Pole Loading Tree Calculation

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 33

Transmission

Type
Angle Deviation
Wind Pressure for
Steel tower
Conductor
Insulator
Number of Circuit
Basic Span
Wind Loading Span
Normal working
Broken wire
Weight Span
Suspension Tower
Normal working
Broken wire
Tension Tower
Normal working
Broken wire
Maximum Working Tower (T) Conductor
Maximum Working Tower (T) Groundwires

Cable
Groundwire :
GSW
weight per meter
diametre
OPGW
weight per meter
diametre
Fitting
Damper
quantity
weight
Conductor
ACSR
weight per meter (kg/m)
diametre (mm)
Insulator
quantity
overall quantity
area
weight
Fitting
Damper
quantity
weight
Spacer
quantity
weight
Jumper

Tension Steel Pole


TSP 30
15
30
70
40
60
1
200
300
200

400
300
400
300
2400
1400

0.446
9.6
0.450
12.8
7.6
2.8
2
1.4

mm
kg
kg
kg

0.984 0.984
21.9 21.9
12
24
438 x
6 kg
36.31 kg
2
4.65 kg
0
1.4 kg
86 kg

254

mm2

Seismic Load

V=

C1 I
R

Wt

V
C1
I
R
Wt

= Horizontal Force
=
0.2 , Batam, Zone 1
=
1.4 , Power Plant Facility
=
2.2 , cantilever column
= Weight of Structure

0.1273 Wt

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 90 deg & Deviation 15 deg
Calculation For Earthwire Loads
Wind
90 o
Deviation
15 o
Wind Span
Weight Span
Minimum Weight Span
Uplift Span
Maximum Working Tension (MWT)
Earthwire Diameter (GSW)
Earthwire Diameter (OPGW)
Wind Pressure on FPA
Wind Load/Meter (GSW)
Wind Load/Meter (OPGW)
Deviation Load

Normal =
300 m,
Broken
=
Normal =
400 m,
Broken
=
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
2
=
40 kg/m
= 40 x 9.6 / 1000
= 0.384 kg/m
= 40 x 12.8 / 1000
= 0.512 kg/m
= 1400 x 2 x sin ( 15 / 2 ) = 365.473 kg

NORMAL (1)

200 m
300 m

0.446 kg/m
0.45 kg/m

BROKEN (2)

TRANVERSE LOAD (GSW)


Due to Wind

300 x 0.384 x cos 15 =

Deviation

111 200 x 0.384 x cos 15 =


=

365.473

TOTAL

74

182.737

477

257

TRANVERSE LOAD (OPGW)


Due to Wind

300 x 0.512 x cos 15 =

Deviation

148 200 x 0.512 x cos 15 =


=

365.473

TOTAL

99

182.737

514

282

MAXIMUM VERTICAL LOAD (GSW)


Due to Weight

400 x 0.446

Fittings
Dampers

2 x 1.4

Worker with Tools

178

300 x 0.446 =

134

7.6

7.6

2.8

2.8

150

150

TOTAL

2 x 1.4

339

294

MAXIMUM VERTICAL LOAD (OPGW)


Due to Weight

400 x 0.45

Fittings
Dampers

2 x 1.4

Worker with Tools


TOTAL

180

7.6

2.8

150

300 x 0.45

2 x 1.4

135

7.6

2.8

150

340

295

TOTAL

LONGITUDINAL LOAD (GSW)


LONGITUDINAL LOAD (OPGW)

0
0

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind90_Dev30_Ew

100 % x MWT
100 % x MWT

=
=

1400
1400
1 of 10

Wind90_Dev30_Ew

1 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 90 deg & Deviation 15 deg
Calculation For Conductor Loads
Wind
90 o
Deviation
15 o
Wind Span
Normal
Weight Span
Normal
Minimum Weight Span
Uplift Span
Maximum Working Tension (for tower design)
Conductor Diameter
Wind Pressure on FPA
Wind Load/Metre
Wind Pressure on Insulator
Insulator Dimension 12 x 438 mm x 254 mm
Deviation Loads

