Professional Documents
Culture Documents
110 MW Steam Turbine Manual
110 MW Steam Turbine Manual
CONTENTS
Description
INTRODUCTION
...
...
Drawing
...
01-00-00
02-00-00
03-00-00
03-02-00
...............................
STEAM TURBINE
...
...
...
3-10-1500-D
3-10-2069-S
11
03-04-00
2-10-1C19-S
...
1-10-2011-S
...
1-10-2010-S
15
............
03-05-00
3-10-OD37-M
17
03-05-05
0-10-1018-S
3-10-2020-S
...
OIL SYSTEM
...............................
19
03-06-00
0-10-1003^8
INJECTOR
3-10-2024-S
............................
...
OIL FILTER
...
..............................
23
03-06-08
3-10-2035-S
................
..............
TRANSFORMER DESCRIPTION
TRANSFORMER
LIMITER DESCRIPTION
LIMITER
...
03-07-00
27
03-07-01
3-10-2036-S
...
...
..............
...
3-10-2032-S
...
3-10-2037-S
..............................
3-10-2040-S
...
25
...
...
29
...
33
03-07-02
03-07-03
...............
...
3-10-2046-S
...
...
3-10-2017-S
3-10-2043-S
POSITIONS OF LIMITER
QUICK CLOSING
RETURN FLAPS
VALVES AND
................
NON
...
37
03-07-04
.................................
3-10-2021-S
3-10-2048-S.
CONTENTS-Contd.
Description
SERVOMOTOR OF L.P QUICK CLOSING
STOP VALVE
..
..
.
L.P QUICK CLOSING INTERCEPTOR
VALVE
..
..
ELECTROMAGNETIC RELAY .
CHANGE OVER VALVE
..
ACCELERATOR
..
..
..
GOVERNING VALVES
.
..
GOVERNING VALVES DRIVE 1 / 4 ..
SERVOMOTOR OF L.P INTERCEPT VALVE
LIFT OF GOVERNING AND INTERCEPTOR
VALVES Vs SECONDARY OIL PRESSURE
EMERGENCY GOVERNORS .
.
EMERGENCY GOVERNOR .
..
TESTER OF OVER SPEED GOVERNORS
OIL DISTRIBUTOR ( DESCRIPTION )
OIL DISTRIBUTOR ..
..
.
NON RETURN VALVE Js 10 ..
.
MAIN RELAY ( DESCRIPTION ) .
MAIN RELAY
.
.
.
MAIN RELAY
.
.
HYDRO-MECHNICAL AXIAL PROTECTION
( DESCRIPTION )
.
..
MECHNICAL PROTECTION OF DISPPLACEMENT
.
..
ELECTROMAGNETIC PROTECTION OF
AXIAL MOVEMENT OF THE THRUST
BEARING COLLAR,RELATIVE EXPANSION OF ROTORS AND CASING ..
ELECTRICAL PROTECTION OF DISPLACEMENT
..
Page. No
43
49
51
53
55
57
59
67
Article No.
_
3-10-2049-S
_
_
_
_
_
03-07-05
_
_
3-10-2047-S
4-10-1063-S
3-10-2041-S
3-10-2028-S
3-10-2042-S
TC-0097-D
( Graph )
_
_
03-07-07
_
03-07-08
_
_
03-07-09
_
03-07-10
_
03-07-11
_
_
73
3-10-2031-S
3-10-2050-S
4-10-1046-S
2-10-1010-S
3-10-2026-S
4-10-1045-S
3-10-2025-S
3-10-2051-S
3-10-2044-S
3-10-2018-S
03-07-12
_
69
Drawing No.
3-10-2023-S
_
_
3-10-2022-S
3-10-2038-S
3-10-2039-S
03-07-14
CONTENTSContd,
Description
TECHNICAL DATA OF ACCESSORIES IN
CONDENSATION AND REGENERATIVE
SYSTEM .............................................................
