Cause and Effect Matrix Hydraulic Starter System: Ge Packaged Power, L.P
Cause and Effect Matrix Hydraulic Starter System: Ge Packaged Power, L.P
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
6.5
IN.HG
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
165.0
mm.HG
PDAHH
mm
LALL
DEG C
TAH
PDSHH-1600
LSLL-1601
TSH-1602
TSL-1603
70.0
DEG F
21.1
DEG C
TAL
PSLL-1605
250.0
PSIG
1724.0
KPaG
PALL
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
ESN
2
3
6.0
IN
152.0
ESN
HE-1610 PERM
4
5
180.0
DEG F
82.2
6
7
8
9
ESN
10
11
TE-1663A1
12
TE-1663A2
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
13
TE-1663A1/A2
-65.0
-65.0
1200.0
1200.0
-45.0
-45.0
390.0
390.0
DEG F
DEG F
-53.9
-53.9
648.9
648.9
-42.7
-42.7
198.9
198.9
DEG C
DEG C
SF
SF
14
TE-1663A1/A2
10.0
DEG F
5.6
DEG C
HD
15
TE-1663SEL
230.0
DEG F
110.0
DEG C
TAHH
16
TE-1663SEL
200.0
DEG F
93.3
DEG C
TAH
DM
17
18
SOV-1619
MOT-1615
MOT-1615FB
HE-1610
0.0
100.0
0.0
100.0
19
20
21
22
23
24
25
NOTES
1. INTENTIONALLY LEFT BLANK
2. SHUTDOWN START SYSTEM BY ALLOWING THE HYDRAULIC PUMP TO RESET TO NEUTRAL POSITION FOR 10 SEC. AND THEN TURN OFF MOT-1615.
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
22
PDSH-6405-60
5.0
IN H2O
127.0
mm H2O
PDAH
PDSHH-6406
8.0
IN H2O
203.2
mm H2O
PDAHH
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
3
4
PDSH-64017
3.5
IN H2O
88.9
mm H2O
PDAH
PDSHH-64018
4.5
IN H2O
114.3
mm H2O
PDAHH
PDT-64257
IN H2O
PDT-64257SEL
PDT-64258
X
ESN
6
-10.0
10.0
-10.2
10.2
-0.1
IN H2O
-10.0
10.0
-10.2
10.2
IN H2O
-65.0
1200.0
-45.0
390.0
200.0
DEG F
-65.0
1200.0
-45.0
390.0
DEG F
-254.0
254.0
-259.1
259.1
mm H2O
SF
-2.54
mm H2O
PDAL
-254.0
254.0
-259.1
259.1
mm H2O
SF
mm H2O
PDAL
-53.9
648.9
-42.7
198.9
DEG C
SF
93.3
DEG C
TAH
-53.9
648.9
-42.7
198.9
DEG C
SF
9
10
PDT-64258SEL
13
11
TE-6401
14
0.1
IN H2O
2.54
X
4
12
DEG F
TE-6401SEL
16
TE-6402
17
TE-6402SEL
150.0
DEG F
65.6
DEG C
TAHH
18
TE-6402SEL
125.0
DEG F
51.7
DEG C
TAH
15
DM
X
19
20
TE-6421
390.0
DEG F
198.9
DEG C
SF
21
TE-6421SEL
293.0
DEG F
145.0
DEG C
TAHH
25
22
TE-6421SEL
-65.0
1200.0
-45.0
275.0
DEG F
135.0
DEG C
TAH
25
23
TE-6421SEL
DEG C
EVENT
25
TE-6422
198.9
DEG C
SF
26
TE-6422SEL
145.0
DEG C
TAHH
25
27
TE-6422SEL
135.0
DEG C
TAH
25
28
TE-6422SEL
DEG C
EVENT
30
TE-6423
198.9
DEG C
SF
31
TE-6423SEL
145.0
DEG C
TAHH
25
32
TE-6423SEL
135.0
DEG C
TAH
25
33
TE-6423SEL
DEG C
EVENT
35
TE-6424
198.9
DEG C
SF
36
TE-6424SEL
145.0
DEG C
TAHH
25
37
TE-6424SEL
135.0
DEG C
TAH
25
38
TE-6424SEL
DEG C
EVENT
40
TE-6425
198.9
DEG C
SF
41
TE-6425SEL
145.0
DEG C
TAHH
25
42
TE-6425SEL
135.0
DEG C
TAH
25
43
TE-6425SEL
DEG C
EVENT
45
TE-6426
198.9
DEG C
SF
46
TE-6426SEL
145.0
DEG C
TAHH
25
47
TE-6426SEL
135.0
DEG C
TAH
25
48
TE-6426SEL
DEG C
EVENT
50
TE-6430
DEG C
SF
51
TE-6430SEL
52
TE-6430SEL
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
24
-65.0
1200.0
-45.0
390.0
DEG F
293.0
DEG F
275.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
29
-65.0
1200.0
-45.0
390.0
DEG F
293.0
DEG F
275.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
34
-65.0
1200.0
-45.0
390.0
DEG F
293.0
DEG F
275.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
39
-65.0
1200.0
-45.0
390.0
DEG F
293.0
DEG F
275.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
44
-65.0
1200.0
-45.0
390.0
DEG F
293.0
DEG F
275.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
DM
X
X
49
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
220.0
DEG F
104.4
DEG C
TAHH
200.0
DEG F
93.3
DEG C
TAH
X
X
DM
53
54
TE-6431
390.0
DEG F
DEG C
SF
55
TE-6431SEL
220.0
DEG F
104.4
DEG C
TAHH
56
TE-6431SEL
-65.0
1200.0
-45.0
200.0
DEG F
-53.9
648.9
-42.7
198.9
93.3
DEG C
TAH
X
X
DM
57
58
TE-6454
390.0
DEG F
198.9
DEG C
SF
59
TE-6454SEL
150.0
DEG F
65.6
DEG C
TAHH
60
TE-6454SEL
-65.0
1200.0
-45.0
140.0
DEG F
-53.9
648.9
-42.7
60.0
DEG C
TAH
TE-6450
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
TE-6499
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
TE-64072
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
DM
61
62
63
64
65
66
67
68
TE-64071
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
70
TE-64259
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
71
DEG C
TAL
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
158.0
DEG F
70.0
DEG C
TAH
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
158.0
DEG F
70.0
DEG C
TAH
69
TE-64259SEL
73
TE-4015A
74
43.0
DEG F
6.1
72
TE-4015ASEL
76
TE-4015B
77
TE-4015BSEL
MOT-4019A - OFF
75
MOT-4019A - OFF
78
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
79
TE-4015C
80
TE-4015CSEL
TE-6493
84
MOT-6417
85
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
158.0
DEG F
70.0
DEG C
TAH
390.0
DEG F
198.9
DEG C
SF
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
X
MOT-4019A - OFF
81
82
-65.0
1200.0
-45.0
-53.9
648.9
-42.7
OPT: GE AVR
83
MOT-6418
87
MOT-6413
88
MOT-6416
86
89
90
K347_K347A
K348
94
TE-4016A
95
CONTROLS MOT-4019A, B, C
91
92
CONTROLS MOT-4019A, B, C
93
TE-4016ASEL
97
TE-4016B
98
-65.0
1200.0
-45.0
-65.0
1200.0
-45.0
-65.0
1200.0
-45.0
390.0
DEG F
390.0
DEG F
390.0
DEG F
40.0
-53.9
648.9
-42.7
-53.9
648.9
-42.7
-53.9
648.9
-42.7
DEG F
198.9
4.0
DEG C
SF
DEG C
TAL
DEG C
SF
DEG C
TAL
DEG C
SF
DEG C
TAL
MOT-4019A - OFF
96
TE-4016BSEL
100
TE-4016C
101
40.0
DEG F
198.9
4.0
MOT-4019A - OFF
99
40.0
DEG F
4.0
198.9
TE-4016CSEL
103
HE-64050
MOT-4019A - OFF
Control By K81
104
HE-64051
Control By K81
102
105
106
NOTES
1. REDUCE LOAD AT 8"WC TO 5" WC. NSD ON THIRD AHH
2. INTENTIONALLY LEFT BLANK
3. START BLOW DOWN AT 1500 MICRO MHO, STOP AT 1200 MICRO MHO
4. SWAP TO BACKUP FAN AND ALARM ONLY IF FANS ARE COMMANDED TO RUN
5. DM IF BOTH SETS OF RTD'S ON THE SAME PHASE FAIL
6. BLOWN DOWN UNTIL CONDUCTIVITY IS AT NORMAL
7. INTENTIONALLY LEFT BLANK
8. GT START CRANK INHIBITED IF GENERATOR STATOR TEMP < 14 DEG F (< 10.0 DEG C). SPACE HEATERS WILL BE USED TO WARM GENERATOR STATOR. WINDINGS PRIOR TO START UP AND GRANT PERMISSIVE. UPON SHUTDOWN OF GT, GENERATOR ENCLOSURE VENTILATION FANS (AS APPLICA
SHALL OPERATE DURING POST SHUTDOWN CRANK CYCLE. WHEN POST SHUTDOWN CRANK CYCLE IS COMPLETED, CONTINUE TO OPERATE VENTILATION FANS UNTIL STATOR WINDING TEMPERATURES HAVE COOLED < 120 DEG F (< 48.9 DEG C), OR WHEN STATOR TEMPERATURES ARE EQUAL TO AMB
