GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


HYDRAULIC STARTER SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

6.5

IN.HG

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

165.0

mm.HG

PDAHH

mm

LALL

DEG C

TAH

PDSHH-1600

START SKID HYDRAULIC PUMP VACUUM HIGH HIGH DIFF PRESS

LSLL-1601

START SKID HYDRAULIC OIL TANK LOW LOW LEVEL

TSH-1602

START SKID HYDRAULIC CASE DRAIN HIGH TEMP

TSL-1603

START SKID HYDRAULIC OIL TANK LOW TEMP

70.0

DEG F

21.1

DEG C

TAL

PSLL-1605

START SKID HYDRAULIC PUMP SUPPLY LOW LOW PRESS

250.0

PSIG

1724.0

KPaG

PALL

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

ESN

2
3

6.0

IN

152.0

ESN

HE-1610 PERM

4
5

180.0

DEG F

82.2

6
7

8
9

ESN

10
11

TE-1663A1

12

TE-1663A2

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP (A2)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

13

TE-1663A1/A2

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP (A1)

-65.0

-65.0

1200.0

1200.0

-45.0

-45.0

390.0

390.0

DEG F

DEG F

-53.9

-53.9

648.9

648.9

-42.7

-42.7

198.9

198.9

DEG C

DEG C

SF

SF

14

TE-1663A1/A2

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP

10.0

DEG F

5.6

DEG C

HD

15

TE-1663SEL

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP

230.0

DEG F

110.0

DEG C

TAHH

16

TE-1663SEL

TURB HYDRAULIC STARTER CLUTCH OIL DRAIN PAN TEMP

200.0

DEG F

93.3

DEG C

TAH

DM

17
18

SOV-1619

SOLENOID OPERATED VALVE - PUMP CONTROL PISTON

MOT-1615

HYDRAULIC STARTER PUMP

MOT-1615FB

HYDRAULIC STARTER PUMP MOTOR STARTER AUX CONTACT

HE-1610

START SKID HYDRAULIC OIL TANK HEATER

0.0

100.0

0.0

100.0

19
20
21
22
23
24
25

NOTES
1. INTENTIONALLY LEFT BLANK
2. SHUTDOWN START SYSTEM BY ALLOWING THE HYDRAULIC PUMP TO RESET TO NEUTRAL POSITION FOR 10 SEC. AND THEN TURN OFF MOT-1615.

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


HYDRAULIC STARTER SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 1 OF 11 PAGE 1 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


VENTILATION AND COMBUSTION AIR

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

22

PDSH-6405-60

AIR INLET FILTER HIGH DIFF PRESS

5.0

IN H2O

127.0

mm H2O

PDAH

PDSHH-6406

AIR INLET FILTER HIGH HIGH DIFF PRESS

8.0

IN H2O

203.2

mm H2O

PDAHH

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

SERIES WIRE THE NC SWITCHES


NSD

3
4

PDSH-64017

BELL MOUTH INLET SCREEN HIGH DIFF PRESS

3.5

IN H2O

88.9

mm H2O

PDAH

PDSHH-64018

BELL MOUTH INLET SCREEN HIGH HIGH DIFF PRESS

4.5

IN H2O

114.3

mm H2O

PDAHH

PDT-64257

TURB ENCLOSURE AIR DIFF PRESS

IN H2O

PDT-64257SEL

TURB ENCLOSURE AIR DIFF PRESS

PDT-64258

GEN ENCLOSURE AIR DIFF PRESS

X
ESN

6
-10.0

10.0

-10.2

10.2
-0.1

IN H2O

-10.0

10.0

-10.2

10.2

IN H2O

-65.0

1200.0

-45.0

390.0
200.0

DEG F

-65.0

1200.0

-45.0

390.0

DEG F

-254.0

254.0

-259.1

259.1

mm H2O

SF

-2.54

mm H2O

PDAL

-254.0

254.0

-259.1

259.1

mm H2O

SF

mm H2O

PDAL

-53.9

648.9

-42.7

198.9

DEG C

SF

93.3

DEG C

TAH

-53.9

648.9

-42.7

198.9

DEG C

SF

9
10

PDT-64258SEL

GEN ENCLOSURE AIR DIFF PRESS

13

11

TE-6401

TURB ROOM AIR OUTLET TEMP (NO. 1)

14

0.1

IN H2O

2.54

X
4

12
DEG F

TE-6401SEL

TURB ROOM AIR OUTLET TEMP (NO. 1)

16

TE-6402

GEN ROOM AIR TEMP

17

TE-6402SEL

GEN ROOM AIR TEMP

150.0

DEG F

65.6

DEG C

TAHH

18

TE-6402SEL

GEN ROOM AIR TEMP

125.0

DEG F

51.7

DEG C

TAH

15
DM
X

19
20

TE-6421

GEN STATOR TEMP PHASE T1/U (NO. 1)

390.0

DEG F

198.9

DEG C

SF

21

TE-6421SEL

GEN STATOR TEMP PHASE T1/U (NO. 1)

293.0

DEG F

145.0

DEG C

TAHH

25

22

TE-6421SEL

GEN STATOR TEMP PHASE T1/U (NO. 1)

-65.0

1200.0

-45.0

275.0

DEG F

135.0

DEG C

TAH

25

23

TE-6421SEL

GEN STATOR TEMP PHASE T1/U (NO. 1)

DEG C

EVENT

25

TE-6422

GEN STATOR TEMP PHASE T2/V (NO. 2)

198.9

DEG C

SF

26

TE-6422SEL

GEN STATOR TEMP PHASE T2/V (NO. 2)

145.0

DEG C

TAHH

25

27

TE-6422SEL

GEN STATOR TEMP PHASE T2/V (NO. 2)

135.0

DEG C

TAH

25

28

TE-6422SEL

GEN STATOR TEMP PHASE T2/V (NO. 2)

DEG C

EVENT

30

TE-6423

GEN STATOR TEMP PHASE T3/W (NO. 3)

198.9

DEG C

SF

31

TE-6423SEL

GEN STATOR TEMP PHASE T3/W (NO. 3)

145.0

DEG C

TAHH

25

32

TE-6423SEL

GEN STATOR TEMP PHASE T3/W (NO. 3)

135.0

DEG C

TAH

25

33

TE-6423SEL

GEN STATOR TEMP PHASE T3/W (NO. 3)

DEG C

EVENT

35

TE-6424

GEN STATOR PHASE T1/U TEMP (NO. 4)

198.9

DEG C

SF

36

TE-6424SEL

GEN STATOR PHASE T1/U TEMP (NO. 4)

145.0

DEG C

TAHH

25

37

TE-6424SEL

GEN STATOR PHASE T1/U TEMP (NO. 4)

135.0

DEG C

TAH

25

38

TE-6424SEL

GEN STATOR PHASE T1/U TEMP (NO. 4)

DEG C

EVENT

40

TE-6425

GEN STATOR PHASE T2/V TEMP (NO. 5)

198.9

DEG C

SF

41

TE-6425SEL

GEN STATOR PHASE T2/V TEMP (NO. 5)

145.0

DEG C

TAHH

25

42

TE-6425SEL

GEN STATOR PHASE T2/V TEMP (NO. 5)

135.0

DEG C

TAH

25

43

TE-6425SEL

GEN STATOR PHASE T2/V TEMP (NO. 5)

DEG C

EVENT

45

TE-6426

GEN STATOR PHASE T3/W TEMP (NO. 6)

198.9

DEG C

SF

46

TE-6426SEL

GEN STATOR PHASE T3/W TEMP (NO. 6)

145.0

DEG C

TAHH

25

47

TE-6426SEL

GEN STATOR PHASE T3/W TEMP (NO. 6)

135.0

DEG C

TAH

25

48

TE-6426SEL

GEN STATOR PHASE T3/W TEMP (NO. 6)

DEG C

EVENT

50

TE-6430

GEN AIR OUTLET TEMP

DEG C

SF

51

TE-6430SEL

52

TE-6430SEL

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

24
-65.0

1200.0

-45.0

390.0

DEG F

293.0

DEG F

275.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

29
-65.0

1200.0

-45.0

390.0

DEG F

293.0

DEG F

275.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

34
-65.0

1200.0

-45.0

390.0

DEG F

293.0

DEG F

275.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

39
-65.0

1200.0

-45.0

390.0

DEG F

293.0

DEG F

275.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

44
-65.0

1200.0

-45.0

390.0

DEG F

293.0

DEG F

275.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
DM
X
X

49
-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

GEN AIR OUTLET TEMP

220.0

DEG F

104.4

DEG C

TAHH

GEN AIR OUTLET TEMP

200.0

DEG F

93.3

DEG C

TAH

X
X

DM

53
54

TE-6431

GEN EXCITER AIR OUTLET TEMP

390.0

DEG F

DEG C

SF

55

TE-6431SEL

GEN EXCITER AIR OUTLET TEMP

220.0

DEG F

104.4

DEG C

TAHH

56

TE-6431SEL

GEN EXCITER AIR OUTLET TEMP

-65.0

1200.0

-45.0

200.0

DEG F

-53.9

648.9

-42.7

198.9
93.3

DEG C

TAH

X
X

DM

57
58

TE-6454

TURB ROOM AIR INLET TEMP (NO. 2)

390.0

DEG F

198.9

DEG C

SF

59

TE-6454SEL

TURB ROOM AIR INLET TEMP (NO. 2)

150.0

DEG F

65.6

DEG C

TAHH

60

TE-6454SEL

TURB ROOM AIR INLET TEMP (NO. 2)

-65.0

1200.0

-45.0

140.0

DEG F

-53.9

648.9

-42.7

60.0

DEG C

TAH

TE-6450

AIR INLET FILTER CONDITIONED COMBUSTION AIR TEMP (SEC A)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

TE-6499

AIR INLET FILTER CONDITIONED COMBUSTION AIR TEMP (SEC B)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

TE-64072

AIR INLET FILTER CONDITIONED VENTILATION AIR TEMP (SEC A)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

DM

61
62
63
64
65
66
67
68

TE-64071

AIR INLET FILTER CONDITIONED VENTILATION AIR TEMP (SEC B)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

70

TE-64259

AIR INLET FILTER AMBIENT TEMP (T0)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

71

DEG C

TAL

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

158.0

DEG F

70.0

DEG C

TAH

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

158.0

DEG F

70.0

DEG C

TAH

69
TE-64259SEL

AIR INLET FILTER AMBIENT TEMP (T0)

73

TE-4015A

MTTB AIR INSIDE HOT TEMP (A)

74

43.0

DEG F

6.1

72
TE-4015ASEL

MTTB AIR INSIDE HOT TEMP (A)

76

TE-4015B

MTTB AIR INSIDE HOT TEMP (B)

77

TE-4015BSEL

MTTB AIR INSIDE HOT TEMP (B)

MOT-4019A - OFF

75
MOT-4019A - OFF

78

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


VENTILATION AND COMBUSTION AIR

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 2 OF 11 PAGE 2 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


VENTILATION AND COMBUSTION AIR

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

79

TE-4015C

MTTB AIR INSIDE HOT TEMP (C)

80

TE-4015CSEL

MTTB AIR INSIDE HOT TEMP (C)

TE-6493

GEN AIR INLET TEMP COMPENSATION (DRIVE END)

84

MOT-6417

TURB ENCLOSURE VENT FAN (A)

85

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

158.0

DEG F

70.0

DEG C

TAH

390.0

DEG F

198.9

DEG C

SF

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

X
MOT-4019A - OFF

81
82

-65.0

1200.0

-45.0

-53.9

648.9

-42.7

OPT: GE AVR

83
MOT-6418

TURB ENCLOSURE VENT FAN (B)

87

MOT-6413

GEN (/GB) ENCLOSURE VENT FAN (A)

88

MOT-6416

GEN (/GB) ENCLOSURE VENT FAN (B)

86

89
90

K347_K347A

MTTB CABINET COOLING

K348

MTTB CABINET HEATING

94

TE-4016A

MTTB AIR INSIDE COLD TEMP (A)

95

CONTROLS MOT-4019A, B, C

91
92

CONTROLS MOT-4019A, B, C

93
TE-4016ASEL

MTTB AIR INSIDE COLD TEMP (A)

97

TE-4016B

MTTB AIR INSIDE COLD TEMP (B)

98

-65.0

1200.0

-45.0

-65.0

1200.0

-45.0

-65.0

1200.0

-45.0

390.0

DEG F

390.0

DEG F

390.0

DEG F

40.0

-53.9

648.9

-42.7

-53.9

648.9

-42.7

-53.9

648.9

-42.7

DEG F

198.9

4.0

DEG C

SF

DEG C

TAL

DEG C

SF

DEG C

TAL

DEG C

SF

DEG C

TAL

MOT-4019A - OFF

96
TE-4016BSEL

MTTB AIR INSIDE COLD TEMP (B)

100

TE-4016C

MTTB AIR INSIDE COLD TEMP (C)

101

40.0

DEG F

198.9

4.0

MOT-4019A - OFF

99
40.0

DEG F

4.0

198.9

TE-4016CSEL

MTTB AIR INSIDE COLD TEMP (C)

