This document summarizes the air system sizing for a school chiller in Dubai, United Arab Emirates. It includes details on the 6 zones covering 4,752 square feet. The central cooling coil is designed to handle a total load of 489.9 MBH with a sensible load of 279.7 MBH at a flow of 98.02 gpm and supply air temperature of 55 degrees Fahrenheit. The central heating coil is sized for a maximum load of 107.8 MBH at a flow of 10.79 gpm. The supply fan is designed for a maximum flow of 7,915 CFM. Outdoor air ventilation is set at 1,648 CFM or 0.35 CFM per square foot
This document summarizes the air system sizing for a school chiller in Dubai, United Arab Emirates. It includes details on the 6 zones covering 4,752 square feet. The central cooling coil is designed to handle a total load of 489.9 MBH with a sensible load of 279.7 MBH at a flow of 98.02 gpm and supply air temperature of 55 degrees Fahrenheit. The central heating coil is sized for a maximum load of 107.8 MBH at a flow of 10.79 gpm. The supply fan is designed for a maximum flow of 7,915 CFM. Outdoor air ventilation is set at 1,648 CFM or 0.35 CFM per square foot
This document summarizes the air system sizing for a school chiller in Dubai, United Arab Emirates. It includes details on the 6 zones covering 4,752 square feet. The central cooling coil is designed to handle a total load of 489.9 MBH with a sensible load of 279.7 MBH at a flow of 98.02 gpm and supply air temperature of 55 degrees Fahrenheit. The central heating coil is sized for a maximum load of 107.8 MBH at a flow of 10.79 gpm. The supply fan is designed for a maximum flow of 7,915 CFM. Outdoor air ventilation is set at 1,648 CFM or 0.35 CFM per square foot
This document summarizes the air system sizing for a school chiller in Dubai, United Arab Emirates. It includes details on the 6 zones covering 4,752 square feet. The central cooling coil is designed to handle a total load of 489.9 MBH with a sensible load of 279.7 MBH at a flow of 98.02 gpm and supply air temperature of 55 degrees Fahrenheit. The central heating coil is sized for a maximum load of 107.8 MBH at a flow of 10.79 gpm. The supply fan is designed for a maximum flow of 7,915 CFM. Outdoor air ventilation is set at 1,648 CFM or 0.35 CFM per square foot
Air System Name ................................... school chiller Equipment Class ............................................ CW AHU Air System Type ..................................................... VAV
Number of zones ............................................................. 6
Floor Area ............................................................... 4752.0 ft Location ............................ Dubai, United Arab Emirates
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM ............................ Peak zone sensible load Space CFM ................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load .......................................................... 40.8 Total coil load ....................................................... 489.9 Sensible coil load ................................................. 279.7 Coil CFM at Jun 1500 ........................................... 6922 Max block CFM at Aug 1700 ................................. 7915 Sum of peak zone CFM ........................................ 7921 Sensible heat ratio ............................................... 0.571 ft/Ton .................................................................... 116.4 BTU/(hr-ft) ........................................................... 103.1 Water flow @ 10.0 F rise .................................... 98.02
Tons MBH MBH CFM CFM CFM
gpm
Load occurs at ................................................... Jun 1500
OA DB / WB .................................................... 114.0 / 85.0 Entering DB / WB ............................................. 82.5 / 69.6 Leaving DB / WB .............................................. 45.1 / 44.6 Coil ADP ..................................................................... 40.9 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 60 Design supply temp. ................................................... 55.0 Zone T-stat Check .................................................... 6 of 6 Max zone temperature deviation .................................. 0.0
F F F F % F OK F
Central Heating Coil Sizing Data
Max coil load ........................................................ 107.8 Coil CFM at Dec 0800 ........................................... 4316 Max coil CFM ........................................................ 7915 Water flow @ 20.0 F drop ................................... 10.79
MBH CFM CFM gpm
Load occurs at ................................................... Dec 0800
BTU/(hr-ft) ................................................................. 22.7 Ent. DB / Lvg DB .............................................. 31.5 / 54.6 F
Preheat Coil Sizing Data
No heating coil loads occurred during this calculation.
Supply Fan Sizing Data
Actual max CFM at Aug 1700 ............................... 7915 CFM Standard CFM ....................................................... 7911 CFM Actual max CFM/ft ................................................ 1.67 CFM/ft
Outdoor Ventilation Air Data
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static .................................................................... 0.00 in wg CFM/person ................................................................ 6.87 CFM/person