Technical data sheet

Easergy Flair 200C


MV substation remote monitoring unit
MV electrical network management

schneider-electric.com/energy-automation

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Contents

Introduction 3
Presentation 4
Fault passage indicators

Relevant measurements

Substation monitoring

Digital control and substation monitoring

10

Characteristics 11
Programmable automation system

12

Communication 14
Web Server

16

Order form

18

Protecting the environment

20

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Introduction

Everywhere in the world, poor quality of electric power supply is no


longer accepted by consumers. In many countries, regulatory standards
have therefore been established to ensure a minimum quality of service
for electricity.
Of the many indexes, those most commonly used are:
SAIDI: standard average interruption duration index - e.g.: 96 minutes/year
SAIFI: standard average interruption frequency index - e.g.: 1.2 interruptions/year.
For power supply companies, the increase in quality of service must go hand-in-hand with an improvement in performance
and competitiveness and control of capital expenditure.
For an optimum response to these needs, power distribution companies are demanding new products and solutions to allow:

Improved reliability :

Efficiency improvement of power distribution:

Reduction in the duration of power cuts in the


event of incidents on the network (SAIDI)

Quality control of distributed voltage: measurement, alarms and


traceability

Reduction in the number of faults: e.g. through


monitoring of MV/LV transformers

Optimization of the network operating plan based on exhaustive data


concerning the network load.

Monitoring and improvement in the quality of


power: performance tools for fault analysis.

Capital expenditure optimisation:

Reduction in direct and indirect


operation costs:

Have precise, reliable data to define changes and investment planning


concerning the MV network load, transformer outgoer or LV outgoer
Safeguard network equipment through preventive actions.

Reduction in response times in the event of


incidents

Easergy products and solutions meet these objectives by providing you


with reliable, maintenance-free equipment that is easy to operate.

Reduction in substation inspection campaigns


for maintenance and measurement campaigns

Schneider Electric is constantly looking for new solutions to simplify the


operation of MV networks.

Vehicule charge (fuel consumption). It will


allow you to participate in the reduction of
CO2 emissions.

DE58915EN

Reduction in service operations upon


equipment failure through remote monitoring:
preventive alarm, overloading of network or
equipment (transformer)
HV/MV

MV loop

T200

T200
4 channels

Flair 200C

Remote control centre


T200
4 channels

T200
Source changeover switch
T200
16 channels

Example of MV loop managed by Easergy solutions

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Presentation

A product dedicated to remote monitoring of MV substations with a high


level of function integration
Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV substations of a public-private distribution
network or in customers substations.
Easergy Flair 200C is a tool that complements control units for MV substations (Easergy T200 I) and conventional fault
passage indicators (Easergy Flair).

The Flair 200C is an efficient tool


for reducing repair and fault finding
times.
It improves quality of service and
operation for power supply
companies.

Easergy Flair 200C is specially designed to meet customers requirements


for the management of MV substations. It provides compact, open
solutions:
Fault passage indicator compatible with any type of earthing system
Substation monitoring: sending of an alarm in the event of an incident
in the substation for efficient maintenance
Power monitoring unit on the MV and LV network for improved
monitoring of load curves and improved power distribution efficiency
Substation digital concentrator for interfacing between the substations
communicating equipment and the control centre
Communication with the remote control centre with call management
upon alarm
IEC61131-1 programmable logic controller (optional) and calculation
formulas (included as standard equipment) to create specific, tailored
applications.

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Presentation

PE57571

Compact cubicle for 1 or 2 measurement and fault current detection


channels
Easergy Flair 200C takes the form of a polycarbonate-ABS enclosure.

On option, Easergy Flair 200C is provided with a second measurement


and fault current detection channel.

The wall-mounting cubicle is provided with a padlocking system.

Main components:
1 Upward-opening door with blocking system
11

2 Power supply terminal block

10

3 Battery

9
8

4 1 or 2 current acquisition, fault current detection and measurement


processing circuits

7
6

5 Digital output (DO) for fault current detection external indications


6 USB configuration port

7 Ethernet communication and configuration port

2
4

8 GSM/GPRS modem (*)

9 SIM card (*)


10 Digital inputs/outputs terminal block
11 Local indications:

Equipment fault

Battery fault

GSM connection status

11
TX
RX
1
2

(*). GSM/GPRS modem version.

AC power on

tx

Transmit data

rx

Receive data

Channel 1 fault current detection

Channel 2 fault current detection

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Fault passage indicators

Easergy Flair 200C detects phase-to-phase and phase-to-earth fault


currents on networks with resistor-earthed, directly earthed or isolated
neutral, and compensated system without voltage measurement.
In the case of compensated (Petersen coil earthed neutral) networks, the value of the earth fault is low relative to the value of
the capacitive currents. As a consequence, conventional ammetric detection cannot be used. Easergy Flair 200C uses a new
Insensitive to Capacitive Currents detection technology.
To enhance the reliability of the information transmitted, detection of a fault current is confirmed by loss of the network.
The network loss information is generated either from the voltage failure information processed based on the power supply,
or from the load current on the line. Two fault current detection algorithms are available in the Easergy Flair 200C catalogue:

Ammetric detector (AMP)

Insensitive to Capacitive Currents (ICC) detector

For networks with resistor-earthed, directly


earthed and isolated neutral

The principle of the ICC detector is based on similarity analysis of phase


and earth fault currents to distinguish between an upstream earth fault
current and a downstream fault without voltage measurement.

