Nepco Non Directional Inverse/ Very Inverse/ Extremely Inverse Time Over Current/ Earth Fault Relays

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

NEPCO

Non Directional Inverse/ Very Inverse/ Extremely Inverse Time Over


Current/ Earth Fault Relays
1. General
Site: NEW KARAK
Circuit: TR2 63.5 MVA 132/33 KV
Phase(s): R,Y,B,N
Type / Model No. ABB REF 615
Serial No.:
Rating Current: 1(A)
Rating Voltage: 110 (V)
Rating Freq.: 50 (Hz)

2. Mechanical Inspection:
3. Tap Continuity Check:

OK
OK

4. Pick up/Drop off test


Existing Setting
Ph
A
Percent
R
1
100%
Y
1
100%
B
1
100%
E/F
0.2
20%

Pick Up Current
A
Percent
1.00
100%
1.01
101%
1.01
101%
0.201
20.1%

Drop Off Current


A
Percent
0.92
92%
0.96
96%
0.96
96%
0.192
19.2%

5. Timing Test (Time multiplier check at 2/4 existing current tap value)
Operating Time (s)
Existing T.M.S %

Multiplier of
current tap
R
3.029
1.504

2
4

30%
Y
3.026
1.502

B
3.030
1.505

6. Instantaneous Over Current Unit


Type
Relay current setting (A)
7. Operation Test
Alarm contact
Trip Contact
Shorting Bridge

30 %
E/F
3.028
1.502

100% T.M.S
R
10.07
4.995

Y
10.07
4.994

Pick Up Current (A)

B
10.07
4.997

E/F
10.07
4.995

Operating Time (msec)

Flag
Trip Lever

8. For numerical relays: Test results stored in Test set are attached
(If applicable)
Remarks
Foreman Name
Foreman Sign.
Date

Form #: QP44/01/F06

Eng. Name
Eng. Sign.
Date

Page 1 of 1

Issue/Rev.: 1/a