=
300 m,
Broken
= 200 m
=
400 m,
Broken
= 300 m
=
0 m
=
0 m
= 1 * 2400
= 2400 kg
= 21.9 mm
Weight =
0.98 kg/m
2
=
40 kg/m
( including grease )
= 2 x 40 x 21.9 / 1000
= 1.75 kg/m
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 15 / 2 ) =
626.526 kg

NORMAL (3)

BROKEN (4)

TRANVERSE LOAD
Due to Wind

300 x 1.752 x cos 15 =

Deviation
Insulator

1 x 1.335 x 60

508 200 x 1.752 x cos 15 =

338

627

313

80

80

TOTAL

1214

732

Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight

1 x 400 x 0.984

394

1 x 300 x 0.984

Insulator

24 x 6

144

24 x 6

36

Fittings

295
144

36

Dampers

2 x 4.65

2 x 4.65

Spacers

0 x 1.4

0 x 1.4

Jumper Weights

86

86

Worker with Tools

150

150

TOTAL

819

721

TOTAL

LONGITUDINAL LOAD

2x100% x MWT = 2400

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind90_Dev30_Cond

2 of 10

Wind90_Dev30_Cond

2 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 90 deg & Deviation 30 deg
Calculation For Earthwire Loads
Wind
90 o
Deviation
30 o
Wind Span
Weight Span
Minimum Weight Span
Uplift Span
Maximum Working Tension (MWT)
Earthwire Diameter (GSW)
Earthwire Diameter (OPGW)
Wind Pressure on FPA
Wind Load/Metre (GSW)
Wind Load/Metre (OPGW)
Deviation Load

Normal =
300 m,
Normal =
400 m,
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
=
12.8 mm
=
40 kg/m2
= 40 x 9.6 / 1000
=
= 40 x 12.8 / 1000
=
= 1400 x 2 x sin ( 30 / 2 )

Broken
Broken

=
=

Weight =
Weight =

200 m
300 m

0.446 kg/m
0.45 kg/m

0.384 kg/m
0.512 kg/m
= 724.693 kg

NORMAL (5)

BROKEN (6)

TRANVERSE LOAD (GSW)


Due to Wind

300 x 0.384 x cos 30 =

Deviation

100 200 x 0.384 x cos 30 =

725

TOTAL

67

362

824

429

TRANVERSE LOAD (OPGW)


Due to Wind

300 x 0.512 x cos 30 =

Deviation

133 200 x 0.512 x cos 30 =

725

TOTAL

89

362

858

451

MAXIMUM VERTICAL LOAD (GSW)


Due to Weight

400 x 0.446

Fittings
Dampers

2 x 1.4

Worker with Tools

178

300 x 0.446 =

134

7.6

7.6

2.8

2.8

150

150

TOTAL

2 x 1.4

339

294

MAXIMUM VERTICAL LOAD (OPGW)


Due to Weight

400 x 0.45

Fittings
Dampers
Worker with Tools
TOTAL

2 x 1.4

180

7.6

2.8

150

300 x 0.45

2 x 1.4

135

7.6

2.8

150

340

295

TOTAL

LONGITUDINAL LOAD (GSW)

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind90_Dev60_Ew

100 % x MWT

1400
3 of 10

LONGITUDINAL LOAD (OPGW)

Wind90_Dev60_Ew

100 % x MWT

1400

3 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 90 deg & Deviation 30 deg
Calculation For Conductor Loads
Wind
90 o
Deviation
30 o
Wind Span
Normal
Weight Span
Normal
Minimum Weight Span
Uplift Span
Maximum Working Tension (for tower design)
Conductor Diameter
Wind Pressure on FPA
Wind Load/Metre
Wind Pressure on Insulator
Insulator Dimension 12 x 438 mm x 254 mm
Deviation Loads

=
300 m,
Broken
=
200 m
=
400 m,
Broken
=
300 m
=
0 m
=
0 m
= 1 * 2400
=
2400 kg
=
21.9 mm
Weight =
0.984 kg/m
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
=
1.752 kg/m
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 30 / 2 ) =
1242.331 kg

