Professional Documents
Culture Documents
CW Closed Loop System - Nitrite PH Control - Flat
CW Closed Loop System - Nitrite PH Control - Flat
Usethediscussionlisttoholdnewsgroupstyledisscussionsontopicsrelevanttoyournetwork.
PostedBy
Post
Started:4/13/201611:29AM
ViewProperties
Reply
CWClosedLoopSystemNitrite&pHControl
MuhamadYunus,AbdulMuhaimin
I'mtreatingCWclosedloopsystemwithnitritebasedcorrosioninhibitor,TRAC109.TherecommendedpHrangeis8.510.5andnitriteconcentrationsupposeto
bemaintainedwithinrangeof6001000ppm.Basedoncurrenttreatment,nitriteleveliskeeparound600800ppm.However,pHofthesystemkeepmaintain
around10.410.6evensometimenitritedropaslowas550ppm(actuallycustomerneedtoblowdownsomeofclosedloopwaterduetopreviousincidentwhere
theirreactorwastrippedandtheybelieveitwascausebyN2producedbyclosedloopsystem),whichhascauseTRAC109needtobeinjectedmostofthetime.
WhatpossibilityforpHmaintainathigherrangeeventhereisfluctuationofnitritelevel?AsTRAC109containofboratethatfunctionaspHbuffer,anycorrelation
betweennitritelevelandpH?Anyonepleaseadvise.
Thankyou
Posted:4/18/20164:42PM
ViewProperties
Reply
ViewProperties
Reply
ViewProperties
Reply
Whatisthesourceofthemakeupwater,andwahtisitspH?
Zambrzuski,Steven
Posted:4/20/20169:50PM
Makeupwatersourceisdemin.pHisaround6.5~7.5
MuhamadYunus,AbdulMuhaimin
Posted:4/21/20164:48AM
DearMuhamad,
TrytouseN8338.WeuseitherewithROUnitwaterandthepHisaround8.0to10.0.
Cavalcanti,Pedro
TheR.O.Unitwaterisaround7.7to8.5.
Bestregards.