HISAC Ultima - Test Report: Header

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HISAC Ultima - Test Report

Test Date Time:

HEADER :

01-02-2016 12:29:09

Substation

765kV Varanasi SS

Breaker ID

802 52

Gas Pressure

0.52MPa

Bay

802

Breaker Type

800HCB50

Air Pressure

NIL

Operator

LNT

Serial Number

100144550007

Oil Pressure

32MPa

Manufacturer

HYOSUNG

Voltage (kV)

800

SETTINGS :
Trigger Option

Close

Sampling Speed (kC)

10

Plot Length(ms)

400

Delay tco (ms)

60

Delay toc (ms)

60

Current Range C1(A)

10

Current Range C2(A)

10

Current Range C3(A)

10

Current Range C4(A)

Current Range C5(A)

Current Range C6(A)

Velocity

Disabled

PIR

Enabled

Auxiliary

Enabled

Analog Channels

Disabled

T1 (mm)

T2 (mm)

217.3

T3 (mm)

Close1

0 mm

Open1

10 mm

DefClose

10 ms

Close2

10 mm

Open2

0 mm

DefOpen

10 ms

Velocity Points :

GRAPH :

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.

03/02/2016

Page 1 Of 2

HISAC Ultima - Test Report


Timing Results :
Close
Contact Time (ms)

84.4

82.6

84.6

Pole Mismatch (ms)

Break Mismatch (ms)

Max Bounce Duration (ms)

2.5

2.7

Total Bounce Duration (ms)

4.2

4.6

No. of Bounces

Travel Results :
TR1

TR2

TR3

TR4

TR5

TR6

Mechanism Travel (mm)

Contact Travel (mm)

Contact Wipe (mm)

Close - Default Travel (mm)

Close - Default Velocity (m/s)

Close - Datum Velocity (m/s)

Close - Over Travel (mm)

C1

C2

C3

C4

C5

C6

8.555

0.176

0.006

C1

C2

C3

C4

C5

C6

Coil Current Results:


Coil Current (A)

Coil Resistance Results:


Coil Resistance (Ohm)

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.

03/02/2016

Page 2 Of 2

You might also like