The document reports the results of an insulation test of medium voltage cables at 2500V for 1 minute with respect to earth. It lists the resistance readings in Gigohms or Megaohms between various parts of a test system, including cables from a 33kV circuit breaker to a transformer primary, transformer secondary cables to drive inputs, and drive outputs to two motors. Several connections showed low insulation values requiring re-termination.
The document reports the results of an insulation test of medium voltage cables at 2500V for 1 minute with respect to earth. It lists the resistance readings in Gigohms or Megaohms between various parts of a test system, including cables from a 33kV circuit breaker to a transformer primary, transformer secondary cables to drive inputs, and drive outputs to two motors. Several connections showed low insulation values requiring re-termination.
The document reports the results of an insulation test of medium voltage cables at 2500V for 1 minute with respect to earth. It lists the resistance readings in Gigohms or Megaohms between various parts of a test system, including cables from a 33kV circuit breaker to a transformer primary, transformer secondary cables to drive inputs, and drive outputs to two motors. Several connections showed low insulation values requiring re-termination.
The document reports the results of an insulation test of medium voltage cables at 2500V for 1 minute with respect to earth. It lists the resistance readings in Gigohms or Megaohms between various parts of a test system, including cables from a 33kV circuit breaker to a transformer primary, transformer secondary cables to drive inputs, and drive outputs to two motors. Several connections showed low insulation values requiring re-termination.