DESCRIPTION OF EQUIPMENT IN CONDEN
SATION AND REGENERATIVE SYSTEM ...
SURFACE CONDENSER ...
...
...
SURFACE CONDENSER ...
...
...
CONDENSER VACUUM CURVES 110 MW ...
75
03-08-00
79
03-09-00'
83
87
89
03-09-02
03-09-04
91
03-09-05
03-10-00
93
03-10-01
95
99
101
103
105
107
03-10-03
03-10-04
03-10-05
03-10-06
03-10-07
03-10-08
109
03-10-09
0-14-1035
014-1036
RC-0038
(Graph)
RC-0039
(Graph)
0-14-1032-A
0-14-1031-A
0-10-1016-S
0-14-1018-A
0-14-1014-A
0-14-1015-A
0-14-1021-A
01.00.00
INTRODUCTION
02.00.00
MAIN TECHNICAL
DATA OF TURBOSETS
02.01.01
The basic parameters:
Rated speed
3,000 rpm
02.01.03
The Quantity of oil for first filling:
For the turbine
approx.
19.000
4,400
liters
23,400
liters
02.01.02
System of the turbine:
4 governing valves + 2 interceptor valves.
Total ;
liters
02.01.04
Rotors rotate at 62 rpm. on
turning gearduring Starting and
Stopping.
3
03.00.00
FUNCTIONAL
DESCRIPTION OF
THE MAIN PARTS
03.01.00
GENERAL DESCRIPTION :
03.01.01
There are two live steam lines
connecting the boiler to the
turbine. There are two cold reheat and two hot reheat lines
connecting the reheater and the
turbine. In each of the two live
steam lines, one electrically operated isolating valve, one water
separator and one quick closing
stop valve are mounted.
03.02.00
TURBINE CASINGS:
03.02.01
The high-pressure part consists of
two horizontally divided concentric casings. The inner casing
is placed in the outer casing in
such a way that it is possible for
it to expand in all directions,
maintaining at the same time the
alignment of the two casings,
while the fixed point of the inner
casing in the axial direction is
between the nozzle chambers.
The free expansion of the inner
casing is also enabled by the
gland connection of the nozzle
chambers with the incoming
steam piping.
The medium pressure part is a
horizontally divided casing with
guide wheels partially mounted in
the casing in carriers and partially
directly in the casing. The steam
supply piping is connected rigidly
with the casing, and steam to the
front carrier chamber is led-in by
an extended pipe which is sealed
by glands at the connecting
branch of the steam chamber.
The low-pressure casing is divided
horizontally and comprises of 3
parts, connected by vertical
flanges. In the front and rear
parts of the casing, both the
bearings of LP rotor and the rear
bearing of MP rotor are located.
The outlet connecting branches
03.03-01
The horizontal flange of the
external high pressure cylinder
along with the bolts on the dividing plane, as well as the flanges
and connecting bolts in the
parting plane of the MP casing
can be heated by live steam
from the interconnecting piping
between the HP emergency stop
valves. The steam supply line
to the heating system of flange
of both the HP and MP casings
is provided with one closing valve
with electric drive whose limit
switches are given an impulse for
the signalling of the OPENCLOSE positions, and also with
a regulating valve with electric
drive. Besides the valves in
both the incoming steam lines,
orifice plates are provided.
The indicator for full or partial
opening of the valve, if provided,
should be located near the relative
expansion indicator of the rotors.
The outlet of steam from the
flanges of both the casings is a
common one, and is connected
across an orifice plate to the
piping of IV extraction before
the quick-closing extraction valve.
The drain from the bottom nuts
of the connecting bolts of each
casing is connected individually
to the piping of chimney steam.
10
03.03.02
Flange heating is resorted to
during:
(i) Cold start.
(ii) Hot start after substantial
outage.
(iii) Rapid increase of load from
a steady low load.
