AH-Series
State of the art Manufacturing Facilities
101SGR/AH/062011
Technical Specifications
Amperes Frame (based on IEC, BS or IS)
TYPE (number of poles 3 & 4)
630
AH-6D
800
AH-8D
800
AHA-08N
1000
AH-10D
1250
AH-12D
1600
AH-16D
2000
AHA-20N
50/105
50/105
50/105
55/121
55/121
55/121
55/121
45/94.5
45/94.5
50/105
50/105
50/105
50/105
50/105
40/40
40/40
40/40
40/40
40/40
40/40
40/40
45 (25)
45 (25)
50 (25)
50 (25)
50 (25)
50 (45)
50 (45)
30/40
30/40
30/40
30/40
30/40
30/40
30/40
250V DC
2000
AH-20D
2500
AH-25D
3200
AH-30D
4000
AH-40D
5000
AH-50C
6300
AH-60C
60/132
65/143
75/165
100/200
100/200
120/264
50/105
50/105
65/143
85/187
85/187
100/220
40/40
40/40
40/40
40/40
40/40
40/40
50(50)
50(50)
65(65)
85(70)
85(70)
100(70)
30/40
30/40
30/40
30/40
30/40
30/40
250V DC
* Rated Service breaking capacity (Ics) & rated ultimate breaking capacity (Icu) are same except at 415V. For other voltages please contact us.
Higher Breaking Capacity ACBs available on request.
Breaker
Type
AH-6D
AH-8D
AHA-08N
AH-10D
1
Front Panel
fitting
AH-16D
Key lock
AH-25D
AH-30D
AH-40D
AH-50C
AH-60C
Types of
mounting
Accessories
for draw-out
type
Types of
spring charging
system
Accessories for
spring charging
system
Under
voltage trip
devices
Close-open
cycle counter
Key interlock
system
10
Micro Processor
based OCR
Accessories for
overcurrent trip
devices
Thermomagnetic
based OCR
11
OCR alarm
switch
12
13
Other
trips
Auxiliary and
Trip indication
switches
Main-circuit
safety shutters
Position switch
ON/OFF 1
Indicator
Cover
AH-20D
3
Terminal 2
connection
arrangement
Operating
button cover
AH-12D
AHA-20N
Position
padlock
Vertical
Draw-out type
Horizontal
Fixed
Door interlock
and 3
defeat facility
Motor Charging
Lifter
Manual Charging
Lifting lugs
Compact
UVT coil
without time
delay for
AC/DC
application
AUH-V-***
Mal Insertion
Prevention Device
Short circuiting
contacts
Castle
key lock
Draw-out
position indicator
Test Jumper
mIT-100 for
general
feeder circuit
mIT-G for 3
generator
protection
OCR checker
(External)
OCR alarm switch
With or
without MCR
24V DC,
Power supply
(External)
With Shunt
Trip
CT for neutral
line
4
Shunt trip
Capacitor
trip
With thermal
O/L relay
Micro-Pro
4.1 / 5.1
for multi purpose
2 Horizontal Terminal upto AH-25D and Vertical Terminal for 30D and above are available as Standard. Additional adaptors for changing to vertical are available as accessories.
3 On request.
4 Required for earth fault protection externally mounted for 3 pole * Dimensions for 4000A fixed breaker available on request.
Technical Specifications
Amperes Frame (based on IEC, BS or IS)
TYPE (number of poles 3 & 4)
630
AH-6D
800
AH-8D
800
AHA-08N
1000
AH-10D
1250
AH-12D
1600
AH-16D
2000
AHA-20N
50/105
50/105
50/105
55/121
55/121
55/121
55/121
45/94.5
45/94.5
50/105
50/105
50/105
50/105
50/105
40/40
40/40
40/40
40/40
40/40
40/40
40/40
45 (25)
45 (25)
50 (25)
50 (25)
50 (25)
50 (45)
50 (45)
30/40
30/40
30/40
30/40
30/40
30/40
30/40
250V DC
2000
AH-20D
2500
AH-25D
3200
AH-30D
4000
AH-40D
5000
AH-50C
6300
AH-60C
60/132
65/143
75/165
100/200
100/200
120/264
50/105
50/105
65/143
85/187
85/187
100/220
40/40
40/40
40/40
40/40
40/40
40/40
50(50)
50(50)
65(65)
85(70)
85(70)
100(70)
30/40
30/40
30/40
30/40
30/40
30/40
250V DC
* Rated Service breaking capacity (Ics) & rated ultimate breaking capacity (Icu) are same except at 415V. For other voltages please contact us.
