Professional Documents
Culture Documents
G Simplex ES Fire Alarm Panels Field Wiring Specifications (900-408 - G)
G Simplex ES Fire Alarm Panels Field Wiring Specifications (900-408 - G)
Document Number:
0900-408
Revision Date:
12-June-13
Revision Level:
REVISION HISTORY
The information contained in this document is proprietary to the Tyco Fire Protection
Products, Westminster, Massachusetts, USA, and is intended for internal use only. Such
information may be distributed to others only by written permission of an authorized Tyco
official.
COPYRIGHT 2011-2013 Tyco Fire Protection Products
Page 2 of 23
REVISION
DATE
DRN/ECO
DESCRIPTION
A
B
03/08/2011
05/12/2011
D11-0003
D11-0008
30-May-12
D12-0009
27-Aug-12
H12-0195
Oct-12-12
D12-0018
01-May-13
D13-0003
12-Jun-13
D13-0007
Initial Revision
Clarify IDNet Conduit requirements (Section 7);
Add BNIC Section (#19) Modify wiring
chart(Section 20)
Added specifications for fiber optic cable, sections
8.2 & 12.1.
Added Isolator notes to General IDNet
Requirements. Secion 7.1.
Removed section TrueAlert non-addressable, as it
was actually all specs for TrueAlert Addressable;
Added IDNAC wiring rules, IDNet1+ and RUI+
Added new modules for RUI+ and IDNAC
Add RP NAC to Glossary; update IDNet shielded,
UTP requirements in section 6.1
Changes per request of Product Management; Main
emphasis-consolidate shielded requirements into
section 19.
Page 3 of 23
TABLE OF CONTENTS
1
SCOPE ................................................................................................................................................................... 5
GLOSSARY: ......................................................................................................................................................... 5
REFERENCES ...................................................................................................................................................... 5
PRECEDENCE ..................................................................................................................................................... 6
RUI ....................................................................................................................................................................... 13
RUI+ ..................................................................................................................................................................... 13
10
11
12
13
14
15
16
17
Page 4 of 23
18
19
TABLES
TABLE 5-1: SUPPRESSOR APPLICATIONS ................................................................................................................................... 8
TABLE 7-1: 4120 NETWORK: MAXIMUM TRANSMISSION DISTANCES, WIRED NETWORK .................................................... 10
TABLE 7-2: 4120 NETWORK: MAXIMUM DISTANCES, OPTICAL FIBER .................................................................................... 11
TABLE 7-3: MULTIMODE FIBER REQUIREMENTS MEDIA MODULES ........................................................................................ 12
TABLE 11-1: MULTI AND SINGLE-MODE FIBER REQUIREMENTS MULTIPLEX MODEM ............................................................ 16
TABLE 19-1 SHIELDED WIRING .................................................................................. ERROR! BOOKMARK NOT DEFINED.23
Page 5 of 23
Scope
This document describes wiring guidelines and restrictions for the field wiring applied to Simplex
ES fire alarm panels. It is intended to be a guide so that unusual or sophisticated applications not
covered by the field wiring drawings/installation instructions can be addressed and engineered. It
supersedes 900-242, Field Wiring Specifications for Simplex Addressable Fire Alarm Panels. The
900-242 superseded the 900-082 Field Wiring Specifications for 4100 /4120/ 4010 Fire Alarm
Panels. Both the above mentioned documents may contain information applicable to this
document.
The document is organized by circuit type, with a general guideline section in front. The intent is
that any fire panel that uses a circuit type would be covered by that section. For example, the
IDNet+ section would cover both 4010ES IDNet and 4100 IDNet+ applications. Any panel
specific requirements will be delineated in the respective section.
All specifications are subject to local authority approval.
Glossary:
4100U: 4100 Upgrade. Successor to the 4100 Classic and 4100 Legacy system
FWD: Field Wiring Drawings
IDC: Initiating Device Circuit.
IDNAC: 2nd generation addressable notification SLC (TrueAlert)
IDNet: addressable SLC for up to 250 addressable devices.
