ABB AG

RTU560
Remote Terminal Unit
Data Sheet
Power Supply 560PSU01
Characteristics

Application

The power supply unit 560PSU01 has the following characteristics and functions:

The power supply unit 560PSU01 generates


the two supply voltages ( 5 V DC and 24 V
DC ) for the RTU560 communication units
within
the
communication
subrack
560CSR01. The output power is sufficient to
supply
the
communication
subrack
560CSR01 with typical configurations.
It is possible to configure redundant power
supplies for project configurations with higher
requirements to availability. In this configuration two power supply units 560PSU01 are
operating in parallel mode. They are able to
take over the full load, if one power supply
fails.
The power supply unit 560PSU01 is available in two versions (Rubrik) for different input voltage ranges:

R0001: Input Range 24 ... 60 V DC

R0002: Input Range 110220 VDC

Potential isolation between the input and


the outputs

Cooling by natural convection

Electronic power limitation

Short-circuit proof

Over-voltage protection

Controlled load balancing

2 light emitting diodes for displaying output voltage U1 and U2

Parallel operation with monitoring of redundant power supply configuration

Alarm indication (relay) in case of failure

S1
F1
+Ue

-Ue
PE

ALARM

+U1
5 VDC
-U1

+U2
24 VDC
-U2

Doc-No.: 1KGT 150 416 V002 1

ABB AG
Data Sheet Power Supply 560PSU01

RTU560

Technical Data
In addition to the RTU560 general technical data,
the following applies:

Input
R0001

R0002

Mechanical Layout
24 to 60 V DC nominal
19,2 69 V DC
(-20 +15 %)
110 to 220 V DC nominal
88 253 V DC
(-20 +15 %)

Voltage Interruption

50 ms; 0 % UN (no failure)

Starting Current:

10 A
according IEC 60870-4
F1 = 3.15 A T
62 %

Fuse
Efficiency:

PCB dimension
Front panel
Weight

Connection Type
Connector

Indirect, 48-pole
Type F DIN 41612

Supply
connection

Indirect, 3-pole,
COMBICON terminal connection
GMSTB 2,5/3-ST-7,62 or
GMVSTBR 2,5/3-ST-7,62

Output
Output Power
De-rating

44.3 W total
-2,5 % per Kelvin
50 Grad C

Output U1
Voltage:

5,0 V DC

Tolerance:

5,0 ... 5,3 V DC

Current min.:

0.2 A

Current max.:

5.5 A

Residual Ripple

30 mVss

Output U2

3HE, Euro-Card format


(160 x 100 mm)
8R, 2 Slots (40 mm)
Ca. 0,6 kg

Environmental Conditions
Temperature

0 ... 70 C

Rel. Humidity

5 ... 95 %
(non condensing)

Ordering Information
Front panel
560PSU01 R0001
560PSU01 R0002

Metal light beige


1KGT 006 600 R0001
1KGT 006 600 R0002

ABB AG
Power Technologies Division
Power Technology Systems

Voltage:

24 V DC

Tolerance:

22,4 ... 26,3 V DC

Current min.:

0A

Kallstadter Str. 1, D-68309 Mannheim


Telephone
+49 (0) 621 381 7592
Fax
+49 (0) 621 381 7622

Current max.:

0,7 A

www.abb.de/pt

Residual Ripple

80 mVss