School 1 System Design

You might also like

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 1

Air System Sizing Summary for school chiller

Project Name: school dubai


Prepared by: al

05-29-2015
12:26PM

Air System Information


Air System Name ................................... school chiller
Equipment Class ............................................ CW AHU
Air System Type ..................................................... VAV

Number of zones ............................................................. 6


Floor Area ............................................................... 4752.0 ft
Location ............................ Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ............................ Peak zone sensible load
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load .......................................................... 40.8
Total coil load ....................................................... 489.9
Sensible coil load ................................................. 279.7
Coil CFM at Jun 1500 ........................................... 6922
Max block CFM at Aug 1700 ................................. 7915
Sum of peak zone CFM ........................................ 7921
Sensible heat ratio ............................................... 0.571
ft/Ton .................................................................... 116.4
BTU/(hr-ft) ........................................................... 103.1
Water flow @ 10.0 F rise .................................... 98.02

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................... Jun 1500


OA DB / WB .................................................... 114.0 / 85.0
Entering DB / WB ............................................. 82.5 / 69.6
Leaving DB / WB .............................................. 45.1 / 44.6
Coil ADP ..................................................................... 40.9
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 60
Design supply temp. ................................................... 55.0
Zone T-stat Check .................................................... 6 of 6
Max zone temperature deviation .................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ........................................................ 107.8
Coil CFM at Dec 0800 ........................................... 4316
Max coil CFM ........................................................ 7915
Water flow @ 20.0 F drop ................................... 10.79

MBH
CFM
CFM
gpm

Load occurs at ................................................... Dec 0800


BTU/(hr-ft) ................................................................. 22.7
Ent. DB / Lvg DB .............................................. 31.5 / 54.6 F

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max CFM at Aug 1700 ............................... 7915 CFM
Standard CFM ....................................................... 7911 CFM
Actual max CFM/ft ................................................ 1.67 CFM/ft

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW ............................................................. 0.00 kW
Fan static .................................................................... 0.00 in wg
CFM/person ................................................................ 6.87 CFM/person

Design airflow CFM ............................................... 1648 CFM


CFM/ft ................................................................... 0.35 CFM/ft

Hourly Analysis Program v4.50

Page 1 of 1

You might also like