103

HE-64050

HEATER ELEMENT-GENERATOR SPACE

MOT-4019A - OFF
Control By K81

104

HE-64051

HEATER ELEMENT-GENERATOR STATOR CORE

Control By K81

102

105
106

NOTES
1. REDUCE LOAD AT 8"WC TO 5" WC. NSD ON THIRD AHH
2. INTENTIONALLY LEFT BLANK
3. START BLOW DOWN AT 1500 MICRO MHO, STOP AT 1200 MICRO MHO
4. SWAP TO BACKUP FAN AND ALARM ONLY IF FANS ARE COMMANDED TO RUN
5. DM IF BOTH SETS OF RTD'S ON THE SAME PHASE FAIL
6. BLOWN DOWN UNTIL CONDUCTIVITY IS AT NORMAL
7. INTENTIONALLY LEFT BLANK
8. GT START CRANK INHIBITED IF GENERATOR STATOR TEMP < 14 DEG F (< 10.0 DEG C). SPACE HEATERS WILL BE USED TO WARM GENERATOR STATOR. WINDINGS PRIOR TO START UP AND GRANT PERMISSIVE. UPON SHUTDOWN OF GT, GENERATOR ENCLOSURE VENTILATION FANS (AS APPLICA
SHALL OPERATE DURING POST SHUTDOWN CRANK CYCLE. WHEN POST SHUTDOWN CRANK CYCLE IS COMPLETED, CONTINUE TO OPERATE VENTILATION FANS UNTIL STATOR WINDING TEMPERATURES HAVE COOLED < 120 DEG F (< 48.9 DEG C), OR WHEN STATOR TEMPERATURES ARE EQUAL TO AMB
9. STOP MOT4060, MOT4061 AT 4 PSIG (27.6 kPaG) DECR.
10. INTENTIONALLY LEFT BLANK.
11. OPEN SOV-4143, SOV-4144 AT 64 % INCR. ; CLOSE AT 55 % DECR.
12. STOP MOT-4060, MOT-4061 AT 16 % DECR.
13. SETTINGS FOR BRUSH GENERATOR
14. INTENTIONALLY LEFT BLANK
15. SETTINGS FOR GE GENERATOR
16. STANDBY VENT FAN IS TURNED ON
17. STANDBY VENT FAN IS TURNED OFF
18. IF AUX SKID TEMP > 100 DEG F (37.8 DEG C) OPEN MAIN INLET DAMPER &EXHAUST DAMPER #2 IF APPLICABLE, WAIT 5 SEC AND TURN MAIN VENT FAN ON
19. IF AUX SKID TEMP < 70 DEG F (< 21.1 DEG C) TURN MAIN FAN OFF, WAIT 60 SECONDS THEN CLOSE MAIN INLET DAMPER & EXHAUST DAMPER #2 IF APPLICABLE; STANDBY FAN BECOMES MAIN FAN.
20. INTENTIONALLY LEFT BLANK
21. INTENTIONALLY LEFT BLANK
22. SERIES WIRE THE N.C. SWITCHES - ALT PDT-64232/234
23. INTENTIONALLY LEFT BLANK
24. "TURBINE ENCLOSURE TEMP LOW, CHECK HEATERS" ALARM. ALARM IS ENABLED AFTER TIME DELAY WHEN BOTH VENT FANS ARE OFF AND THE ENCLOSURE HEATERS ARE ENABLED (K43). ALARM TIME DELAY (TUNABLE) IS SET SO HEATERS HAVE TIME TO WARM THE ENCLOSURE AFTER VENT FAN
25. STATOR SETTINGS FOR 50 HZ MEIDENSHA GENERATOR
26. STATOR SETTINGS FOR 60 HZ MEIDENSHA GENERATOR
27. ALARM IF TEMP < 43 DEG F. ALARM IF ABSOLUTE VALUE OF [((Tmax + 460) - Tavg) / Tavg] > 0.020 WHERE Tavg = [(TE64032 + 460) + (TE64033 + 460)] / 2 AND Tmax = THE HIGHER OF TE64032 AND TE64033.
28. MOT-68358 ON WHEN TE-6454 AT 55F DECR. MOT-68358 OFF WHEN TE-6454 AT 60F INCR. SHUT OFF MOTOR WHEN FIRE DETECTED
29. HEATERS ON WHEN TE-6454 AT 55F DECR. HEATERS OFF WHEN TE-6454 AT 60F INCR. SHUT OFF HEATERS WHEN FIRE DETECTED. SET THERMOSTAT TC-6888 AND TC-6889 TO TURN HEATER OFF AT 100F INCR

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


VENTILATION AND COMBUSTION AIR

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 2 OF 11 PAGE 3 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


GENERATOR LUBE OIL SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

0.0

100.0

-2.0

0.0

100.0

-2.0

ACTION

LT-0001

GEN/GB LUBE OIL TANK LEVEL

102.0

102.0

SF

LT-0001SEL

GEN/GB LUBE OIL TANK LEVEL

97.0

97.0

LAHH

LT-0001SEL

GEN/GB LUBE OIL TANK LEVEL

91.0

91.0

LAH

LT-0001SEL

GEN/GB LUBE OIL TANK LEVEL

61.0

61.0

LAL

LT-0001SEL

GEN/GB LUBE OIL TANK LEVEL

55.0

55.0

LALL

PDT-0015

GEN/GB LUBE OIL FILTER DIFF PRESS

PDT-0015SEL

GEN/GB LUBE OIL FILTER DIFF PRESS

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

OPT: 50 Hz. LT-0001 CONNECTED TO N102 VIA ISOLATOR ISO2


ESN

X
1

HE-0005/8 PERM

ESN

6
0.0

35.0

-0.7

35.7

PSID

20.0

PSID

102.0

PSIG

0.0

241.3

-0.7

35.7

kPaD

SF

137.9

kPaD

PDAH

OPT: 50 HZ

9
10

PT-0029A

GEN/GB LUBE OIL AC PUMP DISCHARGE PRESS (A)

11

PT-0029ASEL

GEN/GB LUBE OIL AC PUMP DISCHARGE PRESS (A)

0.0

100.0

-2.0
40.0

0.0

689.5

PSIG

-13.8

703.3

275.8

kPaD

SF

kPaD

PAL

X
1,3

OPT: 50 HZ
ESN

ESN

ESN

12
13

PT-0029B

GEN/GB LUBE OIL AC PUMP DISCHARGE PRESS (B)

14

PT-0029BSEL

GEN/GB LUBE OIL AC PUMP DISCHARGE PRESS (B)

0.0

100.0

-2.0

102.0

40.0

PSIG

0.0

689.5

PSIG

-13.8

703.3

275.8

kPaD

SF

kPaD

PAL

X
1,3

OPT: 50 HZ

15
16

PT-0123

GEN/GB LUBE OIL DC PUMP DISCHARGE PRESS

17

PT-0123SEL

GEN/GB LUBE OIL DC PUMP DISCHARGE PRESS

19

PDT-0124

GEN/GB LUBE OIL TANK VACUUM PRESS

20

PDT-0124SEL

GEN/GB LUBE OIL TANK VACUUM PRESS

0.0

100.0

-2.0

102.0

20.0

PSIG

0.0

689.5

PSIG

-13.8

703.3

137.9

kPaD

SF

kPaD

PAL

X
1,3

OPT: 50 HZ

18
-5.0

5.0

-5.1

5.1

IN H2O

-1.0

IN H2O

-127.0

127.0

-129.5

129.5

mm H2O

SF

-25.4

mm H2O

PDAH

OPT: 50 HZ

21
22

TE-0020A1

GEN/GB LUBE OIL TANK TEMP (A1)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

OPT: 50 Hz

23

TE-0020A2

GEN/GB LUBE OIL TANK TEMP (A2)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

OPT: 50 Hz

24

TE-0020A1/A2

GEN/GB LUBE OIL TANK TEMP

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

25

TE-0020A1/A2

GEN/GB LUBE OIL TANK TEMP

10.0

DEG F

5.6

DEG C

HD

26

TE-0020SEL

GEN/GB LUBE OIL TANK TEMP

110.0

DEG F

43.3

DEG C

EVENT

27

TE-0020SEL

GEN/GB LUBE OIL TANK TEMP

90.0

DEG F

32.2

DEG C

EVENT

28

TE-0020SEL

GEN/GB LUBE OIL TANK TEMP

70.0

DEG F

21.1

DEG C

TAL

HE-0005/8 OFF
HE-0005/8 ON
X

29
30

TE-0058

GEN/GB LUBE OIL SUPPLY AFTER COOLER TEMP

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

32

TE-6079

GEARBOX BEARING HS PINION TEMP (EXTENSION END)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

33

TE-6079SEL

GB BEARING TEMP HS PINION (EE)

240.0

DEG F

115.6

DEG C

TAHH

34

TE-6079SEL

GB BEARING TEMP HS PINION (EE)

225.0

DEG F

107.2

DEG C

TAH

X
X

OPT: 50 Hz

31
OPT: 50 Hz
ESN

35
36

TE-6080

GEARBOX BEARING HS PINION TEMP (BLIND END)

390.0

DEG F

198.9

DEG C

SF

37

TE-6080SEL

GEARBOX BEARING HS PINION TEMP (BE)

240.0

DEG F

115.6

DEG C

TAHH

38

TE-6080SEL

GEARBOX BEARING HS PINION TEMP (BE)

-65.0

1200.0

-45.0

225.0

DEG F

-53.9

648.9

-42.7

107.2

DEG C

TAH

X
X

OPT: 50 Hz
ESN

39
40

TE-6081

GEARBOX BEARING LSP SHAFT TEMP (EXTENSION END)

390.0

DEG F

198.9

DEG C

SF

41

TE-6081SEL

GEARBOX BEARING LSP SHAFT TEMP (EE)

240.0

DEG F

115.6

DEG C

TAHH

42

TE-6081SEL

GEARBOX BEARING LSP SHAFT TEMP (EE)

-65.0

1200.0

-45.0

225.0

DEG F

-53.9

648.9

-42.7

107.2

DEG C

TAH

X
X

OPT: 50 Hz
ESN

43
44

TE-6082

GEARBOX BEARING LSP SHAFT TEMP (BLIND END)

390.0

DEG F

198.9

DEG C

SF

45

TE-6082SEL

GEARBOX BEARING LSP SHAFT TEMP (BE)

240.0

DEG F

115.6

DEG C

TAHH

46

TE-6082SEL

GEARBOX BEARING LSP SHAFT TEMP (BE)

-65.0

1200.0

-45.0

225.0

DEG F

-53.9

648.9

-42.7

107.2

DEG C

TAH

X
X

OPT: 50 Hz
ESN

47
48

TE-6084

GEARBOX LUBE OIL DRAIN TEMP

390.0

DEG F

198.9

DEG C

SF

49

TE-6084SEL

GEARBOX LUBE OIL DRAIN TEMP

240.0

DEG F

115.6

DEG C

TAHH

50

TE-6084SEL

GEARBOX LUBE OIL DRAIN TEMP

-65.0

1200.0

-45.0

225.0

DEG F

-53.9

648.9

-42.7

107.2

DEG C

TAH

OPT: 50 Hz

MOT-0033A

GEN/GB LUBE OIL AC PUMP (A)

14

OPT: 50 HZ. 0 = PUMP ON

MOT-0033B

GEN/GB LUBE OIL AC PUMP (B)

14

OPT: 50 HZ. 0 = PUMP ON

MOT-0034

GB EMERGENCY DC LUBE OIL PUMP

14

OPT: 50 HZ. 0 = PUMP ON

MOT-6899

GEARBOX TURNING GEAR

14

60

HE-0005

GEN (/GB) LUBE OIL TANK HEATER (A)

61

HE-0008

GEN (/GB) LUBE OIL TANK HEATER (B)

MOT-0236

GEN/GB LUBE AIR/OIL SEPARATOR

OPT: 50 HZ. AUX CONTACT ON MTR STRT USED TO START MOT-0237 (MOT0237 USED W/FIN-FAN OPT ONLY)

MOT-6090

FIN-FAN LUBE OIL COOLER FAN (A)

OPT: FIN-FAN COOLER

MOT-6091

FIN-FAN LUBE OIL COOLER FAN (B)

OPT: FIN-FAN COOLER

MOT-6093

FIN-FAN LUBE OIL COOLER FAN (C)

OPT: FIN-FAN COOLER & 50 HZ

ESN
X

51
52
53
54
55
56
57
58

OPT: 50 HZ

59
USE HE-6005 FOR 60 HZ OR HE-0005 FOR 50 HZ

62
63
64
65
66
67
68
69
70
71

XSH-68327A

FIN-FAN LUBE OIL COOLER FAN "A" HIGH VIBRATION

OPT: FIN-FAN COOLER

XSH-68327B

FIN-FAN LUBE OIL COOLER FAN "B" HIGH VIBRATION

OPT: FIN-FAN COOLER

XSH-68327C

FIN-FAN LUBE OIL COOLER FAN "C" HIGH VIBRATION

LS-60001A

GEARBOX LUBE OIL RUNDOWN TANK LEVEL (LEFT SIDE TANK) (A)

6.0

INCH

152.4

mm

LALL

OPT: 50 Hz. 0 = LIQUID LEVEL BELOW SWITCH

LS-60001B

GEARBOX LUBE OIL RUNDOWN TANK LEVEL (RIGHT SIDE TANK) (B)

6.0

INCH

152.4

mm

LALL

OPT: 50 Hz. 0 = LIQUID LEVEL BELOW SWITCH

72
73
74
75

OPT: FIN-FAN COOLER & 50 HZ

76
77
78
79
80

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


GENERATOR LUBE OIL SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 3 OF 11 PAGE 4 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


GENERATOR LUBE OIL SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

81

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

LS-6041A

GEN LUBE OIL RUNDOWN TANK LEVEL (DRIVE END) (A)

6.0

INCH

152.4

mm

LALL

0 = LIQUID LEVEL BELOW SWITCH

LS-6042A

GEN LUBE OIL RUNDOWN TANK LEVEL (NON-DRIVE END) (A)

