Nepco Non Directional Inverse/ Very Inverse/ Extremely Inverse Time Over Current/ Earth Fault Relays
Nepco Non Directional Inverse/ Very Inverse/ Extremely Inverse Time Over Current/ Earth Fault Relays
Nepco Non Directional Inverse/ Very Inverse/ Extremely Inverse Time Over Current/ Earth Fault Relays
2. Mechanical Inspection:
3. Tap Continuity Check:
OK
OK
Pick Up Current
A
Percent
1.00
100%
1.01
101%
1.01
101%
0.201
20.1%
5. Timing Test (Time multiplier check at 2/4 existing current tap value)
Operating Time (s)
Existing T.M.S %
Multiplier of
current tap
R
3.029
1.504
2
4
30%
Y
3.026
1.502
B
3.030
1.505
30 %
E/F
3.028
1.502
100% T.M.S
R
10.07
4.995
Y
10.07
4.994
B
10.07
4.997
E/F
10.07
4.995
Flag
Trip Lever
8. For numerical relays: Test results stored in Test set are attached
(If applicable)
Remarks
Foreman Name
Foreman Sign.
Date
Form #: QP44/01/F06
Eng. Name
Eng. Sign.
Date
Page 1 of 1
Issue/Rev.: 1/a