1. Features
The CKMC module can be used for:
allowing to operate high inrush current loads in conjunction with power supplies that
have low overload capability or hiccup type of current limitation.
DC loads where a power regulation is necessary, for example in motors and lamps.
Remote power regulation is possible by use of an external potentiometer.
The used technique is PWM (Pulse Width Modulation).
It is equipped with a SoftStart circuit in order to avoid the known current peaks problems
on inductive, capacitive or high dynamic loads as motors, lamps, coils and power supplies.
The power level and the SoftStart duration are adjustable through two internal
potentiometers.
When an external potentiometer is used for remote power regulation this mode is settable
through an internal switch (SW1).
2. Technical data
Parameter
U supply for
control side (UIN)
UOUT (load)
IOUT (load)
SoftStart duration
Power level range
Protections (load
side)
Connections
Mechanical
Environmental
Range
24Vdc (factory set) or 12Vdc
48Vdc max.
4A nominal, max. 6A for 30 s
adjustable 0.5 - 5.0s
adjustable 0 - 100%
- short circuit (T fuse)
- reverse polarity
- transient over voltage
5 clamp contacts for AWG26-14 wire
Plastic enclosure (UL 94 V-0) for DIN
rail, total width = 6mm
Temperature operating range:
-10/+45C
Humidity: max. 85%, non condensing
Remarks
Custom voltages available on
request.
3. WARNING!
Before powering the unit check as follows:
In and out polarity
In and out voltage, UIN max = 28VDC (or 15VDC) and UOUT max = 48VDC
Max. load current, IOUT max = 4A
Pag. 2/3
4. Block diagram
100%
0% max min
Power regulation
Power regulation is always active, with SoftStart ON or SoftStart OFF. SoftStart duration
regulation is active with SoftStart ON.
5. SoftStart settings
With internal potentiometer:
ON
SW1-1 ON
SW1-2 ON
SW1-3 OFF
SW1-4 OFF
With external potentiometer:
ON
SW1-1 OFF
SW1-2 OFF
SW1-3 ON
SW1-4 ON
OFF
SW1-1 ON
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
OFF
SW1-1 OFF
SW1-2 OFF
SW1-3 ON
SW1-4 OFF
Pag. 3/3