6.0

INCH

152.4

mm

LALL

0 = LIQUID LEVEL BELOW SWITCH

85

PT-6026

GEN LUBE OIL SUPPLY PRESS

kPaG

SF

86

PSL-6018

GEN LUBE OIL SUPPLY LOW PRESS

20.0

PSIG

137.9

kPaG

PAL

87

PSLL-6019

GEN LUBE OIL SUPPLY LOW LOW PRESS

12.0

PSIG

82.7

kPaG

PALL

89

PSL-6050

GEN JACKING OIL PUMP INLET LOW PRESS

10.0

PSIG

68.9

kPaG

PAL

90

82
83
84
0.0

100.0

-1.00

106.25

PSIG

0.0

689.5

-6.9

732.6

X
1

ESN

88
PSLL-6051

GEN JACKING OIL PUMP INLET LOW LOW PRESS

92

TE-6021

GEN BEARING TEMP (DRIVE END)

93

TE-6021SEL

GEN BEARING TEMP (DRIVE END)

94

TE-6021SEL

GEN BEARING TEMP (DRIVE END)

95

TE-6021SEL

GEN BEARING TEMP (DRIVE END)

97

TE-6023

GEN BEARING TEMP (NON-DRIVE END)

98

TE-6023SEL

GEN BEARING TEMP (NON-DRIVE END)

99

TE-6023SEL

GEN BEARING TEMP (NON-DRIVE END)

100

TE-6023SEL

GEN BEARING TEMP (NON-DRIVE END)

102

TE-6025

GEN LUBE OIL SUPPLY TEMP

103

TE-6025SEL

GEN LUBE OIL SUPPLY TEMP

104

TE-6025SEL

GEN LUBE OIL SUPPLY TEMP

105

TE-6025SEL

GEN LUBE OIL SUPPLY TEMP

107

TE-6035

GEN BEARING OIL DRAIN TEMP (NON-DRIVE END)

108

TE-6035SEL

109

TE-6035SEL

5.0

PSIG

34.5

kPaG

PALL

198.9

DEG C

SF

ESN

105.0

DEG C

TAHH

12

100.0

DEG C

TAH

12

DEG C

EVENT

198.9

DEG C

SF

105.0

DEG C

TAHH

12

100.0

DEG C

TAH

12

DEG C

EVENT

DEG C

SF

91
-65.0

1200.0

-45.0

390.0

DEG F

221.0

DEG F

212.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
ESN
X
X

96
-65.0

1200.0

-45.0

390.0

DEG F

221.0

DEG F

212.0

DEG F

14.0

-53.9

648.9

DEG F

-42.7

-10.0

X
ESN
X
X

101
-65.0

1200.0

-45.0

390.0

DEG F

190.0

DEG F

160.0

DEG F

40.0

-53.9

648.9

-42.7

198.9
87.8

TAHH

11, 12

DEG C

TAH

11, 12

DEG C

EVENT

198.9

DEG C

SF

71.1

DEG F

4.4

DEG C

DM
ESN
X

106
-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

GEN BEARING OIL DRAIN TEMP (NON-DRIVE END)

194.0

DEG F

90.0

DEG C

TAHH

11, 12

GEN BEARING OIL DRAIN TEMP (NON-DRIVE END)

189.0

DEG F

87.2

DEG C

TAH

11, 12

ESN
X

110
111

TE-6036

GEN BEARING OIL DRAIN TEMP (DRIVE END)

390.0

DEG F

198.9

DEG C

SF

112

TE-6036SEL

GEN BEARING OIL DRAIN TEMP (DRIVE END)

194.0

DEG F

90.0

DEG C

TAHH

11, 12

113

TE-6036SEL

GEN BEARING OIL DRAIN TEMP (DRIVE END)

-65.0

1200.0

-45.0

189.0

DEG F

-53.9

648.9

-42.7

87.2

DEG C

TAH

11, 12

X
ESN
X

114
115

TE-6056

GEN THRUST BEARING TEMP (INBOARD)

390.0

DEG F

198.9

DEG C

SF

116

TE-6056SEL

GEN THRUST BEARING TEMP (INBOARD)

221.0

DEG F

105.0

DEG C

TAHH

11, 12

117

TE-6056SEL

GEN THRUST BEARING TEMP (INBOARD)

-65.0

1200.0

-45.0

212.0

DEG F

-53.9

648.9

-42.7

100.0

DEG C

TAH

11, 12

390.0

DEG F

198.9

DEG C

SF

ESN
X

118
119

TE-6057

GEN THRUST BEARING TEMP (OUTBOARD)

MOT-6031

GEN JACKING OIL PUMP

-65.0

1200.0

-45.0

-53.9

648.9

-42.7

120
121

14

122
123

NOTES
1. PART OF AUXILIARY SYSTEM CHECK SEQUENCE
2. HEATER ON AT 90 DEG. F (32.2 DEG C) DECR AND OFF AT 110 DEG F (43.3 DEG C) INCR. HEATER ALSO THERMOSTATICALLY CONTROLLED AT 90 DEG. F (32.2 DEG C) DECR
3. ESN TO ABORT START IF PRESSURE IS LOW DURING THE AUXILIARY SYSTEM CHECK SEQUENCE. ALARM IF PRESSURE BECOMES LOW AFTER THE AUXILIARY SYSTEM CHECK IS COMPLETED.
4. DURING START CYCLE, OR RUN CYCLE ONE LEVEL SWITCH PER TANK (0) TRIPPED = ALARM. ALL SWITCHES MUST SHOW TANKS FULL (1) BEFORE ALLOWING STARTER ENGAGEMENT.
5. START PERMISSIVE IF TANK LEVEL 60% OR MORE.
6. GT START CRANK INHIBITED IF GENERATOR LUBE OIL SUPPLY TEMPERATURE < 40 DEG F (< 4.4 DEG C), OR IF BEARING METAL TEMP < 14 DEG F (< -10.0 DEG C). WARM LUBE OIL WILL BE USED TO WARM UP BEARING TO 40 DEG F (4.4 DEG C) BEFORE STARTER ENGAGEMENT WILL BE ALLOWED.
7. INTENTIONALLY LEFT BLANK.
8. FOR 60HZ: ONCE XNSD > 3000 RPM THEN SHUTDOWN AC LUBE PUMP AND ENABLE PSL-6017. IF PRESSURE IS LOW THEN START AC PUMP AND KEEP IT ON UNTIL UNIT SHUTDOWN
9. INTENTIONALLY LEFT BLANK.
10. INTENTIONALLY LEFT BLANK.
11. SETTINGS FOR BRUSH GENERATOR
12. SETTINGS FOR MEIDENSHA GENERATOR
13. SETTINGS FOR GE GENERATOR
14. WHEN THE UNIT IS EITHER CRANKING, STARTING OR CRANK SOAK WATER WASHING THE FOLLOWING IS TO BE DONE:
a. FOR 50HZ: SEQUENCE ALL GEN/GB LUBE OIL PUMPS TO VERIFY DISCHARGE PRESSURE. LEAVE PRIMARY AC PUMP ON AFTER PRESSURE VERIFICATIONS ARE COMPLETE.
b. FOR 60HZ: START THE GENERATOR AC LUBE OIL PUMP.
c. START THE HYD. STARTER AND AFTER THE GEN LUBE PUMP HAS RUN FOR 15 SEC. CHECK FOR JACKING OIL PUMP SUCTION PRESSURE. IF PRESSURE PRESENT START THE JACKING OIL PUMP.
d. FOR 50HZ: 15 SEC AFTER STARTING THE JACKING PUMP & IF XN25 > 2200 RPM, START TURNING GEAR MOTOR, AFTER 30 SEC. CHECK IF XNSD > 190 RPM, IF NOT ESN
e. FOR 50HZ: WHEN XNSD > 1000 RPM SHUTDOWN TURNING GEAR AND JACKING OIL PUMP.
f. FOR 60HZ: WHEN XNSD > 1000 RPM SHUTDOWN JACKING OIL PUMP.
g. FOR 50HZ: IF SHUTDOWN SHOULD OCCUR DURING STARTING WHILE TURNING GEAR AND JACKING OIL PUMP ARE ON, SHUTDOWN TURNING GEAR MOTOR IMMEDIATELY, BUT WAIT 15 SEC. BEFORE SHUTTING DOWN JACKING OIL PUMP.
h. FOR 60HZ: IF SHUTDOWN SHOULD OCCUR DURING STARTING WHILE JACKING OIL PUMP IS ON, WAIT 15 SEC. BEFORE SHUTTING DOWN JACKING OIL PUMP.
i. FOR 60HZ: WHEN XNSD > 3000 RPM DE-ENERGIZE AC LUBE OIL PUMP
15. INTENTIONALLY LEFT BLANK.
16. ESN IF PRESSURE IS LOW DURING THE AUXILIARY SYSTEM CHECK SEQUENCE.
ALARM IF PRESSURE BECOMES LOW AFTER THE AUXILIARY SYSTEM CHECK IS COMPLETED.
17. WHEN AC PUMP STARTS IT MUST VERIFY AT THIS PRESSURE IN 15 SECONDS DURING AUXILIARY SYSTEM CHECK SEQUENCE. IF FAIL THEN ESN AND BLOCK TURBINE CRANK.
18. WHEN DC PUMP STARTS IT MUST VERIFY AT THIS PRESSURE IN 15 SECONDS DURING AUXILIARY SYSTEM CHECK SEQUENCE. IF FAIL THEN ESN AND BLOCK TURBINE CRANK.
19. TEMPERATURE MUST BE HIGHER THAN 70 DEG F (21.1 DEG C) FOR ENGINE TO START.
20. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) OPEN IF TE-61069 > 50 DEG F (10.0 DEG C) OR TE-60019 > 50 DEG F (10.0 DEG C)
21. WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) CLOSE IF TE-61069 < 30 DEG F (-1.1 DEG C) AND TE-60019 < 34 DEG F (1.1 DEG C)
22. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS ON IF TE-61069 > 70 DEG F (21.1 DEG C) OR TE-60019 > 70 DEG F (21.1 DEG C) AND ENGINE CRANKING OR RUNNING
23. THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS OFF IF TE-61069 < 35 DEG F (1.7 DEG C) AND TE-60019 < 35 DEG F (1.7 DEG C) OR ENGINE IS NOT CRANKING OR RUNNING

LEGEND
1. SEE LEGEND TAB

A
B

DATE:
07/18/11-ATFL
05/16/12-ATFL

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


GENERATOR LUBE OIL SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 3 OF 11 PAGE 5 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


TURBINE LUBE OIL SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

12.0

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

INCH

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

305.0

ACTION

NOTE

ALARM

LSL-6102

TURB LUBE OIL TANK LOW LEVEL

mm

LAL

PDSH-6120

TURB LUBE OIL SUPPLY FILTER HIGH DIFF PRESS

20.0

PSID

137.9

kPaD

PDAH

PDSHH-6144

TURB LUBE OIL SUPPLY FILTER HIGH HIGH DIFF PRESS

25.0

PSID

172.4

kPaD

PDAHH

PDSH-6118

TURB LUBE OIL SCAVENGE FILTER HIGH DIFF PRESS

20.0

PSID

137.9

kPaD

PDAH

PDSHH-6119

TURB LUBE OIL SCAVENGE FILTER HIGH HIGH DIFF PRESS

25.0

PSID

172.4

kPaD

PDAHH

PDSH-6148

AIR/OIL SEPARATOR FILTER HIGH DIFF PRESS

1.7

PSID

11.7

kPaD

PDAH

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

HE-6104 PERM

2
3

10

4
5

10

NSD

6
7

10

8
9

10

NSD

10
11

60

60

12
13

PDSH-6146

TURB VG LUBE OIL FILTER HIGH DIFF PRESS

kPaD

PDAH

PSLL-6115

TURB LUBE OIL SUPPLY LOW LOW PRESS (XN25>7.8K RPM)

15.0

20.0

PSIG

PSID
103.4

137.9

kPaG

PALL

PSLL-6116

TURB LUBE OIL SUPPLY LOW LOW PRESS (4.5K<XN25<7.8K RPM)

6.0

PSIG

41.4

kPaG

PALL

PSH-6117

TURB LUBE OIL SCAVENGE PUMP DISCHARGE HIGH PRESS

kPaG

PAH

TSL-6113

TURB LUBE OIL TANK LOW TEMP

DEG C

TAL

PT-6121

TURB LUBE OIL SUPPLY PRESS (PLUB)

kPaG

SF

14
15

ESN

16
17

ESN

18
19

100.0

PSIG

689.5

20
21

70.0

DEG F

21.1

22
23

0.0

100.0

-2.0

102.0

PSIG

0.0

689.5

-13.8

703..3

24
25

PT-6122

TURB LUBE OIL SCAVENGE PRESS (PSCV)

0.0

200.0

-4.0

204.0

PSIG

0.0

1379.0

-27.8

1406.5

kPaG

SF

27

TE-6123A

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGBA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

28

TE-6123B

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGBB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

29

TE-6123A/B

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGB)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

30

TE-6123A/B

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGB)

10.0

DEG F

5.6

DEG C

HD

31

TE-6123SEL

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGB)

265.0

DEG F

129.4

DEG C

TAHH

32

TE-6123SEL

TURB LUBE OIL AGB SCAVENGE OIL TEMP (TAGB)

240.0

DEG F

115.5

DEG C

TAH

34

TE-6124A

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBAA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

35

TE-6124B

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBAB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

36

TE-6124A/B

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBA)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

37

TE-6124A/B

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBA)