IDNet+: IDNet which is electrically isolated from internal panel electronics
NAC: Notification Appliance Circuit. Formerly called signal circuit.
Audio NAC: A notification appliance circuit used to control conventional speakers
RP (DC) NAC: Notification appliance circuit using only reverse polarity to activate
conventional DC appliances (e.g. horns, bells, strobes, etc)
RUI: Remote Unit Interface. SLC for expanding 4100 communications to remote cabinets.
RUI+ : an electrically isolated RUI SLC
SLC: Signaling Line Circuit. Supervision by communications rather than fixed resistance.
STP: Shielded Twisted Pair
TrueAlert: a signaling line circuit with addressable Notification Appliances (TAA)
UTP: Unshielded Twisted Pair
Smart Sync: Control of horns and strobes on a single pair of wires.
References
NFPA 70
NFPA 72
5.1
Precedence
In the event of conflict between this document and local authorities, the local authorities
take precedence.
In the event of conflict between this document and NFPA 70, National Electric Code, or
NFPA 72, National Fire Alarm Code, NFPA 70 and 72 take precedence.
In the event of conflict between this document and the field wiring diagrams, Engineering
should be consulted.
In the event of conflict between this document and 0900-242, Field Wiring Specifications
for Simplex Addressable Fire Alarm Panels, this document takes precedence. The 0900242 has been superseded effective with the release of this document.
Page 6 of 23
Wiring Precautions
General Precautions
Page 7 of 23
Transient Suppression
Transient suppression is required where wire leaves the building and re-enters the
next building. Suppression is required regardless if wiring is overhead, aerial or
underground.
The suppression must be bonded to the grounding electrode system per Section 6.2.
Transient suppressors add capacitance and resistance to the circuits they are added
to and therefore must be included in line resistance and capacitance calculations.
o Each 2081-9027 and 2081-9044 adds 0.006uF across the lines and 3 ohms
per line (6 ohms total).
o Each 2081-9028 adds 0.017uF across the lines and adds 0.1 ohm per line
(0.2 ohms total).
Wiring which is installed external to a building must be protected by overvoltage
protectors.
Two suppressors should be installed on circuits installed external to a building, one
where the circuit exits the building, and one where the circuit re-enters another
building.
The suppressors in table #6-1 are recommended for the circuits listed and are UL497B listed.
Table 5-1: Suppressor Applications per the UL1459 Standard:
Suppressor
Circuits Protected
2081-9044
RUI
4120 Network
ZAM Power
Local energy city circuit
Additional Restrictions
Reduce maximum line distance by 1000 feet for first two
suppressors; Each additional reduces distance by 500 feet.
2 Suppressors maximum in any point to point link
200 mA maximum; 3270 feet maximum distance.
(4100 and 4010) Minimum wire size 18AWG
Circuits Protected
IDNet
4010 N2 Comms
IDNAC
TrueAlert SLC
2081-9044
2081-9028
2081-9028
2081-9044
Page 8 of 23
Additional Restrictions
Maximum distance 2500 feet for first two suppressors. Using
two additional suppressors will reduce the maximum line
distance by 1000 feet.
Maximum distance 2500 feet for first two suppressors. Using
two additional suppressors will reduce the maximum line
distance by 1000 feet.
200 mA maximum current, 2500 feet total length on branch
with suppressor. 6 ohms of line resistance must be accounted
for in voltage drop calculations.
Do not mix with 2081-9028. Max 2 suppressors on a branch.
Minimum wire size 20 AWG
1000 feet total length on branch with suppressor. Do not mix
with 2081-9044. Max 2 suppressors on a branch.
25V Audio Only; Contact Engineering or Sales Engineering
for 70V applications
Maximum distance reduced to 4 ohms total when two
suppressors are used.
25V Audio Only; Contact Engineering or Sales Engineering
for 70V applications
Maximum distance 1400 ft; min wire size 18 AWG.
