
10 V: 400 V <18>
1 Vdc
common_
TMonly
10 V: Drive rated
power (kW)
<22>
common_
TMonly
10 V: Motor rated
torque
0.1%
No signal output
available
Displays the motor speed feedback. Display units are determined by o1-03.
U1-06
(45H)
U1-07
(46H)
DC Bus Voltage
U1-08
(47H)
Output Power
U1-09
(48H)
Torque Reference
common_
TMonly
All Modes
Displays the output voltage.
common_
TMonly
All Modes
Displays the DC bus voltage.
All Modes
Displays the output power (this value is calculated internally).
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
All Modes
Displays the input terminal status.
U1-10
(49H)
Parameter List
YEC_
common
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
455
Name
Analog Output
Level
Description
Unit
Page
No signal output
available
No signal output
available
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: 100%
0.1%
0.01 Hz
No signal output
available
No signal output
available
No signal output
available
10 V: 100%
0.1%
10 V: 100%
0.1%
common_
TMonly
All Modes
Displays the output terminal status.
YEC_
common
U1-11
(4AH)
Multi-Function
Digital Output
(terminal M1-M2)
Multi-Function
Photocoupler Output 1
(terminal P1) enabled
Multi-Function
Photocoupler Output 2
(terminal P2) enabled
Not Used
Fault Relay
(terminal MA-MC closed
MA-MC open)
common_
TMonly
All Modes
Verifies the drive operation status.
U1-12
(4BH)
Drive Status
YEC_
common
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
U1-13
(4EH)
U1-14
(4FH)
U1-15
(50H)
U1-16
(53H)
common_
TMonly
All Modes
Displays the signal level to analog input terminal A1.
common_
TMonly
All Modes
Displays the signal level to analog input terminal A2.
common_
TMonly
All Modes
Displays the signal level to analog input terminal A3.
common_
TMonly
All Modes
common_
TMonly
All Modes
U1-17
(58H)
U1-18
(61H)
10 V: Max frequency
Displays output frequency with ramp time and S-curves. Units determined by o1-03.
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
common_
TMonly
All Modes
Displays the parameter number that caused the oPE or Err (EEPROM write error) error.
common_
TMonly
All Modes
Displays the contents of a MEMOBUS/Modbus error.
U1-19
(66H)
MEMOBUS/Modbus Error
Code
YEC_
common
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
U1-21
(77H)
U1-22
(72AH)
456
common_
TMonly
All Modes
Displays the input voltage to terminal V1 on analog input card AI-A3.
common_
TMonly
All Modes
Displays the input voltage to terminal V2 on analog input card AI-A3.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
U1-23
(72BH)
U1-24
(7DH)
U1-25
(4DH)
U1-26
(5BH)
Analog Output
Level
Description
common_
TMonly
All Modes
Unit
Page
10 V: 100%
0.1%
Determined by H6-02
1 Hz
All Modes
Displays the frequency to pulse train input terminal RP.
All Modes
common_
TMonly
No signal output
available
common_
TMonly
No signal output
available
FLASH ID
All Modes
ROM ID
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 and Table A.3)
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
<22> The display resolution depends on the rated output power of the drive after the Drive Duty has been set in parameter C6-01. Drives with a
maximum output up to 11 kW will display this value in units of 0.01 kW (two decimal places). Drives with a maximum output greater than 11
kW will display this value in units of 0.1 kW (one decimal place). Refer to Model Number and Nameplate Check on page 31 for details.
<50> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
Name
U2-01
(80H)
Current Fault
U2-02
(81H)
Previous Fault
U2-03
(82H)
Frequency Reference at
Previous Fault
U2-04
(83H)
U2-05
(84H)
U2-06
(85H)
Analog Output
Level
Description
All Modes
No signal output
available
common_
TMonly
No signal output
available
common_
TMonly
No signal output
available
0.01 Hz
common_
TMonly
No signal output
available
0.01 Hz
common_
TMonly
No signal output
available
<19> <50>
common_
TMonly
No signal output
available
0.01 Hz
common_
TMonly
No signal output
available
0.1 Vac
common_
TMonly
No signal output
available
1 Vdc
common_
TMonly
No signal output
available
0.1 kW
common_
TMonly
No signal output
available
0.1%
common_
TMonly
No signal output
available
common_
TMonly
No signal output
available
No signal output
available
common_
TMonly
No signal output
available
1h
common_
TMonly
No signal output
available
0.01 Hz
common_
TMonly
No signal output
available
All Modes
Displays the frequency reference at the previous fault.
All Modes
Displays the output frequency at the previous fault.
All Modes
Displays the output current at the previous fault.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
Page
common_
TMonly
All Modes
Unit
U2-08
(87H)
U2-09
(88H)
U2-10
(89H)
All Modes
Displays the output voltage at the previous fault.
All Modes
Displays the DC bus voltage at the previous fault.
All Modes
Displays the output power at the previous fault.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
U2-11
(8AH)
U2-12
(8BH)
U2-13
(8CH)
U2-14
(8DH)
U2-15
(7E0H)
U2-16
(7E1H)
All Modes
Displays the input terminal status at the previous fault. Displayed as in U1-10.
All Modes
Displays the output status at the previous fault. Displays the same status displayed in U1-11.
common_
TMonly
All Modes
Displays the operation status of the drive at the previous fault. Displays the same status
displayed in U1-12.
All Modes
Displays the cumulative operation time at the previous fault.
All Modes
Displays the speed reference for the soft starter at the previous fault.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
B
0.10%
Displays the q-axis current for the motor at the previous fault.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Parameter List
457
Name
Motor d-Axis Current at
Previous Fault
Analog Output
Level
Description
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Unit
Page
No signal output
available
0.10%
No signal output
available
0.1 deg
No signal output
available
1C
Displays the d-axis current for the motor at the previous fault.
U2-19
(7ECH)
U2-20
(8EH)
Heatsink Temperature at
Previous Fault
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the degree of rotor deviation when the most recent fault occurred (same status will
appear as shown in U6-10).
common_
TMonly
All Modes
Displays the temperature of the heatsink when the most recent fault occurred.
<19> This value's number of decimal places depends on the drive model and the Heavy/Normal duty selection in parameter C6-01. The value will
have two decimal places (0.01 A) if the drive is set for a Maximum Applicable Motor Capacity up to 11 kW (refer to Table A.2 and Table A.3)
and one decimal place (0.1 A) if the set Maximum Applicable Motor Capacity is higher than 11 kW.
<50> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
Name
U3-01 to
U3-04
(90H to 93H
(800H to
803H))
common_
TMonly
All Modes
Displays the first to the fourth most recent faults.
U3-11 to
U3-14
(94H to 97H
(80AH to
80DH))
Unit
Page
No signal output
available
1h
No signal output
available
1h
Unit
Page
1h
1 Time
No signal output
available
1h
No signal output
available
1%
1%
No signal output
available
1%
No signal output
available
1%
10 V: 100C
1C
No signal output
available
common_
TMonly
All Modes
U3-05 to
U3-10
(804H to
809H)
U3-15 to
U3-20
(80EH to
813H)
Analog Output
Level
Description
All Modes
Displays the cumulative operation time when the first to the fourth most recent faults occurred.
common_
All Modes
Cumulative Operation Time at
TMonly
5th to 10th Most Recent Fault Displays the cumulative operation time when the fifth to the tenth most recent faults occurred.
Name
common_
TMonly
All Modes
U4-01
(4CH)
U4-02
(75H)
Displays the cumulative operation time of the drive. The value for the cumulative operation
No signal output
time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation available
time should start as soon as the power is switched on or only while the Run command is present.
The maximum number displayed is 99999, after which the value is reset to 0.
common_
TMonly
All Modes
No signal output
Displays the number of times the Run command is entered. Reset the number of Run commands available
using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535.
common_
TMonly
All Modes
U4-03
(67H)
U4-04
(7EH)
U4-05
(7CH)
Capacitor Maintenance
U4-06
(7D6H)
U4-07
(7D7H)
IGBT Maintenance
U4-08
(68H)
Heatsink Temperature
458
Analog Output
Level
Description
Displays the cumulative operation time of the cooling fan. The default value for the fan
operation time is reset in parameter o4-03. This value will reset to 0 and start counting again
after reaching 99999.
common_
TMonly
All Modes
Displays main cooling fan usage time in as a percentage of its expected performance life.
Parameter o4-03 can be used to reset this monitor.
common_
TMonly
All Modes
No signal output
Displays main circuit capacitor usage time in as a percentage of their expected performance life. available
Parameter o4-05 can be used to reset this monitor.
common_
TMonly
All Modes
Displays the soft charge bypass relay maintenance time as a percentage of its estimated
performance life. Parameter o4-07 can be used to reset this monitor.
common_
TMonly
All Modes
Displays IGBT usage time as a percentage of the expected performance life. Parameter o4-09
can be used to reset this monitor.
common_
TMonly
All Modes
Displays the heatsink temperature.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
U4-09
(5EH)
LED Check
U4-10
(5CH)
U4-11
(5DH)
U4-13
(7CFH)
U4-14
(7D0H)
U4-16
(7D8H)
Analog Output
Level
Description
All Modes
No signal output
available
common_
TMonly
No signal output
available
1 kWh
No signal output
available
1 MWh
Monitors the drive output power. The value is shown as a 9 digit number displayed across two
monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
All Modes
common_
TMonly
No signal output
available
common_
TMonly
No signal output
available
All Modes
U4-18
(7DAH)
U4-19
(7DBH)
U4-20
(7DCH)
No signal output
available
common_
TMonly
No signal output
available
0.01%
common_
TMonly
No signal output
available
No signal output
available
All Modes
U4-21
(7DDH)
U4-22
(7DEH)
MEMOBUS/Modbus
Communications Reference
U4-23
(7DFH)
common_
TMonly
All Modes
10 V: 100%
common_
TMonly
All Modes
common_
TMonly
No signal output
Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H available
as a four-digit hexadecimal number.
All Modes
Displays drive control data set by an option card as a four-digit hexadecimal number.
0.1%
common_
TMonly
All Modes
<50>
Shows the value of the motor overload detection accumulator. 100% is equal to the oL1
detection level.
All Modes
0.01 A
0.01 Hz
Displays the output frequency when the current value shown in U4-13 occurred.
All Modes
Page
common_
TMonly
Lights all segments of the LED to verify that the display is working properly.
All Modes
Unit
common_
TMonly
No signal output
available
<50> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
Parameter List
No. (Addr.)
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
459
Name
U5-01
(57H)
PID Feedback
U5-02
(63H)
PID Input
U5-03
(64H)
PID Output
U5-04
(65H)
PID Setpoint
U5-05
(7D2H)
U5-06
(7D3H)
Analog Output
Level
Description
common_
TMonly
All Modes
Unit
Page
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
0.01%
Unit
Page
0.1%
0.1%
10 V: Motor
secondary rated
current
0.01%
0.1 Vac
0.1 Vac
0.1%
0.1%
All Modes
Displays the amount of PID input (deviation between PID setpoint and feedback).
common_
TMonly
All Modes
Displays PID control output.
common_
TMonly
All Modes
Displays the PID setpoint.
common_
TMonly
All Modes
Displays the 2nd PID feedback value if differential feedback is used (H3- = 16).
common_
TMonly
All Modes
Displays the difference of both feedback values if differential feedback is used (U5-01 - U5-05).
If differential feedback is not used, then U5-01 and U5-06 will be the same.
Name
Motor Secondary Current (Iq)
U6-02
(52H)
U6-03
(54H)
ASR Input
U6-04
(55H)
ASR Output
U6-05
(59H)
Analog Output
Level
Description
10 V: Motor
All Modes
secondary rated
Displays the value of the motor secondary current (Iq). Motor rated secondary current is 100%. current
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the value calculated for the motor excitation current (Id). Motor rated secondary
current is 100%.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the input and output values when using ASR control.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
10 V: Motor
secondary rated
current
10 V: Max frequency
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the output value for current control relative to motor secondary current (q-axis).
U6-08
(60H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the output value for current control relative to motor secondary current (d-axis).
U6-09
(7C0H)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
10 V: 180 deg
10 V: 180 deg
0.1 deg
10 V: 180 deg
10 V: 180 deg
0.1 deg
common_
TMonly
10 V: 180 deg
10 V: 180 deg
0.1 deg
common_
TMonly
10 V: 180 deg
10 V: 180 deg
0.1 deg
10 V: 65536
1 pulse
Displays the degree of forward phase correction after calculating the deviation of cmp.
U6-10
(7C1H)
U6-13
(7CAH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
Displays the amount of deviation between the actual d-axis / q-axis and the -axis / -axis used
for motor control.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
460
common_
TMonly
All Modes
Monitors the number of pulses for speed detection (PG1).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
U6-19
(7E5H)
U6-20
(7D4H)
U6-21
(7D5H)
Offset Frequency
U6-22
(62H)
Analog Output
Level
Description
common_
TMonly
All Modes
10 V: 65536
Unit
Page
1 pulse
All Modes
10 V: Max frequency
0.1%
0.1%
All Modes
Displays the frequency added to the main frequency reference.
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
10 V: No. of pulses
per revolution
Displays how far the rotor has moved from its last position in PG pulses (multiplied by 4).
U6-25
(6BH)
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
common_
TMonly
10 V: Motor
secondary rated
current
0.01%
common_
TMonly
10 V: Motor
secondary rated
current
0.01%
Unit
Page
0.01%
V/f
V/f w/PG
OLV
OLV/PM
AOLV/PM
CLV/PM
CLV
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Name
DriveWorksEZ Custom
Monitor 1 to 10
U8-11 to
U8-13
(195AH to
195CH)
DriveWorksEZ Version
Control Monitor 1 to 3
All Modes
common_
TMonly
10 V: 100%
All Modes
DriveWorksEZ Version Control Monitor 1 to 3
common_
TMonly
No signal output
available
Parameter List
U8-01 to
U8-10
(1950H to
1959H)
Analog Output
Level
Description
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
461
Name
Setting Range
Resolution
0.0 to 10.0
OLV (2)
CLV (3)
0.1
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
0.00 to 10.00
0.01 s
0.50
0.50
0.50
0.50
0 to 1
0 to 200
1%
120
100
b2-01
b2-04
b3-01
b3-02
b3-14
0 to 1
b8-01
0 to 1
b8-02
0.0 to 10.0
0.1
0.7
1.0
0.01,
0.05
(Motor
Capacity:
55 kW and
above)
0.00 to 10.00
0.01 s
0.50,
2.00
(Motor
Capacity:
55 kW and
above)
C2-01
0.00 to 10.00
0.01 s
0.20
0.20
0.20
0.20
C3-01
0.0 to 2.5
0.1
0.0
1.0
1.0
C3-02
0 to 10000
1 ms
2000
200
C4-01
0.00 to 2.50
0.01
1.00
1.00
1.00
C4-02
0 to 10000
1 ms
200
200
20
C5-01
0.00 to 300.00
0.01
0.20
20.00
C5-02
0.000 to 10.000
0.001 s
0.200
0.500
C5-03
0.00 to 300.00
0.01
0.02
20.00
C5-04
0.000 to 10.000
0.001 s
0.050
0.500
C5-06
0.000 to 0.500
0.001 s
0.004
b8-03
C6-02
1 to F
7 <9>
7 <9>
7 <9>
7 <9>
E1-04
40.0 to 400.0
0.1 Hz
60.0 <44>
60.0 <44>
60.0 <44>
60.0 <44>
E1-05
0.0 to 255.0
0.1 V
575
575
575
575
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
60.0 <44>
60.0 <44>
60.0 <44>
60.0 <44>
E1-07
0.0 to 400.0
0.1 Hz
3.0 <44>
3.0 <44>
3.0 <44>
0.0 <44>
E1-08
0.0 to 255.0
0.1 V
15.0
15.0
11.0
0.0
E1-09
0.0 to 400.0
0.1 Hz
1.5 <44>
1.5 <44>
0.5 <44>
0.0 <44>
E1-10
0.0 to 255.0
0.1 V
9.0
9.0
2.0
0.0
F1-01
0 to 60000
1 ppr
600
600
600
600
F1-05
PG 1 Rotation Selection
0 to 1
F1-09
0.0 to 2.0
0.1 s
1.0
0.0
L1-01
0 to 4
L3-20
0.00 to 5.00
0.01
1.00
1.00
0.30
0.30
L3-21
0.00 to 10.00
0.01
1.00
1.00
1.00
1.00
L4-02
0.0 to 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L4-04
0.0 to 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L8-38
0 to 2
<9>
<9>
<9>
<9>
L8-40
0.00 to 2.00
0.01 s
0.50
0.50
0.50
0.50
o1-03
0 to 3
o1-04
0 to 1
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMRATA). For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized
Drive: CIMR-ABA on page 465.
462
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
b2-01
b2-04
b3-01
b3-02
b3-14
b8-01
b8-02
b8-03
Setting Range
Resolution
0.0 to 10.0
AOLV/PM (6)
CLV/PM (7)
0.1
0.5 Hz
1.0% <41>
0.5% <41>
0.00 to 10.00
0.01 s
0.00
0.00
0.00
0 to 1
0 to 200
1%
0 to 1
1
1
0 to 1
0.0 to 10.0
0.1
0.00 to 10.00
0.01 s
C2-01
0.00 to 10.00
0.01 s
1.00
1.00
1.00
C3-01
0.0 to 2.5
0.1
C3-02
0 to 10000
1 ms
C4-01
0.00 to 2.50
0.01
0.00
0.00
0.00
C4-02
0 to 10000
1 ms
100
100
100
C5-01
0.00 to 300.00
0.01
C5-02
0.000 to 10.000
0.001 s
C5-03
0.00 to 300.00
0.01
C5-04
0.000 to 10.000
0.001 s
C5-06
0.000 to 0.500
0.001 s
C6-02
1 to F
E1-04
40.0 to 400.0
0.1 Hz
<14>
<14>
<14>
E1-05
0.0 to 377.1
0.1 V
<14>
<14>
<14>
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
<14>
<14>
<14>
E1-07
0.0 to 400.0
0.1 Hz
E1-08
0.0 to 377.1
0.1 V
E1-09
0.0 to 400.0
0.1 Hz
<14>
<14>
<14>
E1-10
0.0 to 377.1
0.1 V
F1-01
0 to 60000
1 ppr
1024
1024
1024
F1-05
PG 1 Rotation Selection
F1-09
0 to 1
0.0 to 2.0
0.1 s
L1-01
0 to 4
L3-20
0.00 to 5.00
0.01
0.65
0.65
0.65
L3-21
0.00 to 10.00
0.01
2.50
2.50
2.50
L4-02
0.0 to 20.0
0.1
2.0Hz
4.0% <41>
4.0% <41>
L4-04
0.0 to 20.0
0.1
2.0Hz
4.0% <41>
4.0% <41>
L8-38
0 to 2
L8-40
0.00 to 2.00
0.01s
0.00
0.00
0.00
o1-03
0 to 3
o1-04
0 to 1
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<41> This default value is a calculated as a percentage of the maximum output frequency.
