Easergy Flair 200C: Technical Data Sheet
Easergy Flair 200C: Technical Data Sheet
schneider-electric.com/energy-automation
schneider-electric.com
Introduction 3
Presentation 4
Fault passage indicators
Relevant measurements
Substation monitoring
10
Characteristics 11
Programmable automation system
12
Communication 14
Web Server
16
Order form
18
20
schneider-electric.com
Improved reliability :
DE58915EN
MV loop
T200
T200
4 channels
Flair 200C
T200
Source changeover switch
T200
16 channels
schneider-electric.com
schneider-electric.com
PE57571
Main components:
1 Upward-opening door with blocking system
11
10
3 Battery
9
8
7
6
2
4
Equipment fault
Battery fault
11
TX
RX
1
2
AC power on
tx
Transmit data
rx
Receive data
schneider-electric.com
The ICC algorithm is used on resonance earth. The principle of the ICC
algorithm can also be used with networks with directly earthed and
impedance-earthed neutral, if the value of the capacitive currents is
significant relative to the value
of the earth fault current.
Permanent phase-to-phase and phase-to-earth faults: tripping threshold
confirmed by an acknowledge time and network loss
Fault validation by network loss from the load current
Easergy Flair 200C is also available without the fault detection option.
Characteristics
Detector type
Ammetric detector (AMP)
Mains voltage
4 to 36 kV
4 to 36 kV
Frequency
Type of network
50/60 Hz
50/60 Hz
Resistor-earthed, directly earthed or isolated Compensated, resistor-earthed, isolated or directly earthed
A, B and C configurable
A and B configurable
Configurable from 40 to 800 A in increments of 1 A
A setup: configurable from 20 to 160 A in increments of 1 A
B and C setups: configurable from 2 to 160 A in increments of 1 A
By voltage/By current
By current
Phase fault: configurable from 40 ms to 800 ms in increments of 20 ms
Earth fault: configurable from 40 ms to 800 ms in increments of 20 ms
Configurable Yes/No (duration 3 s)
Configurable Yes/No
Minimum current
Acknowledge time
Fault reset
Indications
Remote control centre: phase at fault, summary of a phase fault, earth fault
Locally: by LED on the enclosure, by external indicator terminal (standard indicator unit)
Detector precision
With sensor:
Standard
High-performance
Standard
High-performance
10%
7%
10%
7%
5%
2%
5%
2%
schneider-electric.com
Measurement recording
Temperature measurement
-- cubicle interior: 2C from 20C to +70C
-- cubicle exterior: interior temperature 9C
Current measurement: I1, I2, I3, I0 and
Iaverage.
4 possible
measurement
setups
Setup 3
Setup 1
Flair
200C
Flair
200C
Power factor.
V2 V1
1
b
MT
MT
b
b
b
V1
V2
V1
V2
b
MT
MT
b
b
b
b
MT
MT
b
b
b
b
MT
MT
b
b
b
MT
MT
b
b
b
V1
b
MT
V2
Current measurement
Setup 4
V
BT
BT
b
b
b
Measurement characteristics
Voltage measurement
Setup 2
Flair
200C
V2 V1
V2 V1
Type of measurement
Input voltage
V2 V1
120/240 Vac
20% +10%; 50/60 Hz
Configurable from 0 to 11 h
200C
Value returned
Type A setup
Number of samples
Measurement precision
Current
Standard sensor
High-performance sensor
Without sensors
Voltage
Power factor
Frequency
Power (without CTs)
Flair
200C
50 Hz
0.02 Hz from 48 to 52 Hz
60 Hz
0.02 Hz from 58 to 62 Hz
1% at 600 A with 0.707 < |PF| < 1 on channel 1
5% at 600 A with 0.707 < |PF| < 1 on channel 2
DE58920
schneider-electric.com
DE58917EN
Example of substation
monitoring point:
LV
switchboard
RM6 24 kV
MV
switchboard
Public
lighting
cabinet
MV/LV transformer
schneider-electric.com
For all the logs, when the maximum storage capacity is reached, the most
recent event erases the oldest event.