Maximum distance 400 ft; min wire size 18 AWG.
220/240VAC circuits that need additional suppression may use any appropriately rated
(IEEE C62-41-1991 Category B) 240V suppressor. It should be UL1449 listed.
5.3.2
If relay IAMs are used to switch 120VAC, the power source to the contacts should be externally
fused by the user with a 1 Amp 250V quick blow fuse, UL listed to Guide #JDYX- Littlefuse
AGC1 or Equivalent. If switching inductive loads, the loads must be suppressed with a suitable
Page 9 of 23
suppression device. While it is preferred this be done by the manufacturer of the device, the loads
may suppressed by adding a device directly across the coil as follows:
120VAC:
o 0560-040 RC Network
24VDC:
o 0184-011-1N4004 Diode
6
6.1
Note: In the following, the term "IDNet channel" is used to mean those lines connected to any one
IDNet Transceiver board ( SPS or IDNet card on 4100U). Parallel runs from the same board do not
constitute separate channels. The term "continuous run" refers to the distance from the panel to the
furthest device when wired Class B. When wired Class A, this is the distance from the primary
output, through all devices and back to the secondary output.
Except for the requirements of Section 19, Shielded wire is no longer needed for IDNet.
Twisted pair is always required for non-isolated IDNet.
A load circuit of up to 10 amps at 240VAC, 50 or 60 Hz, is allowed in the same conduit.
No more than .60f of total capacitance (if shielded, use wire to shield parameter) is
allowed on any IDNet channel. These ratings are inclusive of added transient suppressors,
refer to Section 5.
Maximum resistance for ONE continuous IDNet run (inclusive of added transient
suppressors):
o 35 Ohms with up to 250 IDNet devices on IDNet channel.
o 50 Ohms for up to 125 IDNet devices on IDNet channel
Twisted, shielded pair is required for any IDNet channels run in 500 or more of conduit.
When Line powered Isolators or Isolator Bases are used, maximum line resistance between
Panel and 1st Isolator, and Isolator to Isolator is 10 ohms (780 ft @ 18 AWG).
6.2 IDNet+ requirements (4100-9107, 4100-9108 and 4010ES)
Note: In the following paragraphs the term "IDNet+ channel" is used to mean those lines connected to
all (4) circuits of the IDNet+ (4100-9107) (e.g. Circuit A, Circuit B, Circuit), 4100-3108 (4x5
IDNet1+) and the 4010ES IDNet. Parallel runs from the same board do not constitute separate
channels. The term "continuous run" refers to the distance from the panel to the furthest device when
wired Class B. When wired Class A, this is the distance from the primary output, through all devices
and back to the secondary output.
No more than .60f of total capacitance (if shielded, use wire to wire parameter) is allowed
on any IDNet channel. These ratings are inclusive of added transient suppressors, refer to
Section 5.2.
Maximum resistance for ONE continuous IDNet+ run (per Circuit, inclusive of added
transient suppressors):
o 35 Ohms with up to 250 IDNet devices on IDNet channel.
o 50 Ohms for up to 125 IDNet devices on IDNet channel
Maximum capacitance from IDNet+ (+) of one channel to IDNet+ (+) of another channel is
1f.
Page 10 of 23
Maximum capacitance from IDNet+ (-) of one channel to IDNet+ (-) of another channel is
1f.
7
7.1
Except for the requirements of Section 19, 4120 Network wiring should be 18 AWG
twisted, pair, or 24AWG twisted pair (Telephone Cable). Shielded Cable is allowed for
new installations.
When shielding is used, the shield shall be connected to Earth Ground, at the Left Port end
of span only.
All Network wiring must meet National Electrical Code (NEC) requirements.
No T-tapping of the Network conductors is allowed.
Network wiring is point-to-point only.
Maximum line length between ports at 57,600 and 9600 bits per second is shown in the table
below.