The main consideration while
flange heating, is to avoid excessive relative expansions of the
casings and rotors. (The massive
flanges heat up at a slower rate
during starting than the rotors
which are washed by the hot
steam. During considerable increases in load, the massive cylinders and their flanges similarly lag
behind the rotor in heating up.)
03.04.00
03.04.03
The circuit marked 2 in the
scheme 2-10-1019-S may be connected according to the position
of the change-over valve either
to the 5th extraction piping or
to the condenser.
During starting of the turboset
and whenever the 5th heater is
out of operation, it is necessary to
connect the circuit 2 to the
condenser by means of the
change-over valve by the manual
operation of the respective control
switches in the unit control
room. The position of the
change-over valve which ensures
the exhausting of steam from
glands to the V extraction piping,
after the fifth heater has been
put into operation from the fifth
extraction point, can be achieved
by manual operation of the
appertaining control switch in the
unit control room. At a loss
of pressure in the quick closing
oil system, the change-over valve
automatically exhausts the gland
steam into the condenser (i.e.
1. at the machine cutting off,
2. at the trip of generator from
the grid due to generator protec
tion, 3. on reaching the maximum
condensate level in the fifth
heater or 4. at a pressure drop
below 2.75 ata in the V extrac11
sucked off into the main condenser, and the chimney steam is
exhausted through spray cooler
into the atmosphere by means of
blowers.
The level signaliser gives the
following impulses:
(1) To close the electrical valves
on the steam piping to the
gland steam and chimney
steam condensers.
(2) To open the electrical valve
for admitting the chimney
steam to the spray cooler,
and to open the electrical
valve to admit the gland
steam to the main condenser.
(3) To close the electrical valves
on the suction piping of the
air steam mixture from
chimney steam condenser
to the blowers.
(4) To open the electrical valve
on the incoming condensate
spray to the spray coolers
of the chimney steam.
(5) To the optical and acoustic
signals :
During a faulty connection,
it is necessary to manually
open the bypass valves on
the condensate line so that
03.05.00
03.05.01
All the rotors are mutually connected by means of rigid couplings, including the rotor of the
generator. The critical speed
of the whole system of rotors
manifests in the following ranges
of speeds at the operating conditions :
19002200 rpm Best noticed on
the MP and LP
rotors and generator.
2350 rpm Best noticed on the HP
rotor.
03.05.02
The axial load of the entire system
of rotors is taken up by a doublesided axial bearing, located in the
bearing stand between HP and
MP casings. For checking the
cases of wear or damage of the
axial bearing because of nonpermissible increase of axial force
(for example during the heavy
03.05.03
03.05.05
MECHANICAL TURNING
GEAR DESCRIPTION
03.06.00
OIL SYSTEM
03.06.01
The oil system is shown in scheme
0-10-1003-S in which the main
regulation and protection equipment operated by oil, the fittings,
measuring and electrical control
instruments, are shown schematically. The numbering of the
instruments is done on scheme 010-1003-S.
The lubrication and regulation
systems are mutually interconnected. The main oil tank is
divided by removable screens
into two spaces. Oil is led into
one of these spaces from all the
drains which then flow into the
second space through the screens,
from where the suction is taken to
all the oil pumps. Both the
spaces are provided with level
signalisers (207, 208) for the
maximum level in the first and
the minimum level in the second
space. The oil levels are also
indicated by level gauges.
It is necessary to ensure the cleaning of the screen periodically and
to top up the oil level as required.
The screens must be clean,
especially during the initial commissioning periods. The cleaning
of the screens could be carried
out, even during operation,
because behind the first coarse
screen, there are two fine screens,
which can be alternatively removed and cleaned.
The valve Nd. 15 connected
above the mud collector, serves
for taking oil samples. The
sampling of oil is to be carried
out regularly during operation
and as per the results of the
03.06.06
Part of the oil from the delivery
of the main oil pump (9.512 atg)
flows back to the oil injector in
the oil tank. Using this high
pressure oil (9.512 atg) as the
working fluid, the injector sucks
oil from the main oil tank and
supplies the total required quantity of suction oil to the main oil
pump at a pressure of 0-40-5
atg.
