METHOD STATEMENT FOR

TV SPLITTER INSTALLATION AND WIRING


TERMINATIONS

Page 1 o/3

TV SPLITTER INSTALLATION AND WIRING


TERMINATIONS
MATERIAL TO BE USED:Flush mounted TV splitter metal enclosure with size 150xl50xlOOmm manufactured by
Eletra with sufficient knock outs and frame to install 2 way splitter and 6 way splitter in this
enclosure.
RG 6 - C5760 Coaxial Cable is installed between individual TV outlets and 6 way splitter
boxes installed in ground and first floor.

RG-11 C5034 outlet coaxial cable is installed between the dish in the roof annex floor to the
1s and ground floor splitter boxes.
RG 6 and RG 11 coaxial cables are manufactured by general cables , splitters used are 1x2
one nos and 2x6 two nos .Wisi make.

TOOLS USED:Cutting plier, insulation removing plier, Screw driver set


INSTALLATIQN:Flush mounted metal enclosure for TV splitter boxes are installed in ground and first floor
block walls in line with plaster guides and these enclosures are installed at a height of
600mm from the center of the box to finished floor level as per low current shop drawing
details.

WIRING TERMINATIONS^"
RG11Satellite coaxial cable is pulled from dish at the roof annex floor to the 1st floor TV splitter
box which contains 2-wav and 6 way-splitters Installed in RG-11 cable from dish is connected
to the TV receiver outlet with two input points installed in first floor. From the other outlet
point RG-11 cable is pulled to the input of the 2 way splitter which is installed in first floor TV splitter box.
Page 2 of3

From this 2 way splitter one cable is terminated to the input of the 6 way splitter and its 6
output are terminated with first floor individual TV outlet with RG-6 Coaxial Cable.
From the other output of 2 way slitter RG-11 coaxial cable is terminated to the ground floor
input of 6 way splitter which is installed in ground floor splitter box. 6 outputs of this 6 way
splitter is terminated with RG-6 Coaxial cable to the TV outlets in the ground floor.
No joints are made in the coaxial cable
All coaxial cables are terminated with special metal gland manufactured by
Wisi suitable for respective sized coaxial cables.

Printed circuit layout will be pasted inside splitter boxes

Every connected terminal in splitter boxes and respective T.V. outlets on the floor are identified by
approved labels.

END

Page 3 of 3

AL QASR DEVELOPMENT PROJECT


RIYADH-SAUDI ARABIA
METHOD STATEMENT FOR
CONDUIT DEVICES BACK BOXES,

PANEL ENCLOSURES, TTC, SPLITTER,


AND PULL BOXES INSTALLATION IN
BLOCK WALL

AL QASR PROJECT
PACKAGE 3 B 1 & 3 B 2
B u i l d i n g Typ e T 6 & T6 a

Page 1 of 3

CONDUIT DEVICES BACK BOXES, PANEL


ENCLOSURES, TTC, SPLITTER, AND PULL
BOXES INSTALLATION IN BLOCK WALL
MATERIAL TO BE USED:Galvanized steel back boxes, 7cm x 7cm x 4.7cm depth 1.1 mm wall
thickness with Earth terminals are used for wiring devices as back boxes

Eletra make.
For panel enclosure metallic enclosures zinc coated 1,2mm thick with epoxy
painting ivory color and with required knock out is provided Merlin Gerin

make
Telephone and splitter boxes are steel fabricated 1.2mm thick epoxy painted
and with sufficient knock cuts and the panel is flush type with door and lock
(Electra make)
Conduit is Saudi EGA make sizes used are 20mm, 25mm and 32mm all are
heavy gauge PVC with high impact and high temp resistance and fire
retardant.
TOOLS USED:1.
Concrete cutting grinder machine
2.
Spirit level
3. Measuring Tape
4.
Screw driver Sets
Preparations:The masonry wall is clean for any,, rough, surface and marking is done on the block
walls according to the dimensions approved shop drawing layout and miscellaneous
details for devices back boxes, panel enclosures and TTC, T.V. splitter and intercom
boxes.
INSTALLATIQNS:1. Ensure mortar is fully set before cutting the masonry wall

2. Cutting is done carefully and neatly by concrete cutting grinder machine


without cracking or causing damage to existing civil work.
3. A neat opening is cut of size to receive back boxes / enclosures and fixing plaster.
4. Back boxes are installed flush with nearby plaster guide.
Page 2 of 3

5. Spirit level is used check for horizontal and vertical position of these back boxes,
6. Extension rings will be used if back boxes fixed are found not flush with finish surface.
7. Conduit m sheet metal enclosures and steel back boxes are terminated with male adopter
with bushing and lock nuts.
8. Back boxes / panel enclosures are mounted as per approved height in shop drawing.
9. separate conduits are used for lighting, low current and power
installations.
10 It is made sure that the conduit installed connecting two outlet back
boxes take not more than two number of bends and enter the steel
boxes horizontally or vertically.
ll. Clearance of 150mm for other non electric pipes and three. Times the
diameter for adjacent electric conduit pipe is followed and preferably installed
above non-electric service pipes.

12 pull wires of 2mm dia galvanized steel wire will be installed after back boxes
connecting conduits are fixed by plaster and when plaster is set.
13 All back boxes and pull boxes if used subject to approval are closed
with polystyrene material so as to protect plaster cement from entering
these boxes.
14 Plastering is done for the embedded conduits and around back boxes neatly finishing is
done so that the exposed cover plates covering recessed boxes rest neatly on wall
surface without gaps and fully covering the back boxes.