NORMAL (7)

BROKEN (8)

TRANVERSE LOAD
Due to Wind

300 x 1.752 x cos 30 =

Deviation
Insulator

1 x 1.335 x 60

455 200 x 1.752 x cos 30 =

303

1242

621

80

80

TOTAL

1778

1005

Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight

1 x 400 x 0.984

394

1 x 300 x 0.984

Insulator

24 x 6

144

24 x 6

36

Fittings

295
144

36

Dampers

2 x 4.65

2 x 4.65

Spacers

0 x 1.4

0 x 1.4

Jumper Weights

86

86

Worker with Tools

150

150

TOTAL

819

721

TOTAL

LONGITUDINAL LOAD

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind90_Dev60_Cond

2x100% x MWT =

2400

4 of 10

Wind90_Dev60_Cond

4 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 45 deg & Deviation 15 deg
Calculation For Earthwire Loads
Wind
45 o
Deviation
15 o
Wind Span
Weight Span
Minimum Weight Span
Uplift Span
Maximum Working Tension (MWT)
Earthwire Diameter (GSW)
Earthwire Diameter (OPGW)
Wind Pressure on FPA
Wind Load/Metre (GSW)
Wind Load/Metre (OPGW)
Deviation Load

Normal
Normal

=
300 m,
Broken
=
400 m,
Broken
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 15 / 2 ) =
365.473

NORMAL (9)

=
=

200 m
300 m

0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg

BROKEN (10)

TRANVERSE LOAD (GSW)


Due to Wind

300 x 0.384 x sin 45 x cos 15 =

Deviation

79 200 x 0.384 x sin 45 x cos 15 =

365.473

TOTAL

52

183

444

235

TRANVERSE LOAD (OPGW)


Due to Wind

300 x 0.512 x sin 45 x cos 15 =

Deviation

105 200 x 0.512 x sin 45 x cos 15 =

365.473

TOTAL

70

183

470

253

MAXIMUM VERTICAL LOAD (GSW)


Due to Weight

400 x 0.446

Fittings
Dampers

2 x 1.4

Worker with Tools

178

7.6

2.8

150

TOTAL

300 x 0.446

2 x 1.4

134

7.6

2.8

150

339

294

MAXIMUM VERTICAL LOAD (OPGW)


Due to Weight

400 x 0.45

Fittings
Dampers
Worker with Tools
TOTAL

2 x 1.4

180

7.6

2.8

150

300 x 0.45

2 x 1.4

135

7.6

2.8

150

340

295

TOTAL

LONGITUDINAL LOAD (GSW)

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind45_Dev30_Ew

100 % x MWT

1400
5 of 10

LONGITUDINAL LOAD (OPGW)

Wind45_Dev30_Ew

100 % x MWT

1400

5 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 45 deg & Deviation 15 deg
Calculation For Conductor Loads
Wind
45 o
Deviation
15 o
Wind Span
Normal
Weight Span
Normal
Minimum Weight Span
Uplift Span
Maximum Working Tension (for tower design)
Conductor Diameter
Wind Pressure on FPA
Wind Load/Metre
Wind Pressure on Insulator
Insulator Dimension 12 x 438 mm x 254 mm
Deviation Loads

=
300 m,
Broken
=
200
=
400 m,
Broken
=
300
=
0 m
=
0 m
= 1 * 2400
=
2400
=
21.9 mm
Weight =
0.984
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
= 1.752
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 15 / 2 ) =
626.526

NORMAL (11)

m
m

kg
kg/m
kg/m

kg

BROKEN (12)