9. STOP MOT4060, MOT4061 AT 4 PSIG (27.6 kPaG) DECR.
10. INTENTIONALLY LEFT BLANK.
11. OPEN SOV-4143, SOV-4144 AT 64 % INCR. ; CLOSE AT 55 % DECR.
12. STOP MOT-4060, MOT-4061 AT 16 % DECR.
13. SETTINGS FOR BRUSH GENERATOR
14. INTENTIONALLY LEFT BLANK
15. SETTINGS FOR GE GENERATOR
16. STANDBY VENT FAN IS TURNED ON
17. STANDBY VENT FAN IS TURNED OFF
18. IF AUX SKID TEMP > 100 DEG F (37.8 DEG C) OPEN MAIN INLET DAMPER &EXHAUST DAMPER #2 IF APPLICABLE, WAIT 5 SEC AND TURN MAIN VENT FAN ON
19. IF AUX SKID TEMP < 70 DEG F (< 21.1 DEG C) TURN MAIN FAN OFF, WAIT 60 SECONDS THEN CLOSE MAIN INLET DAMPER & EXHAUST DAMPER #2 IF APPLICABLE; STANDBY FAN BECOMES MAIN FAN.
20. INTENTIONALLY LEFT BLANK
21. INTENTIONALLY LEFT BLANK
22. SERIES WIRE THE N.C. SWITCHES - ALT PDT-64232/234
23. INTENTIONALLY LEFT BLANK
24. "TURBINE ENCLOSURE TEMP LOW, CHECK HEATERS" ALARM. ALARM IS ENABLED AFTER TIME DELAY WHEN BOTH VENT FANS ARE OFF AND THE ENCLOSURE HEATERS ARE ENABLED (K43). ALARM TIME DELAY (TUNABLE) IS SET SO HEATERS HAVE TIME TO WARM THE ENCLOSURE AFTER VENT FAN
25. STATOR SETTINGS FOR 50 HZ MEIDENSHA GENERATOR
26. STATOR SETTINGS FOR 60 HZ MEIDENSHA GENERATOR
27. ALARM IF TEMP < 43 DEG F. ALARM IF ABSOLUTE VALUE OF [((Tmax + 460) - Tavg) / Tavg] > 0.020 WHERE Tavg = [(TE64032 + 460) + (TE64033 + 460)] / 2 AND Tmax = THE HIGHER OF TE64032 AND TE64033.
28. MOT-68358 ON WHEN TE-6454 AT 55F DECR. MOT-68358 OFF WHEN TE-6454 AT 60F INCR. SHUT OFF MOTOR WHEN FIRE DETECTED
29. HEATERS ON WHEN TE-6454 AT 55F DECR. HEATERS OFF WHEN TE-6454 AT 60F INCR. SHUT OFF HEATERS WHEN FIRE DETECTED. SET THERMOSTAT TC-6888 AND TC-6889 TO TURN HEATER OFF AT 100F INCR
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
0.0
100.0
-2.0
0.0
100.0
-2.0
ACTION
LT-0001
102.0
102.0
SF
LT-0001SEL
97.0
97.0
LAHH
LT-0001SEL
91.0
91.0
LAH
LT-0001SEL
61.0
61.0
LAL
LT-0001SEL
55.0
55.0
LALL
PDT-0015
PDT-0015SEL
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
X
1
HE-0005/8 PERM
ESN
6
0.0
35.0
-0.7
35.7
PSID
20.0
PSID
102.0
PSIG
0.0
241.3
-0.7
35.7
kPaD
SF
137.9
kPaD
PDAH
OPT: 50 HZ
9
10
PT-0029A
11
PT-0029ASEL
0.0
100.0
-2.0
40.0
0.0
689.5
PSIG
-13.8
703.3
275.8
kPaD
SF
kPaD
PAL
X
1,3
OPT: 50 HZ
ESN
ESN
ESN
12
13
PT-0029B
14
PT-0029BSEL
0.0
100.0
-2.0
102.0
40.0
PSIG
0.0
689.5
PSIG
-13.8
703.3
275.8
kPaD
SF
kPaD
PAL
X
1,3
OPT: 50 HZ
15
16
PT-0123
17
PT-0123SEL
19
PDT-0124
20
PDT-0124SEL
0.0
100.0
-2.0
102.0
20.0
PSIG
0.0
689.5
PSIG
-13.8
703.3
137.9
kPaD
SF
kPaD
PAL
X
1,3
OPT: 50 HZ
18
-5.0
5.0
-5.1
5.1
IN H2O
-1.0
IN H2O
-127.0
127.0
-129.5
129.5
mm H2O
SF
-25.4
mm H2O
PDAH
OPT: 50 HZ
21
22
TE-0020A1
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
OPT: 50 Hz
23
TE-0020A2
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
OPT: 50 Hz
24
TE-0020A1/A2
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
25
TE-0020A1/A2
10.0
DEG F
5.6
DEG C
HD
26
TE-0020SEL
110.0
DEG F
43.3
DEG C
EVENT
27
TE-0020SEL
90.0
DEG F
32.2
DEG C
EVENT
28
TE-0020SEL
70.0
DEG F
21.1
DEG C
TAL
HE-0005/8 OFF
HE-0005/8 ON
X
29
30
TE-0058
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
32
TE-6079
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
33
TE-6079SEL
240.0
DEG F
115.6
DEG C
TAHH
34
TE-6079SEL
225.0
DEG F
107.2
DEG C
TAH
X
X
OPT: 50 Hz
31
OPT: 50 Hz
ESN
35
36
TE-6080
390.0
DEG F
198.9
DEG C
SF
37
TE-6080SEL
240.0
DEG F
115.6
DEG C
TAHH
38
TE-6080SEL
-65.0
1200.0
-45.0
225.0
DEG F
-53.9
648.9
-42.7
107.2
DEG C
TAH
X
X
OPT: 50 Hz
ESN
39
40
TE-6081
390.0
DEG F
198.9
DEG C
SF
41
TE-6081SEL
240.0
DEG F
115.6
DEG C
TAHH
42
TE-6081SEL
-65.0
1200.0
-45.0
225.0
DEG F
-53.9
648.9
-42.7
107.2
DEG C
TAH
X
X
OPT: 50 Hz
ESN
43
44
TE-6082
390.0
DEG F
198.9
DEG C
SF
45
TE-6082SEL
240.0
DEG F
115.6
DEG C
TAHH
46
TE-6082SEL
-65.0
1200.0
-45.0
225.0
DEG F
-53.9
648.9
-42.7
107.2
DEG C
TAH
X
X
OPT: 50 Hz
ESN
47
48
TE-6084
390.0
DEG F
198.9
DEG C
SF
49
TE-6084SEL
240.0
DEG F
115.6
DEG C
TAHH
50
TE-6084SEL
-65.0
1200.0
-45.0
225.0
DEG F
-53.9
648.9
-42.7
107.2
DEG C
TAH
OPT: 50 Hz
MOT-0033A
14
MOT-0033B
14
MOT-0034
14
MOT-6899
14
60
HE-0005
61
HE-0008
MOT-0236
OPT: 50 HZ. AUX CONTACT ON MTR STRT USED TO START MOT-0237 (MOT0237 USED W/FIN-FAN OPT ONLY)
MOT-6090
MOT-6091
MOT-6093
ESN
X
51
52
53
54
55
56
57
58
OPT: 50 HZ
59
USE HE-6005 FOR 60 HZ OR HE-0005 FOR 50 HZ
62
63
64
65
66
67
68
69
70
71
XSH-68327A
XSH-68327B
XSH-68327C
LS-60001A
GEARBOX LUBE OIL RUNDOWN TANK LEVEL (LEFT SIDE TANK) (A)
6.0
INCH
152.4
mm
LALL
LS-60001B
GEARBOX LUBE OIL RUNDOWN TANK LEVEL (RIGHT SIDE TANK) (B)
6.0
INCH
152.4
mm
LALL
72
73
74
75
76
77
78
79
80
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
81
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
LS-6041A
6.0
INCH
152.4
mm
LALL
LS-6042A
6.0
INCH
152.4
mm
LALL
85
PT-6026
kPaG
SF
86
PSL-6018
20.0
PSIG
137.9
kPaG
PAL
87
PSLL-6019
12.0
PSIG
82.7
kPaG
PALL
89
PSL-6050
10.0
PSIG
68.9
kPaG
PAL
90
82
83
84
0.0
100.0
-1.00
106.25
PSIG
0.0
689.5
-6.9
732.6
X
1
ESN
88
PSLL-6051
92
TE-6021
93
TE-6021SEL
94
TE-6021SEL
95
TE-6021SEL
97
TE-6023
98
TE-6023SEL
99
TE-6023SEL
100
TE-6023SEL
102
TE-6025
103
TE-6025SEL
104
TE-6025SEL
105
TE-6025SEL
107
TE-6035
108
TE-6035SEL
109
TE-6035SEL
5.0
PSIG
34.5
kPaG
PALL
198.9
DEG C
SF
ESN
105.0
DEG C
TAHH
12
100.0
DEG C
TAH
12
DEG C
EVENT
198.9
DEG C
SF
105.0
DEG C
TAHH
12
100.0
DEG C
TAH
12
DEG C
EVENT
DEG C
SF
91
-65.0
1200.0
-45.0
390.0
DEG F
221.0
DEG F
212.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
ESN
X
X
96
-65.0
1200.0
-45.0
390.0
DEG F
221.0
DEG F
212.0
DEG F
14.0
-53.9
648.9
DEG F
-42.7
-10.0
X
ESN
X
X
101
-65.0
1200.0
-45.0
390.0
DEG F
190.0
DEG F
160.0
DEG F
40.0
-53.9
648.9
-42.7
198.9
87.8
TAHH
11, 12
DEG C
TAH
11, 12
DEG C
EVENT
198.9
DEG C
SF
71.1
DEG F
4.4
DEG C
DM
ESN
X
106
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
194.0
DEG F
90.0
DEG C
TAHH
11, 12
189.0
DEG F
87.2
DEG C
TAH
11, 12
ESN
X
110
111
TE-6036
390.0
DEG F
198.9
DEG C
SF
112
TE-6036SEL
194.0
DEG F
90.0
DEG C
TAHH
11, 12
113
TE-6036SEL
-65.0
1200.0
-45.0
189.0
DEG F
-53.9
648.9
-42.7
87.2
DEG C
TAH
11, 12
X
ESN
X
114
115
TE-6056
390.0
DEG F
198.9
DEG C
SF
116
TE-6056SEL
221.0
DEG F
105.0
DEG C
TAHH
11, 12
117
TE-6056SEL
-65.0
1200.0
-45.0
212.0
DEG F
-53.9
648.9
-42.7
100.0
DEG C
TAH
11, 12
390.0
DEG F
198.9
DEG C
SF
ESN
X
118
119
TE-6057
MOT-6031
-65.0
1200.0
-45.0
-53.9
648.9
-42.7
120
121
14
122
123
NOTES
1. PART OF AUXILIARY SYSTEM CHECK SEQUENCE
2. HEATER ON AT 90 DEG. F (32.2 DEG C) DECR AND OFF AT 110 DEG F (43.3 DEG C) INCR. HEATER ALSO THERMOSTATICALLY CONTROLLED AT 90 DEG. F (32.2 DEG C) DECR
3. ESN TO ABORT START IF PRESSURE IS LOW DURING THE AUXILIARY SYSTEM CHECK SEQUENCE. ALARM IF PRESSURE BECOMES LOW AFTER THE AUXILIARY SYSTEM CHECK IS COMPLETED.
