JOB ORDER/EWO NO.

1. FOR LEGEND AND MATERIAL LIST SEE


SHEET OO1

PLANT NO.

J DB-950106
INDEX

DRAWING NUMBER

LOCAL CONTROL STATION


(SEE NOTE 1)
3

ESD

HART MULTIPLEXER
ESD SYSTEM
EXTERNAL TERMINATION
ASSEMBLY
6
24VDC ESD
OUTPUT
4-20MA
ESD
OUTPUT

RS485/232
NETWORK

SMART VALVE
POSITIONER

7
REMOTE WORKSTATION W/
SMART VALVE SOFTWARE
(SEE NOTE 6)

(SEE NOTE 7)

SOV

SOV

ESD HART
HAND HELD

OPEN

CLOSE

(SEE NOTE 1)
INSTRUMENT
AIR SUPPLY

MAIN ZV

SMART ZV ESD I/O REQUIREMENTS


QUANTITY

SIGNAL TYPE

DESCRIPTION

ANALOG (4-20 mA) OUTPUT

ESD OUTPUT TO THE SMART VALVE POSITIONER.


NOTE: CONFIGURE 4 mA VALVE CLOSED AND 20 mA VALVE
OPEN FOR NORMALLY ENERGIZED (FAIL CLOSED) SYSTEM.
CONFIGURE 4 mA VALVE OPEN AND 20 mA VALVE CLOSED
FOR NORMALLY DE-ENERGIZED (FAIL OPEN) SYSTEM.

SCALE:

NONE

ZV "OPEN" LIMIT SWITCH (MOUNTED ON SMART VALVE


POSITIONER MOUNTING KIT)
ZV "CLOSED" LIMIT SWITCH (MOUNTED ON SMART VALVE
POSITIONER MOUNTING KIT)
4

DISCRETE INPUTS

VALVE "OPEN" PUSH BUTTON ON LOCAL ZV CONTROL STATION.


NOTE: LOGIC INTERNAL TO THE ESD SYSTEM PREVENTS THE
ZV FROM BEING RE-OPENED FOLLOWING A TRIP UNTIL ALL
PERMISSIVES ARE MET AND THE "READY-TO-OPEN" LIGHT IS
ENERGIZED.

REV.
NO.

JO/EWO

ENGG.

DESCRIPTION

DESIGN CERTIFICATION
AIR
DRAWN BY

CERT.

PMT

OPRNS.

DESIGN
REVIEW FOR
CERTIFICATION KEY DRAWINGS

UNTIL CERTIFIED AND DATED.

CHECKED BY
DATE COMPLETED

DATE STARTED

JUNE 2000

DISCIPLINE ENGINEER

SOLENOID VALVE MOUNTED BETWEEN SMART VALVE POSITIONER


AND VALVE ACTUATOR.
DISCRETE OUTPUTS

DATE

THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION

VALVE "CLOSE" PUSH BUTTON ON LOCAL ZV CONTROL STATION.

REPLACED ELECT. ELEM. DIAG.


WITH SMART ZV I/O TABLE

01 APR02

PROJECT ENGINEER

NOTE: ONE SOV IS REQUIRED FOR SPRING RETURN AND TWO


ARE REQUIRED FOR DOUBLE ACTING ACTUATORS.
"READY TO OPEN" LIGHT ON LOCAL ZV CONTROL STATION.

CERTIFIED BY:

THIS DRAWING IS NOT TO BE


USED FOR CONSTRUCTION

(NAME)

UNTIL CERTIFIED AND DATED.

SAUDI

SIGNATURE

DATE

ARABIAN OIL COMPANY

REVIEW FOR KEY DRAWINGS

REQUIRED

NOT REQUIRED

CONSTRUCTION AGENCY
OPERATIONS
OTHER

SMART ZV
DOUBLE ACTING ACTUATORS

PLANT NO.

INDEX

M88 J

IDT

SAUDI ARABIA

LIB. DWG.
JOB ORDER/EWO NO.

DRAWING TYPE

DRAWING NUMBER

SHT. NO.

DB-950106

REV. NO.

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO.NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

M88

NOTES:

002 01

Saudi Aramco 2634 ENG. (07/93)

VECTOR
CopyrightSaudi Aramco 2009. All rights reserved.

CADD-03

002 01
SHT. NO.

REV. NO.