Typical Design Criteria for Gravity Sewerage System

Parameter
Pipe Material
Pipe Diameter
Slope
Maximum Velocity
Depth to invert
Depth to crown
Location with respect to water mains
Alignment

Manholes

Drop Manholes
Manhole Diameter

Recommendation
PVC
200 mm minimum diameter to carry peak flow
rate.
To achieve 0.60 m/s
2.5 to 3.0 m/s
3.0 to 3.5 m minimum
1.8 to 2.4 m
3.0 to 3.5 m maximum
H=D/6 minimum
3.0 m horizontally
0.45 m vertically
When crossing
Straight between manholes
Place at:
-junction of two sewers
-change in vertical alignment
-change in pipe size
-at end of each line
Spacing for straight runs
Effluent elev. = Influent elev. 0.03 m

When inflow and outflow inverts


differ more than 0.6 m
1.2 m minimum