Network Speed
57,600 bps
9600 bps
18 Gauge TP Wire.
Maximum capacitance between
conductors: 58 pf. per foot
10,000 feet
17,000 feet
24 Gauge TP Wire.
Maximum capacitance between
conductors: 22 pf. per foot
7,000 feet
12,000 feet
Page 11 of 23
Note: this section refers only to the fiber limitations of the fiber media modules that attach to a
network interface card. For the Fiber Optic Multiplex Modem, refer to section 11.
All fiber cables shall be multimode, graded index. ST style connectors must be used.
No physical strain shall be put on the cables.
There must be no cable bends of less than a two inch radius.
The fiber backbone must comply with, at a minimum, ANSI/TIA/EIA 568-B-3 industry
standards.
Two methods are available for joining fiber cable. Both methods are allowed on a fiber
4120 Network:
o Splices provide a permanent, very low loss, fiber-to-fiber connection and should
only be performed by experienced personnel.
o Couplers provide temporary connection between two ST style connectors with a
loss of 1.2dB.
The characteristics of the 4100-0143 or 4100-6057 fiber optic media card are as follows.
o Maximum attenuation (inclusive of all cabling losses, connector losses, splice
losses, and safety margin):
50/125 cable is 17dB
62.5/125 cable is 20.4dB
Maximum line lengths for 50/125 and 62.5/125 cable with 2 different specified losses per
kilometer are shown in the table below.
Fiber Cable
50/125 Fiber
50/125 Fiber
62.5/125 Fiber
62.5/125 Fiber
Power Margin
4 db
3 db
4 db
3 db
Maximum distance
10,000 feet
15,000 feet
13,000 feet
15,000 feet
Page 12 of 23
The outside plant fiber must comply with ANSI/ICEA S-87-640, and inside plant fiber must
comply with ANSI/ICEA S-83-596. Additionally, it must meet the specifications in the following
table for attenuation and bandwidth for the given fiber type and wavelength.
Optical fiber cable
type
Wavelength
(nm)
Maximum
attenuation
(dB/km)
Minimum bandwidth
capacity for
overfilled launch
50/125 m
Multimode
850
3.5
500
62.5/125 m
Multimode
850
3.5
160
7.2
Modems should only be used on a 4120 network on a Physical Bridge card. Network spans using
modems are discouraged. Under no circumstances should more than a single span (2 modems) in a
network loop be over modem communications.
7.2.1
Telephone circuits must be private leased lines for analog data communications, point to point,
full duplex, no line conditioning or signaling required, two wire line interface with RJ-11
termination.
7.2.2
The modems may be connected directly to one another using twisted pair
copper wire. Unshielded #24 AWG twisted pair wire may be used for direct point to point
communications up to 15,000 feet. Shielded wire may be used in noisy environments. The
shield should only be terminated to earth at one end of the line. The maximum capacitance
must be limited to 22pf per foot.
Page 13 of 23
RUI
Except for the requirements of Section 19, UTP (unshielded twisted pair) wiring may be used.
Maximum cable capacitance of .58uf between conductors and/or 35 ohms total line
resistance, inclusive of added transient suppressors, refer to Section 5.2.
For class B wiring the maximum line length (18 AWG or larger pair) is 2500 feet for one
continuous run, with 10,000 feet maximum total if T-tapping is done.
For class A and/or style 7 wiring, the maximum length is 2500 feet from the Comm A
terminals, through the Class A loop, terminating at the Comm B terminals.
RUI+
10 TrueAlert Addressable/IDNAC
This section gives recommendations for wiring TrueAlert/IDNAC circuits. TrueAlert Addressable,
or TAA, refers to TPS and 4009T SLCs. IDNAC refers to EPS and 4009 Repeater SLCs. IDNAC
is rated for longer distances. Refer to the Installation Instructions / Field Wiring Drawing for the
controller/power supply that you are using for wire size and length limitations due to circuit style,
alarm current loading, and communication circuit unit loading. If there is conflict between these
recommendations and the install instructions requirements, the install instruction takes precedence.