4. DURING START CYCLE, OR RUN CYCLE ONE LEVEL SWITCH PER TANK (0) TRIPPED = ALARM. ALL SWITCHES MUST SHOW TANKS FULL (1) BEFORE ALLOWING STARTER ENGAGEMENT.
5. START PERMISSIVE IF TANK LEVEL 60% OR MORE.
6. GT START CRANK INHIBITED IF GENERATOR LUBE OIL SUPPLY TEMPERATURE < 40 DEG F (< 4.4 DEG C), OR IF BEARING METAL TEMP < 14 DEG F (< -10.0 DEG C). WARM LUBE OIL WILL BE USED TO WARM UP BEARING TO 40 DEG F (4.4 DEG C) BEFORE STARTER ENGAGEMENT WILL BE ALLOWED.
7. INTENTIONALLY LEFT BLANK.
8. FOR 60HZ: ONCE XNSD > 3000 RPM THEN SHUTDOWN AC LUBE PUMP AND ENABLE PSL-6017. IF PRESSURE IS LOW THEN START AC PUMP AND KEEP IT ON UNTIL UNIT SHUTDOWN
9. INTENTIONALLY LEFT BLANK.
10. INTENTIONALLY LEFT BLANK.
11. SETTINGS FOR BRUSH GENERATOR
12. SETTINGS FOR MEIDENSHA GENERATOR
13. SETTINGS FOR GE GENERATOR
14. WHEN THE UNIT IS EITHER CRANKING, STARTING OR CRANK SOAK WATER WASHING THE FOLLOWING IS TO BE DONE:
a. FOR 50HZ: SEQUENCE ALL GEN/GB LUBE OIL PUMPS TO VERIFY DISCHARGE PRESSURE. LEAVE PRIMARY AC PUMP ON AFTER PRESSURE VERIFICATIONS ARE COMPLETE.
b. FOR 60HZ: START THE GENERATOR AC LUBE OIL PUMP.
c. START THE HYD. STARTER AND AFTER THE GEN LUBE PUMP HAS RUN FOR 15 SEC. CHECK FOR JACKING OIL PUMP SUCTION PRESSURE. IF PRESSURE PRESENT START THE JACKING OIL PUMP.
d. FOR 50HZ: 15 SEC AFTER STARTING THE JACKING PUMP & IF XN25 > 2200 RPM, START TURNING GEAR MOTOR, AFTER 30 SEC. CHECK IF XNSD > 190 RPM, IF NOT ESN
e. FOR 50HZ: WHEN XNSD > 1000 RPM SHUTDOWN TURNING GEAR AND JACKING OIL PUMP.
f. FOR 60HZ: WHEN XNSD > 1000 RPM SHUTDOWN JACKING OIL PUMP.
g. FOR 50HZ: IF SHUTDOWN SHOULD OCCUR DURING STARTING WHILE TURNING GEAR AND JACKING OIL PUMP ARE ON, SHUTDOWN TURNING GEAR MOTOR IMMEDIATELY, BUT WAIT 15 SEC. BEFORE SHUTTING DOWN JACKING OIL PUMP.
h. FOR 60HZ: IF SHUTDOWN SHOULD OCCUR DURING STARTING WHILE JACKING OIL PUMP IS ON, WAIT 15 SEC. BEFORE SHUTTING DOWN JACKING OIL PUMP.
i. FOR 60HZ: WHEN XNSD > 3000 RPM DE-ENERGIZE AC LUBE OIL PUMP
15. INTENTIONALLY LEFT BLANK.
16. ESN IF PRESSURE IS LOW DURING THE AUXILIARY SYSTEM CHECK SEQUENCE.
ALARM IF PRESSURE BECOMES LOW AFTER THE AUXILIARY SYSTEM CHECK IS COMPLETED.
17. WHEN AC PUMP STARTS IT MUST VERIFY AT THIS PRESSURE IN 15 SECONDS DURING AUXILIARY SYSTEM CHECK SEQUENCE. IF FAIL THEN ESN AND BLOCK TURBINE CRANK.
18. WHEN DC PUMP STARTS IT MUST VERIFY AT THIS PRESSURE IN 15 SECONDS DURING AUXILIARY SYSTEM CHECK SEQUENCE. IF FAIL THEN ESN AND BLOCK TURBINE CRANK.