Setting Range
Resolution
40.0 to 400.0
0.1 Hz
OLV (2)
CLV (3)
60.0 <44>
60.0 <44>
60.0 <44>
60.0 <44>
E3-04
E3-05
0.0 to 255.0
0.1 V
200.0
200.0
200.0
200.0
E3-06
0.0 to 400.0
0.1 Hz
60.0 <44>
60.0 <44>
60.0 <44>
60.0 <44>
0.0 <44>
E3-07
0.0 to 400.0
0.1 Hz
3.0 <44>
3.0 <44>
3.0 <44>
E3-08
0.0 to 255.0
0.1 V
15.0
15.0
11.0
0.0
E3-09
0.0 to 400.0
0.1 Hz
1.5 <44>
1.5 <44>
0.5 <44>
0.0 <44>
E3-10
0.0 to 255.0
0.1 V
9.0
9.0
2.0
0.0
Parameter List
No.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMRATA). For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized
Drive: CIMR-ABA on page 465.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
463
Units
E1-03
E1-04
E1-05
<18>
V/f
0
1
60.0
2
60.0
3
72.0
4
50.0
5
50.0
6
60.0
60.0
50.0
9
50.0
A
60.0
B
60.0
C
90.0
120.0 180.0
50.0
200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
15.0
15.0
15.0
15.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
15.0
15.0
15.0
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
9.0
9.0
9.0
9.0
8.0
9.0
8.0
9.0
11.0
13.0
11.0
15.0
9.0
9.0
9.0
<18>
E1-09
E1-10
<18>
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
60.0 <44>
60.0 <44>
<14>
200.0
200.0
<14>
60.0 <44>
60.0 <44>
<14>
3.0 <44>
0.0 <44>
11.0
0.0
0.5 <44>
0.0 <44>
<14>
2.0
0.0
<42>
60.0
Hz
E1-06
E1-08
<44>
60.0
<44>
3.0
<44>
15.0
1.5
<44>
9.0
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E2-04 through E2-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMR-ATA).
For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized Drive: CIMR-ABA
on page 465.
Units
E1-03
V/f
0
50.0
A
60.0
B
60.0
C
90.0
120.0 180.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
60.0 <44>
60.0 <44>
<14>
200.0
200.0
<14>
60.0 <44>
60.0 <44>
<14>
3.0 <44>
0.0 <44>
11.0
0.0
0.5 <44>
0.0 <44>
<14>
2.0
0.0
<42>
60.0
60.0
<18>
50.0
50.0
E1-10
60.0
Hz
E1-09
60.0
E1-06
<18>
50.0
200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
E1-08
50.0
<18>
72.0
50.0
E1-05
60.0
Hz
E1-04
60.0
<44>
60.0
<44>
3.0
<44>
14.0
1.5
<44>
7.0
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E2-04 through E2-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMR-ATA).
For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized Drive: CIMR-ABA
on page 465.
464
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Units
E1-03
E1-04
E1-05
<18>
E1-06
E1-07
E1-08
<18>
E1-09
E1-10
<18>
V/f
0
1
60.0
60.0
50.0
50.0
50.0
50.0
60.0
60.0
60.0
60.0
90.0
120.0 180.0
60.0
60.0
60.0
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
12.0
12.0
12.0
12.0
35.0
50.0
35.0
50.0
15.0
20.0
15.0
20.0
12.0
12.0
12.0
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
6.0
6.0
6.0
6.0
5.0
6.0
5.0
6.0
7.0
9.0
7.0
11.0
6.0
6.0
6.0
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
60.0 <44>
60.0 <44>
<14>
200.0
200.0
<14>
60.0 <44>
60.0 <44>
<14>
3.0 <44>
0.0 <44>
11.0
0.0
0.5 <44>
0.0 <44>
<14>
2.0
0.0
F
<42>
60.0
50.0
60.0
60.0
Hz
50.0
60.0
200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
50.0
50.0
60.0
50.0
50.0
50.0
72.0
Hz
60.0
60.0
<44>
60.0
<44>
3.0
<44>
12.0
1.5
<44>
6.0
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E2-04 through E2-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-AAA), Asia (Model code: CIMR-ATA).
For default value of China localized drive (Model code: CIMR-ABA), refer to Default Values of the China Localized Drive: CIMR-ABA
on page 465.
Description
E1-04
OLV
CLV
OLV/PM
AOLV/PM
CLV/PM
50.0 Hz
50.0 Hz
50.0 Hz
<33>
<33>
<33>
E1-06
Base Frequency
50.0 Hz
50.0 Hz
50.0 Hz
<33>
<33>
<33>
E1-07
2.5 Hz
3.0 Hz
0.0 Hz
E1-09
1.3 Hz
0.5 Hz
0.0 Hz
<33>
<33>
0.0 Hz
E3-04
50.0 Hz
50.0 Hz
50.0 Hz
E3-06
50.0 Hz
50.0 Hz
50.0 Hz
E3-07
2.5 Hz
3.0 Hz
0.0 Hz
E3-09
1.3 Hz
0.5 Hz
0.0 Hz
Parameter List
<33> The setting value is dependent on the setting for the input voltage (E1-01).
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
465
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
2A0004
2A0006
2A0008
2A0010
HD
ND
HD
ND
HD
ND
HD
62
63
ND
1
64
65
kW
0.4
0.75
0.75
1.1
1.1
1.5
1.5
2.2
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
b3-04
C5-17 (C5-37)
C6-02
Motor Inertia
288.2
223.7
223.7
196.6
196.6
169.4
169.4
156.8
kgm2
0.0015
0.0028
0.0028
0.0068
0.0068
0.0068
0.0068
0.0088
E2-01 (E4-01)
1.9
3.3
3.3
4.9
4.9
6.2
6.2
8.5
E2-02 (E4-02)
Hz
2.9
2.5
2.5
2.6
2.6
2.6
2.6
2.9
E2-03 (E4-03)
1.2
1.8
1.8
2.3
2.3
2.8
2.8
E2-05 (E4-05)
9.842
5.156
5.156
3.577
3.577
1.997
1.997
1.601
18.4
E2-06 (E4-06)
18.2
13.8
13.8
18.5
18.5
18.5
18.5
E2-10 (E4-10)
14
26
26
38
38
53
53
77
Hex.
1202
1202
1203
1203
FFFF
FFFF
1205
1205
E5-01
L2-02
0.1
0.1
0.2
0.2
0.3
0.3
0.3
0.3
L2-03
0.2
0.3
0.3
0.4
0.4
0.4
0.4
0.5
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.178
0.142
0.142
0.142
0.142
0.166
0.166
0.145
L8-02
115
115
115
115
115
115
115
115
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.178
0.142
0.142
0.142
0.142
0.166
0.166
0.145
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
2A0012
2A0018
2A0021
2A0030
HD
ND
HD
ND
HD
ND
HD
66
67
68
ND
1
6A
kW
2.2
3.0
3.0
3.7
3.7
5.5
5.5
7.5
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
b3-04
156.8
136.4
136.4
122.9
122.9
94.75
94.75
72.69
kgm2
0.0088
0.0158
0.0158
0.0158
0.0158
0.0255
0.026
0.037
E2-01 (E4-01)
8.5
11.4
11.4
14
14
19.6
19.6
26.6
E2-02 (E4-02)
Hz
2.9
2.7
2.7
2.73
2.73
1.5
1.5
1.3
E2-03 (E4-03)
3.7
3.7
4.5
4.5
5.1
5.1
E2-05 (E4-05)
1.601
1.034
1.034
0.771
0.771
0.399
0.399
0.288
15.5
C5-17 (C5-37)
C6-02
Motor Inertia
E2-06 (E4-06)
18.4
19
19
19.6
19.6
18.2
18.2
E2-10 (E4-10)
77
91
91
112
112
172
172
262
Hex.
1206
1206
FFFF
FFFF
1208
1208
120A
120A
E5-01
466
L2-02
0.5
0.5
L2-03
0.5
0.5
0.5
0.6
0.6
0.7
0.7
0.8
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
L8-02
125
125
110
110
110
110
120
120
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
2A0040
2A0056
2A0069
2A0081
HD
ND
HD
ND
HD
ND
HD
6B
6D
ND
1
6E
6F
kW
7.5
11
11
15
15
18.5
18.5
22
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
72.69
70.44
70.44
63.13
63.13
57.87
57.87
51.79
kgm2
0.037
0.053
0.053
0.076
0.076
0.138
0.138
0.165
E2-01 (E4-01)
26.6
39.7
39.7
53
53
65.8
65.8
77.2
E2-02 (E4-02)
Hz
1.3
1.7
1.7
1.6
1.6
1.67
1.67
1.7
E2-03 (E4-03)
11.2
11.2
15.2
15.2
15.7
15.7
18.5
E2-05 (E4-05)
0.288
0.23
0.23
0.138
0.138
0.101
0.101
0.079
E2-06 (E4-06)
15.5
19.5
19.5
17.2
17.2
15.7
20.1
19.5
E2-10 (E4-10)
262
245
245
272
272
505
505
538
Hex.
120B
120B
120D
120D
120E
120E
120F
120F
2
C5-17 (C5-37)
C6-02
E5-01
L2-02
L2-03
0.8
0.9
0.9
L2-04
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
L3-24
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
L8-02
125
125
120
120
120
120
125
125
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
2A0110
2A0138
2A0169
2A0211
HD
ND
HD
ND
HD
ND
HD
70
72
73
ND
1
74
kW
22
30
30
37
37
45
45
b3-04
100
80
80
80
80
80
80
55
80
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
2.00
b8-04
51.79
46.27
46.27
38.16
38.16
35.78
35.78
31.35
kgm2
0.165
0.220
0.220
0.273
0.273
0.333
0.333
0.490
E2-01 (E4-01)
77.2
105
105
131
131
160
160
190
E2-02 (E4-02)
Hz
1.7
1.8
1.8
1.33
1.33
1.6
1.6
1.43
E2-03 (E4-03)
18.5
21.9
21.9
38.2
38.2
44
44
45.6
E2-05 (E4-05)
0.079
0.064
0.064
0.039
0.039
0.03
0.03
0.022
E2-06 (E4-06)
19.5
20.8
20.8
18.8
18.8
20.2
20.2
20.5
E2-10 (E4-10)
538
699
699
823
823
852
852
960
Hex.
1210
1210
1212
1212
1213
1213
1214
1214
C5-17 (C5-37)
C6-02
E5-01
Motor Inertia
L2-02
L2-03
1.1
1.1
1.1
1.1
1.2
1.2
1.3
L2-04
0.6
0.6
0.6
0.6
0.6
L3-24
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
L8-02
130
130
130
130
130
130
125
125
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.355
0.323
0.323
0.32
0.32
0.387
0.387
0.317
Parameter List
No.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
467
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
2A0250
2A0312
2A0360
2A0415
HD
ND
HD
ND
HD
ND
HD
75
76
ND
1
77
78
kW
55
75
75
90
90
110
110
b3-04
80
80
80
80
80
80
80
110
80
b3-06
0.5
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
31.35
23.1
23.1
20.65
20.65
18.12
18.12
18.12
kgm2
0.49
0.90
0.90
1.10
1.10
1.90
1.90
1.90
E2-01 (E4-01)
190
260
260
260
260
260
260
260
E2-02 (E4-02)
Hz
1.43
1.39
1.39
1.39
1.39
1.39
1.39
1.39
E2-03 (E4-03)
45.6
72
72
72
72
72
72
72
E2-05 (E4-05)
0.022
0.023
0.023
0.023
0.023
0.023
0.023
0.023
C5-17 (C5-37)
C6-02
Motor Inertia
E2-06 (E4-06)
20.5
20
20
20
20
20
20
20
E2-10 (E4-10)
960
1200
1200
1200
1200
1200
1200
1200
FFFF
E5-01
Hex.
1215
1215
1216
1216
FFFF
FFFF
FFFF
L2-02
L2-03
1.3
1.5
1.5
1.5
1.5
1.7
1.7
1.7
L2-04
L3-24
0.317
0.533
0.533
0.592
0.592
0.646
0.646
0.646
L8-02
115
115
120
120
120
120
120
120
L8-35
L8-38
n1-03
ms
10
10
10
10
100
100
100
100
n5-02
0.317
0.533
0.533
0.592
0.592
0.646
0.646
0.646
Table B.10 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0002
4A0004
4A0005
4A0007
HD
ND
HD
ND
HD
ND
HD
92
93
94
ND
1
95
kW
0.4
0.75
0.75
1.5
1.5
2.2
2.2
3.0
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
b3-04
C5-17 (C5-37)
C6-02
Motor Inertia
576.4
447.4
447.4
338.8
338.8
313.6
313.6
265.7
kgm2
0.0015
0.0028
0.0028
0.0068
0.0068
0.0088
0.0088
0.0158
E2-01 (E4-01)
1.6
1.6
3.1
3.1
4.2
4.2
5.7
E2-02 (E4-02)
Hz
2.9
2.6
2.6
2.5
2.5
2.7
E2-03 (E4-03)
0.6
0.8
0.8
1.4
1.4
1.5
1.5
1.9
4.360
E2-05 (E4-05)
38.198
22.459
22.459
10.1
10.1
6.495
6.495
E2-06 (E4-06)
18.2
14.3
14.3
18.3
18.3
18.7
18.7
19
E2-10 (E4-10)
14
26
26
53
53
77
77
105
1236
468
E5-01
Hex.
1232
1232
1233
1233
1235
1235
1236
L2-02
0.1
0.1
0.2
0.2
0.3
0.3
0.5
0.5
L2-03
0.2
0.3
0.3
0.4
0.4
0.5
0.5
0.5
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
L8-02
110
110
110
110
110
110
110
110
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.178
0.142
0.142
0.166
0.166
0.145
0.145
0.145
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0009
4A0011
4A0018
4A0023
HD
ND
HD
ND
HD
ND
HD
96
97
ND
1
99
9A
kW
3.0
3.7
3.7
5.5
5.5
7.5
7.5
11
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
265.7
245.8
245.8
189.5
189.5
145.38
145.38
140.88
kgm2
0.0158
0.0158
0.0158
0.0255
0.026
0.037
0.037
0.053
E2-01 (E4-01)
5.7
9.8
9.8
13.3
13.3
19.9
E2-02 (E4-02)
Hz
2.7
2.7
2.7
1.5
1.5
1.3
1.3
1.7
E2-03 (E4-03)
1.9
2.3
2.3
2.6
2.6
5.6
E2-05 (E4-05)
4.360
3.333
3.333
1.595
1.595
1.152
1.152
0.922
E2-06 (E4-06)
19
19.3
19.3
18.2
18.2
15.5
15.5
19.6
E2-10 (E4-10)
105
130
130
193
193
263
263
385
Hex.
FFFF
FFFF
1238
1238
123A
123A
123B
123B
C5-17 (C5-37)
C6-02
E5-01
L2-02
0.5
0.5
0.5
0.5
0.8
0.8
L2-03
0.5
0.6
0.6
0.7
0.7
0.8
0.8
0.9
L2-04
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L3-24
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
L8-02
110
110
110
110
110
110
115
115
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.145
0.154
0.154
0.168
0.168
0.175
0.175
0.265
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0031
4A0038
4A0044
4A0058
HD
ND
HD
ND
HD
ND
HD
9C
9D
9E
ND
1
9F
kW
11
15
15
18.5
18.5
22
22
30
b3-04
100
100
100
100
100
100
100
100
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
140.88
126.26
126.26
115.74
115.74
103.58
103.58
92.54
kgm2
0.053
0.076
0.076
0.138
0.138
0.165
0.165
0.220
E2-01 (E4-01)
19.9
26.5
26.5
32.9
32.9
38.6
38.6
52.3
E2-02 (E4-02)
Hz
1.7
1.6
1.6
1.67
1.67
1.7
1.7
1.8
E2-03 (E4-03)
5.6
7.6
7.6
7.8
7.8
9.2
9.2
10.9
E2-05 (E4-05)
0.922
0.55
0.55
0.403
0.403
0.316
0.316
0.269
E2-06 (E4-06)
19.6
17.2
17.2
20.1
20.1
23.5
23.5
20.7
E2-10 (E4-10)
385
440
440
508
508
586
586
750
Hex.
123D
123D
123E
123E
123F
123F
1240
1240
C5-17 (C5-37)
C6-02
E5-01
L2-02
L2-03
0.9
1.1
L2-04
0.3
0.6
0.6
0.6
0.6
0.6
0.6
0.6
L3-24
0.265
0.244
0.244
0.317
0.317
0.355
0.355
0.323
L8-02
120
120
120
120
115
115
120
120
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
10
10
n5-02
0.265
0.244
0.244
0.317
0.317
0.355
0.355
0.323
Parameter List
No.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
469
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0072
4A0088
4A0103
4A0139
HD
ND
HD
ND
HD
ND
HD
A1
A2
ND
1
A3
A4
kW
30
37
37
45
45
55
55
b3-04
100
100
100
100
100
80
80
75
60
b3-06
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.7
b8-03
0.50
0.50
0.50
0.50
0.50
2.00
2.00
2.00
b8-04
92.54
76.32
76.32
71.56
71.56
67.2
67.2
46.2
kgm2
0.220
0.273
0.273
0.333
0.333
0.490
0.49
0.90
E2-01 (E4-01)
52.3
65.6
65.6
79.7
79.7
95
95
130
E2-02 (E4-02)
Hz
1.8
1.33
1.33
1.6
1.6
1.46
1.46
1.39
E2-03 (E4-03)
10.9
19.1
19.1
22
22
24
24
36
E2-05 (E4-05)
0.269
0.155
0.155
0.122
0.122
0.088
0.088
0.092
C5-17 (C5-37)
C6-02
Motor Inertia
E2-06 (E4-06)
20.7
18.8
18.8
19.9
19.9
20
20
20
E2-10 (E4-10)
750
925
925
1125
1125
1260
1260
1600
1245
E5-01
Hex.