10.1.1 Standard Circuit Wiring
Except for the requirements of Section 19, the preferred media for TAA/IDNAC circuits is
unshielded twisted pair (UTP) wiring. This wiring must have a capacitive rating of less than
60pf/ft and minimum 3 twists (turns) per foot.The insulation rating must be appropriate for the
application. Refer to the installation documents for the TAA/IDNAC controller you are using for
specific wiring distances for each controller or repeater.
10.1.2 Un-controlled Impedance Wiring
Although TrueAlert & IDNAC circuits are intended to run twisted pair (controlled impedance)
wiring, some applications will wish to take advantage of existing wiring that is not twisted pair.
Page 14 of 23
This is only allowed if both conductors of the TAA/IDNAC circuit reside in the same metal
conduit, and only under the conditions listed in this section.
A single TAA/IDNAC circuit may run on up to 1000 feet of non-twisted pair wiring if that
TrueAlert circuit is the only active circuit in the same conduit. This distance includes all T-Taps
and wire branches for Style 4 (Class B). This distance applies to the entire loop run (B terminals
to A terminals) for Style 6 (Class A).
The following recommendations apply to TrueAlert circuits run in a single conduit on non-paired
wiring with other circuits also on non-paired wiring the in the same conduit. Maximum shared
distances include all T-Taps and wire branches sharing the conduit with the other circuit(s) for
Style 4 (Class B) TrueAlert circuits.
A TrueAlert circuit with another TrueAlert circuit(s) 500 max wire run length shared
with any combination of the other circuit(s). Maximum 3 TrueAlert circuits in the conduit.
A TrueAlert circuit with IDNet/MAPNET II circuits 250 max length shared with any
combination of the other circuit(s). Maximum 3 TrueAlert circuits and 1 IDNet/MAPNET
circuit in the conduit.
A TrueAlert circuit with IDNet+ 500 max length shared with any combination of the
other circuit(s). Maximum 3 TrueAlert circuits and circuits in the conduit. You may go the
maximum conduit length of 1000 with a single TrueAlert channel and IDNet+.
A TrueAlert circuit with Simplex Fire Alarm NAC (24V/2Amp) loaded with Strobes,
Horns, Doorholders, or Incandescent bulb loads 500 max wire run length shared with
any combination of the other circuit(s). Maximum 3 total circuits in the conduit.
A TrueAlert circuit with a 120Vac circuit with max 100VA load 500 max wire run
length shared with the 120Vac circuit. Maximum 3 TrueAlert circuits and (1) 120Vac
circuit in the conduit.
No other circuit combinations are recommended when operating TrueAlert circuits on nonpaired wiring.
10.1.3 Shielded Wiring
When using shielded wire for TrueAlert/IDNAC SLCs, the following rules must be followed:
The shielded cable only contains a single active wire pair: the TrueAlert SLC. The cable may
contain other wire pairs enclosed by the shield only if those pairs are disconnected from any
electrical signal generator.
Shielded twisted pair (STP) and un-shielded twisted pair (UTP) are not mixed on the same
TrueAlert SLC.
The shields of all branches, T-taps, or the entire Class A loop must be connected to the
negative return of the circuit at the TrueAlert controller. Note that each end of the shielded
Page 15 of 23
Class A loop is connected to the B(-) and A(-) terminals, respectively. The only exception to
this is described in Transient Suppression, 5.3.
The 10,000 foot total cable rating is limited to STP cable with a maximum capacitive rating of
60pf/ft between a conductor and both the other conductor(s) and the shield. Where the 60pf/ft
specification is exceeded, the total cable rating must be de-rated by the fraction formed by
60/(per foot cap. rating). For instance, a cable rated 100 pf/ft decreases the total foot cable
rating of that TrueAlert SLC to 10,000 x 60/100, or 6,000 feet.
The table below lists the fiber optic specifications of the modem.
