Pole Loading Tree Calculation
Pole Loading Tree Calculation
Pole Loading Tree Calculation
Type
Angle Deviation
Wind Pressure for
Steel tower
Conductor
Insulator
Number of Circuit
Basic Span
Wind Loading Span
Normal working
Broken wire
Weight Span
Suspension Tower
Normal working
Broken wire
Tension Tower
Normal working
Broken wire
Maximum Working Tower (T) Conductor
Maximum Working Tower (T) Groundwires
Cable
Groundwire :
GSW
weight per meter
diametre
OPGW
weight per meter
diametre
Fitting
Damper
quantity
weight
Conductor
ACSR
weight per meter (kg/m)
diametre (mm)
Insulator
quantity
overall quantity
area
weight
Fitting
Damper
quantity
weight
Spacer
quantity
weight
Jumper
400
300
400
300
2400
1400
0.446
9.6
0.450
12.8
7.6
2.8
2
1.4
mm
kg
kg
kg
0.984 0.984
21.9 21.9
12
24
438 x
6 kg
36.31 kg
2
4.65 kg
0
1.4 kg
86 kg
254
mm2
Seismic Load
V=
C1 I
R
Wt
V
C1
I
R
Wt
= Horizontal Force
=
0.2 , Batam, Zone 1
=
1.4 , Power Plant Facility
=
2.2 , cantilever column
= Weight of Structure
0.1273 Wt
Normal =
300 m,
Broken
=
Normal =
400 m,
Broken
=
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
2
=
40 kg/m
= 40 x 9.6 / 1000
= 0.384 kg/m
= 40 x 12.8 / 1000
= 0.512 kg/m
= 1400 x 2 x sin ( 15 / 2 ) = 365.473 kg
NORMAL (1)
200 m
300 m
0.446 kg/m
0.45 kg/m
BROKEN (2)
Deviation
365.473
TOTAL
74
182.737
477
257
Deviation
365.473
TOTAL
99
182.737
514
282
400 x 0.446
Fittings
Dampers
2 x 1.4
178
300 x 0.446 =
134
7.6
7.6
2.8
2.8
150
150
TOTAL
2 x 1.4
339
294
400 x 0.45
Fittings
Dampers
2 x 1.4
180
7.6
2.8
150
300 x 0.45
2 x 1.4
135
7.6
2.8
150
340
295
TOTAL
0
0
Wind90_Dev30_Ew
100 % x MWT
100 % x MWT
=
=
1400
1400
1 of 10
Wind90_Dev30_Ew
1 of 10
=
300 m,
Broken
= 200 m
=
400 m,
Broken
= 300 m
=
0 m
=
0 m
= 1 * 2400
= 2400 kg
= 21.9 mm
Weight =
0.98 kg/m
2
=
40 kg/m
( including grease )
= 2 x 40 x 21.9 / 1000
= 1.75 kg/m
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 15 / 2 ) =
626.526 kg
NORMAL (3)
BROKEN (4)
TRANVERSE LOAD
Due to Wind
Deviation
Insulator
1 x 1.335 x 60
338
627
313
80
80
TOTAL
1214
732
Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight
1 x 400 x 0.984
394
1 x 300 x 0.984
Insulator
24 x 6
144
24 x 6
36
Fittings
295
144
36
Dampers
2 x 4.65
2 x 4.65
Spacers
0 x 1.4
0 x 1.4
Jumper Weights
86
86
150
150
TOTAL
819
721
TOTAL
LONGITUDINAL LOAD
Wind90_Dev30_Cond
2 of 10
Wind90_Dev30_Cond
2 of 10
Normal =
300 m,
Normal =
400 m,
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
=
12.8 mm
=
40 kg/m2
= 40 x 9.6 / 1000
=
= 40 x 12.8 / 1000
=
= 1400 x 2 x sin ( 30 / 2 )
Broken
Broken
=
=
Weight =
Weight =
200 m
300 m
0.446 kg/m
0.45 kg/m
0.384 kg/m
0.512 kg/m
= 724.693 kg
NORMAL (5)
BROKEN (6)
Deviation
725
TOTAL
67
362
824
429
Deviation
725
TOTAL
89
362
858
451
400 x 0.446
Fittings
Dampers
2 x 1.4
178
300 x 0.446 =
134
7.6
7.6
2.8
2.8
150
150
TOTAL
2 x 1.4
339
294
400 x 0.45
Fittings
Dampers
Worker with Tools
TOTAL
2 x 1.4
180
7.6
2.8
150
300 x 0.45
2 x 1.4
135
7.6
2.8
150
340
295
TOTAL
Wind90_Dev60_Ew
100 % x MWT
1400
3 of 10
Wind90_Dev60_Ew
100 % x MWT
1400
3 of 10
=
300 m,
Broken
=
200 m
=
400 m,
Broken