1242
1242
1243
1243
1244
1244
1245
L2-02
L2-03
1.1
1.1
1.1
1.2
1.2
1.2
1.2
1.3
L2-04
0.6
0.6
0.6
0.6
0.6
L3-24
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
L8-02
120
120
110
110
120
120
130
130
L8-35
L8-38
n1-03
ms
10
10
10
10
10
10
30
30
n5-02
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0165
4A0208
4A0250
4A0296
HD
ND
HD
ND
HD
ND
HD
A5
A6
A7
ND
1
A8
kW
75
90
90
110
110
132
132
b3-04
60
60
60
60
60
60
60
160
60
b3-06
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
46.2
38.91
38.91
36.23
36.23
32.79
32.79
30.13
3.30
kgm2
0.90
1.10
1.10
1.90
1.90
2.10
2.10
E2-01 (E4-01)
130
156
156
190
190
223
223
270
E2-02 (E4-02)
Hz
1.39
1.4
1.4
1.4
1.4
1.38
1.38
1.35
E2-03 (E4-03)
36
40
40
49
49
58
58
70
E2-05 (E4-05)
0.092
0.056
0.056
0.046
0.046
0.035
0.035
0.029
C5-17 (C5-37)
C6-02
Motor Inertia
E2-06 (E4-06)
20
20
20
20
20
20
20
20
E2-10 (E4-10)
1600
1760
1760
2150
2150
2350
2350
2850
1249
470
E5-01
Hex.
1246
1246
1247
1247
1248
1248
1249
L2-02
L2-03
1.3
1.5
1.5
1.7
1.7
1.7
1.7
1.8
L2-04
L3-24
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
L8-02
130
130
120
120
120
120
125
125
L8-35
L8-38
n1-03
ms
30
30
30
30
30
30
30
30
n5-02
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
No.
Name
Model CIMR-A
Unit
C6-01
o2-04
Hex.
E2-11 (E4-11)
Default Settings
4A0362
4A0414
4A0515
4A0675
HD
ND
HD
ND
HD
ND
HD
A9
AA
AC
ND
1
AE
kW
160
185
185
220
220
250
315
b3-04
60
60
60
60
60
60
60
355
60
b3-06
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b8-03
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
30.13
30.57
30.57
27.13
27.13
21.76
21.76
23.84
12.00
C5-17 (C5-37)
Motor Inertia
kgm2
3.30
3.60
3.60
4.10
4.10
6.50
11.00
E2-01 (E4-01)
270
310
310
370
370
500
500
650
E2-02 (E4-02)
Hz
1.35
1.3
1.3
1.3
1.3
1.25
1.25
E2-03 (E4-03)
70
81
81
96
96
130
130
130
E2-05 (E4-05)
0.029
0.025
0.025
0.02
0.02
0.014
0.014
0.012
E2-06 (E4-06)
20
20
20
20
20
20
20
20
E2-10 (E4-10)
2850
3200
3200
3700
3700
4700
4700
5560
FFFF
C6-02
E5-01
Hex.
124A
124A
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
L2-03
1.8
1.9
1.9
2.1
2.1
2.3
L2-04
L3-24
0.777
0.864
0.864
0.91
0.91
1.392
1.392
1.667
130
130
140
140
140
140
140
140
L8-35
L8-38
n1-03
ms
30
30
100
100
100
100
100
100
n5-02
0.777
0.864
0.864
0.91
0.91
1.392
1.392
1.667
Parameter List
L8-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
471
E5-01
Name
Unit
Default Settings
0002
0003
0005
0006
0008
Voltage Class
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
Rated Speed
r/min
1800
1800
1800
1800
1800
E5-02
kW
0.4
0.75
1.5
2.2
3.7
E5-03
2.1
4.0
6.9
10.8
17.4
E5-04
E5-05
2.47
1.02
0.679
0.291
0.169
E5-06
mH
12.7
4.8
3.9
3.6
2.5
E5-07
mH
12.7
4.8
3.9
3.6
2.5
E5-09
mVs/rad
E5-24
mV/(r/min)
62.0
64.1
73.4
69.6
72.2
E1-04
Hz
120
120
120
120
120
E1-05
Maximum Voltage
200.0
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
120
120
120
120
120
E1-09
Hz
C5-17
Motor Inertia
kgm2
0.0007
0.0014
0.0021
0.0032
0.0046
L3-24
0.064
0.066
0.049
0.051
0.044
n5-02
0.064
0.066
0.049
0.051
0.044
n8-49
Table B.12 200 V, 3600 r/min Type YASKAWA SMRA Series SPM Motor
No.
E5-01
Name
Unit
Default Settings
0103
0105
0106
0108
Voltage Class
200
200
200
200
Rated Power
kW
0.75
1.5
2.2
3.7
Rated Speed
r/min
3600
3600
3600
3600
E5-02
kW
0.75
1.5
2.2
3.7
E5-03
4.1
8.0
10.5
16.5
E5-04
E5-05
0.538
0.20
0.15
0.097
E5-06
mH
3.2
1.3
1.1
1.1
E5-07
mH
3.2
1.3
1.1
1.1
E5-09
mVs/rad
E5-24
mV/(r/min)
32.4
32.7
36.7
39.7
E1-04
Hz
240
240
240
240
E1-05
Maximum Voltage
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
240
240
240
240
E1-09
Hz
12
12
12
12
C5-17
Motor Inertia
kgm2
0.0007
0.0014
0.0021
0.0032
L3-24
0.137
0.132
0.132
0.122
n5-02
0.137
0.132
0.132
0.122
n8-49
472
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E5-01
Name
Unit
Default Settings
1202
1203
1205
1206
1208
120A
120B
120D
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
1.77
3.13
5.73
8.44
13.96
20.63
28.13
41.4
E5-04
E5-05
8.233
2.284
1.470
0.827
0.455
0.246
0.198
0.094
E5-06
mH
54.84
23.02
17.22
8.61
7.20
4.86
4.15
3.40
E5-07
mH
64.10
29.89
20.41
13.50
10.02
7.43
5.91
3.91
E5-09
mVs/rad
223.7
220.3
240.8
238.0
238.7
239.6
258.2
239.3
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0011
0.0017
0.0023
0.0043
0.0083
0.014
0.017
0.027
L3-24
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
n5-02
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
n8-49
-7.6
-11.5
-9.1
-19.0
-18.7
-23.4
-18.5
-10.9
No.
E5-01
Name
Unit
Default Settings
120E
120F
1210
1212
1213
1214
1215
1216
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
15.00
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
55.4
68.2
80.6
105.2
131.3
153.1
185.4
257.3
E5-05
0.066
0.051
0.037
0.030
0.020
0.014
0.012
0.006
E5-06
mH
2.45
2.18
1.71
1.35
0.99
0.83
0.79
0.44
E5-07
mH
3.11
2.55
2.05
1.82
1.28
1.01
0.97
0.56
E5-09
mVs/rad
248.1
253.6
250.0
280.9
264.2
280.4
311.9
268.0
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.046
0.055
0.064
0.116
0.140
0.259
0.31
0.42
L3-24
0.102
0.101
0.098
0.130
0.127
0.193
0.191
0.187
n5-02
0.102
0.101
0.098
0.130
0.127
0.193
0.191
0.187
n8-49
-16.5
-11.3
-12.8
-16.8
-15.6
-10.7
-9.6
-13.3
Parameter List
E5-04
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
473
E5-01
Name
Unit
Default Settings
1232
1233
1235
1236
1238
123A
123B
123D
123E
123F
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
E5-03
0.89
1.56
2.81
4.27
7.08
10.31
13.65
20.7
27.5
33.4
E5-04
E5-05
25.370
9.136
6.010
3.297
1.798
0.982
0.786
0.349
0.272
0.207
E5-06
mH
169.00
92.08
67.71
34.40
32.93
22.7
16.49
13.17
10.30
8.72
E5-07
mH
197.50
119.56
81.71
54.00
37.70
26.80
23.46
15.60
12.77
11.22
E5-09
mVs/rad
392.6
440.6
478.3
466.3
478.8
478.1
520.0
481.5
498.8
509.5
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0011
0.0017
0.0023
0.0043
0.0083
0.014
0.017
0.027
0.046
0.055
L3-24
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
n5-02
0.092
0.076
0.052
0.066
0.075
0.083
0.077
0.084
0.102
0.101
n8-49
-8.6
-11.5
-10.3
-19.8
-8.5
-11.0
-18.6
-12.5
-15.5
-17.9
No.
E5-01
Name
Unit
Default Settings
1240
1242
1243
1244
1245
1246
1247
1248
1249
124A
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
22
30
37
45
55
75
90
110
132
160
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132
160
E5-03
39.8
52.0
65.8
77.5
92.7
126.6
160.4
183.3
222.9
267.7
E5-04
E5-05
0.148
0.235
0.079
0.054
0.049
0.029
0.019
0.017
0.012
0.008
E5-06
mH
6.81
5.4
4.08
3.36
3.16
2.12
1.54
1.44
1.21
0.97
E5-07
mH
8.47
7.26
5.12
3.94
3.88
2.61
2.06
2.21
1.46
1.28
E5-09
mVs/rad
503.9
561.7
528.5
558.1
623.8
594.5
524.1
583.7
563.6
601.2
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380
380
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
C5-17
Motor Inertia
L3-24
0.098
0.130
0.127
0.193
0.191
0.187
0.208
0.254
0.243
0.338
n5-02
0.098
0.130
0.127
0.193
0.191
0.187
0.208
0.254
0.243
0.338
n8-49
-15.1
-16.8
-14.1
-8.8
-9.6
-10.3
-17.0
-21.7
-10.9
-13.2
474
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
kgm2
0.064
0.116
0.140
0.259
0.31
0.42
0.56
0.83
0.96
1.61
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E5-01
Name
Unit
Default Settings
1302
1303
1305
1306
1308
130A
130B
130D
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
1.88
3.13
5.63
8.33
14.17
20.63
27.71
39.6
E5-04
E5-05
3.190
1.940
1.206
0.665
0.341
0.252
0.184
0.099
E5-06
mH
32.15
26.12
14.72
12.27
8.27
6.49
6.91
4.07
E5-07
mH
41.74
34.30
20.15
14.77
9.81
7.74
7.66
4.65
E5-09
mVs/rad
264.3
269.6
284.3
287.1
284.5
298.0
335.0
303.9
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0017
0.0023
0.0043
0.0083
0.0136
0.017
0.027
0.046
L3-24
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
n5-02
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
n8-49
-6.6
-10.9
-13.5
-9.0
-9.5
-10.1
-6.0
-9.3
No.
E5-01
Name
Unit
Default Settings
130E
130F
1310
1312
1313
1314
1315
Voltage Class
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
kW
15.00
18.50
22.00
30.00
37.00
45.00
55.00
E5-03
55.5
65.6
75.1
105.2
126.0
153.1
186.5
E5-04
E5-05
0.075
0.057
0.041
0.034
0.023
0.015
0.012
E5-06
mH
3.29
2.53
1.98
1.75
1.48
1.04
0.87
E5-07
mH
3.84
3.01
2.60
2.17
1.70
1.31
1.10
E5-09
mVs/rad
311.2
300.9
327.7
354.2
369.6
351.6
374.7
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.055
0.064
0.116
0.140
0.259
0.312
0.42
L3-24
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n5-02
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n8-49
-10.7
-13.2
-15.7
-11.5
-7.0
-11.8
-10.2
Parameter List
E5-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
475
E5-01
Name
Unit
Default Settings
1332
1333
1335
1336
1338
133A
133B
133D
133E
133F
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
E5-03
0.94
1.56
2.81
4.27
6.98
10.21
13.85
19.5
27.4
32.9
E5-04
E5-05
12.760
7.421
4.825
2.656
1.353
0.999
0.713
0.393
0.295
0.223
E5-06
mH
128.60
85.11
58.87
46.42
31.73
26.20
27.06
15.51
12.65
9.87
E5-07
mH
166.96
113.19
80.59
60.32
40.45
30.94
33.45
19.63
15.87
12.40
E5-09
mVs/rad
528.6
544.2
568.5
572.8
562.9
587.6
670.1
612.7
624.6
610.4
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0017
0.0023
0.0043
0.0083
0.0136
0.017
0.027
0.046
0.055
0.064
L3-24
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
n5-02
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
0.085
0.080
n8-49
-6.6
-9.2
-13.5
-12.1
-13.7
-10.1
-12.2
-15.5
-15.1
-16.0
No.
E5-01
Name
Unit
Default Settings
1340
1342
1343
1344
1345
1346
1347
1348
1349
Voltage Class
400
400
400
400
400
400
400
400
400
Rated Power
kW
22
30
37
45
55
75
90
110
132
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
E5-03
37.6
52.5
63.2
76.4
96.1
124.0
153.1
186.5
226.0
E5-04
E5-05
0.164
0.137
0.093
0.059
0.048
0.028
0.024
0.015
0.011
E5-06
mH
7.90
7.01
5.93
4.17
3.11
2.32
2.20
1.45
1.23
E5-07
mH
10.38
8.68
6.79
5.22
4.55
2.97
3.23
1.88
1.67
E5-09
mVs/rad
655.4
708.4
739.2
703.0
747.1
639.3
708.0
640.7
677.0
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.116
0.140
0.259
0.312
0.42
0.56
0.83
0.96
1.61
L3-24
0.122
0.108
0.161
0.160
0.175
0.171
0.213
0.201
0.281
n5-02
0.122
0.108
0.161
0.160
0.175
0.171
0.213
0.201
0.281
n8-49
-15.7
-11.5
-6.8
-11.5
-14.8
-15.8
-19.6
-14.9
-15.1
476
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E5-01
Name
Unit
Default Settings
1402
1403
1405
1406
1408
140A
140B
Voltage Class
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
E5-03
1.88
3.02
6.00
8.85
14.27
20.21
26.67
E5-04
E5-05
4.832
2.704
1.114
0.511
0.412
0.303
0.165
E5-06
mH
48.68
32.31
19.22
12.15
7.94
11.13
6.59
E5-07
mH
63.21
40.24
24.38
15.35
11.86
14.06
8.55
E5-09
mVs/rad
320.4
327.1
364.4
344.4
357.5
430.8
391.5
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.0017
0.0023
0.0083
0.0136
0.0171
0.027
0.046
L3-24
0.062
0.044
0.080
0.090
0.067
0.072
0.088
n5-02
0.062
0.044
0.080
0.090
0.067
0.072
0.088
n8-49
-8.8
-9.9
-9.3
-10.0
-17.7
-12.3
-15.3
No.
E5-01
Name
Unit
Default Settings
140D
140E
140F
1410
1412
1413
1414
Voltage Class
200
200
200
200
200
200
200
Rated Power
kW
11
15
18
22
30
37
45
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
11.0
15
18.50
22.00
30.00
37.00
45.00
E5-03
39.9
55.6
63.5
74.4
104.2
129.6
154.2
E5-04
E5-05
0.113
0.084
0.066
0.048
0.035
0.023
0.016
E5-06
mH
4.96
3.83
3.33
2.38
2.04
1.53
1.16
E5-07
mH
6.12
4.65
4.50
3.15
2.86
2.27
1.54
E5-09
mVs/rad
384.4
372.1
421.3
410.9
436.1
428.8
433.3
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.055
0.064
0.116
0.140
0.259
0.312
0.418
L3-24
0.073
0.062
0.091
0.092
0.125
0.122
0.135
n5-02
0.073
0.062
0.091
0.092
0.125
0.122
0.135
n8-49
-13.9
-14.4
-17.9
-15.9
-17.9
-20.1
-13.7
Parameter List
E5-24
E1-04
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
477
E5-01
Name
Unit
Default Settings
1432
1433
1435
1436
1438
143A
143B
143D
143E
Voltage Class
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
E5-03
0.94
1.51
3.00
4.43
7.08
10.10
13.33
19.9
27.8
E5-04
E5-05
19.320
10.800
4.456
2.044
1.483
1.215
0.660
0.443
0.331
E5-06
mH
194.70
129.20
76.88
48.60
37.58
44.54
26.36
19.10
15.09
E5-07
mH
252.84
160.90
97.52
61.40
47.65
56.26
34.20
24.67
18.56
E5-09
mVs/rad
640.9
654.1
728.8
688.9
702.0
861.5
783.0
762.2
749.6
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.0017
0.0023
0.0083
0.0136
0.0171
0.027
0.046
0.055
0.064
L3-24
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
n5-02
0.062
0.044
0.080
0.090
0.067
0.072
0.088
0.073
0.062
n8-49
-8.8
-9.9
-9.3
-10.0
-12.8
-12.3
-15.3
-16.7
-14.9
No.
E5-01
Name
Unit
Default Settings
143F
1440
1442
1443
1444
1445
1446
1447
1448
Voltage Class
400
400
400
400
400
400
400
400
400
Rated Power
kW
18
22
30
37
45
55
75
90
110
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
18.50
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
E5-03
31.8
37.2
52.1
64.8
76.6
92.0
127.1
150.5
185.4
E5-04
E5-05
0.264
0.192
0.140
0.093
0.063
0.051
0.033
0.027
0.015
E5-06
mH
13.32
9.52
8.16
6.13
4.63
3.96
3.03
2.60
1.89
E5-07
mH
18.00
12.60
11.40
9.10
6.15
5.00
5.14
3.28
2.33
E5-09
mVs/rad
842.7
821.8
872.3
857.7
866.6
854.0
823.1
853.4
829.2
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.116
0.140
0.259
0.312
0.418
0.56
0.83
0.96
1.61
L3-24
0.091
0.092
0.125
0.122
0.135
0.147
0.161
0.154
0.212
n5-02
0.091
0.092
0.125
0.122
0.135
0.147
0.161
0.154
0.212
n8-49
-17.9
-15.9
-17.7
-20.1
-13.8
-12.5
-28.8
-13.3
-11.6
478
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E5-01
Name
Unit
Default Settings
2202
2203
2205
2206
2208
220A
220B
220D
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
1.77
3.54
6.56
8.96
14.79
20.94
29.58
41.1
E5-04
E5-05
2.247
1.132
0.774
0.479
0.242
0.275
0.161
0.111
E5-06
mH
22.32
12.38
8.90
7.39
5.06
5.82
3.86
3.59
E5-07
mH
32.50
15.72
11.96
9.63
6.42
6.74
4.66
4.32
E5-09
mVs/rad
215.2
203.9
219.3
230.6
235.1
251.7
235.7
252.0
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0042
0.0081
0.0133
0.013
0.017
0.027
L3-24
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
n5-02
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
n8-49
-9.3
-6.4
-10.0
-9.9
-9.7
-8.4
-11.5
-13.1
No.