10.0

DEG F

5.6

DEG C

HD

38

TE-6124SEL

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBA)

310.0

DEG F

154.4

DEG C

TAHH

39

TE-6124SEL

TURB LUBE OIL SUMP TGB/A SCAV OIL TEMP (TGBA)

285.0

DEG F

140.6

DEG C

TAH

41

TE-6125A

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBBA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

42

TE-6125B

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBBB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

43

TE-6125A/B

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBB)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

44

TE-6125A/B

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBB)

10.0

DEG F

5.6

DEG C

HD

45

TE-6125SEL

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBB)

330.0

DEG F

165.6

DEG C

TAHH

46

TE-6125SEL

TURB LUBE OIL SUMP B SCAV OIL TEMP (TGBB)

305.0

DEG F

151.7

DEG C

TAH

48

TE-6186A

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBCA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

49

TE-6186B

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBCB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

50

TE-6186A/B

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBC)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

51

TE-6186A/B

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBC)

10.0

DEG F

5.6

DEG C

HD

52

TE-6186SEL

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBC)

340.0

DEG F

171.1

DEG C

TAHH

53

TE-6186SEL

TURB LUBE OIL SUMP C SCAV OIL TEMP (TGBC)

320.0

DEG F

160.0

DEG C

TAH

55

TE-6141A

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBDA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

56

TE-6141B

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBDB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

57

TE-6141A/B

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBD)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

58

TE-6141A/B

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBD)

10.0

DEG F

5.6

DEG C

HD

59

TE-6141SEL

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBD)

315.0

DEG F

157.2

DEG C

TAHH

60

TE-6141SEL

TURB LUBE OIL SUMP D SCAV OIL TEMP (TGBD)

290.0

DEG F

143.3

DEG C

TAH

62

TE-6142A

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBEA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

63

TE-6142B

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBEB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

64

TE-6142A/B

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBE)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

65

TE-6142A/B

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBE)

10.0

DEG F

5.6

DEG C

HD

66

TE-6142SEL

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBE)

315.0

DEG F

157.2

DEG C

TAHH

67

TE-6142SEL

TURB LUBE OIL SUMP E SCAV OIL TEMP (TGBE)

290.0

DEG F

143.3

DEG C

TAH

69

TE-6128A

TURB LUBE OIL SUPPLY TEMP (TLUBA)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

70

TE-6128B

TURB LUBE OIL SUPPLY TEMP (TLUBB)

-65.0

1200.0

-45.0

390.0

DEG F

-53.9

648.9

-42.7

198.9

DEG C

SF

71

TE-6128A/B

TURB LUBE OIL SUPPLY TEMP (TLUB)

-45.0

390.0

DEG F

-42.7

198.9

DEG C

SF

72

TE-6128A/B

TURB LUBE OIL SUPPLY TEMP (TLUB)

10.0

DEG F

5.6

DEG C

HD

73

TE-6128SEL

TURB LUBE OIL SUPPLY TEMP (TLUB)

170.0

DEG F

76.7

DEG C

TAH

26
DEG C

SF

X
8

DM
X
DM
X

33
X
X
8

DM
X
DM
X

40
X
X
8

DM
X
DM
X

47
X
X
8

DM
X
DM
X

54
X
X
8

DM
X
DM
X

61
X
X
8

DM
X
DM
X

68

74

90.0

DEG F

32.2

DEG C

TAL

X
X
8

16

DM

TE-6128SEL

TURB LUBE OIL SUPPLY TEMP (TLUB)

XSH-68327A

FIN-FAN LUBE OIL COOLER FAN "A" HIGH VIBRATION

XAH

X
SWAP MOTOR/FAN

XSH-68327B

FIN-FAN LUBE OIL COOLER FAN "B" HIGH VIBRATION

XAH

SWAP MOTOR/FAN

OPT: FIN-FAN COOLER

XSH-68327C

FIN-FAN LUBE OIL COOLER FAN "C" HIGH VIBRATION

XAH

SWAP MOTOR/FAN

OPT: FIN-FAN COOLER & 50 HZ

MOT-6090

FIN-FAN LUBE OIL COOLER FAN (A)

MOT-6091

FIN-FAN LUBE OIL COOLER FAN (B)

OPT: FIN-FAN COOLER

MOT-6093

FIN-FAN LUBE OIL COOLER FAN (C)

OPT: FIN-FAN COOLER & 50 HZ

75
76

OPT: FIN-FAN COOLER

77
78
79
80
81
82

OPT: FIN-FAN COOLER

83
84
85
86
87
88

SOV-6185

POST SHUTDOWN COOLING AIR VALVE

MOT-6135

TURB LUBE AIR/OIL SEPARATOR

HE-6104

TURB LUBE OIL TANK HEATER

1 = OPEN VALVE

89
90
91
92

93
94

NOTES
1. ESN XN25 > 7800 RPM
2. ESN 4500 RPM < XN25 < 7800 RPM
3. HEATER THERMOSTATICALLY CONTROLLED ON AT 90 DEG F (32.2 DEG C) DECR
4. NOTE DELETED
5. NOTE DELETED
6. HEATER ON PERMISSIVE 60%
7. INTENTIONALLY BLANK
8. HIGH SELECT SENSOR VALUE IS USED. IF BOTH SENSORS ARE OUT OF RANGE THEN DM.
9. INTENTIONALLY BLANK

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


TURBINE LUBE OIL SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 4 OF 11 PAGE 6 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


TURBINE LUBE OIL SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

10.
11.
12.
13.
14.
15.
16.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) OPEN IF TE-61069 > 50 DEG F (10.0 DEG C) OR TE-60019 > 50 DEG F (10.0 DEG C)
WINTERIZED FIN FAN LUBE OIL COOLER LOUVERS (SOV-68349) CLOSE IF TE-61069 < 30 DEG F (-1.1 DEG C) AND TE-60019 < 34 DEG F (1.1 DEG C)
THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS ON IF TE-61069 > 70 DEG F (21.1 DEG C) OR TE-60019 > 70 DEG F (21.1 DEG C) AND ENGINE CRANKING OR RUNNING
THE SELECTED WINTERIZED FIN FAN LUBE OIL COOLER FAN (MOT-6090 OR MOT-6091) IS OFF IF TE-61069 < 35 DEG F (1.7 DEG C) AND TE-60019 < 35 DEG F (1.7 DEG C) OR ENGINE IS NOT CRANKING OR RUNNING
WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN ON IF TE-68347 < 175 DEG F (79.4 DEG C) AND LOUVERS ARE CLOSED.
WINTERIZED FIN FAN LUBE OIL COOLER HEATER HE-68345 WILL TURN OFF IF TE-68347 > 250 DEG F (121.1 DEG C) OR LOUVERS ARE OPEN.
XN25 > 6050 RPM

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


TURBINE LUBE OIL SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 4 OF 11 PAGE 7 OF 16

CUSTOMER: PLN

GE PACKAGED POWER, L.P.

CAUSE AND EFFECT MATRIX


FIRE SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it
is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any
written agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PSHH-6348

PROCESS DESCRIPTION

FIRE SUPPRESSANT AGENT RELEASED

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

150.0

PSIG

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

1034.2

kPaG

PAHH

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

ESN

2
3

FPP_MSD

FPP_MF

FIRE/GAS MONITOR FAILURE

AH

FPP_ALELT

ALARM L.E.L. - TURB ROOM

FIRE/GAS MONITOR SD

AHH
AH

ESN

FPP_ALELG

ALARM L.E.L. - GEN ROOM

AH

FPP_SLELT

SD L.E.L. - TURB ROOM

AHH

FPP_SLELG

SD L.E.L. - GEN ROOM

AHH

10

AE-6304A

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

11

AE-6304A

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

ASHH

13

AE-6304B

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

14

FIRE DETECTED - CONTACT CHANGES STATE ON POWER UP

ESN
ESN

9
X
ESN

12
AE-6304B

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

ASHH

16

AE-6304C

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

17

ASHH

X
ESN

15
AE-6304C

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

19

AE-6304D

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

20

AE-6304D

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

ASHH

22

AE-6304E

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

23

ASHH

X
ESN

18
X
ESN

21
AE-6304E

TURBINE ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

25

AE-6313

GENERATOR ENCLOSURE COMBUSTIBLE GAS DETECTOR

15.0

%LEL

15.0

%LEL

ASH

26

AE-6313

GENERATOR ENCLOSURE COMBUSTIBLE GAS DETECTOR

25.0

%LEL

25.0

%LEL

ASHH

28

AE-3029

TURBINE ENCLOSURE IR GAS DETECTOR

5.0

%LEL

5.0

%LEL

ASH

29

ASHH

X
ESN

24
X
ESN

27
AE-3029

TURBINE ENCLOSURE IR GAS DETECTOR

10.0

%LEL

10.0

%LEL

31

AE-3030

TURBINE ENCLOSURE IR GAS DETECTOR

5.0

%LEL

5.0

%LEL

ASH

32

AE-3030

TURBINE ENCLOSURE IR GAS DETECTOR

10.0

%LEL

10.0

%LEL

ASHH

BE-6300

TURBINE ENCLOSURE OPTICAL FLAME DETECTOR

BE-6302

TURBINE ENCLOSURE OPTICAL FLAME DETECTOR

BE-6311

GENERATOR ENCLOSURE OPTICAL FLAME DETECTOR

BE-6335

TURBINE ENCLOSURE OPTICAL FLAME DETECTOR

HS-6363

CO2 PURGE SWITCH

HS-6305

HORN SILENCE SWITCH

HS-6308

MANUAL RELEASE STATION

HS-6309

MANUAL RELEASE STATION

HS-6312

MANUAL RELEASE STATION

TS-6303

TURBINE ENCLOSURE THERMAL SPOT DETECTOR

TS-6307

GENERATOR ENCLOSURE THERMAL SPOT DETECTOR

TS-6310

GENERATOR ENCLOSURE THERMAL SPOT DETECTOR

X
ESN

30
X
ESN

33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

TS-6314

TURBINE ENCLOSURE THERMAL SPOT DETECTOR

SOV-6359

FIRE SUPPRESSANT AGENT AUTO / MANUAL RELEASE VALVE

SOV-6360

FIRE SUPPRESSANT AGENT AUTO / MANUAL RELEASE VALVE

SOV-6361

FIRE SUPPRESSANT AGENT AUTO / MANUAL RELEASE VALVE

59
60
61
62
63
64
65
66

SOV-6362

FIRE SUPPRESSANT AGENT AUTO / MANUAL RELEASE VALVE

YSA-6306

FIRE / GAS ALARM HORN

YSA-6346

FIRE / GAS ALARM HORN

YSA-6347

FIRE / GAS ALARM HORN

YSL-6301

FIRE / GAS SYSTEM BEACON LIGHT

YSL-6336

FIRE / GAS SYSTEM BEACON LIGHT

YSL-6344

FIRE / GAS SYSTEM BEACON LIGHT

YSL-6345

FIRE / GAS SYSTEM BEACON LIGHT

67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82

ZS-6364

SERVICE BALL VALVE POSITION SWITCH

PSH-63165

HIGH-CO2 DISCHARGE (UPSTREAM) TURBINE SKID

83
84
85
86

NOTES

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


FIRE SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 5 OF 11 PAGE 8 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


WATER WASH

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

LS-6543

WATER WASH TANK LEVEL CONTROL

HS-6505

WATER WASH CONTROL STATION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

23.0

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

23.0

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

LAL

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

MOT-6535 PERM

HE-6536 PERM

VALVES

COMMENTS

2
3
4
5

SOV-6540

WATER WASH PURGE AIR VALVE

MOT-6535

WATER WASH SUPPLY PUMP

1 = OPEN VALVE

HE-6536

WATER WASH TANK HEATER

SOV-6504

WATER WASH OFF-LINE SUPPLY VALVE

1 = OPEN VALVE

SOV-6516

WATER WASH ON-LINE SUPPLY VALVE

1 = OPEN VALVE

6
7
8
9

OPT: WATER WASH TANK HEATER

10
11
12
13
14
15

NOTES
1. INTENTIONALLY LEFT BLANK.
2. HEATER AND PUMP OFF IF LEVEL LOW (HEATER AND PUMP PERMISSIVE).