A fall of pressure to 0.1 atg is
signalled optically by means of
the manostat (147) and further
drop of pressure calls for the
tripping of the machine, as otherwise there is a dangerous possibility of the breaking of the
suction column and loss of oil
in the pressure system.
After achieving the rated speed,
the valve E is slowly closed and
if the correct pressure of about
0.4 atg is maintained at the
suction of the pump, the starting
oil pump is stopped. The valve
E is afterwards opened to such
an extent as to ensure instantaneous flooding of the suction,
in the case of a necessity of
putting the starting oil pump into
operation.
03.06.07
A further part of the oil from the
delivery of main oil pump, is
utilised as lubricating oil, after
reducing the pressure by means of
an electrically operated valve (F)
placed in between two orifice
plates, to a value of 1.00 to 1.15
atg before the bearings. The
valves (K and L) on the inlet
and outlet oil coolers are always
kept fully open. When the pressure of lubricating oil drops to
21
03.06.08
OIL FILTER
DESCRIPTION
03.07.00
REGULATION AND
SAFETY EQUIPMENT FOR
TURBINE PROPER
03.07.01
SPEED SENSING
ELEMENT
27
03.07.02
TRANSFORMER
DESCRIPTION
TRANSFORMER 3-10-2032-S
(marked as TR on 0-10-1003-S):
The pressure of the secondary oil
is regulated by the transformer
(which is led into the transformer
through the pipe union marked
72) in the following way:
The oil is supplied to the
secondary oil system from the
distribution oil through an orifice
plate of 4 mm dia. (located at the
pipe union on the oil distributor
near the oil filter) and is by-passed
into the drain by means of the
cone marked 13. The cone is
connected to a lever arm marked
22, which has a fulcrum at the
roller (71) of the main support (5).
The moment of force of the
secondary oil on the area of cone
is at an equilibrium with the force
acting on the other end of the
beam resulting from the differential pressure from the spring (78)
and the force due to a given
primary oil pressure on the
bellows (8). The tension of the
spring can be varied by moving
the screw (19) by means of levers
marked 26 and 23 (operated by
speed changer) or by rotating
the screw (19) by means of the
gear drive (15) (operated by
nominal speed changer), If the
NON-UNIFORMITY
CHANGER : 3-10-2037-S (NUC
in 0-10-1003-S).
In this position of the nonuniformity changer, the transformer lever arm (supporting
area of the roller) must be in the
horizontal position at a bellows
lift of 2 mm which can be achieved
by screwing in the screw (21) in
the lever arm. The horizontal
position of the beam can be
achieved by adjusting the height
of the eye 25. It may be
necessary to check likewise the
centricity of the cone (13) with
the hole in the flange (17) which
could be damaged if the flat
spring (16) position is adjusted
wrongly. The speed changing device (3-10-2040-S)is to be adjusted
and set by an adjusting nut
18 so that the contact surface
of the outside lever 23 of transformer, (3-10-2032-S) moved by
the roller on the speed changer,
is in a vertical position at a lift
of speed changer of 18 mm from
zero position. The nominal speed
changer is to be initially set to the
mean position (approximately 100
revolutions from one extreme
position), by rotating the shaft
with a square head, which is
protruding out of the bearing
pedestal front wall. The final
setting is to be done afterwards,
during the starting up of the
turboset. At the time of starting
the turbine the hand wheel of the
31
03.07.03
LIMITER DESCRIPTION
DESCRIPTION OF THE
FUNCTION OF LIM1TER
WITH DRIVE AND WITH
SELSYN TRANSMITTER:
FIGURE B :
34
FIGURE A :
03.07.04
37
39
03.07.05
GOVERNING VALVES
03.07.06
EMERGENCY GOVERNORS
EMERGENCY GOVERNORS
4-10-1046-S (Marked FEG,
REG in 0-10-1003-S):
49
03.07.07
TESTER OF EMERGENCY
GOVERNOR (DESCRIPTION)
TESTER OF EMERGENCY
GOVERNOR
2-10-1010-S
(TEG on O-10-1003-S) :
The tester is intended for testing
the correct functioning of the
emergency governors while the
set is running at the rated speed.