=
300 m
=
0 m
=
0 m
= 1 * 2400
=
2400 kg
=
21.9 mm
Weight =
0.984 kg/m
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
=
1.752 kg/m
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 30 / 2 ) =
1242.331 kg
NORMAL (7)
BROKEN (8)
TRANVERSE LOAD
Due to Wind
Deviation
Insulator
1 x 1.335 x 60
303
1242
621
80
80
TOTAL
1778
1005
Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight
1 x 400 x 0.984
394
1 x 300 x 0.984
Insulator
24 x 6
144
24 x 6
36
Fittings
295
144
36
Dampers
2 x 4.65
2 x 4.65
Spacers
0 x 1.4
0 x 1.4
Jumper Weights
86
86
150
150
TOTAL
819
721
TOTAL
LONGITUDINAL LOAD
Wind90_Dev60_Cond
2x100% x MWT =
2400
4 of 10
Wind90_Dev60_Cond
4 of 10
Normal
Normal
=
300 m,
Broken
=
400 m,
Broken
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 15 / 2 ) =
365.473
NORMAL (9)
=
=
200 m
300 m
0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg
BROKEN (10)
Deviation
365.473
TOTAL
52
183
444
235
Deviation
365.473
TOTAL
70
183
470
253
400 x 0.446
Fittings
Dampers
2 x 1.4
178
7.6
2.8
150
TOTAL
300 x 0.446
2 x 1.4
134
7.6
2.8
150
339
294
400 x 0.45
Fittings
Dampers
Worker with Tools
TOTAL
2 x 1.4
180
7.6
2.8
150
300 x 0.45
2 x 1.4
135
7.6
2.8
150
340
295
TOTAL
Wind45_Dev30_Ew
100 % x MWT
1400
5 of 10
Wind45_Dev30_Ew
100 % x MWT
1400
5 of 10
=
300 m,
Broken
=
200
=
400 m,
Broken
=
300
=
0 m
=
0 m
= 1 * 2400
=
2400
=
21.9 mm
Weight =
0.984
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
= 1.752
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 15 / 2 ) =
626.526
NORMAL (11)
m
m
kg
kg/m
kg/m
kg
BROKEN (12)
TRANVERSE LOAD
Due to Wind
Deviation
Insulator
1 x 1.335 x 60
239
627
313
80
80
TOTAL
###
633
Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight
1 x 400 x 0.984
394
1 x 300 x 0.984
Insulator
24 x 6
144
24 x 6
36
Fittings
295
144
36
Dampers
2 x 4.65
2 x 4.65
Spacers
0 x 1.4
0 x 1.4
Jumper Weights
86
86
150
150
TOTAL
819
721
TOTAL
LONGITUDINAL LOAD
Wind45_Dev30_Cond
2x100% x MWT
2400
6 of 10
Wind45_Dev30_Cond
6 of 10
Normal
Normal
=
300 m,
Broken
=
400 m,
Broken
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 30 / 2 ) =
724.693
NORMAL (13)
=
=
200 m
300 m
0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg
BROKEN (14)
Deviation
725
TOTAL
47
362
795
409
Deviation
725
TOTAL
63
362
819
425
400 x 0.446
Fittings
Dampers
2 x 1.4
178
7.6
2.8
150
TOTAL
300 x 0.446
2 x 1.4
134
7.6
2.8
150
339
294
400 x 0.45
Fittings
Dampers
Worker with Tools
TOTAL
2 x 1.4
180
7.6
2.8
150
300 x 0.45
2 x 1.4
135
7.6
2.8
150
340
295
TOTAL
Wind45_Dev60_Ew
100 % x MWT
1400
7 of 10
Wind45_Dev60_Ew
100 % x MWT
1400
7 of 10
=
300 m,
Broken
=
200
=
400 m,
Broken
=
300
=
0 m
=
0 m
= 1 * 2400
=
2400
=
21.9 mm
Weight =
0.984
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
=
1.752
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 30 / 2 ) =
1242.331
NORMAL (15)
m
m
kg
kg/m
kg/m
kg
BROKEN (16)
TRANVERSE LOAD
Due to Wind
Deviation
Insulator
1 x 1.335 x 60
215
1242
621
80
80
TOTAL
1644
916
Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight
1 x 400 x 0.984
394
1 x 300 x 0.984
Insulator
24 x 6
144