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


WATER WASH

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 6 OF 11 PAGE 9 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


FUEL SYSTEM

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

ZY-6201

GAS FUEL METERING VALVE POSITION DEMAND

0.0

100.0

ZE-6201

GAS FUEL METERING VALVE POSITION FEEDBACK

0.0

100.0

ZC6201_FLT

GAS FUEL METERING VALVE DRIVER FAILURE

ZC6201SDRS

SD/ RESET GAS FUEL METERING VALVE DRIVER

FC-6246

GAS FUEL FLOW RATE (SUPPLY)

PSL-6224

GAS FUEL SUPPLY LOW PRESS

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

0.0

100.0

-5.0

102.0

0.0

100.0

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

-5.0

102.0

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

OPT: GAS FUEL (SAC ONLY)


SF

OPT: GAS FUEL (SAC ONLY). USE FOR VALVE MINIMUM POSITION

OPT: GAS FUEL (SAC ONLY)


OPT: GAS FUEL (SAC ONLY). 1 = ENABLE / 0 = SHUTDOWN GAS / 1-0-1 =
RESET

5
6

0.0

345.0

-6.9

351.9

ACFM

0.0

9.8

-0.2

10.0

ACmM

SF

OPT: GAS FUEL (SAC ONLY)

kPaG

PAL

OPT: GAS FUEL (SAC OR DLE)

7
8

600.0

PSIG

4136.9

9
10

PSHH-6226

GAS FUEL SUPPLY HIGH HIGH PRESS

PT-6227

GAS FUEL SUPPLY PRESS (PGAS)

720.0

PSIG

4964.0

kPaG

PAHH

0.0

800.0

-16.0

816.0

PSIG

0.0

5515.8

-110.3

5626.1

kPaG

SF

14

TE-6232A

15
16

ES

OPT: GAS FUEL (SAC OR DLE)


OPT: GAS FUEL (SAC OR DLE)

GAS FUEL SUPPLY TEMP (TGSA)

-70.0

500.0

-65.0

380.0

DEF F

-56.7

260.0

-53.9

193.3

DEG C

SF

OPT: GAS FUEL (SAC OR DLE)

TE-6232B

GAS FUEL SUPPLY TEMP (TGSB)

-70.0

500.0

-65.0

380.0

DEF F

-56.7

260.0

-53.9

193.3

DEG C

SF

TE-6232A/B

GAS FUEL SUPPLY TEMP (TGS)

-65.0

380.0

DEG F

-53.9

193.3

DEG C

SF

17

TE-6232SEL

GAS FUEL SUPPLY TEMP (TGS)

300.0

DEG F

148.9

DEG C

TAHH

18

275.0

DEG F

135.0

DEG C

TAH

11
12
13

TE-6232SEL

GAS FUEL SUPPLY TEMP (TGS)

20

SOV-6249

GAS FUEL SHUTOFF VALVE (UPSTREAM)

21

ZS-6249

GAS FUEL SHUTOFF VALVE CLOSED (UPSTREAM)

23

SOV-6204

GAS FUEL SHUTOFF VALVE (DOWNSTREAM)

24

X
9

OPT: GAS FUEL (SAC OR DLE)

X
DM

19
OPT: GAS FUEL (SAC OR DLE). 1 = OPEN VALVE
X

OPT: GAS FUEL (SAC OR DLE)

22
ZS-6204

GAS FUEL SHUTOFF VALVE CLOSED (DOWNSTREAM)

26

SOV-6208

GAS FUEL VENT VALVE

27

ZS-6208

GAS FUEL VENT VALVE CLOSED

PT-6228

GAS FUEL MANIFOLD PRESS

SOV-62580

FLOW SAFETY VALVE-OFF-SKID TURBINE GAS FUEL BLOCK

OPT: GAS FUEL (SAC OR DLE). 1 = OPEN VALVE


X

OPT: GAS FUEL (SAC OR DLE)

25
OPT: GAS FUEL (SAC OR DLE). 1 = CLOSE VALVE
OPT: GAS FUEL (SAC ONLY)

28
33

0.0

800.0

-16.0

816.0

PSIG

0.0

5515.8

-110.3

5626.1

kPaG

SF

OPT: GAS FUEL (SAC ONLY)

34
35
36

OPT: GAS FUEL (SAC OR DLE). 1 = OPEN VALVE

ZS-62580

POSITION SWITCH - FLOW SAFETY VALVE-OFF-SKID TURBINE GAS FUEL BLOCK

OPT: GAS FUEL (SAC OR DLE)

38

SOV-62581

OPT: GAS FUEL (SAC OR DLE). 1 = CLOSE VALVE

39

ZS-62581

SOLENOID OPERATED VALVE-OFF-SKID TURBINE GAS FUEL VENT


POSITION SWITCH - SOLENOID OPERATED VALVE-OFF-SKID TURBINE GAS FUEL
VENT

37

OPT: GAS FUEL (SAC OR DLE)

40
41

PT-62582

GAS PURGE BOTTLE TEST

42

PT-62582

GAS PURGE BOTTLE TEST

43

PT-62582

GAS PURGE BOTTLE TEST

0.0

800.0

-16.0

816.0

PSIG

10.0

PSIG

0.0

5515.8

-110.3

5626.1

kPaG

68.9

kPaG

SF

PAH

12

EVENT

13

X
X

44
45

NOTES
1. 50 PSI (344.7 kPaG) START PERM.
2. 50 PSI (344.7 kPaG) TRANSFER PERM.
3. SHUTDOWN WATER INJECTION SYSTEM.
4. PUMP OFF AT 1340 PSIG (9239.0 kPaG) INC, 50 PSIG (344.7 kPaG) DEC.
5. TURN OFF NOX WATER INJECTION PUMP
6. INTENTIONALLY LEFT BLANK
7. INTENTIONALLY LEFT BLANK
8. INTENTIONALLY LEFT BLANK.
9. a. IF BOTH TGAS SENSORS ARE WITHIN RANGE LIMITS, DISPLAY THE AVERAGE OF BOTH.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN ALM AND DEFAULT TGAS TO LAST GOOD VALUE.
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A DIFFERENCE BETWEEN SENSORS GREATER THAN 10 DEG F THEN ALM & USE THE HIGHER TGAS VALUE.
d. TGAS VALUE < 20 DEG F (<-6.7 DEG C) OR > 275 DEG F (> 135.0 DEG C) = ALM
10. INTENTIONALLY LEFT BLANK.
11. AFTER INITIAL START + 15 SECONDS IF DISCHARGE PRESSURE < 100 PSIG (< 689.5 kPaG) PUMP WILL BE SHUT OFF.
12. ALARM IF UNIT SHUTDOWN AND GAS VENT VALVE OPEN
13. DURING START UP AND BOTTLE TEST, IF PT-62582 DIFFER (PT6227 - PT62582 >15PSI) FROM PT-6227, ABORT START SEQUENCE
LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


FUEL SYSTEM

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 7 OF 11 PAGE 10 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

PT-6863

INLET STATIC PRESS (P0)

0.0

16.0

8.0

16.0

PSIA

0.0

110.3

55.2

110.3

kPaA

SF

21

PT-6804

HPC DISCHARGE STATIC PRESS (PS3A)

0.0

600.0

10.0

530.0

PSIA

0.0

4136.9

68.9

3654.2

kPaA

SF

PT-6814

HPC DISCHARGE STATIC PRESS (PS3B)

0.0

600.0

10.0

530.0

PSIA

0.0

4136.9

68.9

3654.2

kPaA

PT-6804/14

HPC DISCHARGE STATIC PRESS (PS3)

10.0

530.0

PSIA

68.9

3654.2

kPaA

SF

PT-6804/14

HPC DISCHARGE STATIC PRESS (PS3)

10.0

15.0

PSIA

68.9

103.4

kPaA

HD

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

2
SF

19

DM
5

7
PT-6859A

HPC INLET TOTAL PRESS (P25A)

0.0

100.0

10.0

45.0

PSIA

0.0

689.5

68.9

310.3

kPaA

SF

PT-6859B

HPC INLET TOTAL PRESS (P25B)

0.0

100.0

10.0

45.0

PSIA

0.0

689.5

68.9

310.3

kPaA

SF

10

PT-6859A/B

HPC INLET TOTAL PRESS (P25)

10.0

45.0

PSIA

68.9

310.3

kPaA

SF

20

11

PT-6859A/B

HPC INLET TOTAL PRESS (P25)

10.0

PSIA

68.9

kPaA

HD

18

DM
X

12
13

PT-6860

LPT INLET TOTAL PRESS (P48)

0.0

150.0

10.0

140.0

PSIA

0.0

1034.2

68.9

965.3

kPaA

SF

15

15

PT-6861A

THRUST BALANCE PRESS (PTB1A)

0.0

150.0

10.0

140.0

PSIA

0.0

1034.2

68.9

965.3

kPaA

SF

16

PT-6861B

THRUST BALANCE PRESS (PTB1B)

0.0

150.0

10.0

140.0

PSIA

0.0

1034.2

68.9

965.3

kPaA

SF

17

PT-6861A/B

THRUST BALANCE PRESS (PTB1)

10.0

140.0

PSIA

965.3

kPaA

SF

20

18

PT-6861A/B

THRUST BALANCE PRESS (PTB1)

25.0

PSIA

172.4

kPaA

HD

19

PT-6861A/B

THRUST BALANCE PRESS (PTB1)

6.0

PSIA

41.4

kPaA

HD

21

SE-6800

HPC ROTOR SPEED (XN25A)

0.0

12000.0

0.0

11500.0

RPM

0.0

12000.0

-1.0

11500.0

RPM

SF

2, 3

22

SE-6801

HPC ROTOR SPEED (XN25B)

0.0

12000.0

0.0

11500.0

RPM

0.0

12000.0

-1.0

11500.0

RPM

SF

2, 3

23

SE-6800/6801

HPC ROTOR SPEED (XN25)

0.0

11500.0

RPM

-1.0

11500.0

RPM

SF

2, 3

24

SE-6800/6801

HPC ROTOR SPEED (XN25)

37.5

RPM

37.5

RPM

HD

25

SE-6800/6801SEL

HPC ROTOR SPEED (XN25)

10800.0

RPM

10800.0

RPM

SAHH

26

SE-6800/6801SEL

HPC ROTOR SPEED (XN25)

10700.0

RPM

10700.0

RPM

SAH

14

68.9

DM
0.1

DM

20
RATIO: 1 RPM = 0.74910 HZ
RATIO: 1 RPM = 0.74910 HZ
ES
X
ES
X

27
28

SE-6812

LPT ROTOR SPEED (XNSDA/LEFT)

0.0

5000.0

0.0

4800.0

RPM

0.0

5000.0

-1.0

4800.0

RPM

SF

29

SE-6813

LPT ROTOR SPEED (XNSDB/RIGHT)

0.0

5000.0

0.0

4800.0

RPM

0.0

5000.0

-1.0

4800.0

RPM

SF

30

SE-6812/6813

LPT ROTOR SPEED (XNSD)

0.0

4800.0

RPM

-1.0

4800.0

RPM

SF

31

SE-6812/6813

LPT ROTOR SPEED (XNSD)

40.0

RPM

40.0

RPM

HD

32

SE-6812/6813SEL

LPT ROTOR SPEED (XNSD)

4600.0

RPM

4600.0

RPM

SAHH

33

SE-6812/6813SEL

LPT ROTOR SPEED (XNSD)

4300.0

RPM

4300.0

RPM

SAH

TE-6821A

LPC INLET AIR TEMP (T2A)

140.0

DEG F

60.0

DEG C

SF

11

RATIO: 1 RPM = 0.800 HZ


RATIO: 1 RPM = 0.800 HZ
ES

X
ESN
ES

34
35
36

-70.0

500.0

-65.0

-56.7

260.0

-53.9

TE-6821B

LPC INLET AIR TEMP (T2B)

-70.0

500.0

-65.0

140.0

DEG F

-56.7

260.0

-53.9

60.0

DEG C

SF

11

38

TE-6837A

HPC INLET AIR TEMP (T25A)

-70.0

500.0

-65.0

320.0

DEG F

-56.7

260.0

-53.9

160.0

DEG C

SF

12

39

TE-6837B

HPC INLET AIR TEMP (T25B)

-70.0

500.0

-65.0

320.0

DEG F

-56.7

260.0

-53.9

160.0

DEG C

SF

12

41

TE-6838A

HPC DISCHARGE TEMP (T3A)

-70.0

2200.0

-65.0

1200.0

DEG F

-56.7

1204.4

-53.9

648.9

DEG C

SF

16

42

TE-6838B

HPC DISCHARGE TEMP (T3B)

-70.0

2200.0

-65.0

1200.0

DEG F

-56.7

1204.4

43

TE-6838A/B

HPC DISCHARGE TEMP (T3)

-65.0

1200.0

DEG F

44

TE-6838A/B

HPC DISCHARGE TEMP (T3)

20.0

DEG F

46

TE-6843

LPT INLET GAS TEMP (T48A/UPPER)

-70.0

2200.0

-65.0

2000.0

DEG F

-56.7

1204.4

47

TE-6844

LPT INLET GAS TEMP (T48B/UPPER)

-70.0

2200.0

-65.0

2000.0

DEG F

-56.7

1204.4

48

TE-6845

LPT INLET GAS TEMP (T48C/LOWER)

-70.0

2200.0

-65.0

2000.0

DEG F

-56.7

1204.4

49

TE-6846

LPT INLET GAS TEMP (T48D/LOWER)

-70.0

2200.0

-65.0

2000.0

DEG F

-56.7

50

TE-6847

LPT INLET GAS TEMP (T48E/LOWER)

-70.0

2200.0

-65.0

2000.0

DEG F

51

TE-6848

LPT INLET GAS TEMP (T48F/LOWER)

-70.0

2200.0

-65.0

2000.0

52

TE-6849

LPT INLET GAS TEMP (T48G/UPPER)

-70.0

2200.0

-65.0

53

TE-6850

LPT INLET GAS TEMP (T48H/UPPER)

-70.0

2200.0

54

TE-6843-50

55

37

40
-53.9

648.9

DEG C

SF

16

-53.9

648.9

DEG C

SF

30

11.1

DEG C

HD

31, 49

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

1204.4

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

-56.7

1204.4

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

DEG F

-56.7

1204.4

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

2000.0

DEG F

-56.7

1204.4

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

-65.0

2000.0

DEG F

-56.7

1204.4

-53.9

1093.3

DEG C

SF

4,6

SEE NOTE

LPT INLET GAS TEMP (T48)

-65.0

2000.0

DEG F

-53.9

1093.3

DEG C

SF

TE-6843-50

LPT INLET GAS TEMP (T48)

-65.0

2000.0

DEG F

-53.9

1093.3

DEG C

SF

56

TE-6843-50

LPT INLET GAS TEMP (T48)