E5-01
Name
Unit
Default Settings
220E
220F
2210
2212
2213
2214
2215
2216
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
54.2
68.2
78.6
104.2
129.2
153.1
205.2
260.4
E5-04
E5-05
0.071
0.049
0.040
0.030
0.020
0.013
0.009
0.006
E5-06
mH
2.67
1.98
1.69
1.31
0.88
0.77
0.55
0.40
E5-07
mH
3.10
2.41
2.12
1.61
1.14
1.04
0.69
0.50
E5-09
mVs/rad
253.7
244.6
256.3
283.1
266.3
260.0
261.5
259.3
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.044
0.054
0.063
0.113
0.137
0.252
0.30
0.41
L3-24
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
n8-49
-10.9
-14.3
-15.1
-11.3
-14.1
-18.8
-11.4
-12.2
Parameter List
n5-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
479
E5-01
Name
Unit
Default Settings
2232
2233
2235
2236
2238
223A
223B
223D
Voltage Class
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
0.92
1.77
3.33
4.48
7.50
10.42
14.27
20.5
E5-04
E5-05
8.935
4.570
3.096
1.906
0.972
1.103
0.630
0.429
E5-06
mH
80.14
48.04
35.60
30.31
20.03
23.41
14.86
14.34
E5-07
mH
110.76
64.88
47.84
38.36
24.97
28.70
17.25
17.25
E5-09
mVs/rad
416.5
399.4
438.5
475.5
463.7
485.8
470.4
513.4
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0042
0.0081
0.0133
0.013
0.017
0.027
L3-24
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
n5-02
0.134
0.099
0.094
0.124
0.121
0.081
0.075
0.082
n8-49
-7.5
-8.5
-9.8
-8.2
-9.1
-13.1
-9.2
-12.4
No.
E5-01
Name
Unit
Default Settings
223E
223F
2240
2242
2243
2244
2245
2246
Voltage Class
400
400
400
400
400
400
400
400
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
26.4
34.2
38.8
52.2
65.4
77.6
99.3
130.2
E5-04
E5-05
0.275
0.196
0.160
0.120
0.077
0.052
0.036
0.023
E5-06
mH
9.99
7.92
6.82
5.24
3.57
2.98
1.59
1.59
E5-07
mH
12.37
9.64
8.51
6.44
4.65
3.75
2.78
1.97
E5-09
mVs/rad
505.3
489.2
509.5
566.2
531.6
530.6
515.2
515.2
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.044
0.054
0.063
0.113
0.137
0.252
0.30
0.41
L3-24
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
n5-02
0.099
0.098
0.096
0.127
0.124
0.188
0.186
0.184
n8-49
-15.1
-14.3
-15.3
-11.3
-14.5
-13.2
-22.6
-11.9
480
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
No.
E5-01
Name
Unit
Default Settings
2247
2248
2249
224A
224C
224D
224E
Voltage Class
400
400
400
400
400
400
400
Rated Power
kW
90
110
132
160
200
220
300
Rated Speed
r/min
1750
1750
1750
1750
1750
1750
1750
E5-02
kW
90.00
110.00
132.00
160.00
200.00
250.00
300.00
E5-03
153.1
184.4
229.2
269.8
346.9
421.9
520.8
E5-04
E5-05
0.019
0.017
0.012
0.008
0.005
0.004
0.002
E5-06
mH
1.51
1.43
1.13
0.96
0.65
0.67
0.40
E5-07
mH
1.76
1.92
1.54
1.26
0.88
0.74
0.52
E5-09
mVs/rad
538.3
590.9
548.2
603.9
556.8
593.1
495.4
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Hz
4.4
4.4
4.4
4.4
4.4
4.4
4.4
C5-17
Motor Inertia
kgm2
0.55
0.82
0.96
1.60
1.95
2.82
3.70
L3-24
0.205
0.250
0.244
0.336
0.327
0.379
0.414
n5-02
0.205
0.250
0.244
0.336
0.327
0.379
0.414
n8-49
-8.6
-14.8
-17.5
-12.5
-14.7
-5.1
-16.3
Table B.21 200 V, 1450 r/min Type YASKAWA SST4 Series IPM Motor
No.
E5-01
Name
Unit
Default Settings
2302
2303
2305
2306
2308
230A
230B
230D
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
1.77
3.33
5.94
9.48
14.17
20.42
27.92
39.6
3.154
1.835
0.681
0.308
0.405
0.278
0.180
0.098
E5-06
mH
28.46
19.46
10.00
6.88
8.15
5.77
6.32
3.34
E5-07
mH
39.29
25.89
15.20
9.25
10.76
8.60
8.80
4.61
E5-09
mVs/rad
268.8
256.9
271.9
260.2
286.8
314.9
300.8
292.3
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0081
0.0133
0.0133
0.017
0.027
0.044
L3-24
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
n5-02
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
n8-49
-7.5
-9.4
-13.9
-10.0
-15.0
-17.9
-22.7
-20.5
Parameter List
E5-04
E5-05
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
481
No.
E5-01
Name
Unit
Default Settings
230E
230F
2310
2312
2313
2314
2315
2316
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
15.0
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
54.2
68.3
75.2
102.0
131.3
160.4
191.7
257.3
E5-04
E5-05
0.073
0.055
0.048
0.034
0.023
0.016
0.012
0.007
E5-06
mH
2.94
2.23
2.08
1.67
1.39
0.94
0.82
0.56
E5-07
mH
3.65
2.85
2.66
2.04
1.73
1.22
1.06
0.76
E5-09
mVs/rad
305.1
297.6
355.8
355.4
324.0
302.4
337.2
323.4
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.054
0.063
0.113
0.137
0.252
0.304
0.41
0.55
L3-24
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n5-02
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n8-49
-14.6
-16.4
-11.8
-10.5
-14.5
-17.4
-13.9
-17.5
Table B.22 400 V, 1450 r/min Type YASKAWA SST4 Series IPM Motor
No.
E5-01
Name
Unit
Default Settings
2332
2333
2335
2336
2338
233A
233B
233D
233E
233F
2340
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
E5-03
0.91
1.67
3.02
4.74
7.08
10.21
13.96
20.5
27.1
34.2
37.6
E5-04
E5-05
12.616
7.340
2.724
1.232
1.509
1.112
0.720
0.393
0.291
0.220
0.192
E5-06
mH
113.84
77.84
40.00
27.52
31.73
23.09
25.28
13.36
11.77
8.94
8.32
E5-07
mH
157.16
103.56
60.80
37.00
40.88
34.39
35.20
18.44
14.60
11.40
10.64
E5-09
mVs/rad
490.8
513.8
543.7
520.3
580.8
602.7
601.5
584.6
610.3
595.2
711.6
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.0016
0.0022
0.0081
0.0133
0.0133
0.017
0.027
0.044
0.054
0.063
0.113
L3-24
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
n5-02
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
0.083
0.079
0.118
n8-49
-9.5
-9.4
-13.7
-10.0
-12.9
-19.9
-22.8
-19.8
-14.5
-16.1
-11.8
482
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
No.
E5-01
Name
Unit
Default Settings
2342
2343
2344
2345
2346
2347
2348
2349
234A
234C
234D
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
30
37
45
55
75
90
110
132
160
200
250
Rated Speed
r/min
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
kW
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
200.00
250.00
E5-03
50.9
65.4
80.2
96.1
129.2
153.1
191.7
226.0
268.8
331.3
422.9
E5-04
E5-05
0.136
0.091
0.064
0.048
0.028
0.024
0.015
0.011
0.007
0.006
0.003
E5-06
mH
6.68
5.30
3.76
3.09
2.24
2.20
1.34
1.23
0.92
0.84
0.61
E5-07
mH
8.16
6.80
4.88
4.75
3.03
3.23
2.16
1.67
1.30
1.25
0.89
E5-09
mVs/rad
710.8
652.7
604.8
669.1
646.8
708.0
637.8
677.0
661.7
687.1
655.9
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm2
0.137
0.252
0.304
0.41
0.55
0.82
0.96
1.60
1.95
2.82
3.70
L3-24
0.105
0.157
0.156
0.172
0.169
0.210
0.201
0.279
0.281
0.325
0.341
n5-02
0.105
0.157
0.156
0.172
0.169
0.210
0.201
0.279
0.281
0.325
0.341
n8-49
-10.5
-15.6
-17.4
-21.7
-17.3
-19.6
-24.1
-15.1
-17.0
-19.8
-19.3
Table B.23 200 V, 1150 r/min Type YASKAWA SST4 Series IPM Motor
No.
E5-01
Name
Unit
Default Settings
2402
2403
2405
2406
2408
240A
240B
240D
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
1.77
3.44
5.94
9.17
14.79
20.21
27.40
39.0
E5-04
E5-05
2.680
1.520
1.071
0.542
0.362
0.295
0.162
0.115
E5-06
mH
30.55
15.29
17.48
11.98
8.60
9.54
5.31
4.44
E5-07
mH
42.71
24.28
22.51
15.51
10.69
13.84
8.26
5.68
E5-09
mVs/rad
313.1
313.1
345.3
342.9
363.8
384.3
379.9
370.2
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.0022
0.0042
0.0081
0.0133
0.0168
0.027
0.044
0.054
L3-24
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
n5-02
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
n8-49
-8.4
-11.0
-10.7
-10.7
-9.4
-22.5
-22.2
-16.7
Parameter List
E5-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
483
No.
E5-01
Name
Unit
Default Settings
240E
240F
2410
2412
2413
2414
2415
2416
Voltage Class
200
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
55.9
65.4
77.0
103.5
126.0
153.1
188.5
260.4
E5-04
E5-05
0.083
0.065
0.052
0.035
0.026
0.019
0.013
0.009
E5-06
mH
3.50
2.92
2.55
2.03
1.59
1.24
0.98
0.70
E5-07
mH
4.23
3.79
3.22
2.46
1.92
1.64
1.37
0.97
E5-09
mVs/rad
364.5
404.5
445.1
444.4
447.3
470.8
422.4
418.3
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
190.0
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.063
0.113
0.137
0.252
0.304
0.410
0.55
0.82
L3-24
0.061
0.089
0.090
0.122
0.119
0.132
0.145
0.159
n5-02
0.061
0.089
0.090
0.122
0.119
0.132
0.145
0.159
n8-49
-13.7
-15.2
-10.9
-9.8
-9.3
-11.5
-17.7
-17.1
Table B.24 400 V, 1150 r/min Type YASKAWA SST4 Series IPM Motor
No.
E5-01
Name
Unit
Default Settings
2432
2433
2435
2436
2438
243A
243B
243D
243E
243F
2440
Voltage Class
400
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18
22
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
E5-02
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15
18.50
22.00
E5-03
0.89
1.72
3.02
4.58
7.40
10.21
13.75
19.5
27.7
32.7
39.2
E5-04
E5-05
10.720
6.080
4.336
2.143
1.428
1.199
0.648
0.460
0.325
0.260
0.209
E5-06
mH
122.20
61.16
70.24
46.20
33.87
41.67
21.24
17.76
12.83
11.68
10.09
E5-07
mH
170.80
97.12
90.04
60.28
42.98
69.15
33.04
22.72
17.19
15.16
16.25
E5-09
mVs/rad
626.1
626.1
703.1
727.6
699.0
861.5
759.7
740.4
716.6
809.1
786.2
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.0022
0.0042
0.0081
0.0133
0.0168
0.027
0.044
0.054
0.063
0.113
0.137
L3-24
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
n5-02
0.080
0.081
0.078
0.088
0.066
0.070
0.085
0.071
0.061
0.089
0.090
n8-49
-8.4
-11.0
-9.9
-9.0
-11.4
-23.2
-22.1
-16.7
-20.2
-15.2
-27.7
484
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
No.
E5-01
Name
Unit
Default Settings
2442
2443
2444
2445
2446
2447
2448
2449
244A
244C
Voltage Class
400
400
400
400
400
400
400
400
400
400
Rated Power
kW
30
37
45
55
75
90k
110
132
160
200
Rated Speed
r/min
1150
1150
1150
1150
1150
1150
1150
1150
1150
1150
kW
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
160.00
200.00
E5-03
51.8
63.0
76.6
93.1
128.1
153.1
186.5
221.9
269.8
336.5
E5-04
E5-05
0.140
0.106
0.076
0.051
0.032
0.026
0.015
0.012
0.009
0.007
E5-06
mH
8.12
6.43
4.96
3.99
2.97
2.44
1.87
1.49
1.41
1.22
E5-07
mH
9.84
7.71
6.56
5.39
3.90
3.23
2.46
2.08
1.88
1.51
E5-09
mVs/rad
888.8
857.7
941.6
853.8
829.6
835.6
833.4
848.6
889.1
915.0
E5-24
mV/(r/min)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Maximum Voltage
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Hz
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
C5-17
Motor Inertia
kgm2
0.252
0.304
0.410
0.55
0.82
0.96
1.60
1.95
2.82
3.70
L3-24
0.122
0.119
0.132
0.145
0.159
0.155
0.211
0.214
0.256
0.268
n5-02
0.122
0.119
0.132
0.145
0.159
0.155
0.211
0.214
0.256
0.268
n8-49
-9.8
-10.2
-11.5
-16.0
-15.7
-15.7
-14.7
-16.5
-14.1
-10.4
Parameter List
E5-02
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
485
486
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Appendix: C
MEMOBUS/Modbus Communications
C.1 MEMOBUS/MODBUS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.2 COMMUNICATION SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.3 CONNECTING TO A NETWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.4 MEMOBUS/MODBUS SETUP PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.5 DRIVE OPERATIONS BY MEMOBUS/MODBUS. . . . . . . . . . . . . . . . . . . . . . . . . .
C.6 COMMUNICATIONS TIMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.7 MESSAGE FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.8 MESSAGE EXAMPLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.9 MEMOBUS/MODBUS DATA TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.10 ENTER COMMAND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.11 COMMUNICATION ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C.12 SELF-DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
488
489
490
492
495
496
497
499
501
513
514
515
487
Slave (Drive)
common_
TMonly
Figure C.1 Connecting Multiple Drives to a PLC
488
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Communication Parameters
Protocol
1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps
Data length
8 bit (fixed)
Parity
Stop bit
1 bit (fixed)
MEMOBUS/Modbus
Communications
Specifications
RS-422, RS-485
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
489
YEC_
TMon
ly
S
S+
R
R+
IG
Send ()
Send (+)
Receive ()
Receive (+)
Shield Ground
(TB5)
2. Check or set the termination resistor selection at all slaves. Use the description in Network Termination on
3.
4.
5.
6.
7.
PLC
R
R+
S
S+
IG
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
Drive
OFF
Drive
OFF
Drive
ON
common_
TMonly
490
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
PLC
R
R+
S
S+
IG
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
S
S+
R
R+
IG
S2
Drive
OFF
Drive
OFF
Drive
common_
TMonly
ON
Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination
resistor that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the
termination resistor by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not
located at the network line end.
Figure C.5 illustrates the setting of DIP switch S2.
To set the DIP switch on the terminal board, use an appropriate sized tool with a tip of approximately 8 mm in width.
Figure C.5
SDIP switch S2
ON
O
N
YEC_TM
only
S+
RS-422
or
RS-485
+
R-
OFF
R+
DIP
switch
S2
(OFF: default)
Termination resistor (1/2 W110 )
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
491
Name
Setting Range
Default
H5-01
0 to FFH <1>
1FH
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01
to any value besides 0 assigns the drive its address in the network. Slave address dont need to be assigned in sequential
order, but each address needs to be unique so that no two drives have the same address.
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note: After changing this parameter, the power must be cycled to enable the new setting.
No.
Name
Setting Range
Default
H5-02
0 to 5
H5-02
Communication Speed
H5-02
Communication Speed
1200 bps
38400 bps
2400 bps
57600 bps
4800 bps
76800 bps
9600 bps
115200 bps
19200 bps
Name
Setting Range
Default
H5-03
0 to 2
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
Name
Setting Range
Default
H5-04
0 to 3
492
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Name
Setting Range
Default
H5-05
0 or 1
Setting 0: Disabled
If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered
and the drive will operate as determined by parameter H5-04.
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
No.
Name
Setting Range
Default
H5-06
5 to 65 ms
5 ms
Figure C.6
PLCDrive
DrivePLC
PLCDrive
Command message
Response message
Command message
Time
common_
TMonly
24 bit length
H5-06 setting
Name
Setting Range
Default
H5-07
0 or 1
Name
Setting Range
Default
H5-09
CE Detection Time
0.0 to 10.0 s
2.0 s
No.
Name
Setting Range
Default
H5-10
0 or 1
MEMOBUS/Modbus
Communications
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
493
Name
Setting Range
Default
H5-11
0 or 1
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last
parameter change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications (b1-02,
b1-16 = 2).
No.
Name
Setting Range
Default
H5-12
0 or 1
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start
and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.
494
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Observe drive status and drive control terminal status from a PLC.
Read and write parameters.
Set and reset faults.
Set multi-function inputs. Inputs settings from the input terminals S and from MEMOBUS/Modbus communications
are both linked by an OR operation.
Parameter
Name
Required Setting
b1-01
b1-02
b1-15
b1-16
MEMOBUS/Modbus
Communications
Refer to b1-01: Frequency Reference Selection 1 on page 137 and Refer to b1-02: Run Command Selection 1 on
page 138 for details on external reference parameter selections. Refer to Setting 2: External reference 1/2 selection on
page 219 for instructions on how to select external reference 1 and 2.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
495
Example
Write parameters
<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it
receives a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
Figure C.7
PLCDrive
DrivePLC
PLCDrive
Command message
Response message
Command message
24 bit length
Time
common_
TMonly
Master Send
Wait Time
A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no
response is received within a certain amount of time, the master should try resending the message.
PLCDrive
DrivePLC
PLCDrive
Command message
Response message
Command message
24 bit length
H5-06
setting
Time
common_
TMonly
496
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a
message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves
do not provide a response to a broadcast type message.
Function Code
The three types of function codes are shown in the table below.
Data Length (bytes)
Function
Code
Function Name
Command Message
Response Message
Minimum
Maximum
Minimum
Maximum
37
03H
08H
Loopback test
10H
11
41
Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test)
and the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers
must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.
Error Check
The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure
described below when calculating the CRC-16 checksum for command data or when verifying response data.
Command Data
When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value
received within the message. Both must match before a command is processed.
An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations in the MEMOBUS/Modbus
protocol.
1.
2.
3.
4.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
497
MEMOBUS/Modbus
Communications
Calculation
Description
Calculation
Overflow
Overflow
Address 02H
XOR w result
Shift 1
Shift 1
XOR w A001H
XOR w A001H
XOR result
XOR result
Shift 2
Shift 2
XOR w A001H
XOR w A001H
XOR result
XOR result
Shift 3
Shift 3
Shift 4
Shift 4
XOR w A001H
XOR w A001H
XOR result
XOR result
Shift 5
Shift 5
Shift 6
Shift 6
XOR w A001H
XOR w A001H
XOR result
XOR result
Shift 7
Shift 7
XOR w A001H
Shift 8
XOR result
XOR w A001H
Shift 8
XOR result
XOR w A001H
XOR result
Perform operations with next data (function code)
CRC-16
Response Data
To be sure that the data is valid, perform a CRC-16 calculation on the response message data as described above.
Compare the result to the CRC-16 checksum that was received within the response message. Both should match.