TRANVERSE LOAD
Due to Wind

300 x 1.752 x sin 45 x cos 15 =

Deviation
Insulator

1 x 1.335 x 60

359 200 x 1.752 x sin 45 x cos 15 =

239

627

313

80

80

TOTAL

###

633

Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight

1 x 400 x 0.984

394

1 x 300 x 0.984

Insulator

24 x 6

144

24 x 6

36

Fittings

295
144

36

Dampers

2 x 4.65

2 x 4.65

Spacers

0 x 1.4

0 x 1.4

Jumper Weights

86

86

Worker with Tools

150

150

TOTAL

819

721

TOTAL

LONGITUDINAL LOAD

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind45_Dev30_Cond

2x100% x MWT

2400

6 of 10

Wind45_Dev30_Cond

6 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 45 deg & Deviation 30 deg
Calculation For Earthwire Loads
Wind
45 o
Deviation
30 o
Wind Span
Weight Span
Minimum Weight Span
Uplift Span
Maximum Working Tension (MWT)
Earthwire Diameter (GSW)
Earthwire Diameter (OPGW)
Wind Pressure on FPA
Wind Load/Metre (GSW)
Wind Load/Metre (OPGW)
Deviation Load

Normal
Normal

=
300 m,
Broken
=
400 m,
Broken
=
0 m
=
0 m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 30 / 2 ) =
724.693

NORMAL (13)

=
=

200 m
300 m

0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg

BROKEN (14)

TRANVERSE LOAD (GSW)


Due to Wind

300 x 0.384 x sin 45 x cos 30 =

Deviation

71 200 x 0.384 x sin 45 x cos 30 =

725

TOTAL

47

362

795

409

TRANVERSE LOAD (OPGW)


Due to Wind

300 x 0.512 x sin 45 x cos 30 =

Deviation

94 200 x 0.512 x sin 45 x cos 30 =

725

TOTAL

63

362

819

425

MAXIMUM VERTICAL LOAD (GSW)


Due to Weight

400 x 0.446

Fittings
Dampers

2 x 1.4

Worker with Tools

178

7.6

2.8

150

TOTAL

300 x 0.446

2 x 1.4

134

7.6

2.8

150

339

294

MAXIMUM VERTICAL LOAD (OPGW)


Due to Weight

400 x 0.45

Fittings
Dampers
Worker with Tools
TOTAL

2 x 1.4

180

7.6

2.8

150

300 x 0.45

2 x 1.4

135

7.6

2.8

150

340

295

TOTAL

LONGITUDINAL LOAD (GSW)

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind45_Dev60_Ew

100 % x MWT

1400
7 of 10

LONGITUDINAL LOAD (OPGW)

Wind45_Dev60_Ew

100 % x MWT

1400

7 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 45 deg & Deviation 30 deg
Calculation For Conductor Loads
Wind
45 o
Deviation
30 o
Wind Span
Normal
Weight Span
Normal
Minimum Weight Span
Uplift Span
Maximum Working Tension (for tower design)
Conductor Diameter
Wind Pressure on FPA
Wind Load/Metre
Wind Pressure on Insulator
Insulator Dimension 12 x 438 mm x 254 mm
Deviation Loads

=
300 m,
Broken
=
200
=
400 m,
Broken
=
300
=
0 m
=
0 m
= 1 * 2400
=
2400
=
21.9 mm
Weight =
0.984
=
40 kg/m2
( including grease )
= 2 x 40 x 21.9 / 1000
=
1.752
60 kg/m2
= 1.335 m2
= 2400 x 2 x sin ( 30 / 2 ) =
1242.331

NORMAL (15)

m
m

kg
kg/m
kg/m

kg

BROKEN (16)

TRANVERSE LOAD
Due to Wind

300 x 1.752 x sin 45 x cos 30 =

Deviation
Insulator

1 x 1.335 x 60

322 200 x 1.752 x sin 45 x cos 30 =

215

1242

621

80

80

TOTAL

1644

916

Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight

1 x 400 x 0.984

394

1 x 300 x 0.984

Insulator

24 x 6

144

24 x 6

36

Fittings

295
144

36

Dampers

2 x 4.65

2 x 4.65

Spacers

0 x 1.4

0 x 1.4

Jumper Weights

86

86

Worker with Tools

150

150

TOTAL

819

721

TOTAL

LONGITUDINAL LOAD

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Wind45_Dev60_Cond

2 x MWT

2400

8 of 10

Wind45_Dev60_Cond

8 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 0 deg & Deviation 30 deg
Calculation For Earthwire Loads
Wind
0o
Deviation
30 o
Wind Span
Weight Span
Minimum Weight Span
Uplift Span
Maximum Working Tension (MWT)
Earthwire Diameter (GSW)
Earthwire Diameter (OPGW)
Wind Pressure on FPA
Wind Load/Metre (GSW)
Wind Load/Metre (OPGW)
Deviation Load