19. TEMPERATURE MUST BE HIGHER THAN 70 DEG F (21.1 DEG C) FOR ENGINE TO START.
20. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) OPEN IF TE-61069 > 50 DEG F (10.0 DEG C) OR TE-60019 > 50 DEG F (10.0 DEG C)
21. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) CLOSE IF TE-61069 < 30 DEG F (-1.1 DEG C) AND TE-60019 < 34 DEG F (1.1 DEG C)
22. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS ON IF TE-61069 > 70 DEG F (21.1 DEG C) OR TE-60019 > 70 DEG F (21.1 DEG C) AND ENGINE CRANKING OR RUNNING
23. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS OFF IF TE-61069 < 35 DEG F (1.7 DEG C) AND TE-60019 < 35 DEG F (1.7 DEG C) OR ENGINE IS NOT CRANKING OR RUNNING
LEGEND
1. SEE LEGEND TAB
A
B
DATE:
07/18/11-ATFL
05/16/12-ATFL
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
12.0
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
INCH
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
305.0
ACTION
NOTE
ALARM
LSL-6102
mm
LAL
PDSH-6120
20.0
PSID
137.9
kPaD
PDAH
PDSHH-6144
25.0
PSID
172.4
kPaD
PDAHH
PDSH-6118
20.0
PSID
137.9
kPaD
PDAH
PDSHH-6119
25.0
PSID
172.4
kPaD
PDAHH
PDSH-6148
1.7
PSID
11.7
kPaD
PDAH
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
HE-6104 PERM
2
3
10
4
5
10
NSD
6
7
10
8
9
10
NSD
10
11
60
60
12
13
PDSH-6146
kPaD
PDAH
PSLL-6115
15.0
20.0
PSIG
PSID
103.4
137.9
kPaG
PALL
PSLL-6116
6.0
PSIG
41.4
kPaG
PALL
PSH-6117
kPaG
PAH
TSL-6113
DEG C
TAL
PT-6121
kPaG
SF
14
15
ESN
16
17
ESN
18
19
100.0
PSIG
689.5
20
21
70.0
DEG F
21.1
22
23
0.0
100.0
-2.0
102.0
PSIG
0.0
689.5
-13.8
703..3
24
25
PT-6122
0.0
200.0
-4.0
204.0
PSIG
0.0
1379.0
-27.8
1406.5
kPaG
SF
27
TE-6123A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
28
TE-6123B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
29
TE-6123A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
30
TE-6123A/B
10.0
DEG F
5.6
DEG C
HD
31
TE-6123SEL
265.0
DEG F
129.4
DEG C
TAHH
32
TE-6123SEL
240.0
DEG F
115.5
DEG C
TAH
34
TE-6124A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
35
TE-6124B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
36
TE-6124A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
37
TE-6124A/B
10.0
DEG F
5.6
DEG C
HD
38
TE-6124SEL
310.0
DEG F
154.4
DEG C
TAHH
39
TE-6124SEL
285.0
DEG F
140.6
DEG C
TAH
41
TE-6125A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
42
TE-6125B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
43
TE-6125A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
44
TE-6125A/B
10.0
DEG F
5.6
DEG C
HD
45
TE-6125SEL
330.0
DEG F
165.6
DEG C
TAHH
46
TE-6125SEL
305.0
DEG F
151.7
DEG C
TAH
48
TE-6186A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
49
TE-6186B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
50
TE-6186A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
51
TE-6186A/B
10.0
DEG F
5.6
DEG C
HD
52
TE-6186SEL
340.0
DEG F
171.1
DEG C
TAHH
53
TE-6186SEL
320.0
DEG F
160.0
DEG C
TAH
55
TE-6141A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
56
TE-6141B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
57
TE-6141A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
58
TE-6141A/B
10.0
DEG F
5.6
DEG C
HD
59
TE-6141SEL
315.0
DEG F
157.2
DEG C
TAHH
60
TE-6141SEL
290.0
DEG F
143.3
DEG C
TAH
62
TE-6142A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
63
TE-6142B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
64
TE-6142A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
65
TE-6142A/B
10.0
DEG F
5.6
DEG C
HD
66
TE-6142SEL
315.0
DEG F
157.2
DEG C
TAHH
67
TE-6142SEL
290.0
DEG F
143.3
DEG C
TAH
69
TE-6128A
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
70
TE-6128B
-65.0
1200.0
-45.0
390.0
DEG F
-53.9
648.9
-42.7
198.9
DEG C
SF
71
TE-6128A/B
-45.0
390.0
DEG F
-42.7
198.9
DEG C
SF
72
TE-6128A/B
10.0
DEG F
5.6
DEG C
HD
73
TE-6128SEL
170.0
DEG F
76.7
DEG C
TAH
26
DEG C
SF
X
8
DM
X
DM
X
33
X
X
8
DM
X
DM
X
40
X
X
8
DM
X
DM
X
47
X
X
8
DM
X
DM
X
54
X
X
8
DM
X
DM
X
61
X
X
8
DM
X
DM
X
68
74
90.0
DEG F
32.2
DEG C
TAL
X
X
8
16
DM
TE-6128SEL
XSH-68327A
XAH
X
SWAP MOTOR/FAN
XSH-68327B
XAH
SWAP MOTOR/FAN
XSH-68327C
XAH
SWAP MOTOR/FAN
MOT-6090
MOT-6091
MOT-6093
75
76
77
78
79
80
81
82
83
84
85
86
87
88
SOV-6185
MOT-6135
HE-6104
1 = OPEN VALVE
89
90
91
92
93
94
NOTES
1. ESN XN25 > 7800 RPM
2. ESN 4500 RPM < XN25 < 7800 RPM
3. HEATER THERMOSTATICALLY CONTROLLED ON AT 90 DEG F (32.2 DEG C) DECR
4. NOTE DELETED
5. NOTE DELETED
6. HEATER ON PERMISSIVE 60%
7. INTENTIONALLY BLANK
8. HIGH SELECT SENSOR VALUE IS USED. IF BOTH SENSORS ARE OUT OF RANGE THEN DM.
9. INTENTIONALLY BLANK
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
10.
11.
12.
13.
14.
15.
16.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) OPEN IF TE-61069 > 50 DEG F (10.0 DEG C) OR TE-60019 > 50 DEG F (10.0 DEG C)
WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) CLOSE IF TE-61069 < 30 DEG F (-1.1 DEG C) AND TE-60019 < 34 DEG F (1.1 DEG C)
THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS ON IF TE-61069 > 70 DEG F (21.1 DEG C) OR TE-60019 > 70 DEG F (21.1 DEG C) AND ENGINE CRANKING OR RUNNING
THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS OFF IF TE-61069 < 35 DEG F (1.7 DEG C) AND TE-60019 < 35 DEG F (1.7 DEG C) OR ENGINE IS NOT CRANKING OR RUNNING
WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN ON IF TE-68347 < 175 DEG F (79.4 DEG C) AND LOUVERS ARE CLOSED.
WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN OFF IF TE-68347 > 250 DEG F (121.1 DEG C) OR LOUVERS ARE OPEN.
XN25 > 6050 RPM
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it
is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any
written agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PSHH-6348
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
150.0
PSIG
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
1034.2
kPaG
PAHH
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
ESN
2
3
FPP_MSD
FPP_MF
AH
FPP_ALELT
FIRE/GAS MONITOR SD
AHH
AH
ESN
FPP_ALELG
AH
FPP_SLELT
AHH
FPP_SLELG
AHH
10
AE-6304A
15.0
%LEL
15.0
%LEL
ASH
11
AE-6304A
25.0
%LEL
25.0
%LEL
ASHH
13
AE-6304B
15.0
%LEL
15.0
%LEL
ASH
14
ESN
ESN
9
X
ESN
12
AE-6304B
25.0
%LEL
25.0
%LEL
ASHH
16
AE-6304C
15.0
%LEL
15.0
%LEL
ASH
17
ASHH
X
ESN
15
AE-6304C
25.0
%LEL
25.0
%LEL
19
AE-6304D
15.0
%LEL
15.0
%LEL
ASH
20
AE-6304D
25.0
%LEL
25.0
%LEL
ASHH
22
AE-6304E
15.0
%LEL
15.0
%LEL
ASH
23
ASHH
X
ESN
18
X
ESN
21
AE-6304E
25.0
%LEL
25.0
%LEL
25
AE-6313
15.0
%LEL
15.0
%LEL
ASH
26
AE-6313
25.0
%LEL
25.0
%LEL
ASHH
28
AE-3029
5.0
%LEL
5.0
%LEL
ASH
29
ASHH
X
ESN
24
X
ESN
27
AE-3029
10.0
%LEL
10.0
%LEL
31
AE-3030
5.0
%LEL
5.0
%LEL
ASH
32
AE-3030
10.0
%LEL
10.0
%LEL
ASHH
BE-6300
BE-6302
BE-6311
BE-6335
HS-6363
HS-6305
HS-6308
HS-6309
HS-6312
TS-6303
TS-6307
TS-6310
X
ESN
30
X
ESN
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
TS-6314
SOV-6359
SOV-6360
SOV-6361
59
60
61
62
63
64
65
66
SOV-6362
YSA-6306
YSA-6346
YSA-6347
YSL-6301
YSL-6336
YSL-6344
YSL-6345
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
ZS-6364
PSH-63165
83
84
85
86
NOTES
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
LS-6543
HS-6505
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
23.0
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
23.0
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
LAL
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
MOT-6535 PERM
HE-6536 PERM
VALVES
COMMENTS
2
3
4
5
SOV-6540
MOT-6535
1 = OPEN VALVE
HE-6536
SOV-6504
1 = OPEN VALVE
SOV-6516
1 = OPEN VALVE
6
7
8
9
10
11
12
13
14
15
NOTES
1. INTENTIONALLY LEFT BLANK.
2. HEATER AND PUMP OFF IF LEVEL LOW (HEATER AND PUMP PERMISSIVE).
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
ZY-6201
0.0
100.0
ZE-6201
0.0
100.0
ZC6201_FLT
ZC6201SDRS
FC-6246
PSL-6224
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
0.0
100.0
-5.0
102.0
0.0
100.0
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
-5.0
102.0
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
OPT: GAS FUEL (SAC ONLY). USE FOR VALVE MINIMUM POSITION
5
6
0.0
345.0
-6.9
351.9
ACFM
0.0
9.8
-0.2
10.0
ACmM
SF
kPaG
PAL
7
8
600.0
PSIG
4136.9
9
10
PSHH-6226
PT-6227
720.0
PSIG
4964.0
kPaG
PAHH
0.0
800.0
-16.0
816.0
PSIG
0.0
5515.8
-110.3
5626.1
kPaG
SF
14
TE-6232A
15
16
ES
-70.0
500.0
-65.0
380.0
DEF F
-56.7
260.0
-53.9
193.3
DEG C
SF
TE-6232B
-70.0
500.0
-65.0
380.0
DEF F
-56.7
260.0
-53.9
193.3
DEG C
SF
TE-6232A/B
-65.0
380.0
DEG F
-53.9
193.3
DEG C
SF
17
TE-6232SEL
300.0
DEG F
148.9
DEG C
TAHH
18
275.0
DEG F
135.0
DEG C
TAH
11
12
13
TE-6232SEL
20
SOV-6249
21
ZS-6249
23
SOV-6204
24
X
9
X
DM
19
OPT: GAS FUEL (SAC OR DLE). 1 = OPEN VALVE
X
22
ZS-6204
26
SOV-6208
27
ZS-6208
PT-6228
SOV-62580
25
OPT: GAS FUEL (SAC OR DLE). 1 = CLOSE VALVE
OPT: GAS FUEL (SAC ONLY)
28
33
0.0
800.0
-16.0
816.0
PSIG
0.0
5515.8
-110.3
5626.1
kPaG
SF
34
35
36
ZS-62580
38
SOV-62581
39
ZS-62581
37
40
41
PT-62582
42
PT-62582
43
PT-62582
0.0
800.0
-16.0
816.0
PSIG
10.0
PSIG
0.0
5515.8
-110.3
5626.1
kPaG
68.9
kPaG
SF
PAH
12
EVENT
13
X
X
44
45
NOTES
1. 50 PSI (344.7 kPaG) START PERM.