-65.0

2000.0

DEG F

-53.9

1093.3

DEG C

SF

10

57

TE-6843-50

LPT INLET GAS TEMP (T48)

1000.0

DEG F

537.8

DEG C

HD

58

TE-6843-50

LPT INLET GAS TEMP (T48)

700.0

DEG F

371.1

DEG C

HD

46

59

TE-6843-50

LPT INLET GAS TEMP (T48)

135.0

DEG C

HD

59

60

TE-6843-50

LPT INLET GAS TEMP (T48)

150.0

DEG F

65.6

DEG C

HD

47

60

61

TE-6843-50

LPT INLET GAS TEMP (T48)

1850.0

DEG F

1010.0

DEG C

TAHH

ES

62

TE-6843-50

LPT INLET GAS TEMP (T48)

1750.0

DEG F

954.4

DEG C

TAH

SI

MCD-6865

TURB SUMP TGB/A MAG CHIP DET (CHPDTA)

360.0

OHMS

360.0

OHMS

SFL/SFH

45

275.0

DEG F

90

60

63
64

MCD-6865SEL

TURB SUMP TGB/A MAG CHIP DET (CHPDTA)

67

65

MCD-6866

TURB SUMP B MAGNETIC CHIP DETECTOR (CHPDTB)

68

Ohms

Ohms

Ohms

Ohms

Ohms

Ohms

-80.0

120.0

30.0
75.0

Ohms

Ohms

30.0

Ohms

Ohms

30.0

Ohms

Ohms

30.0

-80.0

120.0

OHMS

75.0

OHMS

MCDAL

OHMS

SFL/SFH

X
52

2.5

66
MCD-6866SEL

TURB SUMP B MAGNETIC CHIP DETECTOR (CHPDTB)

70

MCD-6870

TURB SUMP COM MAGNETIC CHIP DETECTOR (CHPDTC)

71

MCD-6870SEL

TURB SUMP COM MAGNETIC CHIP DETECTOR (CHPDTC)

FCV-6871

VBV ACTUATOR TORQ MOTOR

30.0

360.0

75.0

OHMS
OHMS

360.0

75.0

OHMS

MCDAL

OHMS

SFL/SFH

OHMS

MCDAL

X
52

2.5

69
30.0

360.0

75.0

OHMS
OHMS

360.0

75.0

X
52

2.5

72
73

mA

24,26

DM

74

FCV-6871

VBV ACTUATOR TORQ MOTOR

10.0

mA

10.0

mA

AH

23,28,39

75

FCV-6871

VBV ACTUATOR TORQ MOTOR

15.0

mA

15.0

mA

AHH

23,28,39

76

ZE-6871A-B

VBV LVDT EXCITATION (LEFT/RIGHT)

77

ZE-6871A1

VBVA LVDT RETURN (LEFT, SEC 1)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

78

ZE-6871A2

VBVA LVDT RETURN (LEFT, SEC 2)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

79

ZE-6871A

VBVA LVDT RETURN (LEFT)

-2.0

102.0

-2.0

102.0

SF

80

ZE-6871B1

VBVB LVDT RETURN (RIGHT, SEC 1)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

81

ZE-6871B2

VBVB LVDT RETURN (RIGHT, SEC 2)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

82

ZE-6871B

VBVB LVDT RETURN (RIGHT)

-2.0

102.0

-2.0

102.0

83

ZE-6871

VBV LVDT RETURN

-2.0

102.0

-2.0

102.0

SF

22

84

ZE-6871

VBV LVDT RETURN

9.0

9.0

HD

23,29

85

ZE-6871

VBV LVDT RETURN

10.0

10.0

HD

23,29,57

86

ZE-6871PERR

VBV POSITION/DEMAND DIFFERENCE

3.0

3.0

HD

23,25,27,28

87

ZE-6871PERR

VBV POSITION/DEMAND DIFFERENCE

10.0

10.0

HD

23,25,26

7.0

VRMS

7.0

X
DM

VRMS

SF

X
X
8, 18

8, 18

X
DM

DM

88

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 8 OF 11 PAGE 11 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

89

REV

TAG NO.

FCV-6873

PROCESS DESCRIPTION

VSV ACTUATOR TORQ MOTOR

RANGE LOW
(English)

RANGE HIGH
(English)

-80.0

120.0

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

mA

-80.0

120.0

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

SF

24,26

90

FCV-6873

VSV ACTUATOR TORQ MOTOR

10.0

mA

10.0

mA

AH

23,28,39

91

FCV-6873

VSV ACTUATOR TORQ MOTOR

15.0

mA

15.0

mA

AHH

23,28,39

92

ZE-6873A-B

VSV LVDT EXCITATION (LEFT/RIGHT)

93

ZE-6873A1

VSVA LVDT RETURN (LEFT, SEC 1)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

94

ZE-6873A2

VSVA LVDT RETURN (LEFT, SEC 2)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

95

ZE-6873A

VSVA LVDT RETURN (LEFT)

-2.0

102.0

-2.0

102.0

SF

96

ZE-6873B1

VSVB LVDT RETURN (RIGHT, SEC 1)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

97

ZE-6873B2

VSVB LVDT RETURN (RIGHT, SEC 2)

0.0

100.0

-2.0

102.0

0.0

100.0

-2.0

102.0

SF

98

7.0

VRMS

7.0

ALARM

8, 18

-2.0

102.0

-2.0

102.0

VSV LVDT RETURN

-2.0

102.0

-2.0

102.0

SF

22

VSV LVDT RETURN

3.7

3.7

HD

18,23

101

ZE-6873PERR

VSV POSITION/DEMAND DIFFERENCE

3.0

3.0

HD

23,25,27,28

10.0

HD

23,25,26

198.9

DEG C

SF

ZE-6873PERR

VSV POSITION/DEMAND DIFFERENCE

TE-68310

MTTB CABINET AIR TEMP

105

TE-68310SEL

MTTB CABINET AIR TEMP

106

TE-68310SEL

MTTB CABINET AIR TEMP

32.0

DEG F

0.0

107

TE-68310SEL

MTTB CABINET AIR TEMP

SEE NOTE

SEE NOTE

125.0

DEG F
DEG F

SEE NOTE

SEE NOTE

109

TE-68311

MGTB CABINET AIR TEMP

-45.0

390.0

DEG F

-42.7

198.9

110

TE-68311SEL

MGTB CABINET AIR TEMP

125.0

DEG F

111

TE-68311SEL

MGTB CABINET AIR TEMP

SF

VSVB LVDT RETURN (RIGHT)

104

8, 18

ZE-6873

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

VRMS

ZE-6873

DEG F

START PERM.

SI

ZE-6873B

10.0

ABORT START

DM

99

390.0

SHUT DOWN

100
102

ALM DLY (S)

SI
5
SI

103
-65.0

1200.0

-45.0

-53.9

648.9

-42.7

51.7

DEG C

TAH

DEG C

TAL

DEG C

EVENT

X
X
32

108
-65.0

1200.0

32.0

-53.9

648.9

51.7

DEG F

0.0

DEG C

SF

DEG C

TAH

DEG C

TAL

X
X

112
113

SE-6811

GEN ROTOR SPEED

114

SE-6811_ISOSEL

GEN ROTOR SPEED

116

XE-6807

117

-100.0

5100.0

0.0

5000.0

RPM

5000.0

RPM

SF

SEE NOTE

RPM

-100.0

5100.0

0.0

SEE NOTE

RPM

EVENT

60

VIBRATION ELEMENT-GENERATOR BEARING DRIVE END

3.0

MIL PP

76.2

M PP

XAH

41, 58

10

ESN

115
XE-6807

VIBRATION ELEMENT-GENERATOR BEARING DRIVE END

4.0

MIL PP

101.6

M PP

XAHH

41, 58

119

XE-6808

VIBRATION ELEMENT-GENERATOR BEARING DRIVE END

3.0

MIL PP

76.2

M PP

XAH

41, 58

120

X
SI

118
XE-6808

VIBRATION ELEMENT-GENERATOR BEARING DRIVE END

4.0

MIL PP

101.6

M PP

XAHH

41, 58

122

XE-6809

VIBRATION ELEMENT-GENERATOR BEARING NON-DRIVE END

3.0

MIL PP

76.2

M PP

XAH

41, 58

123

X
SI

121
XE-6809

VIBRATION ELEMENT-GENERATOR BEARING NON-DRIVE END

4.0

MIL PP

101.6

M PP

XAHH

41, 58

125

XE-6810

VIBRATION ELEMENT-GENERATOR BEARING NON-DRIVE END

3.0

MIL PP

76.2

M PP

XAH

41, 58

126

XE-6810

VIBRATION ELEMENT-GENERATOR BEARING NON-DRIVE END

4.0

MIL PP

101.6

M PP

XAHH

41, 58

3.0

IN/SEC PK

76.2

mm/SEC PK

XAH

44

4.0

IN/SEC PK

101.6

mm/SEC PK

XAHH

44

1.4

IN/SEC PK

35.6

mm/SEC PK

XAH

43

2.0

IN/SEC PK

50.8

mm/SEC PK

XAHH

43

2.0

IN/SEC PK

50.8

mm/SEC PK

XAH

45

X
SI

124
X
SI

127
128

XE-6876

129

XE-6876

VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER WIDEBAND/DIRECT


VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER WIDEBAND/DIRECT

X
SI

130
131

XE-6876A

132

XE-6876A

VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER-LP


COMPRESSOR
VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER-LP
COMPRESSOR

X
SI

133
134

XE-6876B

135

XE-6876B

VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER-HP


COMPRESSOR
VIBRATION ELEMENT-COMPRESSOR REAR FRAME ACCELEROMETER-HP
COMPRESSOR

3.0

IN/SEC PK

76.2

mm/SEC PK

XAHH

45

3.0

IN/SEC PK

76.2

mm/SEC PK

XAH

44

X
SI

136
XE-6877

VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETERWIDEBAND/DIRECT


VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETERWIDEBAND/DIRECT

4.0

IN/SEC PK

101.6

mm/SEC PK

XAHH

44

140

XE-6877A

VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETER-LP COMPRESSOR

1.4

IN/SEC PK

35.6

mm/SEC PK

XAH

43

141

137

XE-6877

138
139

XE-6877A

VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETER-LP COMPRESSOR

2.0

IN/SEC PK

50.8

mm/SEC PK

XAHH

43

143

XE-6877B

VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETER-HP COMPRESSOR

2.0

IN/SEC PK

50.8

mm/SEC PK

XAH

45

144

X
SI
X
SI

142
XE-6877B

VIBRATION ELEMENT-TURBINE REAR FRAME ACCELEROMETER-HP COMPRESSOR

3.0

IN/SEC PK

76.2

mm/SEC PK

XAHH

45

146

XE-6897

VIBRATION ELEMENT-GEARBOX BEARING NON-DRIVE END

0.3

IN/SEC PK

7.6

mm/SEC PK

XAH

53

147

X
SI

145
XE-6897

VIBRATION ELEMENT-GEARBOX BEARING NON-DRIVE END

0.5

IN/SEC PK

12.7

mm/SEC PK

XAHH

53

149

XE-6898

VIBRATION ELEMENT-GEARBOX BEARING DRIVE END

0.3

IN/SEC PK

7.6

mm/SEC PK

XAH

53

150

0.5

IN/SEC PK

12.7

mm/SEC PK

XAHH

53

X
SI

148
X

XE-6898

VIBRATION ELEMENT-GEARBOX BEARING DRIVE END

152

BE-6816

BURNER ELEMENT-TURBINE IGNITOR #1

SI
Control by K83

153

BE-6817

BURNER ELEMENT-TURBINE IGNITOR #2

Control by K83

151

154
155

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 8 OF 11 PAGE 12 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

