CENTRAL OPERATING AREA

RMS

CHK'D APPR'D CERT'D

NATIONAL GRID S.A.

DESCRIPTION

ACDB
RELAY SETTING

NO.

DATE

Apr' 2016

BY

RMS

ISSU
UED FOR APPROVAL

CALCULATIONS

REVISIONS
DESIGNED
BY :- RMS
DATE :- Apr' 2016
CHECKED
BY :- NAGOOR
DATE :- Apr' 2016
OPRG. DEPT.
BY :DATE :ENG'G DEPT.
BY :DATE :CERTIFIED
BY :DATE :-

AS BUILT BY

DATE
DOCUMENT TITLE

THIS DOCUMENT IS NOT


TO BE USED FOR
CONSTRUCTION OR FOR
ORDERING MATERIALS
UNTIL CERTIFIED & DATED

INDEX

PLANT

DOCUMENT NO.

C556

CE-444736

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

of

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690

00

CERT'D
APPR'D
RMS

CHK'D

NATIONAL GRID S.A.

CENTRAL OPERATING AREA

This Document Covers Relay Setting Calculations for

400V Incomer Overcurrent setting

400V Incomer Earth Fault setting

400V Incomer Under Voltage setting

400V Incomer Overvoltage setting

NO.

DATE

=B33 Apr' 2016

BY
Y

MS
RM

ISSUED FOR APPROVAL

DESCRIPTION

Page

Feeder Description

Sl. No.

REVISIONS
DESIGNED
BY :- NAGOOR
DATE :CHECKED
BY :- NAGOOR
DATE :OPRG. DEPT.
BY :DATE :ENG'G DEPT.
BY :DATE :CERTIFIED
BY :DATE :-

AS BUILT BY

DATE
DOCUMENT TITLE

THIS DOCUMENT IS NOT


TO BE USED FOR
CONSTRUCTION OR FOR
ORDERING MATERIALS
UNTIL CERTIFIED & DATED

INDEX

PLANT

DOCUMENT NO.

C556

CE-444736

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

of

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690

00

NATIONAL GRID S.A.

400V Incomer O/C, E/F, UV & OV Relay setting calculation:


System Details :
System Voltage (L-L)
System Voltage (L-N)
Frequency
Max. Through Fault current
CT Primary Current
CT Sec. Current
CT Ratio
VT Primary Voltage
VT Secondary Voltage

400
231
60
25000
1000
5
200
380
110

V
V
Hz
A
A
A
V
V

Auxillary Transformer details :


HV Winding Voltage
LV Winding Voltage
Current input

33
400
500

kV
V
kVA

Protection relay details :


Relay Type

MICOM-P141

Overcurrent setting calculations :


IDMTL curve

IEC Standard Inverse

Over load Factor

1.2

Relay Pick up setting

6.000

Relay Pick up choosen setting Ip =

6.00

Required operating time at fault current


=

1.50

sec

Multiples of fault current w.r.t. pick up current setting


I / Ip
=
20.83
the tripping time for I/Ip 20 are identical with those for I/Ip = 20, Thus
Multiples of fault current w.r.t. pick up current setting
=
20.00
Relay operating time at TP=1

=
=

Required TP

=
=
=

Choosen TP
Operating time at selected TP

=
=

0.14/(Mult. Of operating Current


sec
2.27
1.50
0.662
0.66

-1)

2.27

0.14 x TP / (Mult. Of operating Current


sec
1.496

DOCUMENT TITLE
THIS DOCUMENT IS NOT
TO BE USED FOR
CONSTRUCTION OR FOR
ORDERING MATERIALS
UNTIL CERTIFIED & DATED

^0.02

^0.02

-1)

INDEX

PLANT

DOCUMENT NO.

C556

CE-444736

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

of

00

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690

NATIONAL GRID S.A.


2

Earth Fault setting calculations :


IDMTL curve

Inverse S IEC

Recommended Pick up setting

15%

of CT rating

Relay Pick up setting

0.750

Relay Pick up choosen setting Ip =

0.75

Required operating time at fault current


=

1.50

sec

Multiples of fault current w.r.t. pick up current setting


I / Ip
=
166.67
20
the tripping time for I/Ip 20 are identical with those for I/Ip = 20, Thus
Multiples of fault current w.r.t. pick up current setting
=
20
Relay operating time at TP=1

=
=

Required TP

=
=
=

Choosen TP
Operating time at selected TP

=
=

0.14/(Mult. Of operating Current


sec
2.27
/

1.50
0.662
0.66

^0.02

-1)

2.27

0.14 x TP / (Mult. Of operating Current


sec
1.496

^0.02

-1)

Under Voltage setting :