2. 50 PSI (344.7 kPaG) TRANSFER PERM.
3. SHUTDOWN WATER INJECTION SYSTEM.
4. PUMP OFF AT 1340 PSIG (9239.0 kPaG) INC, 50 PSIG (344.7 kPaG) DEC.
5. TURN OFF NOX WATER INJECTION PUMP
6. INTENTIONALLY LEFT BLANK
7. INTENTIONALLY LEFT BLANK
8. INTENTIONALLY LEFT BLANK.
9. a. IF BOTH TGAS SENSORS ARE WITHIN RANGE LIMITS, DISPLAY THE AVERAGE OF BOTH.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN ALM AND DEFAULT TGAS TO LAST GOOD VALUE.
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A DIFFERENCE BETWEEN SENSORS GREATER THAN 10 DEG F THEN ALM & USE THE HIGHER TGAS VALUE.
d. TGAS VALUE < 20 DEG F (<-6.7 DEG C) OR > 275 DEG F (> 135.0 DEG C) = ALM
10. INTENTIONALLY LEFT BLANK.
11. AFTER INITIAL START + 15 SECONDS IF DISCHARGE PRESSURE < 100 PSIG (< 689.5 kPaG) PUMP WILL BE SHUT OFF.
12. ALARM IF UNIT SHUTDOWN AND GAS VENT VALVE OPEN
13. DURING START UP AND BOTTLE TEST, IF PT-62582 DIFFER (PT6227 - PT62582 >15PSI) FROM PT-6227, ABORT START SEQUENCE
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
PT-6863
0.0
16.0
8.0
16.0
PSIA
0.0
110.3
55.2
110.3
kPaA
SF
21
PT-6804
0.0
600.0
10.0
530.0
PSIA
0.0
4136.9
68.9
3654.2
kPaA
SF
PT-6814
0.0
600.0
10.0
530.0
PSIA
0.0
4136.9
68.9
3654.2
kPaA
PT-6804/14
10.0
530.0
PSIA
68.9
3654.2
kPaA
SF
PT-6804/14
10.0
15.0
PSIA
68.9
103.4
kPaA
HD
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
2
SF
19
DM
5
7
PT-6859A
0.0
100.0
10.0
45.0
PSIA
0.0
689.5
68.9
310.3
kPaA
SF
PT-6859B
0.0
100.0
10.0
45.0
PSIA
0.0
689.5
68.9
310.3
kPaA
SF
10
PT-6859A/B
10.0
45.0
PSIA
68.9
310.3
kPaA
SF
20
11
PT-6859A/B
10.0
PSIA
68.9
kPaA
HD
18
DM
X
12
13
PT-6860
0.0
150.0
10.0
140.0
PSIA
0.0
1034.2
68.9
965.3
kPaA
SF
15
15
PT-6861A
0.0
150.0
10.0
140.0
PSIA
0.0
1034.2
68.9
965.3
kPaA
SF
16
PT-6861B
0.0
150.0
10.0
140.0
PSIA
0.0
1034.2
68.9
965.3
kPaA
SF
17
PT-6861A/B
10.0
140.0
PSIA
965.3
kPaA
SF
20
18
PT-6861A/B
25.0
PSIA
172.4
kPaA
HD
19
PT-6861A/B
6.0
PSIA
41.4
kPaA
HD
21
SE-6800
0.0
12000.0
0.0
11500.0
RPM
0.0
12000.0
-1.0
11500.0
RPM
SF
2, 3
22
SE-6801
0.0
12000.0
0.0
11500.0
RPM
0.0
12000.0
-1.0
11500.0
RPM
SF
2, 3
23
SE-6800/6801
0.0
11500.0
RPM
-1.0
11500.0
RPM
SF
2, 3
24
SE-6800/6801
37.5
RPM
37.5
RPM
HD
25
SE-6800/6801SEL
10800.0
RPM
10800.0
RPM
SAHH
26
SE-6800/6801SEL
10700.0
RPM
10700.0
RPM
SAH
14
68.9
DM
0.1
DM
20
RATIO: 1 RPM = 0.74910 HZ
RATIO: 1 RPM = 0.74910 HZ
ES
X
ES
X
27
28
SE-6812
0.0
5000.0
0.0
4800.0
RPM
0.0
5000.0
-1.0
4800.0
RPM
SF
29
SE-6813
0.0
5000.0
0.0
4800.0
RPM
0.0
5000.0
-1.0
4800.0
RPM
SF
30
SE-6812/6813
0.0
4800.0
RPM
-1.0
4800.0
RPM
SF
31
SE-6812/6813
40.0
RPM
40.0
RPM
HD
32
SE-6812/6813SEL
4600.0
RPM
4600.0
RPM
SAHH
33
SE-6812/6813SEL
4300.0
RPM
4300.0
RPM
SAH
TE-6821A
140.0
DEG F
60.0
DEG C
SF
11
X
ESN
ES
34
35
36
-70.0
500.0
-65.0
-56.7
260.0
-53.9
TE-6821B
-70.0
500.0
-65.0
140.0
DEG F
-56.7
260.0
-53.9
60.0
DEG C
SF
11
38
TE-6837A
-70.0
500.0
-65.0
320.0
DEG F
-56.7
260.0
-53.9
160.0
DEG C
SF
12
39
TE-6837B
-70.0
500.0
-65.0
320.0
DEG F
-56.7
260.0
-53.9
160.0
DEG C
SF
12
41
TE-6838A
-70.0
2200.0
-65.0
1200.0
DEG F
-56.7
1204.4
-53.9
648.9
DEG C
SF
16
42
TE-6838B
-70.0
2200.0
-65.0
1200.0
DEG F
-56.7
1204.4
43
TE-6838A/B
-65.0
1200.0
DEG F
44
TE-6838A/B
20.0
DEG F
46
TE-6843
-70.0
2200.0
-65.0
2000.0
DEG F
-56.7
1204.4
47
TE-6844
-70.0
2200.0
-65.0
2000.0
DEG F
-56.7
1204.4
48
TE-6845
-70.0
2200.0
-65.0
2000.0
DEG F
-56.7
1204.4
49
TE-6846
-70.0
2200.0
-65.0
2000.0
DEG F
-56.7
50
TE-6847
-70.0
2200.0
-65.0
2000.0
DEG F
51
TE-6848
-70.0
2200.0
-65.0
2000.0
52
TE-6849
-70.0
2200.0
-65.0
53
TE-6850
-70.0
2200.0
54
TE-6843-50
55
37
40
-53.9
648.9
DEG C
SF
16
-53.9
648.9
DEG C
SF
30
11.1
DEG C
HD
31, 49
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
1204.4
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
-56.7
1204.4
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
DEG F
-56.7
1204.4
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
2000.0
DEG F
-56.7
1204.4
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
-65.0
2000.0
DEG F
-56.7
1204.4
-53.9
1093.3
DEG C
SF
4,6
SEE NOTE
-65.0
2000.0
DEG F
-53.9
1093.3
DEG C
SF
TE-6843-50
-65.0
2000.0
DEG F
-53.9
1093.3
DEG C
SF
56
TE-6843-50
-65.0
2000.0
DEG F
-53.9
1093.3
DEG C
SF
10
57
TE-6843-50
1000.0
DEG F
537.8
DEG C
HD
58
TE-6843-50
700.0
DEG F
371.1
DEG C
HD
46
59
TE-6843-50
135.0
DEG C
HD
59
60
TE-6843-50
150.0
DEG F
65.6
DEG C
HD
47
60
61
TE-6843-50
1850.0
DEG F
1010.0
DEG C
TAHH
ES
62
TE-6843-50
1750.0
DEG F
954.4
DEG C
TAH
SI
MCD-6865
360.0
OHMS
360.0
OHMS
SFL/SFH
45
275.0
DEG F
90
60
63
64
MCD-6865SEL
67
65
MCD-6866
68
Ohms
Ohms
Ohms
Ohms
Ohms
Ohms
-80.0
120.0
30.0
75.0
Ohms
Ohms
30.0
Ohms
Ohms
30.0
Ohms
Ohms
30.0
-80.0
120.0
OHMS
75.0
OHMS
MCDAL
OHMS
SFL/SFH
X
52
2.5
66
MCD-6866SEL
70
MCD-6870
71
MCD-6870SEL
FCV-6871
30.0
360.0
75.0
OHMS
OHMS
360.0
75.0
OHMS
MCDAL
OHMS
SFL/SFH
OHMS
MCDAL
X
52
2.5
69
30.0
360.0
75.0
OHMS
OHMS
360.0
75.0
X
52
2.5
72
73
mA
24,26
DM
74
FCV-6871
10.0
mA
10.0
mA
AH
23,28,39
75
FCV-6871
15.0
mA
15.0
mA
AHH
23,28,39
76
ZE-6871A-B
77
ZE-6871A1
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
78
ZE-6871A2
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
79
ZE-6871A
-2.0
102.0
-2.0
102.0
SF
80
ZE-6871B1
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
81
ZE-6871B2
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
82
ZE-6871B
-2.0
102.0
-2.0
102.0
83
ZE-6871
-2.0
102.0
-2.0
102.0
SF
22
84
ZE-6871
9.0
9.0
HD
23,29
85
ZE-6871
10.0
10.0
HD
23,29,57
86
ZE-6871PERR
3.0
3.0
HD
23,25,27,28
87
ZE-6871PERR
10.0
10.0
HD
23,25,26
7.0
VRMS
7.0
X
DM
VRMS
SF
X
X
8, 18
8, 18
X
DM
DM
88
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
89
REV
TAG NO.