498
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Slave Address
02H
Slave Address
02H
Slave Address
02H
Function Code
03H
Function Code
03H
Function Code
83H
Upper
00H
Data Quantity
08H
Error Code
Lower
20H
Upper
00H
Lower
04H
Upper
45H
Lower
F0H
Starting No.
Data Quantity
CRC-16
Upper
00H
Lower
65H
Upper
00H
Lower
00H
Next storage
register
Upper
00H
Lower
00H
Next storage
register
Upper
01H
Lower
F4H
CRC-16
Upper
AFH
Lower
82H
CRC-16
03H
Upper
F1H
Lower
31H
Loopback Test
Function code 08H performs a loopback test. This test returns a response message with exactly the same content as the
command message and can be used to check communications between the master and slave. User-defined test code and
data values can be set.
The following table shows a message example when performing a loopback test with the slave 1 drive.
Command Message
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
08H
Function Code
08H
Function Code
89H
Upper
00H
Error Code
Lower
00H
Upper
A5H
Lower
37H
Test Code
Data
00H
Lower
00H
Upper
A5H
Lower
37H
Upper
DAH
Lower
8DH
Test Code
Data
CRC-16
Upper
DAH
Lower
8DH
CRC-16
01H
Upper
86H
Lower
50H
MEMOBUS/Modbus
Communications
CRC-16
Upper
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
499
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Function Code
90H
Upper
00H
Error Code
Lower
01H
Upper
00H
Starting No.
Data Quantity
Upper
00H
Lower
01H
Upper
00H
Lower
02H
Number of Bytes
Starting Data
Next Data
CRC-16
04H
Upper
00H
Lower
01H
Upper
02H
Lower
58H
Upper
63H
Lower
39H
Starting No.
Data Quantity
CRC-16
Lower
02H
Upper
10H
Lower
08H
CRC-16
02H
Upper
CDH
Lower
C1H
Note: For the number of bytes in the command message, take double the number of the data quantity.
500
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Register No.
0000H
Contents
Reserved
Operation Commands and Multi-function Inputs
0001H
bit 0
bit 1
bit 2
bit 3
Fault Reset
bit 4
Multi-Function Input 1
Function is ComRef when H1-01 = 40 (Forward/Stop). Refer to d: Reference Settings on page 182 for ComRef explanations.
bit 5
Multi-Function Input 2
Function is ComCtrl when H1-02 = 41 (Reverse/Stop). Refer to d: Reference Settings on page 182 for ComCtrl explanations.
bit 6
Multi-Function Input 3
bit 7
Multi-Function Input 4
bit 8
Multi-Function Input 5
bit 9
Multi-Function Input 6
bit A
Multi-Function Input 7
bit B
Multi-Function Input 8
bit C to F
Reserved
0002H
Frequency Reference
0003H
V/f Gain
0004H
0005H
0006H
0007H
0008H
0009H
000AH
000BH to 000EH
bit 0
bit 1
bit 2
bit 3 to 5
Reserved
bit 6
bit 7
bit 8 to F
Reserved
000FH
0010H to 001AH
001BH
bit 0
Reserved
bit 1
bit 2
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3
bit 4 to B
Reserved
bit C
bit D
bit E
bit F
Reserved
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
001DH
001EH to 001FH
MEMOBUS/Modbus
Communications
Reserved
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
501
Monitor Data
Monitor data can be read only.
Register No.
Contents
Drive Status 1
bit 0
0020H
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
bit 5
bit 6
bit 7
bit 8 to bit D
Reserved
bit E
ComRef status
bit F
ComCtrl status
Fault Contents 1
0021H
bit 0
bit 1
Overvoltage (ov)
bit 2
bit 3
bit 4
bit 5
Reserved
bit 6
bit 7
bit 8
bit 9
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/UL4)
bit A
PG Disconnected (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Excessive Speed Deviation (dEv),
bit B
bit C
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
bit D
bit E
bit F
bit 2
bit 3
bit 4
bit 5
Writing to EEPROM
bit 6 to bit F
Reserved
0023H
0024H
0025H
Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
0026H
0027H
Output Power
0028H
Torque Reference
Fault Contents 2
bit 0
0029H
502
Reserved
bit 1
bit 2
bit 3
bit 4
bit 5
Reserved
bit 6
bit 7 to bit F
Reserved
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Contents
Alarm Contents1
bit 0, 1
002AH
Reserved
bit 2
bit 3
bit 4
bit 5
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
Reserved
bit F
002BH
bit 0
Terminal S1 Closed
bit 1
Terminal S2 Closed
bit 2
Terminal S3 Closed
bit 3
Terminal S4 Closed
bit 4
Terminal S5 Closed
bit 5
Terminal S6 Closed
bit 6
Terminal S7 Closed
bit 7
Terminal S8 Closed
bit 8 to bit F
Reserved
Drive Status 2
bit 0
002CH
During Run
bit 1
Zero Speed
bit 2
Speed Agree
bit 3
bit 4
Frequency Detection 1
bit 5
Frequency Detection 2
bit 6
Drive Ready
bit 7
During Undervoltage
bit 8
During Baseblock
bit 9
bit A
bit B
Over/Undertorque 1, 2
bit C
bit D
bit E
Fault
bit F
Communication Timeout
bit 1
bit 2
bit 3 to 6
Reserved
bit 7
bit 8 to F
Reserved
002EH
Reserved
002FH
0030H
Reserved
0031H
0032H
0033H
Reserved
0034H
0035H
0036H, 0037H
0038H
Reserved
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
003AH
003BH, 003CH
MEMOBUS/Modbus
Communications
002DH
bit 0
Reserved
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
503
Contents
Communications Error Contents <3>
bit 0
003DH
003EH
003FH
0040H to 004AH
CRC Error
bit 1
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
Output Frequency
r/min <4>
0.01% units
Used for various monitors U1-. Refer to U: Monitors on page 455 for parameter details.
Drive status (U1-12)
bit 0
004BH
004CH to 007EH
007FH
0080H to 0097H
0098H
bit 2
bit 3
bit 4
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
bit 9
bit A
Motor 2 selected
bit B
Reserved
bit E
bit F
Used for various monitors U1-, U4-, U5- and U6-. Refer to U: Monitors on page 455 for parameter details.
Alarm Code, Refer to Alarm Register Contents on page 511 for alarm codes.
Used for monitors U2-, U3-. Refer to U: Monitors on page 455 for parameter details and Refer to Fault Trace Contents on page 510 for register
value descriptions.
High Word of Accumulated Operation Time Monitor, 10H units (U4-01)
0099H
009AH
009BH
009CH to 00AAH
00ABH
00ACH
00ADH
00AEH, 00AFH
Reserved
00B0H
00B1H
Reserved
00B2H
00B3H
00B4H
Reserved
00B5H
00B6H
00B7H
00B8H
00B9H to 00BEH
00BFH
504
During Run
bit 1
Frequency Reference
Reserved
Lists the last to digits of operation error code oPE.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Contents
Fault contents 3
00C0H
bit 1
Undervoltage (Uv1)
bit 2
bit 3
bit 4
Reserved
bit 5
bit 6
Overcurrent (oC)
bit 7
Overvoltage (ov)
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Fault contents 4
00C1H
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
Overspeed (os)
bit 8
bit 9
PG Disconnected (PGo)
bit A
bit B
bit C
bit D
bit E
bit F
Fault contents 5
00C2H
bit 0
bit 1
bit 2, 3
Reserved
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to E
Reserved
bit F
Fault contents 6
bit 0
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
Reserved
bit A
bit B to F
Reserved
MEMOBUS/Modbus
Communications
00C3H
Reserved
bit 1
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
505
Contents
Fault contents 7
00C4H
00C5H
00C6H, 00C7H
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6, 7
Reserved
bit 8
bit 9 to B
Reserved
bit C
bit D
bit E
bit F
Reserved
bit 0, 1
Reserved
bit 2
bit 3 to F
Reserved
Reserved
Alarm contents 2
bit 0
00C8H
Undervoltage (Uv)
bit 1
Overvoltage (ov)
bit 2
bit 3
bit 4
Overtorque 1 (oL3)
bit 5
Overtorque 2 (oL4)
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Overspeed (oS)
Alarm contents 3
bit 0
00C9H
bit 1
PG Disconnected (PGo)
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
Reserved
bit 9
bit A
bit B
Reserved
bit C
bit D
bit E
bit F
Alarm contents 4
bit 0
00CAH
506
Reserved
bit 1
bit 2 to 5
Reserved
bit 6
bit 7
bit 9
bit A
PG Disconnected (PGo)
bit B to F
Reserved
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Contents
Alarm Contents 5
00CBH
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
Reserved
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
Alarm Contents 6
bit 0
00CCH
00CDH to 00CFH
bit 1
bit 2
bit 3
bit 4
bit 5 to 7
Reserved
bit 8
bit 9 to F
Reserved
Reserved
CPF Contents 1
00D0H
bit 0, 1
Reserved
bit 2
bit 3
bit 4, 5
Reserved
bit 6
bit 7
bit 8
bit 9, A
Reserved
bit B
bit C
bit D
bit E
bit F
Reserved
00D1H
00D2H
00D3H to 00D7H
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
bit 0
bit 1
bit 2
bit 3
bit 4 to F
Reserved
MEMOBUS/Modbus
Communications
CPF Contents 2
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
507
Contents
oFA0x Contents (CN5-A)
00D8H
bit 0
bit 1
bit 2
bit 3, 4
Reserved
bit 5
bit 6
bit 7 to F
Reserved
00D9H
00DAH to 00DBH
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
Reserved
oFA3x Contents (CN5-A)
00DBH
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
00DCH
bit 0
bit 1
bit 2
bit 3, 4
Reserved
bit 5
bit 6
bit 7 to F
Reserved
00DDH
00DEH to 00DFH
508
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
Reserved
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Contents
oFb3x Contents (CN5-B)
00E0H
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
00E1H
bit 1
bit 2
bit 3, 4
Reserved
bit 5
bit 6
bit 7 to F
Reserved
00E2H
00E3H, 00E4H
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved
Reserved
oFC3x Contents (CN5-C)
00E5H
00E6H to 00FFH
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
Reserved
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
509
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Contents
Digital Input Command
bit 0
0001H
0002H
bit 1
bit 2, 3
Reserved
bit 4
External Fault
bit 5
Fault Reset
bit 6 to B
Reserved
bit C
bit D
bit E
bit F
Frequency Reference
30000/100%
510
Fault Name
Fault Code
Fault Name
0002H
Undervoltage (Uv1)
0096H
0003H
0097H
0004H
0098H
0006H
0099H
0007H
Overcurrent (oC)
009AH
0008H
Overvoltage (ov)
009BH
0009H
009CH
000AH
009DH
000BH
009EH
000CH
009FH
000DH
00A0H
000EH
00A1H
000FH
00A2H
0010H
00A3H
0011H
00A4H
0012H
0101H
0013H
0102H
0014H
0103H
0015H
0106H
0016H
0107H
0018H
Overspeed (oS)
0111H
0019H
0112H
001AH
PG Disconnect (PGo)
0113H
001BH
0114H
001CH
0115H
001DH
0116H
001EH
0117H
001FH
0118H
0020H
0131H
0021H
0132H
0022H
0133H
0025H
0134H
0026H
0135H
0027H
0136H
0028H
0137H
0029H
0138H
002AH
0139H
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Fault Name
Fault Code
Fault Name
002BH
013AH
0030H
013BH
0032H
013CH
0033H
013DH
0034H
013EH
0035H
0201H
0036H
0202H
0037H
0205H
0038H
0206H
003BH
0210H
0041H
0211H
0042H
0212H
0043H
0213H
0044H
0214H
0045H
0215H
0046H
0216H
0047H
0217H
0048H
0231H
0049H
0232H
004DH
0233H
004EH
0234H
004FH
0235H
0052H
0236H
0083H
0237H
0084H
0238H
0087H
0239H
0088H
023AH
0089H
023BH
008CH
023CH
008DH
023DH
008EH
023EH
008FH
0300H
0091H
0301H
0092H
0302H
0093H
0305H
0094H
0306H
0095H
Alarm Code
Fault Name
0001H
Undervoltage (Uv)
0020H
0002H
Overvoltage (ov)
0022H
0003H
0027H
0004H
0028H
0005H
Overtorque 1 (oL3)
002AH
0006H
Overtorque 2 (oL4)
002BH
PG Disconnected (PGo)
0007H
0031H
0008H
0032H
0009H
0033H
000AH
0034H
000BH
0035H
000CH
0036H
000DH
0038H
000EH
0039H
000FH
003AH
0010H
Overspeed (oS)
003BH
0011H
003CH
0012H
PG Disconnected (PGo)
003DH
0014H
003EH
0015H
003FH
0016H
0040H
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
MEMOBUS/Modbus
Communications
Alarm Code
511
512
Fault Name
Alarm Code
Fault Name
0041H
0018H
0042H
001AH
0043H
001BH
0044H
001DH
0045H
001EH
0049H
001FH
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Description
0900H
Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter changes remain even if the power
supply is cycled.
0910H
Writes data in the RAM only. Parameter changes are lost when the drive is shut off.
Note: Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The Enter
command registers are write-only. Consequently, if these registers are read, then the register address will be invalid (Error code:
02H). An Enter command is not required if reference or broadcast data are sent to the drive.
H5-11 = 0
H5-11 = 1
G7, F7
V7
Data is accepted even if one setting is invalid. The invalid setting will Error occurs if only one setting is invalid. All data that was sent are
be discarded. No error message occurs.
discarded.
MEMOBUS/Modbus
Communications
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
513
Error Code
01H
Cause
Function Code Error
Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
Register Number Error
02H
03H
Read data or write data is greater than 16 bits. Invalid command message quantity.
In a write message, the Number of Data Items contained within the message does not equal twice the amount of data words (i.e., the total of Data 1+ Data
2, etc.).
21H
Control data or parameter write data is outside the allowable setting range.
Attempted to write a contradictory parameter setting.
22H
During run, the user attempted to write a parameter that cannot be written to during run.
During an EEPROM memory data error (CPF06), the master attempted to write to a parameter other than A1-00 to A1-05, E1-03, or o2-04.
Attempted to write to read-only data.
23H
24H
514
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
C.12 Self-Diagnostics
C.12 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the selfdiagnosis function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait
at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
YEC_TMonly
DM
DM+
H2
H1
HC
S
S+
R
R+
IG
MP
RP
E(G) FM AC AM P1 P2 PC SC
SC A1 A2 A3 +V AC -V
S1 S2 S3 S4 S5 S6 S7 S8
4. With the power off, wire the drive as shown in the following diagram, connecting terminals R+ and S+, R- and S-,
and S6 and SC.
MEMOBUS/Modbus
Communications
operating normally.
When a fault occurs, the drive will display
on the keypad display.
8. Turn off the power supply.
9. Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Set back jumper S3 to its original position.
Set terminal S6 to its original function.
10. Return to normal operation.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
515
C.12 Self-Diagnostics
516
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Appendix: D
Standards Compliance
This appendix explains the guidelines and criteria for maintaining CE and UL standards.
D.1 SECTION SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.2 EUROPEAN STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.3 UL STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D.4 SAFE DISABLE INPUT FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
518
520
526
530
517
WARNING
518
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded wire for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair
wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting other
devices.
Standards
Compliance
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
519
YEC_common
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
Low Voltage Directive: 2006/95/EC
EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives
displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure
compliance with CE standards. After setting up the device, verify that conditions meet European standards.
Fuse Type
Manufacturer: Bussmann
Model
520
2A0004
FWH-70B
70
2A0006
FWH-70B
70
2A0008
FWH-70B
70
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0018
FWH-90B
90
2A0021
FWH-90B
90
2A0030
FWH-100B
100
2A0040
FWH-200B
200
2A0056
FWH-200B
200
2A0069
FWH-200B
200
2A0081
FWH-300A
300
2A0110
FWH-300A
300
2A0138
FWH-350A
350
2A0169
FWH-400A
400
2A0211
FWH-400A
400
2A0250
FWH-600A
600
2A0312
FWH-700A
700
2A0360
FWH-800A
800
2A0415
FWH-1000A
1000
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Model
CIMR-A
Manufacturer: Bussmann
Model
4A0002
FWH-40B
40
4A0004
FWH-50B
50
4A0005
FWH-70B
70
4A0007
FWH-70B
70
4A0009
FWH-90B
90
4A0011
FWH-90B
90
4A0018
FWH-80B
80
4A0023
FWH-100B
100
4A0031
FWH-125B
125
4A0038
FWH-200B
200
4A0044
FWH-250A
250
4A0058
FWH-250A
250
4A0072
FWH-250A
250
4A0088
FWH-250A
250
4A0103
FWH-250A
250
4A0139
FWH-350A
350
4A0165
FWH-400A
400
4A0208
FWH-500A
500
4A0250
FWH-600A
600
4A0296
FWH-700A
700
4A0362
FWH-800A
800
4A0414
FWH-800A
800
4A0515
FWH-1000A
1000
4A0675
FWH-1200A
1200
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive also comply with EMC guidelines.
Standards
Compliance
1. Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
521
B
A
D
U/T1
V/T2
W/T3
YEC_common
A Drive
B 10 m max cable length between drive and motor
C Motor
D Metal conduit
E Ground wire should be as short as possible.
5. Ground the largest possible surface area of the shield to the metal conduit when using braided shield cable.
Yaskawa recommends using a cable clamp.
Figure D.3
C
A Braided shield cable
B Metal panel
YEC_common
B
C Cable clamp (conductive)
522
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
L3
L2
K
L1
PE
B
C
D
L3 L2 L1
J
E
D
I
A
G
A
B
C
D
E
F
G
H
I
J
K
YEC_common
Motor
Cable clamp
Ground plate (scrape off any visible paint)
EMC noise filter
Make sure the ground wire is grounded
Standards
Compliance
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
523
Type
Weight
(kg)
Dimensions
[W x D x H]
(mm)
YxX
Figure
FS5972-10-07
10
1.2
141 46 330
115 313
FS5972-18-07
18
1.3
141 46 330
115 313
2A0008
2A0010
2A0012
2A0018
2A0021
FS5972-35-07
35
2.1
206 50 355
175 336
FS5972-60-07
60
4.0
236 65 408
205 390
FS5972-100-35
100
3.4
90 150 330
65 255
FS5972-170-40
170
6.0
102 365
FS5972-250-37
250
11.7
90 498
FS5972-410-99
410
10.5
235 120
FS5972-600-99
600
11
235 120
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
FS5972-10-07
10
1.1
141 46 330
115 313
FS5972-18-07
18
1.7
141 46 330
115 313
4A0007
4A0009
4A0011
4A0018
4A0023
FS5972-35-07
35
2.1
206 50 355
175 336
FS5972-60-07
60
236 65 408
202 390
FS5972-100-35
100
3.4
90 150 330
65 255
FS5972-170-35
170
4.7
102 365
FS5972-250-37
250
11.7
90 498
FS5972-410-99
400
10.5
235 120
FS5972-600-99
600
11
235 120
FS5972-800-99
800
31.5
275 210
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
524
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Y
W
H
X
W
Y
D
D
Figure 1
Figure 2
W
YEC_common
Figure 3
Figure D.5 EMC Filter Dimensions
DC Reactor
Model
Rating
UZDA-B
5.4 A
8 mH
UZDA-B
3.2 A
28 mH
Standards
Compliance
Note: Contact Yaskawa for information about DC reactors for other models.