Normal
Normal

=
300 m,
Broken
=
400 m,
Broken
=
0m
=
0m
=
1400 kg
=
9.6 mm
Weight =
=
12.8 mm
Weight =
=
40 kg/m2
= 40 x 9.6 / 1000
=
0.384
= 40 x 12.8 / 1000
=
0.512
= 1400 x 2 x sin ( 30 / 2 ) =
724.693

NORMAL (17)

=
=

200 m
300 m

0.446 kg/m
0.45 kg/m
kg/m
kg/m
kg

BROKEN (18)

TRANVERSE LOAD (GSW)


Due to Wind

300 x 0.384 x sin 0

Deviation

725

TOTAL

200 x 0.384 x sin 0

362

725

362

TRANVERSE LOAD (OPGW)


Due to Wind

300 x 0.512 x sin 0

Deviation

725

TOTAL

200 x 0.512 x sin 0

362

725

362

MAXIMUM VERTICAL LOAD (GSW)


Due to Weight

400 x 0.446

Fittings
Dampers

2 x 1.4

Worker with Tools

178

7.6

2.8

150

TOTAL

300 x 0.446

2 x 1.4

134

7.6

2.8

150

339

294

MAXIMUM VERTICAL LOAD (OPGW)


Due to Weight

400 x 0.45

Fittings
Dampers

2 x 1.4

Worker with Tools


TOTAL

180

7.6

2.8

150

300 x 0.45

2 x 1.4

135

7.6

2.8

150

340

295

TOTAL

LONGITUDINAL LOAD (GSW)

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD

Maximum Working Tension

100 % x MWT

Due to Wind

300 x 0.384 x sin 30 =

58

TOTAL
LONGITUDINAL LOAD (OPGW)

1458
0

Maximum Working Tension

100 % x MWT

Due to Wind

300 x 0.512 x sin 30 =

TOTAL

Wind0_Dev60_Ew

1400

1400
77
1477

9 of 10

Wind0_Dev60_Ew

9 of 10

UNFACTORED LOADS IN KILOGRAMS TSP 30


Tension Steel Pole With Wind 0 deg & Deviation 30 deg
Calculation For Conductor Loads
Wind
0 o
Deviat
30 o
Wind Span
Normal
=
Weight Span
Normal
=
Minimum Weight Span
=
Uplift Span
=
Maximum Working Tension (for tower desig=
Conductor Diameter
=
Wind Pressure on FPA
=
Wind Load/Metre
=
Wind Pressure on Insulator
Insulator Dim 12 x 438 mm x 254 mm
=
Deviation Loads
=

300 m,
Broken
=
200 m
400 m,
Broken
=
300 m
0 m
0 m
1 * 2400
=
2400 kg
21.9 mm
Weight =
0.984 kg/m
40 kg/m2
( including grease )
2 x 40 x 21.9 / 1000
=
1.752 kg/m
60 kg/m2
1.335 m2
2400 x 2 x sin ( 30 / 2 )
=
1242.331 kg

NORMAL (19)

BROKEN (20)