Fiber Cable
Single-mode fiber
Multimode fiber2
Max Attenuation
15dB
6dB
Notes:
1. The maximum attenuation for SMF should have the desired power margin (recommended
min: 3dB) subtracted, then the remaining attenuation can be divided between connector and
fiber loss (e.g. 15dB-3dB=12dB. Fiber of 0.34dB/km and no splices yields
12/0.34=35.3km).
2. Single-mode fiber is preferred in all applications.
3. No more than three splices should be used in a given linkfor multimode fiber.
4. All multimode fiber must be graded index (GRIN).
5. The modem operates at 1310nm and 1550nm wavelengths. Typical fiber attenuation at the
time of this publication at these wavelengths is single-mode: 0.34dB/km, multimode:
1dB/km.
6. Attenuation measurements should be taken using a 1300nm/1310nm source.
11.1 Fiber Optic Cable Requirements
The fiber optic cabling must be compliant with, at a minimum, TIA-EIA-568-B. Note that this
standard defines outside plant as Telecommunications infrastructure designed for installation
exterior to buildings.
The outside plant fiber must comply with ANSI/ICEA S-87-640, and inside plant fiber must
comply with ANSI/ICEA S-83-596. Additionally, it must meet the specifications in the following
table for attenuation and bandwidth for the given fiber type and wavelength.
Wavelength
(nm)
Page 16 of 23
Maximum
attenuation
(dB/km)
Minimum
bandwidth capacity
for overfilled launch
50/125 m
Multimode
1300
1.5
500
62.5/125 m
Multimode
1300
1.5
500
1310
1.0
N/A
1550
1.0
N/A
1310
0.5
N/A
1550
0.5
N/A
Single-mode
inside plant cable
Single-mode
outside plant cable
Page 17 of 23
For circuits with 2 wire smoke detectors 50 ohms is the maximum line resistance. For
circuits with dry contacts 800 ohms is the maximum line resistance.
For either normally open contacts or 2 wire detectors the maximum distance for the IDNet
Monitor ZAM zone is 2,000 feet or 10 ohms, whichever comes first.
Except for the requirements of Section 19, any NEC 760 wire meeting circuit parameters
listed below may be used.
Maximum current, maximum wiring distance, and ratings for all notification (signal)
circuits and control relays can be found in the applicable field wiring diagrams or
installation instructions. The minimum wire size connected to control relay or auxiliary
relay contacts must adhere to National Electrical Code NFPA 70.
The maximum wire size is 12 AWG or the terminal block rating, whichever is lower.
The maximum distances are defined in the applicable Installation Instructions.
Wheelock protocol circuits must follow the same wiring restrictions as SmartSync.
Any NEC 760 wire meeting circuit parameters listed below may be used.
All 24 I/O wiring must be a minimum of 18 AWG. The maximum wire size is 12 AWG or
the terminal block specification, whichever is smaller.
Switch input: maximum one way distance 400 feet on unshielded wire.
Lamp output: maximum one way distance 400 feet on unshielded wire.
No AC wiring allowed in the same conduit. Exception: System power. Cable to I/Os
must be twisted. Maximum distance 400 feet on unshielded wire.
Distance with Shielded wire:
o Switch input: maximum one way distance 2500 feet.
o Lamp output: maximum one way distance 600 feet or 2 ohms total whichever
comes first.
o If shielded wire is used, connect shield to 0V of module power source.
Page 18 of 23
Page 19 of 23
Except for the requirements of Section 19, UTP wiring is required, #18 AWG minimum.
Speaker circuit wiring distances can be found in the applicable field wiring drawings or
installation instructions.
Page 20 of 23
(566-243, non CRC cards) the maximum line distance is 2500 feet, total (not point to point)
following the same rules as the point-to-point distance.
Maximum 18AWG STP distance is 1000 feet point to point. This requires cable of less
than 55pF/ft line to line for .055uF or less at 1000 ft. When using older Digital Audio
Riser Interface Cards (566-243, non CRC cards) the maximum line distance is 1000 feet,
total (not point to point) following the same rules as the point-to-point distance. One
exception for the 1000 feet limit is Mineral Insulated Cable (Pyrotenax 2/18-215T). It has
been tested and complies up to a 2000-foot distance.