Higher Breaking Capacity ACBs available on request.
Breaker
Type
AH-6D
AH-8D
AHA-08N
AH-10D
1
Front Panel
fitting
AH-16D
Key lock
AH-25D
AH-30D
AH-40D
AH-50C
AH-60C
Types of
mounting
Accessories
for draw-out
type
Types of
spring charging
system
Accessories for
spring charging
system
Under
voltage trip
devices
Close-open
cycle counter
Key interlock
system
10
Micro Processor
based OCR
Accessories for
overcurrent trip
devices
Thermomagnetic
based OCR
11
OCR alarm
switch
12
13
Other
trips
Auxiliary and
Trip indication
switches
Main-circuit
safety shutters
Position switch
ON/OFF 1
Indicator
Cover
AH-20D
3
Terminal 2
connection
arrangement
Operating
button cover
AH-12D
AHA-20N
Position
padlock
Vertical
Draw-out type
Horizontal
Fixed
Door interlock
and 3
defeat facility
Motor Charging
Lifter
Manual Charging
Lifting lugs
Compact
UVT coil
without time
delay for
AC/DC
application
AUH-V-***
Mal Insertion
Prevention Device
Short circuiting
contacts
Castle
key lock
Draw-out
position indicator
Test Jumper
mIT-100 for
general
feeder circuit
mIT-G for 3
generator
protection
OCR checker
(External)
OCR alarm switch
With or
without MCR
24V DC,
Power supply
(External)
With Shunt
Trip
CT for neutral
line
4
Shunt trip
Capacitor
trip
With thermal
O/L relay
Micro-Pro
4.1 / 5.1
for multi purpose
2 Horizontal Terminal upto AH-25D and Vertical Terminal for 30D and above are available as Standard. Additional adaptors for changing to vertical are available as accessories.
3 On request.
4 Required for earth fault protection externally mounted for 3 pole * Dimensions for 4000A fixed breaker available on request.
Overcurrent Release
Thermal Magentic Trip Device: Type TM
Microprocessor Based Overcurrent Trip Device: Type mIT-100 & mIT-G
Intelligent Release: Type MicroPro Relay 4.0 & 4.1
TM
n Direct acting electromagnetic instantaneous trip device with fixed factory set release, settings 3 - 50 kA
n Adjustable overload settings 80% - 120%.
n Provision for remote tripping / electrical reset as optional features with overload relay.
mIT is a true RMS sensing overcurrent trip device, requiring no external supply for its basic function. It is available in two types,
i.e., mIT100 for industrial application and mITG for generator protection.
n MicroPro 4.1
n Error free and user friendly setting of current and time delay.
n MicroPro 5.1
MicroPro 4.1
Type of Protection
n Overload protection
n Neutral Protection
Other Features
IS 9000 - PG4
n Zone Selectivity
IS 9000 - PG3
n Ampere Meter
Vibration Test
IEC 255 - 4
Radio Frequency
Interference (RFI)
IEC 801- 3
Electrostatic Discharge
(ESD)
IEC 801- 2
IEC 801- 4
n LCD display
n LCD display and fault LED retention in case of power failure
(EFT)
Surge
IEC 801- 5
MicroPro 5.1
Impulse
IEC 255 - 4
Protection thresholds and delays are set using the keypad. The
selected value are momentarily displayed in amperes.
Type of Protection
n Overload protection
n Short Circuit current protection
t
I>
t>
Ig
I >>
0.5+
tg
2.5+
-0.05
-0.1
-0.2
-0.3
x lo
I>
I>
I >>
-2.5
-5
-10
-15
t >>
ON
LTD
t>
Sec
IG
STD
4+
-5
-5
-10
-15
IG
-50
-100
-150
-200
tG
I >>
-50
-100
-150
-200
t >>
x lo
ms
n Neutral Protection
Other Features
n Zone Selectivity
n Ampere Meter
INS
50+ % lo
4+
-1
-1
-TEST
-LONG
-SHORT
DIP
- ON
FUNCTION
BLOCKING
NORMAL
15%+
1 2 3 4
NORMAL
TEST MODE
-1
-1
-2
-2
GFT
RESET
50+
ms
-LTD
-STD
-INS
-GFT
-2
-3
I >>
x lo
n LCD display
n LCD display and fault LED retention in case of power failure
Overcurrent Release
Thermal Magentic Trip Device: Type TM
Microprocessor Based Overcurrent Trip Device: Type mIT-100 & mIT-G
Intelligent Release: Type MicroPro Relay 4.0 & 4.1
TM
n Direct acting electromagnetic instantaneous trip device with fixed factory set release, settings 3 - 50 kA
n Adjustable overload settings 80% - 120%.
