Typical Design Criteria For Gravity Sewerage System Parameter Recommendation
Typical Design Criteria For Gravity Sewerage System Parameter Recommendation
Parameter
Pipe Material
Pipe Diameter
Slope
Maximum Velocity
Depth to invert
Depth to crown
Location with respect to water mains
Alignment
Manholes
Drop Manholes
Manhole Diameter
Recommendation
PVC
200 mm minimum diameter to carry peak flow
rate.
To achieve 0.60 m/s
2.5 to 3.0 m/s
3.0 to 3.5 m minimum
1.8 to 2.4 m
3.0 to 3.5 m maximum
H=D/6 minimum
3.0 m horizontally
0.45 m vertically
When crossing
Straight between manholes
Place at:
-junction of two sewers
-change in vertical alignment
-change in pipe size
-at end of each line
Spacing for straight runs
Effluent elev. = Influent elev. 0.03 m