NOTES
1. a. IF BOTH XNSD SPEED PICKUPS ARE WITHIN RANGE, DISPLAY THE AVERAGE SPEED OF BOTH XNSD PICKUPS.
b. ONE XNSD PICKUP OUT OF RANGE = ALM - ANNUNCIATE LOSS OF PICKUP - REMOVE FROM AVERAGE & DISPLAY THE REMAINING IN RANGE XNSD SPEED PICKUP.
BOTH XNSD PICKUPS OUT OF RANGE = ES - DEFAULT TO LAST GOOD VALUE - ANNUNCIATE LOSS OF BOTH XNSD PICKUPS.
c. A DIFFERENCE OF > 40 RPM BETWEEN XNSD PICKUPS = ALM - ANNUNCIATE DIFFERENCE BETWEEN PICKUPS & USE THE PICKUP WITH THE HIGHER VALUE.
2. a. IF BOTH XN25 SPEED PICKUPS ARE WITHIN RANGE, DISPLAY THE AVERAGE OF BOTH XN25 SPEED PICKUPS.
b. ONE XN25 PICKUP IS OUT OF RANGE = ALM - ANNUNCIATE LOSS OF PICKUP - REMOVE FROM THE AVERAGE & DISPLAY THE REMAINING IN RANGE XN25 SPEED PICKUP.
BOTH N25 PICKUPS OUT OF RANGE = ES - DEFAULT TO 2000 RPM & ANNUNCIATE LOSS OF BOTH XN25 SPEED PICKUPS.
c. A DIFFERENCE OF > 37.5 RPM BETWEEN N25 PICKUPS = ALM - ANNUNCIATE DIFFERENCE BETWEEN PICKUPS AND USE THE PICKUP WITH THE HIGHER VALUE.
3. a. FOLLOWING FUEL IGNITION, IF dXN25/DT < 10 RPM/SEC AND XN25 RPM < 6050 RPM THEN ESN ON FAIL TO ACCELERATE.
b. IF XNSD IS < 1250 RPM & XN25 CONTROL HAS BEEN ACHIEVED FOR > 60 SECONDS = ES AND ANNUNCIATE POWER TURBINE FAILED TO BREAKAWAY
c. IF XN25 IS < 1700 RPM AND > 30 SECONDS FOLLOWING INITIAL STARTER ENGAGEMENT FOR ENGINE/BOILER PURGE SEQUENCE = ESN AND ANNUNCIATE FAIL TO CRANK.
d. AFTER ENGINE/BOILER PURGE SEQUENCE, IF XN25 IS < 1700 RPM AFTER 10 SECONDS FOLLOWING THE STARTER RE-ENGAGEMENT FOR FUEL IGNITION SEQUENCE = ESN AND ANNUNCIATE FAIL TO CRANK.
e. IF XN25 < 4600 RPM > 90 SEC AFTER INITIATION OF FUEL = ES AND ANNUNCIATE FAILURE TO REACH STARTER CUTOUT.
f. IF XN25 < 6050 RPM > 120 SEC AFTER INITIATION OF FUEL = ES AND ANNUNCIATE FAILURE TO REACH XN25 IDLE.
g. IF XN25 < 300 RPM FOR > 10 MINUTES AFTER AN ES OR ESN, A 4 HOUR LOCKOUT OCCURS.
4. ALL THERMOCOUPLES THAT ARE IN RANGE WILL BECOME PART OF THE AVERAGE AND THE AVERAGE WILL BE DISPLAYED.
a. FOR SAC: IF 10 SECONDS AFTER GAS FUEL ON (1700 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
b. FOR DLE: IF 15 SECONDS AFTER GAS FUEL ON (1700 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
c. FOR SAC: IF 20 SECONDS AFTER LIQ FUEL ON (1200 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
d. FOR DLE: IF 15 SECONDS AFTER LIQ FUEL ON (1200 RPM N25) AND FLAME INDICATION IS NOT PRESENT = ES - ANNUNCIATE FAIL TO LITE
e. IF T48 AVERAGE > 400 DEG F & THEN < 400 DEG F WHILE STARTING OR RUNNING = ES AND ANNUNCIATE FLAME OUT.
f. DURING STARTING (BETWEEN 0-6050 N25 RPM) IF T48 AVERAGE > T48 BACKUP START SCHEDULE + 200 DEG F (93.3 DEG C) FOR > 3 SECONDS = ES
5. IF T48 AVERAGE > 1750 DEG F (> 954.4 DEG C) OR MORE THAN 1.0 SEC = ALM, T48 AVERAGE > 1850 DEG F (> 1010.0 DEG C) FOR MORE THAN 1.0 SECOND = ES
6. ANY THERMOCOUPLE OUT OF RANGE = ALM & REMOVE BAD THERMOCOUPLE FROM THE AVERAGE. THERMOCOUPLE CONSIDERED OUT OF RANGE IF <-65 DEG F (-53.9 DEG C) AND N25SEL <4600 RPM OR < 350 DEG F (< 176.7 DEG C) AND N25SEL =>4600 RPM AND FUEL ON OR > 1900 DEG F (> 1037.8 DEG C).
7. LOSS OF 3 ADJACENT SENSORS = ALM.
8. REMOVE BAD SENSOR FROM AVERAGE
9. LOSS OF ANY 4 SENSORS OR MORE = ALM.
10. LOSS OF THE T48 AVERAGE FOR >90 SEC = ALM. DEFAULT T48REF = 1999 DEG F (1092.8 DEG C)
11. a. IF BOTH T2 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN DM & DEFAULT T2 VALUE TO 135 DEG F (57.2 DEG C).
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 18 DEG F (10.0 DEG C) THE ALM & USE THE HIGHER VALUE.
12. a. IF BOTH T25 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM AVERAGE. IF BOTH SENSORS OUT OF RANGE THEN DM & DEFAULT T25 VALUE TO 250 DEG F (121.1 DEG C).
c. IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 18 DEG F (10.0 DEG C) THE ALM & USE THE HIGHER VALUE.
13. a. IF FLAME SENSOR = TRUE AND FUEL OFF FOR 1.0 SECOND OR IF FLAME SENSOR = FALSE AND FUEL ON AND T48SEL > 400 DEG F (> 204.4 DEG C) FOR Z_FLMTMR SECONDS THEN FAIL SENSOR AND ALM. (Z_FLMTMR = 0.320 SECONDS)
b. IF BOTH FLAME SENSORS = TRUE AND FUEL ON FOR 1.0 SECOND THEN FAIL BOTH SENSORS HIGH AND ALM
c. IF BOTH FLAME SENSORS = FALSE FOR Z_FLMTMR SECONDS AND FUEL ON AND T48SEL > 400 DEG F (> 204.4 DEG C) THEN FAIL BOTH SENSORS LOW AND ALM
d. IF BOTH FLAME SENSORS FAIL AND N25 <9200 RPM THEN INITIATE ES.
14. IF DIFFERENCE >10 PSID BETWEEN SENSORS = ALM & SELECT MODEL WEIGHTED AVERAGE.
15. P48 FAILURE PER INPUT SENSOR FAULT LOGIC TABLE IN CONTROL SPEC. P48ESTENSW = TRUE SO DM WILL NOT OCCUR.
16. a. IF BOTH T3 SENSORS ARE WITHIN RANGE LIMITS THEN USE THE AVERAGE VALUE OF PAIR.
b. IF ONE SENSOR OUT OF RANGE THEN ALM & REMOVE BAD SENSOR FROM THE AVERAGE.
17. a. IF BOTH PS3 TRANSMITTERS ARE WITHIN RANGE DISPLAY THE AVERAGE OF BOTH PS3 XMITTERS.
b. ONE TRANSMITTER OUT OF RANGE = ALARM & REMOVE THE BAD XMITTER FROM THE AVERAGE - BOTH XMITTERS OUT OF RANGE = DM FOR SAC UNIT, ES FOR DLE UNIT
c. PS3 DIFFERENCE BETWEEN XMITTERS BETWEEN 10 PSIA (68.9 kPaA) AND 15 PSIA (103.4 kPaA) FOR MORE THEN 5 SECONDS = ALARM & USE AVERAGE VALUE
d. PS3 DIFFERENCE BETWEEN XMITTERS GREATER THAN 15 PSIA (103.4 kPaA) AND FOR MORE THEN 0.1 SECONDS = ALM & SELECT HIGHER VALUE FOR SAC UNIT, ES FOR DLE UNIT
18. HIGH SIGNAL SELECT.
19. USE AVERAGE VALUE.
20. DEFAULT TO LAST GOOD VALUE.
21. DEFAULT TO 14.649 PSIA (101.0 kPaA)
22. SET TORQUE MOTOR OUTPUT TO 0 mA
23. XN25 > 4600 RPM
24. TORQUE MOTOR FAILURE WITH ALL COILS OPEN OR ANY COIL SHORT FOR > 500 mSEC
25. DIFFERENCE BETWEEN DEMAND AND POSITION
26. SET TM OUTPUT TO 0 mA
27. STEADY STATE LIMIT ERROR
28. dXN25/dT < 150 RPM/S FOR 5 SEC
29. LOW SIGNAL SELECT
30. FOR PC, IF BOTH SENSORS OUT OF RANGE THEN ALM. DERATE PS3 REFERENCE SCHEDULE AND SET T3SEL TO T3MODEL.
31. FOR PC, IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 20 DEG F (11.1 DEG C) THEN ALM & USE THE WEIGHTED AVERAGE TOWARD THE T3 MODEL.
32. MTTB COOLING OUTPUT = 1 WHEN CABINET AIR TEMP (TE-68310) > 65 DEG F (>18.3 DEG C), OUTPUT = 0 WHEN CABINET AIR TEMP < 60 DEG F (<15.6 DEG C)
MTTB HEATING OUTPUT = 1 WHEN CABINET AIR TEMP (TE-68310) < 35 DEG F (< 1.7 DEG C), OUTPUT = 0 WHEN CABINET AIR TEMP > 40 DEG F (> 4.4 DEG C)
A/C UNIT OUTSIDE FAN IS TURNED ON WHEN MTTB COOLING OUTPUT = ON
A/C UNIT INSIDE FAN IS ON ALL THE TIME.
33. INTENTIONALLY LEFT BLANK
34. INTENTIONALLY LEFT BLANK
35. INTENTIONALLY LEFT BLANK
36. INTENTIONALLY LEFT BLANK
37. INTENTIONALLY LEFT BLANK
38. INTENTIONALLY LEFT BLANKR
39. IF NULL SHIFT
40. IF ENGINE FLAME SENSOR OUTPUT > 2797 DEG F (> 1536.1 DEG C) = INDICATION OF FLAME. IF SENSOR OUTPUT < 2781 DEG F (< 1527.2 DEG C) (TUNABLE BETWEEN 2725 TO 2790 DEG F (1496.1 TO 1532.2 DEG C)) = LOSS OF FLAME.
41. IF GENERATOR ROTOR LEVEL > 3.0 MIL PP ( > 76.2 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 1 SEC = ALM. IF GENERATOR ROTOR LEVEL > 4.0 MIL PP (> 101.6 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 0.1 SEC = SI
42. IF XNSD SPEED >= 3000 RPM AND < 3590 3N25REF <N25MAX, LP ROTOR LEVEL > 1.75 IN/SEC PK (> 44.45 mm/SEC PK) FOR MORE THAN 1.0 SEC = ALM. IF LP ROTOR LEVEL > 2.5 IN/SEC PK (> 63.5 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
43. IF LP ROTOR LEVEL > 1.4 IN/SEC PK (> 35.56 mm/SEC PK) FOR MORE THAN 1.0 SEC (25 TO 80HZ) = ALM. IF LP ROTOR LEVEL > 2.0 IN/SEC PK (> 50.8 mm/SEC PK) FOR MORE THAN 0.1 SEC (25 TO 80 HZ) = SI
44. IF CRF OR WIDEBAND > 3.0 IN/SEC PK (76.2 mm/SEC PK) FOR MORE THAN 1.0 SEC = ALM. IF CRF OR WIDEBAND > 4.0 IN/SEC PK (101.6 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
45. IF HP ROTOR LEVEL > 2.0 IN/SEC PK (> 50.8 mm/SEC PK) FOR MORE THAN 1.0 SEC (100 TO 200 HZ) = ALM. IF HP ROTOR LEVEL > 3.0 IN/SEC PK (> 76.2 mm/SEC PK) FOR MORE THAN 0.1 SEC (100 TO 200 HZ) = SI
46. FOR DLE: IF (N25SEL > N25IDL - 100) AND THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 700 DEG F(371.1 DEG C) FOR 60 SEC = ALARM
47. FOR DLE: IF BURNER MODE 15 AND THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 150 DEG F (65.6 DEG C) FOR 60 SEC = ALARM
48. INTENTIONALLY LEFT BLANK
49. FOR PD/PF, IF BOTH SENSORS ARE IN RANGE BUT HAVE A VALUE DIFFERENCE GREATER THAN 20 DEG F (11.1 DEG C) AND XN25 > 4600 RPM THEN ALM AND SELECT HIGHER VALUE
50. INTENTIONALLY LEFT BLANK
51. INTENTIONALLY LEFT BLANK
52. CHIP DETECTORS ALARM WHEN < 100 OHMS. INPUT BLOCK HAS 301 OHM ELEVATOR TIED ACROSS INPUTS. 100 OHMS PARALLELED WITH 301 OHM => 75.06 OHMS
53. IF GEARBOX SHAFT LEVEL > 0.3 IN/SEC PK ( > 7.62 mm/SEC PK) FOR MORE THAN 1 SEC = ALM. IF GEARBOX SHAFT LEVEL > 0.5 IN/SEC PK (> 12.7 mm/SEC PK) FOR MORE THAN 0.1 SEC = SI
54. ALARM AND BLOCK TURBINE CRANK IF EITHER THE A OR B POSITION SENSORS OF A BRAKE ELEMENT DOES NOT MATCH THE OPEN/CLOSE BRAKE COMMAND WITHIN 5 SECONDS.
55. ESN IF BOTH A AND B POSITION SENSORS OF A BRAKE ELEMENT DO NOT MATCH THE OPEN/CLOSE BRAKE COMMAND WITHIN 5 SECONDS.
56. a. IF CLUTCH VIBRATION LEVEL > 0.4 IN/SEC PK (10.2 mm/SEC PK) FOR MORE THAN 1.0 SEC= ALM
b. IF CLUTCH VIBRATION LEVEL > 0.6 IN/SEC PK (15.2 mm/SEC PK) FOR MORE THAN 2.0 SEC= SI WHEN NOT SYNCH CONDENSING, OR ESN WHEN SYNCH CONDENSING.
c. IF CLUTCH VIBRATION LEVEL > 0.8 IN/SEC PK (20.3 mm/SEC PK) FOR MORE THAN 0.1 SEC= SI WHEN NOT SYNCH CONDENSING, OR ESN WHEN SYNCH CONDENSING.
57. ALM
58. WHEN TM ACTIVE (1000 TO 2890 RPM FOR 50HZ, 1000 TO 3450 RPM FOR 60HZ): IF GENERATOR ROTOR LEVEL > 4.5 MIL PP ( > 114.3 M PP) FOR ANY DRIVE END X OR Y FOR MORE THAN 2.0 SEC = ALM. IF GENERATOR ROTOR LEVEL > 6.0 MIL PP (> 152.4 M PP) FOR DRIVE END X OR Y FOR MORE THAN 1.0 SEC = SI
59. a. FOR SAC: IF XN25R IS > 8080 RPM AND ANY THERMOCOUPLE OUTSIDE THE SPREAD (T48MAX - T48MIN) OF 275 DEG F (135 DEG C) FOR > 2 SEC = ALM
b. ANY THERMOCOUPLE WITH A DIFFERENCE OF <- 1000 OR > 1000 DEG F (<- 537.8 OR > 537.8 DEG C) FROM THE AVERAGE = ALM & SHALL BE REMOVED FROM THE AVERAGE
60. IF ABSOLUTE VALUE OF((XNSD LPT SPEED / 1.209) - GEN ROTOR SPEED) IS > 50 RPM FOR 10.0 SEC THEN ESN