n Provision for remote tripping / electrical reset as optional features with overload relay.
mIT is a true RMS sensing overcurrent trip device, requiring no external supply for its basic function. It is available in two types,
i.e., mIT100 for industrial application and mITG for generator protection.
n MicroPro 4.1
n Error free and user friendly setting of current and time delay.
n MicroPro 5.1
MicroPro 4.1
Type of Protection
n Overload protection
n Neutral Protection
Other Features
IS 9000 - PG4
n Zone Selectivity
IS 9000 - PG3
n Ampere Meter
Vibration Test
IEC 255 - 4
Radio Frequency
Interference (RFI)
IEC 801- 3
Electrostatic Discharge
(ESD)
IEC 801- 2
IEC 801- 4
n LCD display
n LCD display and fault LED retention in case of power failure
(EFT)
Surge
IEC 801- 5
MicroPro 5.1
Impulse
IEC 255 - 4
Protection thresholds and delays are set using the keypad. The
selected value are momentarily displayed in amperes.
Type of Protection
n Overload protection
n Short Circuit current protection
t
I>
t>
Ig
I >>
0.5+
tg
2.5+
-0.05
-0.1
-0.2
-0.3
x lo
I>
I>
I >>
-2.5
-5
-10
-15
t >>
ON
LTD
t>
Sec
IG
STD
4+
-5
-5
-10
-15
IG
-50
-100
-150
-200
tG
I >>
-50
-100
-150
-200
t >>
x lo
ms
n Neutral Protection
Other Features
n Zone Selectivity
n Ampere Meter
INS
50+ % lo
4+
-1
-1
-TEST
-LONG
-SHORT
DIP
- ON
FUNCTION
BLOCKING
NORMAL
15%+
1 2 3 4
NORMAL
TEST MODE
-1
-1
-2
-2
GFT
RESET
50+
ms
-LTD
-STD
-INS
-GFT
-2
-3
I >>
x lo
n LCD display
n LCD display and fault LED retention in case of power failure
Type
4.1
5.1
Pick up
Delay
Pick up
1.5-10 Ir in 10 steps:
1.5, 2, 2.5, 3, 4, 5, 6, 8, 9, 10
Delay
Pick up
Delay
Pick up
Short Circuit
Instantaneous
Earth Fault
N Protection
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
LCD Display
Available
Available
Trip History
Zone selectivity
Available
Available
Settings Adjustment by
Knob
Keypad
Load current
Phase, N & E
Phase, N & E
Fault current
To remote
Measurements
INDICATIONS
Communication
Inputs
: From The CTs with 200mA rated output one for each phase and one for Neutral current measurement.
Output
Red Led
: indications for different the types of the fault/tripping such as Over load, Short Ckt, Earth Fault, Instantaneous, Neutral.
Green Led
Type
4.1
5.1
Pick up
Delay
Pick up
1.5-10 Ir in 10 steps:
1.5, 2, 2.5, 3, 4, 5, 6, 8, 9, 10
Delay
Pick up
Delay
Pick up
Short Circuit
Instantaneous
Earth Fault
N Protection
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
LCD Display
Available
Available
Trip History
Zone selectivity
Available
Available
Settings Adjustment by
Knob
Keypad
Load current
Phase, N & E
Phase, N & E
Fault current
To remote
Measurements
INDICATIONS
Communication
Inputs
: From The CTs with 200mA rated output one for each phase and one for Neutral current measurement.
Output
Red Led
: indications for different the types of the fault/tripping such as Over load, Short Ckt, Earth Fault, Instantaneous, Neutral.
Green Led
Communication Module
Communication module is an accessory of MicroPro Relay and is an
optional module for the customer who needs additional features.The
module gets connected to Micropro by two wires through general
protocol & through 485 port, can be connected to Master PC. The
communication module acts as a master for the MicroPro relay and as a
slave to the supervisor PC.