During normal operation, the
hand wheel (60) is screwed out to
the extreme position on the left,
so that the bushes marked 5 and 6
mounted on that are kept away
from the tip of the rotor and also
no oil is admitted to the tester
through the unions A and B. If
the front (rear) emergency governor marked FEG (REG) is to
be tested while the machine is at
rated speed, it is necessary to
supply pressure oil to the unions
A (B), by rotating the distributor
(marked DTR on 0-10-1003-S)
by about 150 from the middle
position to the right (left). By
rotating the hand wheel towards
the right, the tester moves towards
the rotor and the pressure oil
enters the inner (outer) canals in
the bush marked 5 and 6 and
in the space of front (rear)
emergency governor, till the pin
of the governor comes out. The
pressure of oil at the moment of
tripping, measured by the pressure
gauge 57 should be compared
with oil pressure, ascertained at
51
03.07.08
OIL DISTRIBUTOR
(DESCRIPTION)
DISTRIBUTOR 3-10-2026-S
(DTR in 0-10-1003-S) :
The distributor helps to achieve
the following three objectives :
(1) To divide the system of
quick closing oil into two
parts, right and left, through
the main relay.
(2) The sequential testing of
both the emergency governors by the emergency
tester.
(3) The sequential setting of
both parts of the main relay
to operating positions.
The distributor is connected
through union 15 to the distributing oil, which however does
not flow further, at normal operation of the machine when the
distributor is always in the neutral
position (position 1).
03.07.09
MAGNETIC RELAY
(DESCRIPTION)
03.07.10
ACCELERATOR RELAY
(DESCRIPTION)
57
03.07.11
MAIN RELAY
(DESCRIPTION)
65
03.07.12
HYDRO-MECHANICAL AXIAL
PROTECTION (DESCRIPTION)
HYDRO-MECHANICAL AXIAL
PROTECTION 3-10-2023-S (206
as per Drg. 0-10-1003-S) 3-100037-M:
The proper setting of the protection is carried out with the rotor
pressed towards the generator,
by adjusting the respective connection of slide 1 with lever 16.
The testing of the proper functioning of the protection is performed before the start of the unit
or before synchronising, by slowly
pressing by hand, the armature
of the magnet (38) to the bottom
position by which link 4 and the
two armed lever (14) move the
slide away from the middle
position and thus making contact
in the manostat.
The testing for a proper functioning of the circuit can be performed
also, by energising the magnet by
pressing the respective push
button in the control panel. The
circuit of the electro-magnet will
be intercepted automatically by a
time relay after 3 seconds.
67
03.07.13
1 + 3.5 mm
1.5 mm
Relative expansion
of LP rotor with
respect to LP
casing
+ 4 mm
2 mm
03.07.14
73
03.08.00
TECHNICAL DATA OF
ACCESSORIES IN CONDENSATION AND REGENERATIVE
SYSTEM
03.08.01
Two-way surface condensers
2 Nos.
Each of cooling area3380 sq.m.
Quantity of cooling water for both
the condensers 15400 Cu.m/hr.
Resistance on water side of each
condenser
5 m.w.cl.
03.08.02
One two-stage steam jet air
ejector of ' Duplex Type ', each
with its own condenser:
Minimum pressure of working
Steam
7 ata
Temperature of steam
300C
Steam
Consumption
1600
Kg/hr.
03.08.03
03.08.05
Two fans for exhausting the steam
air mixture from the chimney
steam condenser.
Oil
Quantity
800 1/mt.