TRANVERSE LOAD
Due to Wind

300 x 1.752 x sin 0

Deviation
Insulator

1 x 1.335 x 60

= 1242

621

80

TOTAL

200 x 1.752 x sin 0

80
1322

701

Proportion / Face
MAXIMUM VERTICAL LOAD
Due to Weight

1 x 400 x 0.984

394

1 x 300 x 0.984

Insulator

24 x 6

144

24 x 6

36

Fittings

295
144

36

Dampers

2 x 4.65

2 x 4.65

Spacers

0 x 1.4

0 x 1.4

Jumper Weights

86

86

Worker with Tools

150

TOTAL

150

819

721

MINIMUM VERTICAL LOAD


TOTAL
UPLIFT VERTICAL LOAD
TOTAL
LONGITUDINAL LOAD
Maximum Working Tension

2 x 100 % x MWT

Due to Wind

300 x 1.752 x sin 30 =

263

TOTAL

Wind0_Dev60_Cond

2400

2663

10 of 10

kg
EarthWire
Normal

Conductor

Broken

GSW
OPGW
GSW
OPGW
Normal
Broken
Transv Vertical Transv Vertical Transv Vertical Long
Transv Vertical Long
Transv Vertical Transv Vertical Long
Win90_Dev0_Bal
477
339
514
340
257
294
1400
282
295
1400
1214
819
732
721
2400
Win90_Dev1_Bal
824
339
858
340
429
294
1400
451
295
1400
1778
819
1005
721
2400
Win45_Dev0_Bal
444
339
470
340
235
294
1400
253
295
1400
1066
819
633
721
2400
Win45_Dev1_Bal
795
339
819
340
409
294
1400
425
295
1400
1644
819
916
721
2400
Win0_Dev3_UnBal
725
339
725
340
362
294
1458
362
295
1477
1322
819
701
721
2663

Win90_Dev0_Bal
Win90_Dev1_Bal
Win45_Dev0_Bal
Win45_Dev1_Bal
Win0_Dev1_UnBal

4.675
8.085
4.356
7.799
7.107

-3.322
-3.322
-3.322
-3.322
-3.322

5.039
8.411
4.613
8.029
7.107

-3.338
-3.338
-3.338
-3.338
-3.338

2.520
4.206
2.306
4.015
3.553

-2.885
-2.885
-2.885
-2.885
-2.885

kN
13.729
13.729
13.729
13.729
14.294

2.762
4.423
2.478
4.168
3.553

-2.897
-2.897
-2.897
-2.897
2.897

13.729
13.729
13.729
13.729
14.482

5.953
8.718
5.227
8.061
6.482

-4.017
-4.017
-4.017
-4.017
-4.017

3.589
4.928
3.104
4.491
3.437

-3.534
-3.534
-3.534
-3.534
-3.534

11.768
11.768
11.768
11.768
13.057

Tension Steel Pole


Loading Diagram In Kg
Wind 90o
Deviation 15 deg

Double Circuit
TSP 30
Case 001 : Normal

Case 002 : EearthWire & Top Conductor Broken

477

514

257

514

1400
339

340

294

1214

1214

340

732

1214

2400
819

819

721

1214

1214

819

1214

1214

819

819

1214

1214

819

819

1214

1214

819

Wind Pressure
On Structure
90o

819

819

819

Wind Pressure
On Structure
90o

Tower SelfWeight

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 2 (Not Yet Included)

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Case 003 : Top & Middle Conductor Broken

Case 004 : Top & Bottom Conductor Broken

477

514

339

477

514

340

339

732

1214

2400

340

732

1214

2400
721

819

732

721
1214

819

1214

1214

2400
721

819

1214

819
1214

819

732

1214

2400
819
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win90_Dev30_Bal

721
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 90o
Deviation 15 deg

Double Circuit
TSP 30

Case 005 : Middle & Bottom Conductor Broken


477

514

339

340

1214

1214

819

819

732

1214

2400
721

819

732

1214

2400
721
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win90_Dev30_Bal

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 90o
Deviation 30 deg

Double Circuit
TSP 30
Case 006 : Normal

Case 007 : EearthWire & Top Conductor Broken

824

858

429

858

1400
339

340

294

1778

1778

340

1005

1778

2400
819

819

721

1778

1778

819

1778

819
1778

819

Wind Pressure
On Structure
90o

Seismic Load on Center of Mass of Structure


SF 2 (Not Yet Included)
Case 008 : Top & Middle Conductor Broken

Case 009 : Top & Bottom Conductor Broken


824

340

858

339

1005

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

858

339

1778

819

Tower SelfWeight

824

819

1778

819

Wind Pressure
On Structure
90o

1778

819

1778

819

819

1778

2400

340

1005

1778

2400
721

819

1005

721
1778

819

1778

1778

2400
721

819

1778

819
1778

819

1005

1778

2400
819
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)
Win90_Dev60_Bal

721
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)
1 of xx

Win90_Dev60_Bal

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 90o
Deviation 30 deg

Double Circuit
TSP 30

Case 010 : Middle & Bottom Conductor Broken


824

858

339

340

1778

1778

819

819

1005

1778

2400
721

819

1005

1778

2400
721
Wind Pressure
On Structure
90o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win90_Dev60_Bal