The module can accept 9 different Digital inputs and has two relays
inside whose contacts are brought out on the terminals which are D/O
types.
There are 3 LEDs on the front indicating status of 1. Communication between Micro Pro and Comm. Module
2. Communication between Comm. Module and Master PC.
The module has relay outputs corresponding to the type of fault occurred in the MicroPro. There are total 7 Relays and contact
of each relay is available for feeding to alarm annunciator or any other control .
The module has built in Power supply card and DC supply for the relay can be obtained from this module.If the relay card is not
used then the module becomes power supply module.The power supply card is common with Communication module
Operation - PSRM
The PSRM module when connected to Micro pro will get the information of type of fault and in which phase the fault has
occurred. Corresponding to this a particular relays will operate and the output contacts of the relay will change the status.
Through 3 DIP switches, one can block the function. Blocking ensures that the particular output contact corresponding to the
function have no effect even if the function in the relay device is activated. The contacts will remain open if DIP switches are
used to block the function. There will be option of providing 4 or 7 relays.
Operation
Auxiliary Supply
Input:
Output:
24V DC 10%
Relays
Number of relays:
Contact rating:
Contacts:
4 or 7 nos.
125V AC, 0.6A or 110V DC 0.6A
1 terminal pair from each relay
Extension functions:
Extension provides operation of relays. Signal for such operation are sent by MicroPro on RS485 serial data
communication interface. The relays operate on following faults:
1. Over current [I>]
2. Phase current High set [I>>}
3. Earth Fault [IE>]
4. Neutral Over current [IN>]
5. Circuit Breaker failure [CBF] 6. Pre-trip alarm [W]
7. Spare
Function blocking:
DIP switches are provided for selectively blocking any of the above functions.
7 Position DIP switch works as follows:
Case 1: Number of relays =7: Each position corresponds to one of the above functions and in the same sequence.
When a switch is in OFF position, the corresponding function is blocked. This means that relay will not trip when its
assigned fault occurs.
Operates one of the relays whose contacts are available on the terminals
as soon as MicroPro exceeds the threshold of the trip.
Because of the above capabilities all the relevant information related to
Case 2: Number of relays =4: The enabled functions are assigned to consecutive relays. Not more than 4
functions can be enabled since there are only 4 relays.
status of the relay can be furnished to the Master. The information can
also be used for zone selectivity interlocking by using the contacts of the
relevant relay.
Connections
Z1 ~ D19
Di & Do outputs
ZO / COMMON/DO
= Zone selectivity
Total Terminals: 21
Communication Device
Type
RS485 Master
Size:
W x H x D in mm: 119 x 63 x 50
Communication Module
Communication module is an accessory of MicroPro Relay and is an
optional module for the customer who needs additional features.The
module gets connected to Micropro by two wires through general
protocol & through 485 port, can be connected to Master PC. The
communication module acts as a master for the MicroPro relay and as a
slave to the supervisor PC.
The module can accept 9 different Digital inputs and has two relays
inside whose contacts are brought out on the terminals which are D/O
types.
There are 3 LEDs on the front indicating status of 1. Communication between Micro Pro and Comm. Module
2. Communication between Comm. Module and Master PC.
The module has relay outputs corresponding to the type of fault occurred in the MicroPro. There are total 7 Relays and contact
of each relay is available for feeding to alarm annunciator or any other control .
The module has built in Power supply card and DC supply for the relay can be obtained from this module.If the relay card is not
used then the module becomes power supply module.The power supply card is common with Communication module
Operation - PSRM
The PSRM module when connected to Micro pro will get the information of type of fault and in which phase the fault has
occurred. Corresponding to this a particular relays will operate and the output contacts of the relay will change the status.
Through 3 DIP switches, one can block the function. Blocking ensures that the particular output contact corresponding to the
function have no effect even if the function in the relay device is activated. The contacts will remain open if DIP switches are
used to block the function. There will be option of providing 4 or 7 relays.
Operation
Auxiliary Supply
Input:
Output:
24V DC 10%
Relays
Number of relays:
Contact rating:
Contacts:
4 or 7 nos.
125V AC, 0.6A or 110V DC 0.6A
1 terminal pair from each relay
Extension functions:
Extension provides operation of relays. Signal for such operation are sent by MicroPro on RS485 serial data
communication interface. The relays operate on following faults:
1. Over current [I>]
2. Phase current High set [I>>}
3. Earth Fault [IE>]
4. Neutral Over current [IN>]
5. Circuit Breaker failure [CBF] 6. Pre-trip alarm [W]
7. Spare
Function blocking:
DIP switches are provided for selectively blocking any of the above functions.