Pressure
2.7 atg; Head 23
metres of water column.
R.P.M.
- 1450
03.08.04
Lubricating
A.C. Motor:
Rating
9 K.W./415v/50c/sec,
Np =- 6 KW. 1465
rpm.
Speed
D.C. Motor :
Rating 8.5 K.W./220 v, D.C.
Speed
1465 rpm,
75
03.08.08
2 x 25 1/mt.
50 atg.
Quantity
2660 1/m.
Head 215 metres of water
column.
Speed
-- 1450 rpm.
Np
142 K.W.
Temperature of working medium
40C.
Squirrel cage induction motor :
Rated capacity 175 K.W./6600v/
50 cps.
03.08.11
Condensate booster pump
(100CJH/7)-2 Nos.
Quantity
1150 1/m.
Head 153 metres of water
column.
Speed
1475 rpm.
Np
~~ 43 K.W.
Temperature
120C
Squirrel cage induction Motor :
Rated capacity of Motor:
55 K.W./415 v/3^/50 cps.
03.08.12
Boiler feed pump (200 KHI)
2 Nos.
Each for 100% output. Quantity
8180 I/minute.
~ 450t/hr
Head
1960 metres of
water column.
Speed
4500 rpm.
Np
3140 KW.
Temperature 158C.
Each of area
80 Sq.m. on
steam side.
Number of ' U ' tubes 242.
Size
15/13 mm.
Resistance on water side at a flow
of 272.143 t/hr 10.1 m.w.cl.
Test pressure on waterside
42 atg.
03.08.14
Two low pressure heaters of the
Hnd stage heating Vertical
Design :
Area
80 sq.m.
Quantity of steam for condensing
3800v/kg/hr.
Number of ' U' tubes 256
Size
15/13 mm.
Resistance on water side at a flow
of 273.143 t/hr is about
4.74 m.w.cl.
Safety valve on steam side is set
at
6 atg.
Test pressure on water side
42 atg.
Test pressure on steam side with
water
9 atg.
77
03.08.17
Low pressure heaters (IIIrd
stage, IVth stage and Vth
stage of) heating Vertical
Design :
Each :
Area on steam side 250 sq.m.
Number of 'U' tubes 710
Size
15/13 mmResistance on water side at a flow
of 308.469 t/hr. is about
6.36 m.w.cl.
Safety valve setting pressure on
steam side
6 atg.
The test pressure on water side
42 atg.
The test pressure on steam side
with water
9 atg.
Size of tubes
25/15 mm.
Resistance on water side at a flow
of 361.5 t/hr. in spiral tubes
16 m.w.cl.
Resistance on water side at a flow
of 60 t/hr. in ' W tubes
16 m.w.cl.
Setting pressure for safety valve
on steam side
20 atg.
Test pressure on water side
450 atg.
Test pressure on steam side with
water
30 atg.
03.08.20
One high pressure heater of
VHIth stage heating Vertical
Design :
03.08.18
One condensate expander at
the pressure level of IIId
stage heating :
Safety valve setting pressure
6 atg.
Test pressure with water 9 atg.
03.08.19
One high pressure heater
Vllth stage heating Vertical
Design :
Area on steam side 308 sq.m.
Number of spiral steel tubes
240
78
03.09,00
DESCRIPTION OF EQUIPMENT
IN CONDENSATION AND
REGENERATIVE SYSTEM
03.09.01
CONDENSERS:
The surface condensers are supported on springs which take up
the weight of the condenser, and
the weight of one half of the
cooling water in the condenser.
The condensers are firmly connected with the exhaust branches
on the LP casing. Through the
inlet steam branches each condenser, on the water side is vertically
divided, into two independent
double path circuits which enables
the cleaning of water space of the
condensers in stages, during the
operation of the turboset at
reduced outputs as per diagram
RC-0050. If the cleaning takes
place during operation, one half
of both the condensers which are
on the common cooling water
circuit, should be put out of
operation.
