JAZAN REFINERY AND TERMINAL PROJECT

TR PROJECT NO.

UNIT
02220

J20

PURCHASE ORDER NUMBER

EQUIPMENT
0222001010T153

J20-GM-1101A/B /J20-GM-2101A/B

REVIEW RESPONSE BY CONTRACTOR:


Purchaser review and comments do not indicate either responsibility or liability for accuracy and completeness of this document or alter any contractual terms
and conditions:
REJECTED

REVIEWED WITH
COMMENTS

REVIEWED WITHOUT
COMMENTS

COMMENTS AS
NOTED

REVIEWED AS
BUILT

FOR INFORMATION
DATE:

16/JUL/2015

TITLE : MOTOR DATASHEET

JAZAN
VENDOR IDENTIFICATION:

SAUDI ARABIA
TR-Tecnical

SUBVENDOR IDENTIFICATION:

Vendor ID : 10029031
Plant ID: 30006786
VENDOR DOCUMENT NUMBER:

REVISION

12

J20-0399905030-30
VDDR Code:

NMR Code:
HDD-0010

TRJ DOCUMENT NUMBER: V-02220-J20-GM-1101A-0001

601
REVISION: B
C

Thursday, June 04, 2015


Technical Data Center
PO Box 12118
Fort Wayne, IN 46862

Customer:

ITT GOULDS PUMPS CO., LT


35 OKSANSANDAN-RO, OKSAN
HEUNGDEOK-GU
CHEONGJU-SI CHUNGBUK, KR 3633912

DataPack Document, Version: v14129223.03

Customer Order / Item:


Customer Part:
MODEL NUMBER:
Outline Drawing:
Connection Diagram:
Instruction Book:
Design Code:
Type:
Frame:
Phases:
Poles:
Output Power:
RPM:
Voltage:
Hertz:
Amps - FL:
Service Factor:

Sales Order No:

21400717

Order Line No:

None
5KS284XAA2014
4002B5828PAP5597
GEM2034E-FIG7
GEI-56128
28BD1129A
KS
284T
3
4
25 (18.6 KW)
1775
460
60
28.9
1.00

Estimated Weight:
Time Rating:
Enclosure:
Encl Construction:
Ambient Max(C):
Insulation Class:
NEMA Design:
Nominal Efficiency:
Guaranteed Efficiency:
KVA Code:
Max KVAR:
Power Factor:
Bearing - DE:
Bearing - ODE:

5200016067
4.1
460 Lbs
CONT
TEFC
841
50
H
B
93.6%
93.0%
G
6.7
86.5
6310ZC3
6310ZC3

Enclosure is Totally Enclosed Fan-Cooled

Stamped Nameplate Notes:


IEEE-STD-841-2009
DE BRG 50BC03XP3 ODE BRG 50BC03XP3
INVERTER DUTY PER NEMA MG1 PART 31
ALTERNATE RATING FOR PWM CONTROL:1.0SF 50C AMBIENT
VAR TORQUE RANGE 0-60 HZ
STAMP NP249A5499AJ AS BELOW:
MODEL:5KS284XAA2014
S/N: XXX
EX NA IIC T3 GC IECEX CSA.09.0012
CLASS I, ZONE 2, AEX NA IIC T3
-25C <= TAMB <= 50C
Additional Information:
4P - T EXTN
STANDARD FLOOR MOUNT
C/BOX 137 CU IN-1.50 NPT & 0.5 NPT WITH TERMINAL BOARD
F1 CONDUIT BOX MOUNTING
PAINTED FRAME ID & SHAFT,
FAN COVER INSIDE & ODE E/S OUTSIDE
ROUTINE AND 5 POINT VIBRATION TESTS INCL IN C/BOX
INPRO SEAL BOTH ENDS
E/SHLD GROUND STUD MTD ON DE C/BOX SIDE NEAR FOOT
SHAFT RUNOUT LIMIT .0015" TIR
Visit us: www.gemotors.com
Page 2 of 7

Thursday, June 04, 2015


Technical Data Center
PO Box 12118
Fort Wayne, IN 46862

Customer:

ITT GOULDS PUMPS CO., LT


35 OKSANSANDAN-RO, OKSAN
HEUNGDEOK-GU
CHEONGJU-SI CHUNGBUK, KR 3633912

DataPack Document, Version: v14129223.03

COPPER WASHER UNDER HEADS OF BEARING CAP BOLTS


APPLY TITE-SEAL (A50CD427A) ON BEARING CAP SCREWS, RABBETS,
AND PLUG THREADS
OIL RESISTANT SLEEVING ON LEADS
ESTIMATED AVG SOUND POWER 75.1 DBA
LRA <650% FLA
ARAMCO/YERP APCS#1B - RAL 6021 PALE GREEN
MOTOR FULL LOAD SLIP: 0.01388
STARTING TIME AT 80% VOLTAGE: 64 SEC WITH MAX INERTIA
OF 467 LB-FT2 WHERE THE LOAD TORQUE VARIES WITH THE
SQUARE OF THE SPEED
CONDUIT BOXES ARE SUITABLE TO IP66 DEGREE OF PROTECTION

Visit us: www.gemotors.com


Page 3 of 7