Earthing Test Certificate PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

TEST CERTIFICATE OF EARTHING SOIL RESISTANCE

Testing kits

SEW STANDARD 1120ER (DIGITAL EARTH RESISTANCE TESTER) 1229345


PASSED

Calibrations

TESTER NOT UP TO A YEAR YET AND


ADJUSTABLE

Range

Acceptance <

Name & Qualifications:


Musa A Gafar
Technical Diploma,ND,HND and
C&G of london
Date of Test :18th February,2016

5ohms > Abnormal

Distance between Earth Electrode and Auxiliary Earth Spike


(C1):15m
Locations

Directions

Q.C

52% of
15m

62% of
15m

72% of
15m

Average
Earth Voltage: 2v

Lighting Arrestor

Length

7.80

9.30

10.80

9.30

Slonberger/Car park
Side

Ohms

50.20

50.60

50.80

50.53

Soil Resistance :50.53ohms


Soil Resistivity :469.93ohm-m
Comment: greater than 5ohm : Abnormal/not Accept
Lighting Arrestor

Length

7.80

9.30

10.80

9.30

Generator Side

Ohms

4.70

4.78

4.84

4.77

Earth Voltage: 1V

Soil Resistance :4.77ohms


Soil Resistivity :44.36ohm-m
Comment: below 5ohm : Normal/Accept
Transformer

Length

7.80

9.30

10.80

9.30

Building Front

Ohms

4.50

4.80

4.68

4.66

Earth Voltage: 1V

Soil Resistance :4.66ohms


Soil Resistivity :43.34ohm-m
Comment: below 5ohm : Normal/Accept
Name of Inspector _______________ Signature:__________________
Cluster Manager
Name of Inspector _______________ Signature: __________________