After closing the valve on the
inlet of cooling water to the
respective halves of the condenser,
and after closing the respective
deaerating valves of the steam
space, the water from these halves
which are put out of operation
are drained simultaneously. The
water chambers are separated
from the steam space by means
of the tube end plates, which are
painted with two coats of APCODUR 66 Black on the water side,
after the completion of the roller
expansion of cooling water tubes.
If there is a leakage in the tube
03.09.02
Starting Ejector:
This serves for the quick evacuation of the turboset during
starling. It consists of the steam
chambers from which the steam
is led through the nozzle into the
mixing chamber, to which is
connected the mixing nozzle with
the diffuser. The working steam
led into the ejector through the
steam chamber flows through
the steam nozzle attaining a
high velocity. This creates a.
vacuum in the mixing chamber
and the air sucked from the
condenser to the mixing chamber
entrapping it in the flow of steam,
and is led through the mixing
nozzle and through a diffuser,
into the exhaust and to the
atmosphere.
The starting ejector is provided
with a pressure gauge for the
measurement of steam pressure
in the steam chamber ; and a
vacuum gauge for the measurement of vacuum in the mixing
chamber.
STEAM JET AIR EJECTOR
:
This ejector sucks off the steam
air mixture from the condenser
during operation because of the
leakage in the flange connections
by defective sealing of glands.
The ejector works with the superheated steam, and the condensate
03.09.03
85
03.09.04
87
03.09.05
LEVEL CONTROLLER IN
THE CONDENSER
(0-10-1016-S) :
The level controller maintains an
approximately constant condensate level in the hot well during
the running of the turboset, and
thus maintains a practically constant suction head for the condensate pumps. Its construction and
location ensures the flow of
minimum required quantity of
condensate for the cooling of
steam jet air ejectors. It is
located on the common delivery
piping of the condensate pumps,
and the float chamber of the
controller (6) is connected at its
bottom part with the hot well
and at its top with the steam
space of the condenser, so that
the level in the float chamber
corresponds to the level in the
condenser hot well.
The float with the lever (8)
follows the level of the condensate in the floatchamber. The gear
segments (3) and (5) are used as a
transfer mechanism between the
level of condensate and the
position of the regulating slide
(4). so as to ensure minimum
friction and the prevention of
90
03.10.00
REGENERATIVE SYSTEM
91
03.10.01
93
03.10.03
the expander of working condensate to the suction of condensate booster pumps. The heating
steam condensate from the V and
IV extractions are cascaded in
stages to the III LPH.
The III LPH is provided with
two independent level signalisers.
At a non-permissible rise of level
in the III LPH, the following
impulses are given :
(1) To close the valve in the III
extraction piping to heat up
the III LPH ;
(2) To close the valve on the in
coming heating steam to IV
LPH ;
(3) To close the valve on the
inter-connection
between
the III extraction and ex
pander of working conden
sate ;
(4) To close the non-return
quick closing valve in the
IV extraction piping.
(5) Optical and acoustic signal.
By the above, III and IV LPH
are put out of operation on the
steam side. It is therefore neces
sary to manually open the by-pass
of the heater on the water side,
and afterwards to close the valves
on the inlet to III LPH and
on the outlet of IV LPH, and
then to close the valve on the
evacuation of air to the
condenser. Furthermore, to
open the valve on the draining
of condensate of heating
steam from V LPH
95
03.10.04
CYCLE OF IV STAGEHEATING
99
03.10.05
102
03.10.06
The slearn from the sixth extraction of the turbine is used for
heating up the deaerator of the
feed water tank through a reduction station which maintains a
constant pressure of 6 ata. On
low loads, that is when the
pressure in V] extraction is not
enough, the steam is admitted
through a second reduction
station from the VI11 extraction
of the turbine.
03,10.07
03.10.08
107
03.10.09
TESTING OF SIGNALISATION
AND PROTECTION SYSTEM OF
HEATERS