7 Position DIP switch works as follows:
Case 1: Number of relays =7: Each position corresponds to one of the above functions and in the same sequence.
When a switch is in OFF position, the corresponding function is blocked. This means that relay will not trip when its
assigned fault occurs.
Operates one of the relays whose contacts are available on the terminals
as soon as MicroPro exceeds the threshold of the trip.
Because of the above capabilities all the relevant information related to
Case 2: Number of relays =4: The enabled functions are assigned to consecutive relays. Not more than 4
functions can be enabled since there are only 4 relays.
status of the relay can be furnished to the Master. The information can
also be used for zone selectivity interlocking by using the contacts of the
relevant relay.
Connections
Z1 ~ D19
Di & Do outputs
ZO / COMMON/DO
= Zone selectivity
Total Terminals: 21
Communication Device
Type
RS485 Master
Size:
W x H x D in mm: 119 x 63 x 50
(3P) (4P)
Panel Cutout
AH - 30D to AH - 40D
AH - 50C to AH - 60C
(3P) (4P)
Panel Cutout
(3P) (4P)
Panel Cutout
D
E
D
a
AH - 6D to AH - 25D
L
M
98
80
134
110
134
110
141
247
247
308
308
308
308
285
295
295
363
363
363
363
180
3P
316
368
416
466
498
548
590
4P
416
468
546
596
658
708
780
3P
215
199
270
248
311
289
373.5
F
4P
215
199
270
248
311
289
373.5
3P
215
199
270
248
311
289
373.5
4P
332
299
400
378
471
449
563.5
505
487
655
575
655
575
685
120
120
138
138
93
93
90
J
3P
122
100
163
100
163
100
125
K
4P
122
100
163
100
163
100
125
3P
270
270
270
268
L
4P
270
270
270
268
3P
117
137
166
191
4P
117
137
166
191
509
379
570
396
599
422
584
205
187
289
269
149
129
166
3P
100
100
130
130
160
160
190
4P
100
100
130
130
160
160
190
3P
15
15
40
4P
15
15
40
3P
334
480
480
U
4P
334
480
480
3P
154
198
236
4P
254
328
396
3P
154
198
236
4P
154
198
236
Terminal Arrangements
AH - 6D ~ 25D (Fixed)
AH - 30D (Fixed)
P
p
4-f15
107
107
107
107
115
115
115
117
117
194
194
194
210
20
15
20
15
20
20
15
25
20
25
25
25
25
30
30
30
30
35
35
30
50
35
55
55
55
55
8
8
12
12
20
20
20
15
15
15
15
22
16
45
45
50
45
55
60
45
80
80
140
140
140
140
112.5
112.5
112.5
112.5
112.5
112.5
112.5
112.5
AH
D/O(6D,8D)&(AHA-08N) 46.8
FIX (6D,8D)&(AHA-08N)
D/O (20D-25D)
FIX (20D-25D)
D/O (30D)
FIX (30D)
D/O (40D)
D/O (50C-60C)
10
60
46.8
60
46.8
46.8
60
60
80
106
119
106
146
i
3P
112.5
112.5
112.5
112.5
175
175
175
225
j
4P
175
175
175
175
240
255
255
320
3P
112.5
112.5
112.5
112.5
175
175
175
225
4P
175
175
175
175
240
255
255
320
50
50
50
50
65
80
80
95
48
48
48
48
48
48
48
48
157
157
157
157
213
200
200
246
65
65
65
65
150
30
30
30
440
440
440
440
553
578
578
619.5
25
mm
Terminal blocks
for control
circuits 36-M4
25
M8 tapped
hole for
earth terminal
62
P
M8 tapped
hole for
earth terminal
FIXED
530
550
DRAWOUT
550
570
3-f15
W
P
Earth terminal M8
Type of ACBs
(3P) Mounting
(4P) holes 3-14
630
35
17.5
Earth terminal M8