FCV-6873
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
-80.0
120.0
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
mA
-80.0
120.0
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
SF
24,26
90
FCV-6873
10.0
mA
10.0
mA
AH
23,28,39
91
FCV-6873
15.0
mA
15.0
mA
AHH
23,28,39
92
ZE-6873A-B
93
ZE-6873A1
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
94
ZE-6873A2
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
95
ZE-6873A
-2.0
102.0
-2.0
102.0
SF
96
ZE-6873B1
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
97
ZE-6873B2
0.0
100.0
-2.0
102.0
0.0
100.0
-2.0
102.0
SF
98
7.0
VRMS
7.0
ALARM
8, 18
-2.0
102.0
-2.0
102.0
-2.0
102.0
-2.0
102.0
SF
22
3.7
3.7
HD
18,23
101
ZE-6873PERR
3.0
3.0
HD
23,25,27,28
10.0
HD
23,25,26
198.9
DEG C
SF
ZE-6873PERR
TE-68310
105
TE-68310SEL
106
TE-68310SEL
32.0
DEG F
0.0
107
TE-68310SEL
SEE NOTE
SEE NOTE
125.0
DEG F
DEG F
SEE NOTE
SEE NOTE
109
TE-68311
-45.0
390.0
DEG F
-42.7
198.9
110
TE-68311SEL
125.0
DEG F
111
TE-68311SEL
SF
104
8, 18
ZE-6873
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
VRMS
ZE-6873
DEG F
START PERM.
SI
ZE-6873B
10.0
ABORT START
DM
99
390.0
SHUT DOWN
100
102
SI
5
SI
103
-65.0
1200.0
-45.0
-53.9
648.9
-42.7
51.7
DEG C
TAH
DEG C
TAL
DEG C
EVENT
X
X
32
108
-65.0
1200.0
32.0
-53.9
648.9
51.7
DEG F
0.0
DEG C
SF
DEG C
TAH
DEG C
TAL
X
X
112
113
SE-6811
114
SE-6811_ISOSEL
116
XE-6807
117
-100.0
5100.0
0.0
5000.0
RPM
5000.0
RPM
SF
SEE NOTE
RPM
-100.0
5100.0
0.0
SEE NOTE
RPM
EVENT
60
3.0
MIL PP
76.2
M PP
XAH
41, 58
10
ESN
115
XE-6807
4.0
MIL PP
101.6
M PP
XAHH
41, 58
119
XE-6808
3.0
MIL PP
76.2
M PP
XAH
41, 58
120
X
SI
118
XE-6808
4.0
MIL PP
101.6
M PP
XAHH
41, 58
122
XE-6809
3.0
MIL PP
76.2
M PP
XAH
41, 58
123
X
SI
121
XE-6809
4.0
MIL PP
101.6
M PP
XAHH
41, 58
125
XE-6810
3.0
MIL PP
76.2
M PP
XAH
41, 58
126
XE-6810
4.0
MIL PP
101.6
M PP
XAHH
41, 58
3.0
IN/SEC PK
76.2
mm/SEC PK
XAH
44
4.0
IN/SEC PK
101.6
mm/SEC PK
XAHH
44
1.4
IN/SEC PK
35.6
mm/SEC PK
XAH
43
2.0
IN/SEC PK
50.8
mm/SEC PK
XAHH
43
2.0
IN/SEC PK
50.8
mm/SEC PK
XAH
45
X
SI
124
X
SI
127
128
XE-6876
129
XE-6876
X
SI
130
131
XE-6876A
132
XE-6876A
X
SI
133
134
XE-6876B
135
XE-6876B
3.0
IN/SEC PK
76.2
mm/SEC PK
XAHH
45
3.0
IN/SEC PK
76.2
mm/SEC PK
XAH
44
X
SI
136
XE-6877
4.0
IN/SEC PK
101.6
mm/SEC PK
XAHH
44
140
XE-6877A
1.4
IN/SEC PK
35.6
mm/SEC PK
XAH
43
141
137
XE-6877
138
139
XE-6877A
2.0
IN/SEC PK
50.8
mm/SEC PK
XAHH
43
143
XE-6877B
2.0
IN/SEC PK
50.8
mm/SEC PK
XAH
45
144
X
SI
X
SI
142
XE-6877B
3.0
IN/SEC PK
76.2
mm/SEC PK
XAHH
45
146
XE-6897
0.3
IN/SEC PK
7.6
mm/SEC PK
XAH
53
147
X
SI
145
XE-6897
0.5
IN/SEC PK
12.7
mm/SEC PK
XAHH
53
149
XE-6898
0.3
IN/SEC PK
7.6
mm/SEC PK
XAH
53
150
0.5
IN/SEC PK
12.7
mm/SEC PK
XAHH
53
X
SI
148
X
XE-6898
152
BE-6816
SI
Control by K83
153
BE-6817
Control by K83
151
154
155
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
NOTES
1. a. IF BOTH XNSD SPEED PICKUPS ARE WITHIN RANGE, DISPLAY THE AVERAGE SPEED OF BOTH XNSD PICKUPS.
b. ONE XNSD PICKUP OUT OF RANGE = ALM - ANNUNCIATE LOSS OF PICKUP - REMOVE FROM AVERAGE & DISPLAY THE REMAINING IN RANGE XNSD SPEED PICKUP.
BOTH XNSD PICKUPS OUT OF RANGE = ES - DEFAULT TO LAST GOOD VALUE - ANNUNCIATE LOSS OF BOTH XNSD PICKUPS.
c. A DIFFERENCE OF > 40 RPM BETWEEN XNSD PICKUPS = ALM - ANNUNCIATE DIFFERENCE BETWEEN PICKUPS & USE THE PICKUP WITH THE HIGHER VALUE.
2. a. IF BOTH XN25 SPEED PICKUPS ARE WITHIN RANGE, DISPLAY THE AVERAGE OF BOTH XN25 SPEED PICKUPS.
b. ONE XN25 PICKUP IS OUT OF RANGE = ALM - ANNUNCIATE LOSS OF PICKUP - REMOVE FROM THE AVERAGE & DISPLAY THE REMAINING IN RANGE XN25 SPEED PICKUP.
BOTH N25 PICKUPS OUT OF RANGE = ES - DEFAULT TO 2000 RPM & ANNUNCIATE LOSS OF BOTH XN25 SPEED PICKUPS.
c. A DIFFERENCE OF > 37.5 RPM BETWEEN N25 PICKUPS = ALM - ANNUNCIATE DIFFERENCE BETWEEN PICKUPS AND USE THE PICKUP WITH THE HIGHER VALUE.
3. a. FOLLOWING FUEL IGNITION, IF dXN25/DT < 10 RPM/SEC AND XN25 RPM < 6050 RPM THEN ESN ON FAIL TO ACCELERATE.
b. IF XNSD IS < 1250 RPM & XN25 CONTROL HAS BEEN ACHIEVED FOR > 60 SECONDS = ES AND ANNUNCIATE POWER TURBINE FAILED TO BREAKAWAY
c. IF XN25 IS < 1700 RPM AND > 30 SECONDS FOLLOWING INITIAL STARTER ENGAGEMENT FOR ENGINE/BOILER PURGE SEQUENCE = ESN AND ANNUNCIATE FAIL TO CRANK.
d. AFTER ENGINE/BOILER PURGE SEQUENCE, IF XN25 IS < 1700 RPM AFTER 10 SECONDS FOLLOWING THE STARTER RE-ENGAGEMENT FOR FUEL IGNITION SEQUENCE = ESN AND ANNUNCIATE FAIL TO CRANK.
e. IF XN25 < 4600 RPM > 90 SEC AFTER INITIATION OF FUEL = ES AND ANNUNCIATE FAILURE TO REACH STARTER CUTOUT.
f. IF XN25 < 6050 RPM > 120 SEC AFTER INITIATION OF FUEL = ES AND ANNUNCIATE FAILURE TO REACH XN25 IDLE.
g. IF XN25 < 300 RPM FOR > 10 MINUTES AFTER AN ES OR ESN, A 4 HOUR LOCKOUT OCCURS.