Maximum resistance is 40 (point to point for newer DARICS, total for older DARICS
[566-243]).
If a shield is used (for retrofit applications), connect the shield to earth through a mounting
screw at the transmit end of each leg. (Digital Audio Controller- Primary cable; Remote
cabinets-Secondary cable.) The shield may also be floating.
18 BNIC Ethernet
The BNIC signal is standard 10/100 Ethernet. General requirements are:
Page 21 of 23
10/100Base-T connection
Cable: Cat 5 (or greater)
Connectors: RJ45
Maximum length-100 Meters (328 ft)
Intended to be connected via customers LAN
Cable not to be extended outside the host building directly from BNIC
The BNIC supports Auto-MDIX (Straight or Crossover cable can be connected to the
BNIC, the BNIC will automatically switch as needed)
Do not connect Power over Ethernet (PoE) signals to the BNIC.
Port A has Earth Fault Detection on the LAN wires.
Generally, Port B should be used to connect to customer building network, although Port A
can also be used (be sure the signal you are connecting is not PoE).
Table 19-1 shows when shielded wire must be used. It applies when any of the listed signals are run
in 500 or more of conduit, and the corresponding signal is also in conduit (does not have to be the
same conduit.) Both signals do not need to be in 500 of conduit. A ground fault or test by an AHJ of
operation while grounded may increase the coupling between circuits to a level that could cause
interference. If any of the signals listed will be in 500 or more of conduit, and any of the other
signals are used in a system, the table applies.
Page 22 of 23
Table 19-1 also applies if cables are not in conduit but are bundled closely together for 500 ft or more.
To use the table, select the signal in the leftmost column and compare it to the cell that corresponds to
the signal being mixed in the top row. STP= Shielded Twisted Pair; UTP=Unshielded Twisted Pair
Example: A system will have at least 500ft of conduit containing RUI and/or IDNet. From the table,
the RUI must use STP, and the IDNet must use STP. When there are two circuits, both of which
require STP, one may be wired with UTP if desired (see note below table).
NOTES:
Notice the requirement changes to UTP if IDNet+ (4100-3107, -3108 or 4010ES) is used
instead of IDNet.
IDNAC refers to TrueAlert Addressable circuits on the 4100 EPS or the 4009 IDNAC
Repeater. TAA refers to circuits on the TPS or the 4009T.
ES audio NAC refers to 4100U or 4100ES NACs and 4100U/ES amplifiers. For older voice
NACs, refer to the older field wiring specs.
SmartSync is AKA TrueAlert non-addressable. The same wiring restrictions also apply to
Wheelock protocol NACs.
Page 23 of 23
Table 19-1: Wiring Requirements for Mixed Circuits in Conduit or Closely Bundled(3)
Mix With> IDNet /
Signal \/
RUI
IDNet /
STP(1)
RUI
IDNet+/
UTP
RUI+
IDNet+ /
RUI+
IDNAC
TAA
TPS/4009T
Smart
Sync
RP (DC)
NAC
Analog
Riser
DAR
4120
Net
ES Audio
NAC
UTP
STP(1)
STP(1)
STP(1)
STP(1)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
IDNAC
STP(1)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
TAA (TPS/
4009T)
Smart
Sync
RP (DC)
NAC
Analog
Riser
STP(1)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
STP(1)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
STP(1)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
DAR
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
4120 Net
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
ES Audio
NAC(2)
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
UTP
(1)When STP shows as being required for circuits being evaluated and both circuits show STP
needed, only one of the two needs to use STP. The other may use UTP. This applies to more than
2 circuits as well: 2of 3 must use STP with one circuit allowed UTP, etc.
(2) Any Audio NACs using the 25V Constant Supervision Module (4100-1259) must use STP
wiring with the shield connected to system 0v.
(3) All circuits run Outdoors require STP wiring and Transient Suppression in accordance with
Chapter 5.