Stage-1 Setting

75%

of Un

Stage-1 Setting

82.50

Stage-1 Time Delay

2.00

Sec

Stage-2 Setting

70%

of Un

Stage-2 Setting

77.00

Stage-2 Time Delay

2.00

Sec

Stage-1 Setting

105%

of Un

Stage-1 Setting

115.50

Stage-1 Time Delay

2.00

Stage-2 Setting

110%

of Un

Stage-2 Setting

121.00

Stage-2 Time Delay

2.00

Over Voltage setting :

DOCUMENT TITLE
THIS DOCUMENT IS NOT
TO BE USED FOR
CONSTRUCTION OR FOR
ORDERING MATERIALS
UNTIL CERTIFIED & DATED

Sec

Sec

INDEX

PLANT

DOCUMENT NO.

C556

CE-444736

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

of

00

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690

NATIONAL GRID S.A.


400V Incomer O/C, E/F, UV & OV Relay Setting Summary:
Relay Type :
Parameter
CT AND VT RATIOS
Phase CT Primary
Phase CT Sec'y.
Phase VT Primary
Phase VT Sec'y.
OVERCURRENT

P141
Range

Manuf.
Default Setting

Alstom
Proposed Setting
1000
5
380
110

Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse

I>1 Function

IEC S Inverse

IEC S Inverse

Non-Directional

Non-directional

1xIn
1
1
1

1.00
0.66
1.00

IN2>1 Function

Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse

IEC S Inverse

IEC S Inverse

IN2>1 Direction
IN2>1 Current Set
IN2>1 Time Delay
IN2>1 TMS
IN2>2 Time Dial

Non-Directional
0.08xIn 4.0xIn
0100
0.0251.2
0.01.100

Non-Directional
0.2xIn
1
1
1

Non-directional

Non-Directional
Directional Fwd
Directional Rev
0.08xIn 4.0xIn
0100
0.0251.2
0.01.100

I>1 Direction
I>1 Current Set
I>1 Time Delay
I>1 TMS
I>1 Time Dial
EARTH FAULT2 (Derived)

THIS DOCUMENT
IS NOT TO BE
USED FOR
CONSTRUCTION
OR FOR
ORDERING
MATERIALS
UNTIL CERTIFIED
& DATED

DOCUMENT TITLE

6.00

0.75
1.00
0.66
1.00

INDEX

PLANT

DOCUMENT NO.

C556

CE-444736

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

of

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690

00

NATIONAL GRID S.A.


Parameter
Volt Protection
Undervoltage
V<Measur't Mode
V<Operate Mode
V<1 Function
V<1 Voltage set
V<1 Time Delay
V<1 TMS
V<1 Poledead Inh
V<2 Status
V<2 Voltage set
V<2 Time Delay
V<2 Poledead Inh

Range

Phase to Phase
Phase to Neutral
Any Phase
Three Phase
Disabled
DT
IDMT
10/40V for 110/440V respectively
120/480V for 110/440V respectively
0.100
0.5.100
Enabled
Disabled
Enabled
Disabled
10/40V for 110/440V respectively
120/480V for 110/440V respectively
0100
Enabled
Disabled

Default Setting

Proposed Setting

Phase-Phase

Phase to Neutral

Any Phase

Any Phase

DT

DT
82.50

10s
1

2.00
1.00

Enabled

Enabled

Disabled

Disabled
77.00

5s

2.00

Enabled

Enabled

Phase-Phase

Phase to Neutral

Any Phase

Any Phase

DT

DT

Overvoltage
V>Measur't Mode
V>Operate Mode
V>1 Function
V>1 Voltage set
V>1 Time Delay
V>1 TMS
V>2 Status
V>2 Voltage set
V>2 Time Delay

THIS DOCUMENT
IS NOT TO BE
USED FOR
CONSTRUCTION
OR FOR
ORDERING
MATERIALS
UNTIL CERTIFIED
& DATED

Phase to Phase
Phase to Neutral
Any Phase
Three Phase
Disabled
DT
IDMT
60/240V for 110/440V respectively
185/740V for 110/440V respectively
0.100
0.5.100
Enabled
Disabled
60/240V for 110/440V respectively
185/740V for 110/440V respectively
0100

DOCUMENT TITLE

115.50
10s
1

2.00
1.00

Disabled

Disabled
121.00

5s

INDEX

PLANT

C556

2.00

SHEET NO.

REV NO.

RELAY SETTING CALCULATIONS


FOR ACDB PANEL

CE-444736

of

132/33kV AL JOWA SUBSTATION


QASSIM

SAUDI ARABIA

JOB ORDER NO.

DWG. CONT. SHT.

CE-444690