4. ALL THERMOCOUPLES THAT ARE IN RANGE WILL BECOME PART OF THE AVERAGE AND THE AVERAGE WILL BE DISPLAYED.
a. FOR SAC: IF 10 SECONDS AFTER GAS FUEL ON (1700 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
b. FOR DLE: IF 15 SECONDS AFTER GAS FUEL ON (1700 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
c. FOR SAC: IF 20 SECONDS AFTER LIQ FUEL ON (1200 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
d. FOR DLE: IF 15 SECONDS AFTER LIQ FUEL ON (1200 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
e. IF T48 AVERAGE > 400 DEG F & THEN < 400 DEG F WHILE STARTING OR RUNNING = ES AND ANNUNCIATE FLAME OUT.
f. DURING STARTING (BETWEEN 0-6050 N25 RPM) IF T48 AVERAGE > T48 BACKUP START SCHEDULE + 200 DEG F (93.3 DEG C) FOR > 3 SECONDS = ES
5. IF T48 AVERAGE > 1750 DEG F (> 954.4 DEG C) OR MORE THAN 1.0 SEC = ALM, T48 AVERAGE > 1850 DEG F (> 1010.0 DEG C) FOR MORE THAN 1.0 SECOND = ES
6. ANY THERMOCOUPLE OUT OF RANGE = ALM & REMOVE BAD THERMOCOUPLE FROM THE AVERAGE. THERMOCOUPLE CONSIDERED OUT OF RANGE IF <-65 DEG F (-53.9 DEG C) AND N25SEL <4600 RPM OR < 350 DEG F (< 176.7 DEG C) AND N25SEL =>4600 RPM AND FUEL ON OR > 1900 DEG F (> 1037.8 DEG C).
7. LOSS OF 3 ADJACENT SENSORS = ALM.
8. REMOVE BAD SENSOR FROM AVERAGE
9. LOSS OF ANY 4 SENSORS OR MORE = ALM.
10. LOSS OF THE T48 AVERAGE FOR >90 SEC = ALM. DEFAULT T48REF = 1999 DEG F (1092.8 DEG C)
11. a. IF BOTH T2 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN DM & DEFAULT T2 VALUE TO 135 DEG F (57.2 DEG C).
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 18 DEG F (10.0 DEG C) THE ALM & USE THE HIGHER VALUE.
12. a. IF BOTH T25 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN DM & DEFAULT T25 VALUE TO 250 DEG F (121.1 DEG C).
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 18 DEG F (10.0 DEG C) THE ALM & USE THE HIGHER VALUE.
13. a. IF FLAME SENSOR = TRUE AND FUEL OFF FOR 1.0 SECOND OR IF FLAME SENSOR = FALSE AND FUEL ON AND T48SEL > 400 DEG F (> 204.4 DEG C) FOR Z_FLMTMR SECONDS THEN FAIL SENSOR AND ALM. (Z_FLMTMR = 0.320 SECONDS)
b. IF BOTH FLAME SENSORS = TRUE AND FUEL ON FOR 1.0 SECOND THEN FAIL BOTH SENSORS HIGH AND ALM
c. IF BOTH FLAME SENSORS = FALSE FOR Z_FLMTMR SECONDS AND FUEL ON AND T48SEL > 400 DEG F (> 204.4 DEG C) THEN FAIL BOTH SENSORS LOW AND ALM
d. IF BOTH FLAME SENSORS FAIL AND N25 <9200 RPM THEN INITIATE ES.
14. IF DIFFERENCE >10 PSID BETWEEN SENSORS = ALM & SELECT MODEL WEIGHTED AVERAGE.
15. P48 FAILURE PER INPUT SENSOR FAULT LOGIC TABLE IN CONTROL SPEC. P48ESTENSW = TRUE SO DM WILL NOT OCCUR.
16. a. IF BOTH T3 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE OF PAIR.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM THE AVERAGE.
17. a. IF BOTH PS3 TRANSMITTERS ARE WITHIN RANGE DISPLAY THE AVERAGE OF BOTH PS3 XMITTERS.
b. ONE TRANSMITTER OUT OF RANGE = ALARM & REMOVE THE BAD XMITTER FROM THE AVERAGE - BOTH XMITTERS OUT OF RANGE = DM FOR SAC UNIT, ES FOR DLE UNIT
c. PS3 DIFFERENCE BETWEEN XMITTERS BETWEEN 10 PSIA (68.9 kPaA) AND 15 PSIA (103.4 kPaA) FOR MORE THEN 5 SECONDS = ALARM & USE AVERAGE VALUE
d. PS3 DIFFERENCE BETWEEN XMITTERS GREATER THAN 15 PSIA (103.4 kPaA) AND FOR MORE THEN 0.1 SECONDS = ALM & SELECT HIGHER VALUE FOR SAC UNIT, ES FOR DLE UNIT
18. HIGH SIGNAL SELECT.
19. USE AVERAGE VALUE.
20. DEFAULT TO LAST GOOD VALUE.
21. DEFAULT TO 14.649 PSIA (101.0 kPaA)
22. SET TORQUE MOTOR OUTPUT TO 0 mA
23. XN25 > 4600 RPM
24. TORQUE MOTOR FAILURE WITH ALL COILS OPEN OR ANY COIL SHORT FOR > 500 mSEC
25. DIFFERENCE BETWEEN DEMAND AND POSITION
26. SET TM OUTPUT TO 0 mA
27. STEADY STATE LIMIT ERROR
28. dXN25/dT < 150 RPM/S FOR 5 SEC
29. LOW SIGNAL SELECT
30. FOR PC, IF BOTH SENSORS OUT OF RANGE THEN ALM. DERATE PS3 REFERENCE SCHEDULE AND SET T3SEL TO T3MODEL.
31. FOR PC, IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 20 DEG F (11.1 DEG C) THEN ALM & USE THE WEIGHTED AVERAGE TOWARD THE T3 MODEL.
32. MTTB COOLING OUTPUT = 1 WHEN CABINET AIR TEMP (TE-68310) > 65 DEG F (>18.3 DEG C), OUTPUT = 0 WHEN CABINET AIR TEMP < 60 DEG F (<15.6 DEG C)
MTTB HEATING OUTPUT = 1 WHEN CABINET AIR TEMP (TE-68310) < 35 DEG F (< 1.7 DEG C), OUTPUT = 0 WHEN CABINET AIR TEMP > 40 DEG F (> 4.4 DEG C)
A/C UNIT OUTSIDE FAN IS TURNED ON WHEN MTTB COOLING OUTPUT = ON
A/C UNIT INSIDE FAN IS ON ALL THE TIME.
33. INTENTIONALLY LEFT BLANK
34. INTENTIONALLY LEFT BLANK
35. INTENTIONALLY LEFT BLANK
36. INTENTIONALLY LEFT BLANK
37. INTENTIONALLY LEFT BLANK
38. INTENTIONALLY LEFT BLANKR
39. IF NULL SHIFT
40. IF ENGINE FLAME SENSOR OUTPUT > 2797 DEG F (> 1536.1 DEG C) = INDICATION OF FLAME. IF SENSOR OUTPUT < 2781 DEG F (< 1527.2 DEG C) (TUNABLE BETWEEN 2725 TO 2790 DEG F (1496.1 TO 1532.2 DEG C)) = LOSS OF FLAME.
41. IF GENERATOR ROTOR LEVEL > 3.0 MIL PP ( > 76.2 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 1 SEC = ALM. IF GENERATOR ROTOR LEVEL > 4.0 MIL PP (> 101.6 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 0.1 SEC = SI
42. IF XNSD SPEED >= 3000 RPM AND < 3590 3N25REF <N25MAX, LP ROTOR LEVEL > 1.75 IN/SEC PK (> 44.45 mm/SEC PK) FOR MORE THAN 1.0 SEC = ALM. IF LP ROTOR LEVEL > 2.5 IN/SEC PK (> 63.5 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
43. IF LP ROTOR LEVEL > 1.4 IN/SEC PK (> 35.56 mm/SEC PK) FOR MORE THAN 1.0 SEC (25 TO 80HZ) = ALM. IF LP ROTOR LEVEL > 2.0 IN/SEC PK (> 50.8 mm/SEC PK) FOR MORE THAN 0.1 SEC (25 TO 80 HZ) = SI
44. IF CRF OR WIDEBAND > 3.0 IN/SEC PK (76.2 mm/SEC PK) FOR MORE THAN 1.0 SEC = ALM. IF CRF OR WIDEBAND > 4.0 IN/SEC PK (101.6 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
45. IF HP ROTOR LEVEL > 2.0 IN/SEC PK (> 50.8 mm/SEC PK) FOR MORE THAN 1.0 SEC (100 TO 200 HZ) = ALM. IF HP ROTOR LEVEL > 3.0 IN/SEC PK (> 76.2 mm/SEC PK) FOR MORE THAN 0.1 SEC (100 TO 200 HZ) = SI
46. FOR DLE: IF (N25SEL > N25IDL - 100) AND THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 700 DEG F(371.1 DEG C) FOR 60 SEC = ALARM
47. FOR DLE: IF BURNER MODE 15 AND THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 150 DEG F (65.6 DEG C) FOR 60 SEC = ALARM
48. INTENTIONALLY LEFT BLANK
49. FOR PD/PF, IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 20 DEG F (11.1 DEG C) AND XN25 > 4600 RPM THEN ALM AND SELECT HIGHER VALUE
50. INTENTIONALLY LEFT BLANK
51. INTENTIONALLY LEFT BLANK
52. CHIP DETECTORS ALARM WHEN < 100 OHMS. INPUT BLOCK HAS 301 OHM ELEVATOR TIED ACROSS INPUTS. 100 OHMS PARALLELED WITH 301 OHM => 75.06 OHMS
53. IF GEARBOX SHAFT LEVEL > 0.3 IN/SEC PK ( > 7.62 mm/SEC PK) FOR MORE THAN 1 SEC = ALM. IF GEARBOX SHAFT LEVEL > 0.5 IN/SEC PK (> 12.7 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
54. ALARM AND BLOCK TURBINE CRANK IF EITHER THE A OR B POSITION SENSORS OF A BRAKE ELEMENT DOES NOT MATCH THE OPEN/CLOSE BRAKE COMMAND WITHIN 5 SECONDS.