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
525
D.3 UL Standards
D.3 UL Standards
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
Figure D.6
UL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions
described below must be met to maintain compliance when using this drive in combination with other equipment:
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Main Circuit Terminal Wiring
Cable Connectors
Yaskawa recommends using UL-listed copper wires (rated at 75C), and closed-loop connectors or CSA-certified ring
connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp
tool to install connectors per manufacturer recommendation. Table D.4 lists a suitable closed-loop connector
manufactured by JST Corporation.
Table D.4 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Wire Gauge
mm2 (AWG)
0.75 (18)
1.25 (16)
2 (14)
3.5/5.5 (12/10)
8 (8)
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R2-3.5
M4
R2-4
M5
R2-5
M6
R2-6
M4
R5.5-4
M5
R5.5-5
M6
R5.5-6
M8
R5.5-8
M4
8-4
M5
R8-5
M6
R8-6
M8
R8-8
M4
14-4 <1>
M5
R14-5
M6
R14-6
M8
R14-8
M10
R22-10
M12
R22-12
30/38 (3/2)
M12
R38-12
M12
R60-12
80 (2/0)
M12
R80-12
100 (4/0)
M12
R100-12
M10
150-10
M12
150-12
M10
200-10
M12
R200-12
M12
325-12
14 (6)
22 (4)
150 (250/300MCM)
200 (400MCM)
325 (600/650MCM)
526
Tightening Torque
Nxm (lbxin.)
Terminal Screws
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
D.3 UL Standards
<1> Use the specified crimp terminals (Model 14.NK4) when using CIMR-A2A0030, 2A0040, 4A0018, and 4A0023 with 14 mm2 (6 AWG).
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75C 600 Vac UL-approved vinyl-sheathed insulation.
The installation manual specifies that branch circuit protection should be provided by any of the following:
Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
Time-delay Class RK5 fuses sized at 225% of the drive input rating
Table D.5 Recommended Input Fuse Selection
Model
CIMR-A
Fuse Type
Manufacturer: Bussmann
Model
2A0004
FWH-70B
70
2A0006
FWH-70B
70
2A0008
FWH-70B
70
2A0010
FWH-70B
70
2A0012
FWH-70B
70
2A0018
FWH-90B
90
2A0021
FWH-90B
90
2A0030
FWH-100B
100
2A0040
FWH-200B
200
2A0056
FWH-200B
200
2A0069
FWH-200B
200
2A0081
FWH-300A
300
2A0110
FWH-300A
300
2A0138
FWH-350A
350
2A0169
FWH-400A
400
2A0211
FWH-400A
400
2A0250
FWH-600A
600
2A0312
FWH-700A
700
2A0360
FWH-800A
800
2A0415
FWH-1000A
1000
4A0002
FWH-40B
40
4A0004
FWH-50B
50
4A0005
FWH-70B
70
4A0007
FWH-70B
70
4A0009
FWH-90B
90
4A0011
FWH-90B
90
4A0018
FWH-80B
80
4A0023
FWH-100B
100
4A0031
FWH-125B
125
4A0038
FWH-200B
200
4A0044
FWH-250A
250
4A0058
FWH-250A
250
4A0072
FWH-250A
250
4A0088
FWH-250A
250
4A0103
FWH-250A
250
4A0139
FWH-350A
350
4A0165
FWH-400A
400
4A0208
FWH-500A
500
4A0250
FWH-600A
600
4A0296
FWH-700A
700
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Standards
Compliance
D
527
D.3 UL Standards
Fuse Type
Model
CIMR-A
Manufacturer: Bussmann
4A0362
Model
FWH-800A
800
4A0414
FWH-800A
800
4A0515
FWH-1000A
1000
4A0675
FWH-1200A
1200
Terminal Signal
P1, P2, PC
RP, AC
MP, AC
H1, H2, HC
DM+, DM-
Use the internal control power supply of the drive or an external class 2
power supply.
528
Description
Disabled
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below
the rated speed. The motor overload detection level (oL1) is automatically reduces when running below the motor rated
speed.
Selects protection characteristics for a motor with self-cooling capability within a speed range of 10:1. The motor
overload detection level (oL1) is automatically reduced when running below 1/10 of the motor rated speed.
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
D.3 UL Standards
Setting
Description
Selects protection characteristics for a motor capable of cooling itself at any speed including zero speed (externally
cooled motor). The motor overload detection level (oL1) is constant over the entire speed range.
Selects protection characteristics for a variable torque PM motor. The motor overload detection level (oL1) is
automatically reduces when running below the motor rated speed.
Selects protection characteristics for a constant torque PM motor. The motor overload detection level (oL1) is constant
over the whole speed range.
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below
the rated speed. The motor overload detection level (oL1) is automatically reduces when running below the motor rated
speed.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable the motor overload protection (L1-01 = 1 to 5) when connecting the drive to a single motor, unless another motor
overload preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts
off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually
calculated as long as the drive is powered up.
L1-02 Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is
running at 60 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the
set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Figure D.7
Time (min)
10
7
3
Cold Start
1
0.4
Hot Start
0.1
0
100
150
200
Standards
Compliance
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
529
Inputs / Outputs
Operation Time
Failure Probability
Time from input open to drive output stop is less than 1 ms.
Demand Rate Low
PFD = 5.15E-5
PFH = 1.2E-9
Performance Level
The Safe Disable Inputs satisfy all requirements of Performance Level (PL) d according to ISO13849-1. (Note: DC
from EDM considered.)
Precautions
DANGER! Improper use of the Safe Disable function can result in serious injury or even death.
Make sure the whole system or machinery that the Safe Disable function is used in complies with safety requirements. When
implementing the Safe Disable function into the safety system of a machine, a thorough risk assessment for the whole system has to
be carried out to assure it complies with relevant safety norms (e.g., EN954/ISO13849, IEC61508, EN/IEC62061,...).
DANGER! When using a PM motor, even if the drive output is shut off by the Safe Disable function, a break down of two output
transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180 degree
(electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function.
This is not a concern with induction motors.
DANGER! The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically
isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the
drive input side as well as the drive output side.
DANGER! When using the Safe Disable inputs, make sure to remove the wire links between terminals H1, H2, and HC that were
installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause injury or even
death.
DANGER! All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating
normally, there is a risk of serious personal injury.
DANGER! Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should
be permitted to wire, inspect, and maintain the Safe Disable input.
NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 1 ms for drive output to shut off completely. The
sequence set up to trigger terminals H1 and H2 should make sure that both terminals remain open for at least 1 ms in order to properly
interrupt drive output.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the
Safe Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
When utilizing the Safe Disable function, use only the EMC filters recommended in EMC Filters on page 524.
530
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Main Power
24 Vdc
Control
Circuit
HC
Feedback
Safety
Outputs
Jumper S3
Setting:
SINK
H1
Gate Block 1
N Power Module P
H2
Gate Block 2
DM+
>=1
DMDrive
YEC_common
M
Motor coasts
to stop
Output
Frequency
Run Command
Run
Stop
H1, H2 Input
Drive Output
Normal operation
Safe Torque-Off
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive
output. If the motor was running before the Safe Disable inputs opened, then the motor will coast to stop, regardless of
the stopping method set in parameter b1-03.
Notice that the Safe Torque Off state can only be achieved using the Safe Disable function. Removing the Run
command stops the drive and shuts the output off (baseblock), but does not create a Safe Torque Off status.
Note: To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor
has completely stopped.
The Safe Disable function can only be deactivated when a Run command is not active.
When Safe Disable was activated during stop, normal operation can be resumed by simply turning on both Safe Disable
inputs (i.e., by deactivating Safe Torque Off).
Standards
Compliance
When Safe Disable was activated during run, first the Run command has to be removed and then the Safe Disable inputs
have to be turned on before the drive can be restarted.
D
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
531
Input 2, H2-HC
OFF
OFF
OFF
Hbb (flashes)
ON
OFF
ON
HbbF (flashes)
OFF
ON
ON
HbbF (flashes)
ON
ON
ON
Normal display
With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This
signal should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit
leaving the Safe Torque Off status in case the safety circuit malfunctions. Refer to the instruction manual of the safety
device for details on this function.
Digital Operator Display
When both Safe Disable inputs are open, Hbb will flash in the digital operator display.
Should only one of the Safe Disable channels be on while the other is off, HbbF will flash in the display to indicate that
there is a problem in the safety circuit or in the drive. This display should not appear under normal conditions if the Safe
Disable circuit is utilized properly. Refer to Alarm Codes, Causes, and Possible Solutions on page 323 to resolve
possible errors.
532
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Appendix: E
Quick Reference Sheet
The following tables have been provided for the users convenience. Fill in the cells that have
been left blank as is appropriate for your drive, and keep this information as a quick reference
guide to drive and motor data as well as parameter settings
E.1 DRIVE AND MOTOR SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534
E.2 MULTI-FUNCTION I/O TERMINAL SETTINGS RECORD . . . . . . . . . . . . . . . . . . . 535
E.3 USER SETTING TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
533
CIMR-AA2A0021FAA
MODEL :
MAX APPLI. MOTOR : 5.5kW / 3.7kW REV : A
INPUT : AC3PH 200-240V 50/60Hz 24A/18.9A
OUTPUT : AC3PH 0-240V 0-400Hz 21A/17.5A
MASS : 3.5 kg
PRG : 1010
O/N
:
S/N
:
FILE NO : E131457
TYPE 1 ENCLOSURE
IP20
IND.CONT.EQ.
7J48 B
Software version
YEC_
common
PASS
MADE IN JAPAN
Enclosure type
Items
Model
Description
CIMR-A
Serial Number
Date of Usage
Motor
Induction Motor
Items
Description
Items
Description
Manufacturer
Model
Hz
kW
r/min
Description
Items
Description
Manufacturer
Model
Hz
kW
r/min
534
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
E.2
These tables have been provided for the customer to keep a record of the functions assigned to each multi-function
terminal.
Used/Reserved
S1
H1-01=
S2
H1-02=
S3
H1-03=
S4
H1-04=
S5
H1-05=
S6
H1-06=
S7
H1-07=
S8
H1-08=
Memo
Used/Reserved
RP
H6-01=
A1
H3-02=
A2
H3-10=
A3
H3-06=
Memo
Used/Reserved
M1-M2
Memo
H2-01=
Used/Reserved
P1
H2-02=
P2
H2-03=
Memo
Used/Reserved
AM
H4-04=
Memo
Quick Reference
Sheet
FM
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
535
No.
Name
User
Setting
No.
Name
A1-00
Language Selection
b5-11
A1-01
b5-12
A1-02
b5-13
A1-03
Initialize Parameters
b5-14
A1-04
Password
b5-15
A1-05
Password Setting
b5-16
A1-06
Application Preset
b5-17
A1-07
b5-18
b5-19
b5-20
A2-01 to
A2-32
User Parameters 1 to 32
A2-33
b5-34
b1-01
b5-35
b1-02
b5-36
b1-03
b5-37
b1-04
b5-38
b1-05
b5-39
b1-06
b5-40
b1-07
b6-01
b1-08
b6-02
b1-14
b6-03
b1-15
b6-04
b1-16
b7-01
b1-17
b7-02
b2-01
b2-02
b8-02
b2-03
b8-03
b2-04
b8-04
b2-08
b8-05
b2-12
b8-06
b2-13
b9-01
b2-18
b9-02
b3-01
C1-01
Acceleration Time 1
b3-02
C1-02
Deceleration Time 1
b3-03
C1-03
Acceleration Time 2
b3-04
C1-04
Deceleration Time 2
b3-05
C1-05
b3-06
C1-06
b3-10
C1-07
b3-14
C1-08
b3-17
C1-09
b3-18
C1-10
b3-19
C1-11
b3-24
C2-01
b3-25
C2-02
b4-01
C2-03
b4-02
C2-04
b5-01
b8-01
Fast-Stop Time
C3-01
b5-02
C3-02
b5-03
C3-03
b5-04
C3-04
b5-05
C3-05
b5-06
C3-21
b5-07
C3-22
b5-08
536
b5-09
b5-10
C3-23
C3-24
C4-01
User
Setting
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
C4-02
Name
User
Setting
No.
Name
d4-08
C4-03
d4-09
C4-04
d4-10
C4-05
d5-01
C4-06
d5-02
C4-07
d5-03
C5-01
d5-04
Speed Limit
C5-02
d5-05
C5-03
d5-06
C5-04
d5-08
C5-05
ASR Limit
d6-01
C5-06
d6-02
C5-07
d6-03
C5-08
d6-06
C5-12
d7-01
Offset Frequency 1
C5-17
Motor Inertia
d7-02
Offset Frequency 2
C5-18
d7-03
Offset Frequency 3
C5-21
E1-01
C5-22
E1-03
C5-23
E1-04
C5-24
E1-05
Maximum Voltage
C5-25
E1-06
Base Frequency
C5-26
E1-07
C5-27
E1-08
C5-28
E1-09
C5-32
E1-10
C5-37
Motor 2 Inertia
E1-11
C5-38
E1-12
C6-01
E1-13
Base Voltage
C6-02
E2-01
C6-03
E2-02
C6-04
E2-03
C6-05
E2-04
C6-09
E2-05
d1-01
Frequency Reference 1
E2-06
d1-02
Frequency Reference 2
E2-07
d1-03
Frequency Reference 3
E2-08
d1-04
Frequency Reference 4
E2-09
d1-05
Frequency Reference 5
E2-10
d1-06
Frequency Reference 6
E2-11
d1-07
Frequency Reference 7
E3-01
d1-08
Frequency Reference 8
E3-04
d1-09
Frequency Reference 9
E3-05
d1-10
Frequency Reference 10
E3-06
d1-11
Frequency Reference 11
E3-07
d1-12
Frequency Reference 12
E3-08
d1-13
Frequency Reference 13
E3-09
d1-14
Frequency Reference 14
E3-10
d1-15
Frequency Reference 15
E3-11
d1-16
Frequency Reference 16
E3-12
d1-17
E3-13
d2-01
E4-01
d2-02
E4-02
d2-03
E4-03
d3-01
Jump Frequency 1
E4-04
d3-02
Jump Frequency 2
E4-05
d3-03
Jump Frequency 3
E4-06
d3-04
E4-07
d4-01
E4-08
d4-03
E4-09
d4-04
E4-10
d4-05
E4-11
E5-01
E5-02
E5-03
d4-06
d4-07
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
User
Setting
Quick Reference
Sheet
No.
537
Name
User
Setting
No.
Name
E5-04
F6-20
E5-05
F6-21
E5-06
F6-22
E5-07
F6-23
E5-09
F6-24
E5-11
F6-25
E5-24
F6-26
F1-01
F6-30
F1-02
F6-31
F1-03
F6-32
F1-04
F6-35
F1-05
PG 1 Rotation Selection
F6-36
F1-06
F6-50
F1-08
F6-51
F1-09
F6-52
F1-10
F6-53
F1-11
F6-54
F1-12
PG 1 Gear Teeth 1
F6-55
F1-13
PG 1 Gear Teeth 2
F6-56
F1-14
F6-57
F1-18
F6-58
F1-19
F6-59
F1-20
F6-60
F1-21
PG 1 Signal Selection
F6-61
F1-30
F6-62
F1-31
F6-63
F1-32
PG 2 Rotation Selection
F1-33
PG 2 Gear Teeth 1
H1-01
F1-34
PG 2 Gear Teeth 2
H1-02
F1-35
F1-36
H1-03
H1-04
H1-05
H1-06
H1-07
H1-08
F1-37
F2-01
F2-02
F2-03
F3-01
F3-03
F4-01
F4-02
F4-03
F4-04
H2-01
F4-05
H2-02
F4-06
H2-03
F4-07
H2-06
F4-08
H3-01
F5-01
H3-02
F5-02
H3-03
F5-03
H3-04
F5-04
H3-05
F5-05
H3-06
F5-06
H3-07
F5-07
H3-08
F5-08
H3-09
F5-09
538
H3-10
F6-01
H3-11
F6-02
H3-12
F6-03
H3-13
F6-04
H3-14
F6-06
H4-01
F6-07
H4-02
H4-03
F6-08
F6-10
H4-04
User
Setting
F6-11
H4-05
F6-14
H4-06
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
H4-07
L5-02
L5-04
H4-08
L5-05
H5-01
H5-02
H5-03
H5-04
H5-05
H5-06
H5-07
H5-09
CE Detection Time
H5-10
H5-11
H5-12
H6-01
H6-02
H6-03
H6-04
H6-05
H6-06
H6-07
No.
Name
Auto Restart Fault Output Operation Selection
L6-01
L6-02
L6-03
L6-04
L6-05
L6-06
L6-08
L6-09
L6-10
L6-11
L7-01
L7-02
L7-03
L7-04
L7-06
L7-07
L8-01
H6-08
L8-02
L1-01
L8-03
L1-02
L8-05
L1-03
L8-07
L1-04
L8-09
L1-05
L8-10
L1-13
L8-11
L2-01
L8-12
L2-02
L8-15
L2-03
L8-18
L2-04
L8-19
L2-05
L8-27
L2-06
L8-29
L2-07
L8-35
L2-08
L8-38
L2-10
L8-40
L2-11
L8-41
L2-29
L8-55
L3-01
n1-01
L3-02
n1-02
L3-03
n1-03
L3-04
n1-05
L3-05
n2-01
L3-06
n2-02
L3-11
n2-03
L3-17
n3-01
n3-02
L3-20
n3-03
L3-21
n3-04
L3-22
n3-13
L3-23
n3-14
L3-24
n3-21
L3-25
n3-23
L3-26
n5-01
L3-27
n5-02
L4-01
n5-03
L4-02
n6-01
L4-03
n6-05
L4-04
n8-01
L4-05
n8-02
L4-06
n8-35
L4-07
n8-45
L5-01
n8-47
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
User
Setting
Quick Reference
Sheet
User
Setting
No.
539
Name
n8-48
Pull-In Current
n8-49
No.