15.Visual inspection is done for correct fixing and workmanship.

END

. Page 3 of 3

AL QASR DEVELOPMENT PROJECT


RIYADH - AUDI ARABIA
METHOD STATEMENT
FOR

POWER, TELEPHONE, INTECOM, TV


POWER CABLES ,WIRES, PULLING IN
RESPECTIVE FIRST FIX DEVICE BOXES
AND PANEL ENCLOSURE

PACKAGE 3 B 1 & 3 B 2
B u i l d i n g Typ e T 6 & T6 a

Page I of4

POWER, TELEPHONE, INTECOM, TV


CABLES, WIRES AND PULLING IN RESPECTIVE FIRST FIX
DEVICE BOXES AND IN PANEL ENCLOSURE
MATERIAL TO BE USED:Power Cables are of stranded cu conductor multicore XLPE insulated PVC sheathed feeder
cables 0.6/lKV of 90C temperature manufactured by Jeddah Cables.
Telephone wires and cables 2 and 12 paired are multi paired indoor type solid plain copper
conductor 0.6 mm dia PVC insulated and shielded, manufactured by Amaco cables.
Intercom wires are 3 pair, PVC insulated and unshielded type manufactured by General cables.

TV wires used are RG-6 and R6 - 1 1 coaxial cables, PVC insulated ,PVC sheathed.
EQUIPMENT AND TOOLS:1.
2.
3.
4.

Pull wires 30 mts 3.5mm flat


Locally made mandrel test kit
Nylon Rope size 8mm dia
Pull wire of 2mm dia solid steel galvanized wire.

Preparation:1. Following site delivery wires and cables are stored in dry areas and protected from
weather ,fumes, water.
2. All under ground power ,telephone. TV and power and Intercom conduits are mandrel
tested to check and clear any blockage.
3. All telephone, intercom, TV and power conduits are freed of burrs and cleaned and dried.
4. Conduits in concrete slabs, block walls are installed with 2mm dia. solid Galvanized
steel wires to check the conduits are free of any blockage and retained in empty conduits
with wooden blocks fastened at the end.
5. Post mandrel testing Nylon rope ,2mm dia galvanized steel wire is installed in all
under ground power and other conduits respectively and retained.

Page 2 of 3

INSTALLATTONS:Using the pre installed galvanized steel pull wire approved sizes of TV, Telephone and
intercom wiring is installed in the respective conduiting.
Power cables are pulled using already installed Nylon rope in the power conduits.
3M lubricants are used for pulling wires or cables if the character of pull would otherwise
damage conductors insulation or jacket
At outlets, a slack of 200mm extra wire is left and at every pull box extra length of 250 mm is
left for device terminations
Tagging is done for cables and all wires in pull boxes panel boards, outlet box, as a guide for
making connections.
Post pulling the ends of conductors and cables are wrapped with insulation tape, capped and
kept in respective device back boxes, panel enclosures and safely protected.

Testing :Visual inspection is conducted for workmanship Megger test is


carried for cables and wires Insulation debris if any is cleaned.

END

Page 3 o/3

AL QASR DEVELOPMENT PROJECT


RIYADH- SAUDI ARABIA
METHOD STATEMENT
FOR

TTC TERMINAL INSTALLATION AND TELEPHONE


WIRING TERMINATION

AL QASR PROJECT

PACKAGE 3 B 1 & 3 B 2
B u i l d i n g Typ e T 6 & T6 a

Page I of 3

TTC TERMINAL INSTALLATION AND


TELEPHONE WIRING TERMINATION
MATERIAL TO BE USED:Telephone terminal cabinet is made of steel enclosure with size 150 x
150 x 100 mm with sufficient knock outs and front door with lock. This
cabinet is flush mounted with labeling sheet equipped with relevant terminal
block and have 20 % spare for future expansion and wiring for extra
terminal blocks.
Terminal block are of Krone make and have thermo plastic bodies, Nickel
plated brass connectors galvanized screw terminals in both sides, wire guide

and have following specifications.


range of conductor diameter: up to 1.2mm
dielectric strength:
1500V (r, m, s)
minimum insulation resistance: 1000 M ohms at 500 V (dc)
Ambient Temp:
Relative Humidity:
Terminal block:

40 C
5 to 95%
10 pairs

Telephone cables used are 2p shielded 0.6mm dia.used between telephone


cabinet and telephone outlets.
12 pair shielded 0.6mm dia.is used between STC box to telephone terminal

cabinet.
Both the wires / cables are AM AGO make.
Tools used:0. Screw driver set
1 . Telephone wire punching tool
2. Hand Crimping tools
3. Lugs 0.6 mm dia.

Page 2 of3

INSTALLATION AND TERMINATIQNS:2 Nos. Telephone terminal blocks are installed on the guide rails provided in the telephone
terminal cabinet and the terminal blocks are fitted with nuts and bolts of required size.
12 pair incoming telephone cable is also terminated in the terminals of same
terminal block but on the incoming side of terminals.
All 2 pair outgoing telephone cables are terminated at the telephone outlets at respective floors.
These outlets are installed according to low current layout shop drawing at a height of 300mm
from finished floor level where RJ 1 1 jack connector assembly is in built in the outlet.
Filled in circuit directory is pasted inside telephone terminal cabinet and
every connected terminal inside respective outlets on the floor are identified
by approved labels.
The testing for continuity of the lines inside villa is carried out upon completion.

END