55. ESN IF BOTH A AND B POSITION SENSORS OF A BRAKE ELEMENT DO NOT MATCH THE OPEN/CLOSE BRAKE COMMAND WITHIN 5 SECONDS.
56. a. IF CLUTCH VIBRATION LEVEL > 0.4 IN/SEC PK (10.2 mm/SEC PK) FOR MORE THAN 1.0 SEC= ALM
b. IF CLUTCH VIBRATION LEVEL > 0.6 IN/SEC PK (15.2 mm/SEC PK) FOR MORE THAN 2.0 SEC= SI WHEN NOT SYNCH CONDENSING, OR ESN WHEN SYNCH CONDENSING.
c. IF CLUTCH VIBRATION LEVEL > 0.8 IN/SEC PK (20.3 mm/SEC PK) FOR MORE THAN 0.1 SEC= SI WHEN NOT SYNCH CONDENSING, OR ESN WHEN SYNCH CONDENSING.
57. ALM
58. WHEN TM ACTIVE (1000 TO 2890 RPM FOR 50HZ, 1000 TO 3450 RPM FOR 60HZ): IF GENERATOR ROTOR LEVEL > 4.5 MIL PP ( > 114.3 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 2.0 SEC = ALM. IF GENERATOR ROTOR LEVEL > 6.0 MIL PP (> 152.4 M PP) FOR DRIVE END X OR Y FOR MORE THAN 1.0 SEC = SI
59. a. FOR SAC: IF XN25R IS > 8080 RPM AND ANY THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 275 DEG F (135 DEG C) FOR > 2 SEC = ALM
b. ANY THERMOCOUPLE WITH A DIFFERENCE OF <- 1000 OR > 1000 DEG F (<- 537.8 OR > 537.8 DEG C) FROM THE AVERAGE = ALM & SHALL BE REMOVED FROM THE AVERAGE
60. IF ABSOLUTE VALUE OF((XNSD LPT SPEED / 1.209) - GEN ROTOR SPEED) IS > 50 RPM FOR 10.0 SEC THEN ESN
DATE:
07/18/11-ATFL
LEGEND
1. SEE LEGEND TAB
38
39
A
B
B
REVISION LIST
ORIGINAL ISSUE
TE-6837A
TE-6837B
-70.0
-70.0
500.0
500.0
-65.0
-65.0
250.0
250.0
DEG F
DEG F
-56.7
-56.7
260.0
260.0
-53.9
-53.9
121.0
121.0
DEG C
DEG C
SF
SF
12
12
X
X
05/16/12-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
86G
GEN 86 TRIP
A15
A17
AVR_SC
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
ES
2
AT FUEL INITIATION, ACTIVATE FOR 1 SECOND.
1 = 0 RPM. POWER UP CHANGES RELAY
5
6
13
AVR_RV
AVR EXCITATION ON
AVR_LV
WX
GEN MW SIGNAL
11
BVX
12
BFX
13
GVX
GEN VOLTAGE
14
BVX1
15
BFX1
16
BVX2
UTILITY VOLTAGE
17
BFX2
UTILITY FREQUENCY
19
CHG_24VLO
20
CHG_ACF
21
CHG_DCF
22
CHG_GF
23
CHG_LO125
NSD
24
K1_VALVE
ESN
25
K1_SHUTDWN
ESN
26
8
9
4-20 mA = 0-60 MW
10
50 Hz: 4-20 mA = 0-15 kVAC
50 Hz: 4-20 mA = 45-55 Hz
50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 45-55 Hz
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 45-55 Hz
18
DM
SUMMARY_SD
28
DSM_LA
29
DSM_RA
ES3
ESN
ES1_2_10_3
ESN
HORN
HORN
37
IGPS_52GT
38
IGPS_FA
39
IGPS_MF
IGPS FAILURE
40
IGPS_PSA
42
K229
43
K230
44
K231
45
K232
46
K28
SYNCHRONIZER ENABLE
47
K5_K115
48
K230_K232
ISOCH/DROOP CONTROL
49
K85_K85A
50
LRS
27
ONLY ACTIVE WHEN DSM ENABLED
ONLY ACTIVE WHEN DSM ENABLED
30
31
32
33
ESTR-1,2,10/ESGR3
34
35
36
NSD
X
41
1 = CLOSED, 0 = OPEN
1 = ISOC, 0 = DROOP
1 = BREAKER CLOSE PERMISSIVE, 0 = TRIP BREAKER
1 = REMOTE, 0 = LOCAL
51
52
DC_STRTR1
53
MCC_DEV27
54
CUST_DCLOS
X
X
55
RGF
56
SS_K100-102
AUTO/MANUAL SYNC
57
SSW1_2
58
TSS_STOP
59
TSS_START
LOCAL START
ESN
ESN
OPTIONAL
1 = AUTO, 0 = MANUAL. K102 USED FOR UTILITY SYNCH OPTION ONLY
ESN
60
61
VIB_MON_HP
62
VIB_MON_LP
63
VIB_MON_TM
64
VIB_SYS_MF
65
VIB_SYS_SA
66
VIB_SYS_SD
ACTIVATE => 1000 XNSD SPEED < 3590 & N25SEL < N25MAX
SI
67
68
NOTES
1. IF UNIT IS RUNNING: OUTPUT = 1 AND LATCH, WHEN XNSD > 3060 RPM. OUTPUT = 0 AND UNLATCH, WHEN XNSD SPEED < 3240 RPM IF ESN OR ES OR STOPPING AND GENERATOR BREAKER OPEN. OUTPUT = 1 IF SYNCHRONOUS CONDENSER MODE ACTIVE.
LEGEND
1. SEE LEGEND TAB
DATE:
07/18/11-ATFL
REVISION LIST
A
ORIGINAL ISSUE
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.
LINE
REV
TAG NO.
PROCESS DESCRIPTION
RANGE LOW
(English)
RANGE HIGH
(English)
LIMIT DECR
(English)
LIMIT INCR
(English)
ENGLISH UNIT
RANGE LOW
(Metric)
RANGE HIGH
(Metric)
LIMIT DECR
(Metric)
LIMIT INCR
(Metric)
METRIC UNIT
ACTION
NOTE
ALARM
SHUT DOWN
ABORT START
START PERM.
CRANK PERM.
MOTORS
HEATERS
VALVES
COMMENTS
3
4
SAS_CUST_R
SAS_CUST_L
CUST_SCLK
CHW_STPERM
10
CHW_RESET
11
CHW_86TRIP
86 TRIP (CUSTOMER)
12
BUT_86TRIP
6
7
OPTIONAL
8
OPTIONAL
OPTIONAL
ES
X
OPTIONAL
13
GEN_BKR_FL
14
CHW_R_STRT
ES
15
CHW_R_STP
OPTIONAL
16
CHW_ACK
18
CUST_T2
-40.0
120.0
-40.0
48.9
OPTIONAL
19
CUST_T1
-40.0
120.0
-40.0
48.9
OPTIONAL
CUST_SD
OPTIONAL
17
20
21
OPTIONAL
22
23
NOTES
LEGEND
1. SEE LEGEND TAB
A
B
REVISION LIST
ORIGINAL ISSUE
ROWS 1 AND 2 REMOVED
DATE:
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12
CUSTOMER: PLN
SITE: Palembang, South Sumatra, Indonesia
LINE
Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict confidence with the
understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned
on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this
drawing.
REV
THE FOLLOWING ALARM AND SHUTDOWN TYPES GIVE BOTH AUDIO AND VISUAL INDICATION OF A FAULT CONDITION ON THE TURBINE CONTROL PANEL
(Old Naming Convention Shown In Parenthesis)
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
ACTION ABBREVIATIONS
37
AL - Alarm Low
ALL - Alarm Low Low
AH - Alarm High
AHH - Alarm High High
HD - High Difference
SFL/SFH - Signal Fail Low / Signal Fail High
38
39
40
41
42
43
44
A
B
REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET
DATE
07/18/11-ATFL
05/16/12-ATFL
ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12