j
j
q
20
660
m m
(3P)
(4P)
Terminal blocks
for control
circuits 36-M4
70 45
25
j
j
W
N
P P
54
mm
Mounting
holes 3-14
(3P)
(4P)
j
j
25
54 45
x
m
iq
25
3-f15
Terminal
blocks for
control circuit
36-M4
d
P
(4P)
(3P)
W
630
25
54 45
50
3-f15
Mounting
holes 3-12
25
25
3-12
V
U
2-11
AH - 40D Drawout
Mounting holes 3-14
550
Mounting Holes
4x12
AH - 30D Drawout
AH - 20D~25D
AH - 6D~16D
AHA-20N
Y
20D - 25D
30D - 40D
50C - 60C
530 550
660
715
690
745
550 590
680
735
710
765
820
885
11
(3P) (4P)
Panel Cutout
AH - 30D to AH - 40D
AH - 50C to AH - 60C
(3P) (4P)
Panel Cutout
(3P) (4P)
Panel Cutout
D
E
D
a
AH - 6D to AH - 25D
L
M
98
80
134
110
134
110
141
247
247
308
308
308
308
285
295
295
363
363
363
363
180
3P
316
368
416
466
498
548
590
4P
416
468
546
596
658
708
780
3P
215
199
270
248
311
289
373.5
F
4P
215
199
270
248
311
289
373.5
3P
215
199
270
248
311
289
373.5
4P
332
299
400
378
471
449
563.5
505
487
655
575
655
575
685
120
120
138
138
93
93
90
J
3P
122
100
163
100
163
100
125
K
4P
122
100
163
100
163
100
125
3P
270
270
270
268
L
4P
270
270
270
268
3P
117
137
166
191
4P
117
137
166
191
509
379
570
396
599
422
584
205
187
289
269
149
129
166
3P
100
100
130
130
160
160
190
4P
100
100
130
130
160
160
190
3P
15
15
40
4P
15
15
40
3P
334
480
480
U
4P
334
480
480
3P
154
198
236
4P
254
328
396
3P
154
198
236
4P
154
198
236
Terminal Arrangements
AH - 6D ~ 25D (Fixed)
AH - 30D (Fixed)
P
p
4-f15
107
107
107
107
115
115
115
117
117
194
194
194
210
20
15
20
15
20
20
15
25
20
25
25
25
25
30
30
30
30
35
35
30
50
35
55
55
55
55
8
8
12
12
20
20
20
15
15
15
15
22
16
45
45
50
45
55
60
45
80
80
140
140
140
140
112.5
112.5
112.5
112.5
112.5
112.5
112.5
112.5
AH
D/O(6D,8D)&(AHA-08N) 46.8
FIX (6D,8D)&(AHA-08N)
D/O (20D-25D)
FIX (20D-25D)
D/O (30D)
FIX (30D)
D/O (40D)
D/O (50C-60C)
10
60
46.8
60
46.8
46.8
60
60
80
106
119
106
146
i
3P
112.5
112.5
112.5
112.5
175
175
175
225
j
4P
175
175
175
175
240
255
255
320
3P
112.5
112.5
112.5
112.5
175
175
175
225
4P
175
175
175
175
240
255
255
320
50
50
50
50
65
80
80
95
48
48
48
48
48
48
48
48
157
157
157
157
213
200
200
246
65
65
65
65
150
30
30
30
440
440
440
440
553
578
578
619.5
25
mm
Terminal blocks
for control
circuits 36-M4
25
M8 tapped
hole for
earth terminal
62
P
M8 tapped
hole for
earth terminal
FIXED
530
550
DRAWOUT
550
570
3-f15
W
P
Earth terminal M8
Type of ACBs
(3P) Mounting
(4P) holes 3-14
630
35
17.5
Earth terminal M8
j
j
q
20
660
m m
(3P)
(4P)
Terminal blocks
for control
circuits 36-M4
70 45
25
j
j
W
N
P P
54
mm
Mounting
holes 3-14
(3P)
(4P)
j
j
25
54 45
x
m
iq
25
3-f15
Terminal
blocks for
control circuit
36-M4
d
P
(4P)
(3P)
W
630
25
54 45
50
3-f15
Mounting
holes 3-12
25
25
3-12
V
U
2-11
AH - 40D Drawout
Mounting holes 3-14
550
Mounting Holes
4x12
AH - 30D Drawout
AH - 20D~25D
AH - 6D~16D
AHA-20N
Y
20D - 25D
30D - 40D
50C - 60C
530 550
660
715
690
745
550 590
680
735
710
765
820
885
11
AH-Series
AH-Series