Name
T2-16
n8-51
T2-17
n8-54
T3-01
n8-55
Load Inertia
T3-02
n8-57
T3-03
Motor Inertia
n8-62
T3-04
n8-65
o1-01
o1-02
o1-03
o1-04
o1-10
o1-11
o2-01
o2-02
o2-03
o2-04
o2-05
o2-06
o2-07
o3-01
o3-02
o4-01
o4-02
o4-03
o4-05
o4-07
o4-09
o4-11
o4-12
o4-13
r1-01 to
r1-40
T1-00
User
Setting
q1-01 to
q6-07
540
User
Setting
T1-01
T1-02
T1-03
T1-04
T1-05
T1-06
T1-07
T1-08
T1-09
T1-10
T1-11
T2-01
T2-02
T2-03
PM Motor Type
T2-04
T2-05
T2-06
T2-07
T2-08
T2-09
T2-10
T2-11
T2-12
T2-13
T2-14
T2-15
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Index
Symbols
-. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
+1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
+2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
+3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
+V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67
67
67
67
76
Numerics
1800 r/min Type Yaskawa SMRA Series SPM Motor
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24 V Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-Wire Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-Wire Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-Wire Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-Wire Sequence Wiring Diagram . . . . . . . . . . . . . . . . . . . . . .
5th Most Recent Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
472
380
133
133
218
218
458
A
A/D Conversion Error . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 310
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
A1000 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
A1-02 (Motor 1 Control Mode) Dependent Parameters. . . . . . 462
A2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
AC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76, 77
AC Reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Accel/Decel Rate Calculation Gain . . . . . . . . . . . . . . . . . . . . . 264
Accel/Decel Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303, 399
Accel/Decel Time Setting Units . . . . . . . . . . . . . . . . . . . . . . . . 168
Accel/Decel Time Switching Frequency . . . . . . . . . . . . . . . . . 167
Acceleration Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Acceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Acceleration Time Pull-In Current . . . . . . . . . . . . . . . . . . . . . . 450
Acceleration/Deceleration Pull-In Current. . . . . . . . . . . . . . . . 285
Access Level Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . 127, 132
Action Selection below Minimum Output Frequency . . . . . . . 141
Additional DC Bus Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . 265
Adjusted Slip Calculation Error . . . . . . . . . . . . . . . . . . . . . . . . 332
Adjusting the ASR Parameters. . . . . . . . . . . . . . . . . . . . . . . . . 173
AEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
AFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
AFR Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
AFR Time Constant 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
AFR Time Constant 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
AI-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
AI-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Alarm Outputs for Maintenance Monitors . . . . . . . . . . . . . . . . 353
Alarm Register 007FH Contents . . . . . . . . . . . . . . . . . . . . . . . 511
Alarms and Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Allowable Frequency Fluctuation . . . . . . . . . . . . . . . . . . 397, 398
Allowable Voltage Fluctuation . . . . . . . . . . . . . . . . . . . . . 397, 398
ALM LED Light. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
AM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Ambient Temperature and Installation Method Derating. . . . . 404
Ambient Temperature Setting. . . . . . . . . . . . . . . . . . 274, 403, 446
Analog Filter Time Constant . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Analog Frequency Reference Fluctuation Limit . . . . . . . . . . . 189
Analog Frequency Reference Sample/Hold . . . . . . . . . . . . . . . 223
B
B1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
B2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Backing Up Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . 127
Base Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200, 318
Base Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Baseblock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Baseblock Signal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Basic Auto-Tuning Preparations. . . . . . . . . . . . . . . . . . . . . . . . 116
Basic Start-up and Motor Tuning . . . . . . . . . . . . . . . . . . . . . . . 103
bb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 323
Before Auto-Tuning the Drive . . . . . . . . . . . . . . . . . . . . . . . . . 116
Bi-Directional Speed Search Selection. . . . . . . . . . . . . . . . . . . 151
boL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310, 323
Bottom Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Braking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
Braking Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379, 385
Braking Resistor Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Braking Resistor Overheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Braking Resistor Overheat Protection . . . . . . . . . . . . . . . . . . . 399
Braking Resistor Overload Protection . . . . . . . . . . . . . . . . . . . 386
Braking Resistor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Braking Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Braking Transistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Braking Transistor Overload Fault . . . . . . . . . . . . . . . . . . 310, 323
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
541
C
Cable Length Between Drive and Motor . . . . . . . . . . . . . . . . . . 73
CALL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 323
Cannot Change Parameter Settings . . . . . . . . . . . . . . . . . . . . . 340
Cannot Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 324
CANopen Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 214, 216
Capacitor Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Capacitor Maintenance Setting . . . . . . . . . . . . . . . . . . . . 291, 451
Capacitor Maintenance Time . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Carrier Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . 178, 397, 398
Carrier Frequency and Current Derating . . . . . . . . . . . . . . . . . 180
Carrier Frequency Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
Carrier Frequency during Rotational Auto-Tuning . . . . . . . . . 180
Carrier Frequency Lower Limit . . . . . . . . . . . . . . . . . . . . . . . . 179
Carrier Frequency Proportional Gain . . . . . . . . . . . . . . . . . . . . 179
Carrier Frequency Reduction . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Carrier Frequency Reduction Off-Delay Time. . . . . . . . . . . . . 276
Carrier Frequency Reduction Selection . . . . . . . . . . . . . . . . . . 276
Carrier Frequency Selection. . . . . . . . . . . . . . . . . . . 179, 300, 301
Carrier Frequency Setting Error. . . . . . . . . . . . . . . . . . . . 308, 331
Carrier Frequency Upper Limit . . . . . . . . . . . . . . . . . . . . . . . . 179
CC-Link Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214, 216
CE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 306, 310, 324
CE Detection Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
CE Low Voltage Directive Compliance . . . . . . . . . . . . . . . . . . 520
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
CF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 310
Changing Parameter Settings or Values . . . . . . . . . . . . . . . . . . . 99
Circulation fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 36
Closed Loop Vector control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Closed Loop Vector Control for PM Motors . . . . . . . . . . . . . . . 30
Closed-Loop Crimp Terminal Size . . . . . . . . . . . . . . . . . . . . . 526
Coast to stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Coast to Stop with Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Command Messages from Master to Drive . . . . . . . . . . . . . . . 496
Communication Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Communication Fault Detection Selection . . . . . . . . . . . . . . . 493
Communication Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Communication Option Card Reference . . . . . . . . . . . . . . . . . 459
Communication Option Station Number Setting Error
(CC-Link, CANopen, MECHATROLINK-II) . . . . . . . . . . . . . 323
Communication Parity Selection . . . . . . . . . . . . . . . . . . . . . . . 492
Communication Speed Selection . . . . . . . . . . . . . . . . . . . . . . . 492
Communications Enter Function Selection . . . . . . . . . . . . . . . 494
Communications Error Operation Selection . . . . . . . . . . . . . . 214
Communications Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496
Comparing Parameter Settings. . . . . . . . . . . . . . . . . . . . . . . . . 337
Complementary PG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Compressor Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Connected Machinery Vibrates When Motor Rotates . . . . . . . 344
Connecting a DC Reactor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Connecting a Noise Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
Connecting a Suppression Diode . . . . . . . . . . . . . . . . . . . . . . . . 77
Connecting a Surge Absorber. . . . . . . . . . . . . . . . . . . . . . . . . . 389
Connecting an AC Reactor. . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Connecting Braking Units in Parallel. . . . . . . . . . . . . . . . . . . . 387
Connecting Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . 382
Connecting to a PC (USB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Connection of a Motor PTC . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Continuous Electrothermal Operation Selection . . . . . . . . . . . 251
Control Board Connection Error . . . . . . . . . . . . . . . . . . . . . . . 311
542
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
D
D Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
d References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Daily Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351
d-Axis ACR Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
d-Axis Current for High Efficiency Control. . . . . . . . . . . . . . . 285
DC Bus Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
DC Bus Pre-Charge Relay Maintenance Setting . . . . . . . . . . . 291
DC Bus Undervoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
DC Bus Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
DC Bus Voltage Adjustment Gain . . . . . . . . . . . . . . . . . . . . . . 263
DC Bus Voltage at Previous Fault . . . . . . . . . . . . . . . . . . . . . . 457
DC Bus Voltage Setpoint during KEB . . . . . . . . . . . . . . . . . . . 258
DC Injection Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
DC Injection Braking at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . 345
DC Injection Braking Current . . . . . . . . . . . . . . . . . . . . . 145, 345
DC Injection Braking Input Timing Diagram . . . . . . . . . . . . . 225
DC Injection Braking Start Frequency . . . . . . . . . . . . . . . . . . . 144
DC Injection Braking Time at Start . . . . . . . . . . . . . . . . . . . . . 145
DC Injection Braking Time at Stop . . . . . . . . . . . . . . . . . . . . . 145
DC Injection Braking to Stop . . . . . . . . . . . . . . . . . . . . . . . . . . 140
DC Reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
DC Reactors for EN 61000-3-2 Compliance . . . . . . . . . . . . . . 525
Deceleration Rate Calculation Gain . . . . . . . . . . . . . . . . . . . . . 444
Deceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Deceleration Time at Stall Prevention during
Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260, 444
Defaults by Drive Model Selection (o2-04) and
ND/HD (C6-01) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
Delay Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Derivative Time (D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Desired DC Bus Voltage during KEB . . . . . . . . . . . . . . . . . . . 443
dEv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 306, 312, 324
DeviceNet Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 214, 216
dFPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
DI-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
DI-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Diagnosing and Resetting Faults . . . . . . . . . . . . . . . . . . . . . . . 338
Digital Input Card Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Digital Input Option Card Input Selection . . . . . . . . . . . . . . . . 212
Digital Input Option DI-A3 Data Length Selection . . . . . . . . . 213
Digital Input Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35, 36, 93, 94
Digital Operator Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Digital Operator Display Selection . . . . . . . . . . . . . . . . . 287, 450
Digital Operator Installation Methods and Required Tools . . . . 45
Digital Operator Keypad Functions . . . . . . . . . . . . . . . . . . . . . 288
Digital Operator Menu and Screen Structure . . . . . . . . . . . . . . . 96
Digital Operator Remote Installation . . . . . . . . . . . . . . . . . . . . . 45
Digital Operator Remote Usage . . . . . . . . . . . . . . . . . . . . . . . . . 44
Digital Output Card Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Digital Output Option Card Terminal Function Selection . . . . 214
Digital Text Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Dimensions for IP00 Enclosure
200 V Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
400 V Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Dimensions for IP20/NEMA Type 1 Enclosure
200 V Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
400 V Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
DIP Switch S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
DIP Switch S1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
DIP Switch S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37, 87, 491
DM- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
DM+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
dnE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 324
DO-A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
DO-A3 Output Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . 214
DO-A3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Drive Baseblock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Drive Capacity Setting Fault . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Drive Capacity Signal Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Drive Cooling Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Drive Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35
Drive Cover 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Drive cover 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Drive Derating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
Drive Disabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 324
Drive Does Not Allow Selection of Rotational
Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
Drive Duty Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Drive Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97, 98
Drive Mode Unit Monitor Selection. . . . . . . . . . . . . . . . . 287, 450
Drive Model Mismatch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Drive Model Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Drive Models and Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Drive Motor Overload Protection. . . . . . . . . . . . . . . . . . . . . . . 528
Drive Operation Status at Previous Fault . . . . . . . . . . . . . . . . . 457
Drive Overheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Drive Overheat Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Drive Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 318
Drive Ready . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Drive Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Drive Short-Circuit Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
Drive Slave Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 492
Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Drive Standard Connection Diagram . . . . . . . . . . . . . . . . . . . . . 56
Drive Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Drive Transmit Wait Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Drive Unit Setting Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Drive Unit Signal Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Drive Watt Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
Drive/kVA Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451
DriveWizard Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128, 380
DriveWorksEZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
DriveWorksEZ Connection Parameters . . . . . . . . . . . . . . . . . . 292
DriveWorksEZ Custom Monitor 1 to 10 . . . . . . . . . . . . . . . . . 461
DriveWorksEZ Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
DriveWorksEZ Function Selection. . . . . . . . . . . . . . . . . . . . . . 135
DriveWorksEZ Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
DriveWorksEZ Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Droop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Droop Control Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Droop Control Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Droop Control Limit Selection . . . . . . . . . . . . . . . . . . . . . . . . . 163
DRV LED Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
During Frequency Output Time Chart . . . . . . . . . . . . . . . . . . . 235
During Run 2, Motor Switch Command Input . . . . . . . . . . . . . 307
During Run Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
dv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
dv2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
dv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
dv3 Detection Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
dv4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
dv4 Detection Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
dWAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 312
Dwell Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162, 303
Dwell Reference at Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Dwell Reference at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Dwell Time at Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Dwell Time at Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
DWEZ Connection Parameters. . . . . . . . . . . . . . . . . . . . . . . . . 452
DWEZ Version Control Monitor 1 to 3 . . . . . . . . . . . . . . . . . . 461
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
543
dWFL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Dynamic Braking Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Dynamic Braking Transistor . . . . . . . . . . . . . . . . . . . . . . 306, 320
E
E (G). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
E3-01 (Motor 2 Control Mode) Dependent Parameters. . . . . . 463
EEPROM Memory Data Error. . . . . . . . . . . . . . . . . . . . . . . . . 311
EEPROM Write Error . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 313
EF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 324
EF0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 313, 324
EF1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF1 to EF7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 307
EF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 324
EF7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 325
EF8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 325
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
EMC Filter and Drive Installation for CE Compliance . . . . . . 523
EMC Filter Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
EMC Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524
EMC Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
EMC Guidelines Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . 521
EN61800-3 C2 Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524
Enclosure Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Encoder Z-Pulse Offset . . . . . . . . . . . . . . . . . . . . . . . . . . 123, 208
End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
End1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 332
End2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 332
End3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 332
End4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
End5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
End6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
End7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Energy Saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Energy Saving Coefficient Value . . . . . . . . . . . . . . . . . . . . . . . 164
Energy Saving Control Filter Time Constant. . . . . . . . . . . . . . 164
Energy Saving Control Selection . . . . . . . . . . . . . . . . . . . . . . . 164
Energy Saving Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Enter Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
Enter command necessary . . . . . . . . . . . . . . . . . . . . . . . . . . . . 494
Enter command not necessary . . . . . . . . . . . . . . . . . . . . . . . . . 494
Enter Command Settings when Upgrading the Drive . . . . . . . 513
Enter Command Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
Enter Data from the Motor Nameplate. . . . . . . . . . . . . . . . . . . 118
Er-01. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-02. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-03. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-04. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-05. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-08. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-09. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 333
Er-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
Er-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 334
Er-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 334
Er-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Er-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
544
F
Fan Connector Cable (CN6) . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Fan Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 356
Fan Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 36, 364
Fan Relay Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 36, 363
Fast Stop Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Fast Stop Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Fault Causes and Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
Fault Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 306, 310
Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294, 338, 458
Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Fault Reset Interval Time . . . . . . . . . . . . . . . . . . . . . . . . . 267, 445
Fault Reset Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Fault Reset Operation Selection . . . . . . . . . . . . . . . . . . . . 267, 445
Fault Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Fault Trace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294, 338, 457
Fault Trace / History Register Contents . . . . . . . . . . . . . . . . . . 510
Fault Trace Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304, 305
FbH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 307, 313, 325
FbL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 307, 314, 325
Feed Forward Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Feed Forward Control Diagram . . . . . . . . . . . . . . . . . . . . . . . . 282
Feed Forward Control Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Feed Forward Control Selection. . . . . . . . . . . . . . . . . . . . . . . . 282
Ferrule Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Ferrule Terminal Types and Sizes . . . . . . . . . . . . . . . . . . . . . . . 79
Ferrule-Type Wire Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Field Forcing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Field Forcing Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Field Forcing Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Field Weakening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Field Weakening Frequency Limit . . . . . . . . . . . . . . . . . . . . . . 194
Field Weakening Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Fine-Tuning Advanced Open Loop Vector Control for PM
Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Fine-Tuning Closed Loop Vector Control . . . . . . . . . . . . . . . . 301
Fine-Tuning Closed Loop Vector Control for PM Motors . . . . 302
Fine-Tuning Open Loop Vector Control. . . . . . . . . . . . . . . . . . 300
Fine-Tuning Open Loop Vector Control for PM Motors . . . . . 301
Fine-Tuning V/f Control and V/f Control with PG . . . . . . . . . 300
FJOG/RJOG Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Formula to calculate the amount of voltage drop. . . . . . . . . . . . 68
Forward Regenerative Torque Limit . . . . . . . . . . . . . . . . 271, 446
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
G
General Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 314
Ground Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 314
Ground Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Ground Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
H
H1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
H1 Multi-Function Digital Input Selections. . . . . . . . . . . . . . . 432
H2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
H3 Multi-Function Analog Input Settings . . . . . . . . . . . . . . . . 439
Hbb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 325
HbbF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 325
HC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
HCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 325
HD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
HD and ND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35, 36
Heatsink Cooling Fan Off-Delay Time. . . . . . . . . . . . . . . . . . . 274
Heatsink Cooling Fan Operation Delay Time . . . . . . . . . . . . . 446
Heatsink Cooling Fan Operation Selection . . . . . . . . . . . 274, 446
Heatsink Overheat . . . . . . . . . . . . . . . . . . . . . . 306, 307, 317, 326
Heatsink Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
Heavy Duty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32, 178, 396
Heavy Duty Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
High Current Alarm Selection . . . . . . . . . . . . . . . . . . . . . . . . . 276
High Frequency Injection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
High Frequency Injection during Overexcitation
Deceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
High Performance Operation Using OLV or CLV . . . . . . . . . . 105
High Slip Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
High Slip Braking Current Limit . . . . . . . . . . . . . . . . . . . . . . . 280
High Slip Braking Deceleration Frequency Width. . . . . . . . . . 279
High Slip Braking Dwell Time at Stop. . . . . . . . . . . . . . . . . . . 280
High Slip Braking oL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
High Slip Braking Overload Time . . . . . . . . . . . . . . . . . . . . . . 280
High Slip Suppression Current Level . . . . . . . . . . . . . . . . . . . . 281
High-slip Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
High-Slip Braking Current Limit . . . . . . . . . . . . . . . . . . . . . . . 448
High-Slip Braking Deceleration Frequency Width. . . . . . . . . . 448
High-Slip Braking Dwell Time at Stop . . . . . . . . . . . . . . . . . . 448
High-slip Braking oL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
High-Slip Braking Overload Time . . . . . . . . . . . . . . . . . . 319, 448
High-Slip Suppression Current Level. . . . . . . . . . . . . . . . . . . . 448
Hoist Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
HSB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Hunting Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Hunting Prevention Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Hunting Prevention Gain Setting . . . . . . . . . . . . . . . . . . . 278, 447
Hunting Prevention Gain while in Reverse . . . . . . . . . . . 278, 448
Hunting Prevention Selection . . . . . . . . . . . . . . . . . . . . . . 278, 447
Hunting Prevention Time Constant . . . . . . . . . . . . . . . . . 278, 447
HVAC Fan Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
I
I Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
iFEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
IG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
IGBT Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 458
IGBT Maintenance Setting . . . . . . . . . . . . . . . . . . . . . . . . 292, 451