Events
10000
Alarms
2 000
System
6000
Mesures
PE57508EN
Event log
30000
schneider-electric.com10
Easergy Flair 200C offers full access to all status and measurement
information and the controls of connected devices.
They are treated as an internal variable on which specific processing operations can be performed: archiving, monitoring,
control, alarms, etc.
Example of substation
communicating equipment:
Sepam protective relay
Power monitoring unit
LV circuit breaker
Customer counter
(or counting digital input)
Public lighting management.
LV
circuit-breaker
SM6 24 kV
MV switchboard
Metering
frame
PE57573En
MV/LV transformer
Number of slaves
Sepam
protection relay
PowerLogic
power meter
Twido
programmable
logic controller
Advantys OTB
input/output
module
schneider-electric.com11
Inputs/Outputs
Dielectric
Electromagnetic
Voltage
Battery
Type
Battery life from 20C to
+70C
Lifetime at 20C
6 inputs
3 outputs
IEC 60255-5
AC supply input
IEC 60255-5
IEC 60255-5
Rapid transients
IEC 61000-4-4
Electrostatic discharge
Radiated electromagnetic field
Radio frequency in common mode
50 Hz magnetic field
IEC
IEC
IEC
IEC
Surge
IEC 61000-4-5
IEC 61000-4-11
61000-4-2
61000-4-3
61000-4-6
61000-4-8
Power cuts:
Pulse magnetic field immunity
Damped oscillatory wave immunity
IEC 61000-4-9
IEC 61 000-4-12
level 3; criterion A
Environmental characteristics
Temperature
Relative humidity
Salt spray test
Storage temperature
IEC
IEC
IEC
IEC
IEC
60068-2-1 /
60068-2-2
60068-2-30
60068-2-11
60068-2-14
20C to + 70C
95%; 144 h ((6 x 12-h cycles at 55C + 12 h at 25C)
168 h
40C to +70C; maximum variation of 5C per min.
Mechanical characteristics
Cubicle material
Vibrations
Dimensions
Weight (typical)
Protection index
Polycarbonate
IEC 60068-2-6
HxWxD
IEC 60529
schneider-electric.com12
The Flair 200C is fitted with various devices allowing to perform specific
tailored functions or applications:
Calculation formulas available as a standard feature in the equipment.
An IEC 61131-3 programmable logic controller available as an option, and including a RTU control programming workshop
and a possible communication between equipment.
EM100043EN
Calculation formulas
The calculation formulas are available as a standard feature in the Flair
200C.They can be used in the Flair 200C to create relatively simple logic
equations not requiring a programme to be written in PLC language.
Example
Typical applications that can be created with
the calculation formulas:
Calculation of analogue values to
determine averages, alarms or any other
calculation based on variables.
Combinations of variables, such as:
-- Combining phase and neutral faults
rather than indicating them separately
-- Defining a synthesis of internal faults
-- Managing other equipment of the MV
substation such as the light control,
etc.
Use of a Digital Output (DO) for external
indication of earth fault and/or phase fault
presence.
schneider-electric.com13
The existing variables of the Flair 200C that can be used in the
programmes are: TSD, TSS, TM, TSL, DI, DO.
Virtual variables can also be created for the PLC programmes. They can
also be type: DI, DO, DDI, DDO, AI, AO.
EM100042EN
Optionally, the Flair 200C can incorporate the IEC 61131-3 programmable logic controller. This allows the user to create
specific tailored client applications.
Instruction List
The platforms programme can be loaded onto the equipment and then
checked via the Flair 200C Web server.
DM101151EN
Embedded
PLC
RTU Control :
development
platform
Programs
download
Variables exchanges
T200/F200C software
schneider-electric.com14
SCADA
Communication networks:
GSM/GPRS, Ethernet, PSTN, Radio...
or Ethernet
(1) Master-Master: this option is used to limit exchanges with non-permanent transmission media (Radio, GSM, GPRS, PSTN). A device
speaks only when it has something to say. On the other hand, the SCADA no longer controls the data flow and collisions between messages
can occur when several devices take control to speak at the same time. Easergy Flair 200C includes collision avoidance algorithms to deal
with this problem.