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 45o
Deviation 15 deg

Double Circuit
TSP 30
Case 011 : Normal

Case 012 : EearthWire & Top Conductor Broken

444

470

235

470

1400
339

340

###

1066

1066

340

633

1066

2400
819

819

721

1066

1066

819

1066

819
1066

819

1066

819

Wind Pressure
On Structure
45o

1066

819

1066

819

819

1066

819

819

Wind Pressure
On Structure
45o

Tower SelfWeight

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 2 (Not Yet Included)

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Case 013 : Top & Middle Conductor Broken

Case 014 : Top & Bottom Conductor Broken

444

470

339

444

340

470

###

633

1066

2400

340

633

1066

2400
721

819

633

721
1066

819

1066

1066

2400
721

819

1066

819
1066

819

633

1066

2400
819
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win45_Dev30_Bal

721
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 45o
Deviation 15 deg

Double Circuit
TSP 30

Case 015 : Middle & Bottom Conductor Broken


444

470

339

340

1066

1066

819

819

633

1066

2400
721

819

633

1066

2400
721
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win45_Dev30_Bal

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 45o
Deviation 30 deg

Double Circuit
TSP 30
Case 016 : Normal

Case 017 : EearthWire & Top Conductor Broken

795

819

409

819

1400
339

340

294

1644

1644

340

916

1644

2400
819

819

721

1644

1644

819

1644

819
1644

819

Wind Pressure
On Structure
45o

Seismic Load on Center of Mass of Structure


SF 2 (Not Yet Included)
Case 018 : Top & Middle Conductor Broken

Case 019 : Top & Bottom Conductor Broken


795

340

819

339

916

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

819

339

1644

819

Tower SelfWeight

795

819

1644

819

Wind Pressure
On Structure
45o

1644

819

1644

819

819

1644

2400

340

916

1644

2400
721

819

916

721
1644

819

1644

1644

2400
721

819

1644

819
1644

819

916

1644

2400
819
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win45_Dev60_Bal

721
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 45o
Deviation 30 deg

Double Circuit
TSP 30

Case 020 : Middle & Bottom Conductor Broken


795

819

339

340

1644

1644

819

819

916

1644

2400
721

819

916

1644

2400
721
Wind Pressure
On Structure
45o

819

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win45_Dev60_Bal

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 0o
Deviation 30 deg

Double Circuit
TSP 30
Case 021 : Normal

Case 022 : EearthWire & Top Conductor Broken

725

362
1458
339

294

1322

701
2663
819

721

1322

1322

819

819

1322

1322

819

819

Wind Pressure
On Structure
0o

Wind Pressure
On Structure
0o

Tower SelfWeight

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 2 (Not Yet Included)

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Case 023 : Top & Middle Conductor Broken

Case 024 : Top & Bottom Conductor Broken

725

725

339

339

701

701

2663

2663
721

721

701

1322

2663
721

819

1322

701
2663
819
Wind Pressure
On Structure
0o

721

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win0_Dev60_UnBal

Wind Pressure
On Structure
0o

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

1 of xx

Tension Steel Pole


Loading Diagram In Kg
Wind 0o
Deviation 30 deg

Double Circuit
TSP 30

Case 025 : Middle & Bottom Conductor Broken


725

339
1322

819
701
2663
721
701
2663
721
Wind Pressure
On Structure
0o

Tower SelfWeight

Seismic Load on Center of Mass of Structure


SF 1.5 (Not Yet Included)

Win0_Dev60_UnBal

1 of xx