IGBT Maintenance Time (50%) . . . . . . . . . . . . . . . . . . . . . . . . 326
IGBT Maintenance Time (90%) . . . . . . . . . . . . . . . . . . . . . . . . 327
Induced Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
Induced Voltage Constant Unit Selection . . . . . . . . . . . . . . . . . 123
Induction Voltage Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Inertia Detection Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Inertia Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Inertia Tuning Frequency Reference . . . . . . . . . . . . . . . . . . . . 124
Inertia Tuning Reference Amplitude . . . . . . . . . . . . . . . . . . . . 124
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Initial Rotor Position Detection Selection . . . . . . . . . . . . . . . . 284
Initial Rotor Position Estimation Current . . . . . . . . . . . . . . . . . 284
Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Initialization required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Initialize Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127, 133
Input Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397, 398
Input Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391, 520, 527
Input Noise Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Input Phase Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 320
Input Phase Loss Protection Selection . . . . . . . . . . . . . . . 273, 446
Input Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397, 398
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
545
J
Jog Frequency Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Jump Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184, 303
Jump Frequency Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Jumper S3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
K
KEB Acceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . 258, 442
KEB Deceleration Time . . . . . . . . . . . . . . . . . . . . . . . . . . 257, 442
KEB Detection Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
KEB Function Related Adjustments . . . . . . . . . . . . . . . . . . . . 256
KEB Method Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
KEB Operation Using a KEB Input . . . . . . . . . . . . . . . . . . . . . 253
KEB Operation Using L2-02 and KEB Input . . . . . . . . . . . . . 254
KEB Operation Using L2-02, Without KEB Input . . . . . . . . . 254
KEB Operation Using L2-10 and KEB Input . . . . . . . . . . . . . 255
KEB Operation Using L2-10, Without KEB Input . . . . . . . . . 255
KEB Operation Wiring Example . . . . . . . . . . . . . . . . . . . . . . . 256
KEB Ride-Thru End Detection . . . . . . . . . . . . . . . . . . . . . . . . 254
KEB Ride-Thru Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
KEB Ride-Thru Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
KEB Start Output Frequency Reduction . . . . . . . . . . . . . . . . . 443
Keys and Displays on the Digital Operator . . . . . . . . . . . . . . . . 93
kWh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
kWh Monitor Initial Value Selection . . . . . . . . . . . . . . . . . . . . 452
kWh Monitor Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
kWh, Lower 4 Digits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
kWh, Upper 5 Digits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
546
L
L Protection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
LCD Operator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Leakage Inductance Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Leakage Inductance Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
LED Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
LED Screen Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
LF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 314
LF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 314
Line Driver PG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
Line-to-Line Motor Resistance Online Tuning . . . . . . . . . . . . 449
Line-to-Line Resistance Error . . . . . . . . . . . . . . . . . . . . . 308, 333
LO/RE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95, 102, 125
LO/RE (LOCAL/REMOTE) Key Function Selection . . . . . . . 288
LO/RE LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
LO/RE Light. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Load Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 449
Load Falls When Brake is Applied . . . . . . . . . . . . . . . . . . . . . 343
Load Inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286, 450
Load Inertia Ratio. . . . . . . . . . . . . . . . . . . . . . . 177, 264, 319, 444
LOCAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
LOCAL/REMOTE Key Function Selection . . . . . . . . . . . . . . 451
LOCAL/REMOTE Run Selection . . . . . . . . . . . . . . . . . . . . . . 143
Loopback Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499
Loss of Reference Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
Low Voltage Wiring for Control Circuit Terminals . . . . . . . . . 528
LT-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
LT-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
LT-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
LT-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
M
M1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
M2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
MA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Magnetic Contactor (Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Magnetic Flux Compensation Value . . . . . . . . . . . . . . . . . . . . 146
Main Circuit Connection Diagram . . . . . . . . . . . . . . . . . . . . 58, 74
Main Circuit Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Main Circuit Terminal and Motor Wiring . . . . . . . . . . . . . . . . . 73
Main Circuit Terminal Block Configuration . . . . . . . . . . . . . . . 60
Main Circuit Terminal Functions . . . . . . . . . . . . . . . . . . . . . . . . 67
Main Circuit Terminal Wiring . . . . . . . . . . . . . . . . . . . . . . 74, 526
Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Main Power Circuit Voltage Adjustment Gain. . . . . . . . . . . . . 443
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353, 354
Maintenance Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Maintenance Monitor Settings . . . . . . . . . . . . . . . . . . . . . . . . . 291
Maintenance Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . 294, 458
Master Speed Reference Lower Limit . . . . . . . . . . . . . . . . . . . 184
Max. Motor Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maximum Applicable Motor Capacity. . . . . . . . . . . . . . . 397, 398
Maximum Output Frequency . . . . . . . . . . . . . . . . . . 200, 397, 398
Maximum Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . 397, 398
Maximum Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
MB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Mechanical Weakening Detection . . . . . . . . . . . . . . . . . . . . . . 269
Mechanical Weakening Detection 1 . . . . . . . . . 306, 307, 318, 327
Mechanical Weakening Detection 2 . . . . . . . . . . . . . . . . . . . . . 321
Mechanical Weakening Detection Operation . . . . . . . . . . 269, 445
Mechanical Weakening Detection Speed Level . . . . . . . . 270, 445
Mechanical Weakening Detection Start Time . . . . . . . . . 270, 445
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
547
Coefficient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Motor PTC Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Motor Pull Out or Step Out Detection . . . . . . . . . . . . . . . . . . . 321
Motor q-Axis Current at Previous Fault. . . . . . . . . . . . . . . . . . 457
Motor q-Axis Inductance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Motor Rated Current . . . . . . . . . . . . 118, 120, 201, 207, 452, 528
Motor Rated Power . . . . . . . . . . . . . . . . . . . . . 119, 203, 207, 452
Motor Rated Slip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121, 201
Motor Rated Voltage . . . . . . . . . . . . . . . . . . . . . . . . 118, 119, 452
Motor Rotates After the Drive Output is Shut Off. . . . . . . . . . 345
Motor Rotates Faster Than the Frequency Reference . . . . . . . 343
Motor Rotates in One Direction Only . . . . . . . . . . . . . . . . . . . 342
Motor Secondary Current (Iq) . . . . . . . . . . . . . . . . . . . . . . . . . 460
Motor Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Motor Selection 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
Motor Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Motor Speed at Previous Fault . . . . . . . . . . . . . . . . . . . . . . . . . 457
Motor Speed Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Motor Speed Error 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Motor Speed Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Motor Stalls During Acceleration or With Large Loads . . . . . 342
Motor Stator Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Motor Switch during Run. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Motor Temperature Input Filter Time . . . . . . . . . . . . . . . 251, 442
Motor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Mounting Hole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35, 36
MP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Multi-Function Analog Input Selection Error . . . . . . . . . 308, 330
Multi-Function Analog Input Terminal Settings . . . . . . . . . . . 240
Multi-Function Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 237
Multi-Function Analog Output Terminal AM Bias . . . . . . . . . 243
Multi-Function Analog Output Terminal AM Gain . . . . . . . . . 243
Multi-Function Analog Output Terminal AM Monitor
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Multi-Function Analog Output Terminal AM Signal
Level Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Multi-Function Analog Output Terminal FM Bias . . . . . . . . . 243
Multi-Function Analog Output Terminal FM Gain . . . . . . . . . 243
Multi-Function Analog Output Terminal FM Monitor
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Multi-Function Analog Output Terminal FM Signal
Level Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Multi-Function Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . 242
Multi-Function Digital Input Terminal Settings. . . . . . . . . . . . 217
Multi-Function Digital Inputs . . . . . . . . . . . . . . . . . . . . . . 76, 217
Multi-Function Digital Output . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Multi-Function Digital Output Terminal Settings . . . . . . . . . . 228
Multi-Function Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . 227
Multi-Function Input Selection Error. . . . . . . . . . . . . . . . . . . . 329
Multi-Function Input Setting Error . . . . . . . . . . . . . . . . . . . . . 308
Multi-Function Photocoupler Output . . . . . . . . . . . . . . . . . . . . . 77
Multiple Drive Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Multiple Drive Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Multi-Step Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
N
n Advanced Performance Set Up . . . . . . . . . . . . . . . . . . . . . . . 447
n2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Navigating the Drive and Programming Modes . . . . . . . . . . . . 97
ND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
ndAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
NEMA 1 Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
NetRef/ComRef Function Selection. . . . . . . . . . . . . . . . . . . . . 215
Network Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
Node setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Noise From the Drive or Output Lines When the Drive
548
O
oC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 315
oFA00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 315
oFA01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 315
oFA03 to oFA06 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
oFA10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
oFA11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
oFA12 to oFA17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
oFA30 to oFA43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305, 315
oFb00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFb01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFb02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFb03 to oFb11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFb12 to oFb17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFb30 to oFb43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFC00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFC01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFC02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316
oFC03 to oFC11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
oFC12 to oFC17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
oFC30 to oFC43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
Offset Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195, 461
oH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 317, 326
oH1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 317
oH2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 326
oH3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 317, 326
oH4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 317
oL1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 318
oL2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 318, 345
oL2 Characteristics Selection at Low Speeds . . . . . . . . . 275, 446
oL3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 318, 326
oL4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 318, 326
oL5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 318, 327
oL7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 319
Online Tuning Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
Online Tuning Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
oPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
oPE Fault Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329, 456
oPE01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 329
oPE02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 329
oPE03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 329
oPE04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 329
oPE05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 330
oPE06 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 330
oPE07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 330
oPE08 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 330
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
P
P Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
P1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
P2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Parameter Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Parameter Range Setting Error . . . . . . . . . . . . . . . . . . . . . . . . . 329
Parameter Selection Error. . . . . . . . . . . . . . . . . . . . . . . . . 308, 330
Parameter Setting Range Error . . . . . . . . . . . . . . . . . . . . . . . . . 308
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Parameters for KEB Ride-Thru . . . . . . . . . . . . . . . . . . . . . . . . 256
Parameters that Change with the Motor Code Selection . . . . . 472
Parameters to Minimize Motor Hunting and Oscillation . . . . . 303
PASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 327
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127, 134
Password Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Password Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Peak Hold Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Peak Hold Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 459
Performance Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Performance Life Monitors Maintenance Monitors . . . . . . . . . 353
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377
Permanent Magnet Motor Control . . . . . . . . . . . . . . . . . . . . . . 106
PF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 320
PG 1 Division Rate for PG Pulse Monitor . . . . . . . . . . . . . . . . 210
PG 1 Gear Teeth 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
PG 1 Gear Teeth 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
549
550
Q
q-axis ACR Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 460
R
R- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
R+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
R/L1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Radiated and Radio Frequency Noise . . . . . . . . . . . . . . . . . . . 391
Ramp to stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Rated Current Depending on Carrier Frequency . . . . . . . . . . . 180
Rated Current Setting Alarm . . . . . . . . . . . . . . . . . . . . . . 308, 332
Rated Output Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . 397, 398
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
S
S-. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
S+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
S/L2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Safe Disable Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
Safe Disable Function Wiring Example (Source Mode) . . . . . 531
Safe Disable Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
Safe Disable Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Safe Disable Monitor Output Function and Digital Operator
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532
Safe Disable Signal Input . . . . . . . . . . . . . . . . . . . . . . . . . 307, 325
Safety Hazard Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Safety Input and EDM Terminal Status . . . . . . . . . . . . . . . . . . 532
Safety Monitor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Safety Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
Save Disable Signal Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
SC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
S-Curve Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 168, 303
SE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307, 327
Search Operation Voltage Limit . . . . . . . . . . . . . . . . . . . . . . . . 165
Self-diagnosing function of the serial communication
interface circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515
SEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 320
Serial Communication Terminals . . . . . . . . . . . . . . . . . . . . . . . . 77
Serial Communication Transmission Error . . . . . . . . . . . 306, 323
Serial Communications Cable Connection Terminals
(TB5). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
Serial Communications Terminal and DIP Switch S2 . . . . . . . 491
Serviceable Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Setup Group Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Setup Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Shielded Twisted-Pair Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Short Circuit Brake Time at Start . . . . . . . . . . . . . . . . . . . . . . . 146
Short Circuit Brake Time at Stop . . . . . . . . . . . . . . . . . . . . . . . 146
Short Circuit Braking Current . . . . . . . . . . . . . . . . . . . . . . . . . 146
SI-C3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Side-by-Side Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Side-by-Side Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
Side-by-Side Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Simple Motor Setup Using V/f Control . . . . . . . . . . . . . . . . . . 104
Simplified Setup Using the Setup Group . . . . . . . . . . . . . . . . . 100
SI-N3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Single Drive KEB Ride-Thru 1 . . . . . . . . . . . . . . . . . . . . . . . . 253
Single Drive KEB Ride-Thru 2 . . . . . . . . . . . . . . . . . . . . . . . . 253
Sink Mode (0 V Common), Internal Power Supply . . . . . . . . . . 81
Sink/source jumper S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Sink/Source Mode, External Power Supply . . . . . . . . . . . . . . . . 82
SI-P3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
SI-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
SI-T3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Slave Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
Slip Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Slip Compensation Gain . . . . . . . . . . . . . . . . . . . . . . . . . . 169, 301
Slip Compensation Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Slip Compensation Primary Delay Time . . . . . . . . . . . . . 169, 301
Slip Compensation Selection during Regeneration . . . . . . . . . 169
Soft Charge Bypass Relay Maintenance. . . . . . . . . . . . . . . . . . 458
Soft Charge Bypass Relay Maintenance Time . . . . . . . . . . . . . 326
Soft Charge Circuit Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Soft CLA Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
551
552
T
T Motor Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
T/L3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Target DC Bus Voltage for Overvoltage Suppression
and Stall Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Task Complete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403
Terminal A1 Bias Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Terminal A1 Function Selection. . . . . . . . . . . . . . . . . . . . . . . . 237
Terminal A1 Gain Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Terminal A1 Signal Level Selection. . . . . . . . . . . . . . . . . . . . . 237
Terminal A2 Bias Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Terminal A2 Function Selection. . . . . . . . . . . . . . . . . . . . . . . . 239
Terminal A2 Gain Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Terminal A2 Input Signal Selection . . . . . . . . . . . . . . . . . . . . . . 85
Terminal A2 Signal Level Selection. . . . . . . . . . . . . . . . . . . . . 239
Terminal A3 Bias Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Terminal A3 Function Selection. . . . . . . . . . . . . . . . . . . . . . . . 238
Terminal A3 Gain Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Terminal A3 Signal Level Selection. . . . . . . . . . . . . . . . . . . . . 238
Terminal Block (TB 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminal Block (TB 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminal Block (TB 4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminal Block (TB 5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminal Block (TB 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Terminal Block Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Terminal Board . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35, 36, 37, 373
Terminal Board Connection Error . . . . . . . . . . . . . . . . . . . . . . 311
Terminal Board Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Terminal Board Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Terminal Board Wiring Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Terminal Connections for Communication
Self-Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515
Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35, 61
Terminal cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Terminal Cover 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Terminal Cover Screw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Terminal M1-M2 Function Selection . . . . . . . . . . . . . . . . . . . . 227
Terminal M1-M2 Output Selection . . . . . . . . . . . . . . . . . . . . . 214
Terminal M3-M4 Output Selection . . . . . . . . . . . . . . . . . . . . . 214
Terminal P1-PC Function Selection . . . . . . . . . . . . . . . . . . . . . 227
Terminal P1-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal P2-PC Function Selection . . . . . . . . . . . . . . . . . . . . . 227
Terminal P2-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal P3-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal P4-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal P5-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal P6-PC Output Selection . . . . . . . . . . . . . . . . . . . . . . 214
Terminal V1 Monitor Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Terminal V1 Monitor Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Terminal V1 Monitor Selection . . . . . . . . . . . . . . . . . . . . . . . . 213
Terminal V1 Signal Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Terminal V2 Monitor Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Terminal V2 Monitor Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
U
U Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
U/T1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
U2, U3 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292, 451
UL Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526
UL Standards Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526
UL3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306, 307, 321, 328
V
-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
V/f Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
V/f Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
V/f Control Mode Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
V/f Control Mode Tuning Parameters . . . . . . . . . . . . . . . . . . . 300
V/f control using motor speed feedback. . . . . . . . . . . . . . . . . . . 30
V/f Control with Simple Speed Feedback . . . . . . . . . . . . . . . . 244
V/f Data Setting Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . 308, 331
V/f Gain During Speed Search . . . . . . . . . . . . . . . . . . . . . . . . . 150
V/f Pattern Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
V/f Pattern Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 464
V/f Pattern Display Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
V/f Pattern for Motor 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
V/f Pattern for Motor 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
V/f Pattern Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196, 343
V/T2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
vAEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
VERIFY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Verify Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Verifying Parameter Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
vFyE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
voF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322, 328
Voltage Class, Capacity Mismatch . . . . . . . . . . . . . . . . . . . . . . 337
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
553
W
W/T3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Water Supply Pump Application . . . . . . . . . . . . . . . . . . . . . . . 108
Watt Hour Output Example . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Watt Hour Output Unit Selection . . . . . . . . . . . . . . . . . . . . . . . 236
Watt Loss 200 V Class Three Phase Models . . . . . . . . . . . . . . 401
Watt Loss 400 V Class Three Phase Models . . . . . . . . . . . . . . 401
Wire Gauge, Three Phase 200 V Class . . . . . . . . . . . . . . . . . . . 69
Wire Gauge, Three Phase 400 V Class . . . . . . . . . . . . . . . . . . . 70
Wire Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68, 79
Wiring Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Wiring Diagram for 2-Wire Sequence . . . . . . . . . . . . . . . . . . . 224
Wiring Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Wiring the Control Circuit Terminal . . . . . . . . . . . . . . . . . . . . . 79
WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Writing Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Writing to Multiple Registers. . . . . . . . . . . . . . . . . . . . . . . . . . 500
Z
Z Pulse Correction Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Z Pulse Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Z Pulse Noise Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . .
Z Pulse Offset Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zero Phase Reactor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zero Servo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zero Servo Completion Width . . . . . . . . . . . . . . . . . . . . . . . . .
Zero Servo Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zero Servo Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Zero-Speed Time Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
554
335
312
312
115
379
165
165
321
165
229
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
MANUAL NO. SIEP C710616 21B
Published in Japan
Revision Number
Section
August 2009
Date of Publication
All
Revised Content
January 2009
All
September 2008
First Edition
YASKAWA ELECTRIC SIEP C710616 21C YASKAWA AC Drive A1000 Technical Manual
555
Technical Manual
IRUMA BUSINESS CENTER (SOLUTION CENTER)
480, Kamifujisawa, Iruma, Saitama, 358-8555, Japan
Phone: 81-4-2962-5696 Fax: 81-4-2962-6138
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580
http://www.yaskawa.co.jp
No. 18 Xizang Zhong Road, Room 1702-1707, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
2008-2009 YASKAWA ELECTRIC CORPORATION. All rights reserved.