24 x 6
36
Fittings
295
144
36
Dampers
2 x 4.65
2 x 4.65
Spacers
0 x 1.4
0 x 1.4
Jumper Weights
86
86
150
150
TOTAL
819
721
TOTAL
LONGITUDINAL LOAD
Wind45_Dev60_Cond
2 x MWT
2400
8 of 10
Wind45_Dev60_Cond
8 of 10
Normal
Normal
=
300 m,
Broken
=
400 m,
Broken
=
0m
=
0m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 30 / 2 ) =
724.693
NORMAL (17)
=
=
200 m
300 m
0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg
BROKEN (18)
Deviation
725
TOTAL
362
725
362
Deviation
725
TOTAL
362
725
362
400 x 0.446
Fittings
Dampers
2 x 1.4
178
7.6
2.8
150
TOTAL
300 x 0.446
2 x 1.4
134
7.6
2.8
150
339
294
400 x 0.45
Fittings
Dampers
2 x 1.4
180
7.6
2.8
150
300 x 0.45
2 x 1.4
135
7.6
2.8
150
340
295
TOTAL
100 % x MWT
Due to Wind
58
TOTAL
LONGITUDINAL LOAD (OPGW)
1458
0
100 % x MWT
Due to Wind
TOTAL
Wind0_Dev60_Ew
1400
1400
77
1477
9 of 10
Wind0_Dev60_Ew
9 of 10
300 m,
Broken
=
200 m
400 m,
Broken
=
300 m
0 m
0 m
1 * 2400
=
2400 kg
21.9 mm
Weight =
0.984 kg/m
40 kg/m2
( including grease )
2 x 40 x 21.9 / 1000
=
1.752 kg/m
60 kg/m2
1.335 m2
2400 x 2 x sin ( 30 / 2 )
=
1242.331 kg
NORMAL (19)
BROKEN (20)
TRANVERSE LOAD
Due to Wind
Deviation
Insulator
1 x 1.335 x 60
= 1242
621
80
TOTAL
80
1322
701
Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight
1 x 400 x 0.984
394
1 x 300 x 0.984
Insulator
24 x 6
144
24 x 6
36
Fittings
295
144
36
Dampers
2 x 4.65
2 x 4.65
Spacers
0 x 1.4
0 x 1.4
Jumper Weights
86
86
150
TOTAL
150
819
721
2 x 100 % x MWT
Due to Wind
263
TOTAL
Wind0_Dev60_Cond
2400
2663
10 of 10
kg
EarthWire
Normal
Conductor
Broken
GSW
OPGW
GSW
OPGW
Normal
Broken
Transv Vertical Transv Vertical Transv Vertical Long
Transv Vertical Long
Transv Vertical Transv Vertical Long
Win90_Dev0_Bal
477
339
514
340
257
294
1400
282
295
1400
1214
819
732
721
2400
Win90_Dev1_Bal
824
339
858
340
429
294
1400
451
295
1400
1778
819
1005
721
2400
Win45_Dev0_Bal
444
339
470
340
235
294
1400
253
295
1400
1066
819
633
721
2400
Win45_Dev1_Bal
795
339
819
340
409
294
1400
425
295
1400
1644
819
916
721
2400
Win0_Dev3_UnBal
725
339
725
340
362
294
1458
362
295
1477
1322
819
701
721
2663
Win90_Dev0_Bal
Win90_Dev1_Bal
Win45_Dev0_Bal
Win45_Dev1_Bal
Win0_Dev1_UnBal
4.675
8.085
4.356
7.799
7.107
-3.322
-3.322
-3.322
-3.322
-3.322
5.039
8.411
4.613
8.029
7.107
-3.338
-3.338
-3.338
-3.338
-3.338
2.520
4.206
2.306
4.015
3.553
-2.885
-2.885
-2.885
-2.885
-2.885
kN
13.729
13.729
13.729
13.729
14.294
2.762
4.423
2.478
4.168
3.553
-2.897
-2.897
-2.897
-2.897
2.897
13.729
13.729
13.729
13.729
14.482
5.953
8.718
5.227
8.061
6.482
-4.017
-4.017
-4.017
-4.017
-4.017
3.589
4.928
3.104
4.491
3.437
-3.534
-3.534
-3.534
-3.534
-3.534
11.768
11.768
11.768
11.768
13.057
Double Circuit
TSP 30
Case 001 : Normal
477
514
257
514
1400
339
340
294
1214
1214
340
732
1214
2400
819
819
721
1214
1214
819
1214
1214
819
819
1214
1214
819
819
1214
1214
819
Wind Pressure
On Structure
90o
819
819
819
Wind Pressure
On Structure
90o
Tower SelfWeight
Tower SelfWeight
477
514
339
477
514
340
339
732
1214
2400
340
732
1214
2400
721
819
732
721
1214
819
1214
1214
2400
721
819
1214
819