DATE:
07/18/11-ATFL

LEGEND
1. SEE LEGEND TAB

38
39

A
B
B

REVISION LIST
ORIGINAL ISSUE
TE-6837A
TE-6837B

HPC INLET AIR TEMP (T25A)


HPC INLET AIR TEMP (T25B)

-70.0
-70.0

500.0
500.0

-65.0
-65.0

250.0
250.0

DEG F
DEG F

-56.7
-56.7

260.0
260.0

-53.9
-53.9

121.0
121.0

DEG C
DEG C

SF
SF

12
12

X
X

05/16/12-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


AUXILIARY SYSTEMS

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 8 OF 11 PAGE 13 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


MISCELLANEOUS

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

86G

GEN 86 TRIP

A15

FUEL SYSTEM INITIALIZE

A17

GEN ZERO SPEED SWITCH

AVR_SC

LOWER VOLTAGE BY CUSTOMER SERIAL REMOTE

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

ES

2
AT FUEL INITIATION, ACTIVATE FOR 1 SECOND.
1 = 0 RPM. POWER UP CHANGES RELAY

5
6

ONLY ACTIVE WHEN IN REMOTE CONTROL (PULSE OUT). OPTIONAL

13

AVR_RV

AVR EXCITATION ON

AVR_LV

RAISE VOLTAGE BY CUSTOMER SERIAL REMOTE

WX

GEN MW SIGNAL

11

BVX

BUS VOLTAGE (52G SYNCH)

12

BFX

BUS FREQUENCY (52G SYNCH)

13

GVX

GEN VOLTAGE

14

BVX1

BUS VOLTAGE (52U SYNCH)

15

BFX1

BUS FREQUENCY (52U SYNCH)

16

BVX2

UTILITY VOLTAGE

17

BFX2

UTILITY FREQUENCY

19

CHG_24VLO

LOW BATTERY VOLTAGE (24VDC)

20

CHG_ACF

BATTERY CHARGERS FAILURE - AC

21

CHG_DCF

BATTERY CHARGERS FAILURE - DC

22

CHG_GF

BATTERY CHARGERS GROUND FAULT

23

CHG_LO125

LOW BATTERY VOLTAGE (125VDC)

NSD

24

K1_VALVE

SHUTDOWN FUEL AND NOX SUPPRESSION

ESN

25

K1_SHUTDWN

CRITICAL PATH SHUTDOWN

ESN

26

ONLY ACTIVE WHEN IN REMOTE CONTROL (PULSE OUT). OPTIONAL

8
9

4-20 mA = 0-60 MW

10
50 Hz: 4-20 mA = 0-15 kVAC
50 Hz: 4-20 mA = 45-55 Hz
50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 45-55 Hz
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 0-15 kVAC
OPT: UTILITY BREAKER SYNCH. 50 Hz: 4-20 mA = 45-55 Hz

18
DM

SUMMARY_SD

SUMMARY CRITICAL SHUTDOWN

28

DSM_LA

LOWER XNSD SPEED

29

DSM_RA

RAISE XNSD SPEED

ES3

LOCAL EMERGENCY STOP

ESN

ES1_2_10_3

REMOTE EMERGENCY STOP

ESN

HORN

HORN

37

IGPS_52GT

IGPS 52G TRIP

38

IGPS_FA

IGPS FAULT ALARM

39

IGPS_MF

IGPS FAILURE

40

IGPS_PSA

IGPS POWER SUPPLY ALARM

42

K229

GEN BREAKER CLOSED

43

K230

GEN BREAKER OPEN

44

K231

BUS/UTILITY BREAKER CLOSED

45

K232

BUS/UTILITY BREAKER OPEN

46

K28

SYNCHRONIZER ENABLE

47

K5_K115

SYSTEM RESET (VIB/ESD BUS)

48

K230_K232

ISOCH/DROOP CONTROL

49

K85_K85A

CIRCUIT BREAKER CONTROL

50

LRS

LOCAL/ REMOTE CONTROL SELECTION

OPT: 125VDC BATTERY

27
ONLY ACTIVE WHEN DSM ENABLED
ONLY ACTIVE WHEN DSM ENABLED

30
31
32
33

ESTR-1,2,10/ESGR3

34
35
36

NSD
X

41
1 = CLOSED, 0 = OPEN

1 = ISOC, 0 = DROOP
1 = BREAKER CLOSE PERMISSIVE, 0 = TRIP BREAKER
1 = REMOTE, 0 = LOCAL

51
52

DC_STRTR1

53

MCC_DEV27

LOSS OF MCC POWER SUPPLY

54

CUST_DCLOS

LOSS OF DC POWER ON SYSTEM (CUSTOMER)

GEN/GB EMERGENCY DC LUBE OIL PUMP CNTRL IN AUTO

X
X

55

RGF

GEN ROTOR GROUND FAULT

56

SS_K100-102

AUTO/MANUAL SYNC

57

SSW1_2

58

TSS_STOP

LOCAL NORMAL STOP

59

TSS_START

LOCAL START

ESN

OPT: 50 Hz. MOT-0034

ESN
OPTIONAL
1 = AUTO, 0 = MANUAL. K102 USED FOR UTILITY SYNCH OPTION ONLY

TURB EXTERNAL OVERSPEED

ESN

60
61

VIB_MON_HP

62

VIB_MON_LP

INHIBIT VIB MON BELOW LP IDLE

63

VIB_MON_TM

VIBRATION SYSTEM TRIP MULTIPLY

INHIBIT VIB MON BELOW HP IDLE

64

VIB_SYS_MF

VIBRATION SYSTEM MALFUNCTION

65

VIB_SYS_SA

VIBRATION SUMMARY ALARM

66

VIB_SYS_SD

VIBRATION SUMMARY SHUTDOWN

ACTIVATE => 1000 XNSD SPEED < 3590 & N25SEL < N25MAX

SI

67
68

NOTES
1. IF UNIT IS RUNNING: OUTPUT = 1 AND LATCH, WHEN XNSD > 3060 RPM. OUTPUT = 0 AND UNLATCH, WHEN XNSD SPEED < 3240 RPM IF ESN OR ES OR STOPPING AND GENERATOR BREAKER OPEN. OUTPUT = 1 IF SYNCHRONOUS CONDENSER MODE ACTIVE.

LEGEND
1. SEE LEGEND TAB
DATE:
07/18/11-ATFL

REVISION LIST
A

ORIGINAL ISSUE

NO CHANGES THIS SHEET

05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


MISCELLANEOUS

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 9 OF 11 PAGE 14 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN

CAUSE AND EFFECT MATRIX


CUSTOMER INTERFACE

SITE: Palembang, South Sumatra, Indonesia

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict
confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is
loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written
agreement or purchase order that incorporates or relates to this drawing.

LM6000 MICRONET CONTROL

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW
(English)

RANGE HIGH
(English)

LIMIT DECR
(English)

LIMIT INCR
(English)

ENGLISH UNIT

RANGE LOW
(Metric)

RANGE HIGH
(Metric)

LIMIT DECR
(Metric)

LIMIT INCR
(Metric)

METRIC UNIT

ACTION

NOTE

ALARM

ALM DLY (S)

SHUT DOWN

ABORT START

START PERM.

CRANK PERM.

MOTORS

HEATERS

VALVES

COMMENTS

3
4

SAS_CUST_R

RAISE XNSD SPEED (MANUAL)

INHIBITED WHEN DSM ENABLED

SAS_CUST_L

LOWER XNSD SPEED (MANUAL)

INHIBITED WHEN DSM ENABLED

CUST_SCLK

SYNC CONTROL CLOCK (CUSTOMER)

CHW_STPERM

PERMISSIVE START (CUSTOMER)

10

CHW_RESET

RESET (AL / NLO SD ONLY) (CUSTOMER)

11

CHW_86TRIP

86 TRIP (CUSTOMER)

12

BUT_86TRIP

BUS/UTILITY 86 TRIP (CUSTOMER)

6
7

OPTIONAL

8
OPTIONAL
OPTIONAL
ES
X

OPTIONAL

13

GEN_BKR_FL

GEN BREAKER FAILURE (CUSTOMER)

14

CHW_R_STRT

REMOTE START (CUSTOMER)

ES

CUSTOMER'S ZONE CLEAR SIGNAL. OPTIONAL


OPTIONAL

15

CHW_R_STP

REMOTE NORMAL STOP (CUSTOMER)

OPTIONAL

16

CHW_ACK

ALARM ACKNOWLEDGE (CUSTOMER)

18

CUST_T2

TURBINE INLET TEMP (T2 AVERAGE)

-40.0

120.0

-40.0

48.9

OPTIONAL

19

CUST_T1

AIR FILTER INLET TEMP (T1)

-40.0

120.0

-40.0

48.9

OPTIONAL

CUST_SD

TURB-GEN SUMMARY SHUTDOWN (CUSTOMER)

OPTIONAL

17

20
21

OPTIONAL

22
23

NOTES

LEGEND
1. SEE LEGEND TAB

A
B

REVISION LIST
ORIGINAL ISSUE
ROWS 1 AND 2 REMOVED

DATE:
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


CUSTOMER INTERFACE

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 10 OF 11 PAGE 15 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: PLN
SITE: Palembang, South Sumatra, Indonesia

CAUSE AND EFFECT MATRIX


LEGEND

LM6000 MICRONET CONTROL

LINE

Copyright 2011
GE Packaged Power, L.P.
All rights reserved.
This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict confidence with the
understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned
on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this
drawing.

REV

SHUTDOWN / CONTROL ACTION

THE FOLLOWING ALARM AND SHUTDOWN TYPES GIVE BOTH AUDIO AND VISUAL INDICATION OF A FAULT CONDITION ON THE TURBINE CONTROL PANEL
(Old Naming Convention Shown In Parenthesis)

3
4
5

ALM (ALARM) - ALM-NS


This gives an audio and visual indication of a fault condition only. This is not a shutdown condition.
Some ALMs are classified as an NS (No-Start) alarm. An NS alarm allows the unit to continue running.
However, once the unit is stopped, the NS alarm condition must be reset before the unit can be started again.

6
7
8
9
10

ESN (FSLO) - Emergency Stop No motoring (Fast Stop Lock-Out)


Immediately shutdown the unit by shutting off fuel, water / steam and trip the breaker.
When N25 (HP shaft) coasts down below 300 RPM and if the T48 temperature is above 1150 degrees F (621 degrees C) then a 4-hour lockout will be initiated after a 10 minute delay.
The 4-hour lockout can be avoided if the ESN condition can be reset and a turbine crank initiated within the 10 minute delay period.
A 15 minute crank cycle must complete to reset the 10 minute delay timer.
If the crank cycle is interrupted, causing N25 to coast below 300 RPM, and if the high T48 temperature persists, then a 4-hour lockout period is initiated.

11
12
13
14
15
16
17

ES (FSWM) - Emergency Stop (Fast Stop With Motoring)


Immediately shutdown the unit by shutting off fuel, water / steam and trip the breaker.
When N25 (HP shaft) coasts down to 1700 RPM, engage starter and crank for 15 minutes.

18
19
20
21

SI (SDTI) - Step to Idle (Step Decel To Idle)


Immediately step the megawatt load to minimum. The breaker will open upon minimum load.
If the SI condition cannot be reset within 10 seconds then a normal stop without motoring occurs.

22
23
24
25

DM (SML) - Decelerate to Minimum load (Slow to Minimum Load)


Fast load shed within 20 seconds (Decel rate at 9 RPM/Sec). If the DM condition cannot be reset within 5 minutes then an NSD occurs.

26
27
28

NSD (CDLO) - Normal ShutDown (CoolDown LockOut)


Shed load and water / steam at the normal stop rate of 0.75 RPM/Sec. Open breaker when minimum load is achieved.
Idle at synchronous speed for 5 minutes maximum to cool down unit and then shut off fuel, water / steam.
When N25 (HP shaft) coasts down to 1700 RPM, engage starter and crank for 15 minutes.
If the NSD condition can be reset within the shutdown period, then the NSD shutdown is aborted.

29
30
31
32
33
34
35
36

ACTION ABBREVIATIONS

37

AL - Alarm Low
ALL - Alarm Low Low
AH - Alarm High
AHH - Alarm High High
HD - High Difference
SFL/SFH - Signal Fail Low / Signal Fail High

38
39
40
41
42
43
44

A
B

REVISION LIST
ORIGINAL ISSUE
NO CHANGES THIS SHEET

DATE
07/18/11-ATFL
05/16/12-ATFL

====== END ======

ORIGINATED: 07/18/11
PRINTED: 7/5/2012 1:56 PM
REV DATE: 05/16/05/16/05/16/12

CAUSE AND EFFECT MATRIX


LEGEND

DRAWING NO: 7236887-730149


REV: B
EC: 96647
SHEET 11 OF 11 PAGE 16 OF 16