Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

How to Calculate the Required Capacity kVA

Rating for 3 Phase Transformers


Issue:
Calculation of kVA capacity for a Three Phase Transformer, based on Winding Voltage
and Amperage information.

Product Line:
Low Voltage (LV) Transformers
Learn more about DOE 2016 Energy Efficient Transformers by Schneider Electric

Environment:
Applies to all Three Phase Transformers.

Cause:
kVA sizing must often be calculated from Primary or Secondary Winding Voltage
and Amperage information.

Resolution:

To do this you must have at least two pieces of information:


I.
II.

the load line-to-line voltage (V)

the maximum load phase current (I)

kVA = (V * I * 1.732) / 1000


where 1.732 is the simple numerical value for the square root of 3 (1.7320508...)
Then round up to the next standard 3ph kVA rating as found in Section 14 of
SquareD/Schneider Electric Catalog, Digest 177.
Example: V = 208, I = 175; Therefore: kVA = (208 x 175 x 1.732) / 1000 =
63.05kVA

This calculates to 63+ kVA, thus we round up to 75kVA. From the Digest,
a EX75T3H will satisfactorily serve this load.
Note: This is a simple kVA calculation and does not take into account possible
special load requirements, such as found with motors or some medical equipment.
For assistance, contact the Schneider Electric US Customer Care Center.

You might also like