(2) In GPRS, the protocols manage the Permanent or Semi-permanent transmission mode. The Modbus TCP/IP and DNP IP protocols can
also manage the transmission mode Non permanent serving to limit data flows.
schneider-electric.com15
Technical characteristics
Non-insulated
Maximum transmission speed: 38400 bit/s
Main functions
Direct link and management of external transmission
devices:
Direct: radio modem
Hayes: telephone, GSM
Signals management:
Rx, Tx, DCD, DTR, DSR, RTS, CTS, RI
Signals management:
Rx, Tx, squelch, DCD, RTS
Parity, frame errors
FFSK modulation
1200-2400 baud
Reception level: -30 to +10 dBm on 600 Ohm
Transmission level: -10 dBm or 0 dBm
Receive access impedance: 600 Ohm or high impedance
Signals management:
Rx, Tx, squelch, Send Cd
Parity, frame errors
Management:
Parity, frame errors
GSM/GPRS modem
Dual-band modem GSM and GPRS (or four bands 900/1800/850/1900 MHz, availability to be confirmed)
Transmission data:
Ethernet port
Test mode:
Carrier generation
Test mode:
Carrier generation
IP protocols
schneider-electric.com16
DE58914EN
Web server
On-site
maintenance
GSM/GPRS, PSTN,
Ethernet/Intranet
GSM/GPRS
Ethernet
SMS
alert
Maintenance
and operation
services
PE57505EN
schneider-electric.com17
PE57506EN
Web serveur
Easier maintenance
Updating of software versions or change of protocol by downloading from
a PC.
Two software versions are saved. It is possible to switch between the two
versions.
Analysis of system Event Log file:
-- Storage of transmission events (to determine the origin of a
recurring communication fault)
-- Indication of transmission errors (CRC error, collisions, PSTN line
out of order, switchover to redundancy, etc.)
-- Indication of system events (start-up, resetting, change of
configuration, etc.).
PE57510EN
schneider-electric.com18
channels
x)
01
02
2 - PowerMeter
A
B
- Power Supply
4 - Protocols
M2
I2
D2
xx
5 - Modem
2
4
G
F
B
C
6 - Ethernet port
Z
E
Z
R
8 - Detector type
Z
A
D
Z
P
FR
EN
SP
PO
CH
GE
TU
PK
1 channels
2 channels
Without
With
Standard
Modbus et Modbus TCP
CEI 870-5-101 and CEI 870-5-104
DNP3 and DNP3 TCP
Other, contact us
Non-insulated RS232
RS232/485 insulated 2,5 kV
Quadriband GSM/GPRS with antenna and 5 m cable
PSTN
V23 FSK Radio modem: 600-1200 bauds
FFSK Radio modem: 1200-2400 bauds
Without
With
Without
Modbus Master RS485 modem, insulated 2 kV (R)
Without fault detection
Ammetric
ICC
Without
With
French
English
Spanish
Portuguese
Chinese
German
Turkish
Poland
To work out the reference of your Flair 200C, copy below the codes located to the left of the boxes you have checked
beforehand.
F2
10
Z-
Quantity :
schneider-electric.com19
Accessories
The Flair 200C is compatible with all current sensors of the Easergy range
and available commercially.
Easergy Flair 200C is calibrated in factory with the Easergy sensors to
assure you the announced performance.
Two ranges of opening and self-locking sensors are available in the
Easergy Flair 200C catalogue in the form of ready-to-connect kits.
DE58911
Setup type
Type A setup
com I3 I2 I1
Current sensors
High-performance
sensors
Resin-coated CTs
of the Easergy T200
monitoring and
control unit range
Type B setup
com Io I3 I1
Type C setup
com Io I3 I1
Reference
Quantity
Setup type A
59968
Setup type B
MV258152
Setup type C
L1 L2 L3
MV258153
Setup type A
MV258171
Setup type B
MV258172
Setup type C
MV258173
Setup type D
MV258174
59988
T200-CFG- ETH-3
T200-CFG- ETH-10
Configuration cables
schneider-electric.com20
Document Number ENMED305014EN - 062016 2016 Schneider Electric. All rights reserved.