1214
819
732
1214
2400
819
Wind Pressure
On Structure
90o
819
Tower SelfWeight
Win90_Dev30_Bal
721
Wind Pressure
On Structure
90o
819
Tower SelfWeight
1 of xx
Double Circuit
TSP 30
514
339
340
1214
1214
819
819
732
1214
2400
721
819
732
1214
2400
721
Wind Pressure
On Structure
90o
819
Tower SelfWeight
Win90_Dev30_Bal
1 of xx
Double Circuit
TSP 30
Case 006 : Normal
824
858
429
858
1400
339
340
294
1778
1778
340
1005
1778
2400
819
819
721
1778
1778
819
1778
819
1778
819
Wind Pressure
On Structure
90o
340
858
339
1005
Tower SelfWeight
858
339
1778
819
Tower SelfWeight
824
819
1778
819
Wind Pressure
On Structure
90o
1778
819
1778
819
819
1778
2400
340
1005
1778
2400
721
819
1005
721
1778
819
1778
1778
2400
721
819
1778
819
1778
819
1005
1778
2400
819
Wind Pressure
On Structure
90o
819
Tower SelfWeight
721
Wind Pressure
On Structure
90o
819
Tower SelfWeight
Win90_Dev60_Bal
1 of xx
Double Circuit
TSP 30
858
339
340
1778
1778
819
819
1005
1778
2400
721
819
1005
1778
2400
721
Wind Pressure
On Structure
90o
819
Tower SelfWeight
Win90_Dev60_Bal
1 of xx
Double Circuit
TSP 30
Case 011 : Normal
444
470
235
470
1400
339
340
###
1066
1066
340
633
1066
2400
819
819
721
1066
1066
819
1066
819
1066
819
1066
819
Wind Pressure
On Structure
45o
1066
819
1066
819
819
1066
819
819
Wind Pressure
On Structure
45o
Tower SelfWeight
Tower SelfWeight
444
470
339
444
340
470
###
633
1066
2400
340
633
1066
2400
721
819
633
721
1066
819
1066
1066
2400
721
819
1066
819
1066
819
633
1066
2400
819
Wind Pressure
On Structure
45o
819
Tower SelfWeight
Win45_Dev30_Bal
721
Wind Pressure
On Structure
45o
819
Tower SelfWeight
1 of xx
Double Circuit
TSP 30
470
339
340
1066
1066
819
819
633
1066
2400
721
819
633
1066
2400
721
Wind Pressure
On Structure
45o
819
Tower SelfWeight
Win45_Dev30_Bal
1 of xx
Double Circuit
TSP 30
Case 016 : Normal
795
819
409
819
1400
339
340
294
1644
1644
340
916
1644
2400
819
819
721
1644
1644
819
1644
819
1644
819
Wind Pressure
On Structure
45o
340
819
339
916
Tower SelfWeight
819
339
1644
819
Tower SelfWeight
795
819
1644
819
Wind Pressure
On Structure
45o
1644
819
1644
819
819
1644
2400
340
916
1644
2400
721
819
916
721
1644
819
1644
1644
2400
721
819
1644
819
1644
819
916
1644
2400
819
Wind Pressure
On Structure
45o
819
Tower SelfWeight
Win45_Dev60_Bal
721
Wind Pressure
On Structure
45o
819
Tower SelfWeight
1 of xx
Double Circuit
TSP 30
819
339
340
1644
1644
819
819
916
1644
2400
721
819
916
1644
2400
721
Wind Pressure
On Structure
45o
819
Tower SelfWeight
Win45_Dev60_Bal
1 of xx
Double Circuit
TSP 30
Case 021 : Normal
725
362
1458
339
294
1322
701
2663
819
721
1322
1322
819
819
1322
1322
819
819
Wind Pressure
On Structure
0o
Wind Pressure
On Structure
0o
Tower SelfWeight
Tower SelfWeight
725
725
339
339
701
701
2663
2663
721
721
701
1322
2663
721
819
1322
701
2663
819
Wind Pressure
On Structure
0o
721
Tower SelfWeight
Win0_Dev60_UnBal
Wind Pressure
On Structure
0o
Tower SelfWeight
1 of xx
Double Circuit
TSP 30
339
1322
819
701
2663
721
701
2663
721
Wind Pressure
On Structure
0o
Tower SelfWeight
Win0_Dev60_UnBal
1 of xx