Permanent phase-to-phase and phase-toearth faults: triggering threshold confirmed by


an acknowledge time and network loss
(Fast) phase-to-phase and transient phase-toearth faults (not confirmed by network loss)
Each type of fault has an associated counter
that can provide relevant information
concerning the number of faults for
maintenance

The ICC algorithm is used on resonance earth. The principle of the ICC
algorithm can also be used with networks with directly earthed and
impedance-earthed neutral, if the value of the capacitive currents is
significant relative to the value
of the earth fault current.
Permanent phase-to-phase and phase-to-earth faults: tripping threshold
confirmed by an acknowledge time and network loss
Fault validation by network loss from the load current

Fault confirmation by network loss

Operation on network with sustained fault or not.

Inrush filtering function at power up to


prevent untimely detection when switching on
loads.

Easergy Flair 200C is also available without the fault detection option.

Characteristics

Easergy Flair 200C then acts only as a substation measuring, supervision,


monitoring and control unit.

Detector type
Ammetric detector (AMP)

Insensitive to Capacitive Currents detector (ICC)

Mains voltage

4 to 36 kV

4 to 36 kV

Frequency
Type of network

50/60 Hz
50/60 Hz
Resistor-earthed, directly earthed or isolated Compensated, resistor-earthed, isolated or directly earthed

Type of sensor setup


Phase fault
Earth fault

A, B and C configurable
A and B configurable
Configurable from 40 to 800 A in increments of 1 A
A setup: configurable from 20 to 160 A in increments of 1 A
B and C setups: configurable from 2 to 160 A in increments of 1 A
By voltage/By current
By current
Phase fault: configurable from 40 ms to 800 ms in increments of 20 ms
Earth fault: configurable from 40 ms to 800 ms in increments of 20 ms
Configurable Yes/No (duration 3 s)

Network monitoring mode


Fault acknowledge time
Inrush
Operation with sustained fault

Configurable Yes/No

Minimum current

Configurable from 5 to 20 A in increments of 1 A

Acknowledge time

Configurable from 1 to 100 s in increments of 1 s

Network time without fault

Configurable from 1 to 10 s in increments of 1 s

Fault reset

Automatic upon voltage return: configurable Yes/No


After time delay: configurable from 1 to 12 h in increments of 1 h
At a distance via the remote control centre
Manual by push button on the enclosure

Indications

Remote control centre: phase at fault, summary of a phase fault, earth fault
Locally: by LED on the enclosure, by external indicator terminal (standard indicator unit)

Detector precision

With sensor:
Standard

High-performance

Standard

High-performance

Without power monitoring unitoption

10%

7%

10%

7%

With power monitoring unit option

5%

2%

5%

2%

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Relevant measurements

Measurement recording

Temperature measurement
-- cubicle interior: 2C from 20C to +70C
-- cubicle exterior: interior temperature 9C
Current measurement: I1, I2, I3, I0 and
Iaverage.

Measurements available with


power monitoring unit option
Current measurement: I1, I2, I3, I0 and
Iaverage
LV and MV voltage measurement and
monitoring
Frequency
Active, reactive and apparent power
Active and reactive energy with capability
for counter indexing

Easergy Flair 200C offers various modes for recording measurements


and transmitting them to the remote control centre. The criteria can be
combined together:
V
Recording: local recording in the Flair 200C internal log.
Flair
200C
Event recording: measurement transmitted at the request of the remote
control centre.
Dial-up: measurements are transmitted at the initiative of the Flair 200C
when the requisite conditions are met.
Measurements can be recorded in several ways:
-- regularly: sampled or averaged value with configurable period
V
-- upon exceeding a high or low threshold
Flair
-- upon variation or dead band (variation %)
200C
V2 V1
-- upon regular recording of Min. and Max. values over 1, 7 or 14
days.

4 possible
measurement
setups

Setup 3

Setup 1

Flair
200C

Flair
200C

Power factor.

V2 V1

Measurements and detection of possible fault


currents according to various setups
Setups
Fault detector
Current
Voltage
Power
Energy
Power factor

1
b
MT
MT
b
b
b

V1

V2

V1

V2

b
MT
MT
b
b
b

b
MT
MT
b
b
b

b
MT
MT
b
b
b

MT
MT
b
b
b

V1
b
MT

V2

Current measurement

Setup 4
V

BT
BT
b
b
b

Measurement characteristics
Voltage measurement

Setup 2

Flair
200C

V2 V1

V2 V1

Type of measurement

Flair from the power source


Single-phase

Input voltage

V2 V1
120/240 Vac
20% +10%; 50/60 Hz

Transformer time index (phase shift)

Configurable from 0 to 11 h

Network voltage rating (scaled)

Configurable from 200 to 36,000 V

200C

Value returned

V1 MV or LV: true rms value up to H15

Type A setup

I1, I2 and I3: true rms value up to H15


I0: value calculated from I1 + I2 + I3 (H1)
Average 3I:V from I1, I2 and I3

Type B and C setups

I1 and I3: true


Flair rms value up to H15
200C
I0: true rmsV2
value
up to H3
V1
I2: value calculated from I0-I1-I3 (H1)
Average 3I: from I1, I2 and I3

Number of samples

36 per period (50/60 Hz)

Measurement precision
Current

Standard sensor

5% from 100 to 500 A

High-performance sensor

2% from 100 to 500 A

Without sensors

0.5% from 100 to 500 A

Voltage

1% from 90 to 265 Vac

Power factor

1% at 600 A with 0.707 < |PF| < 1 on channel 1


5% at 600 A with 0.707 < |PF| < 1 on channel 2

Frequency
Power (without CTs)

Flair
200C

50 Hz

0.02 Hz from 48 to 52 Hz

60 Hz

0.02 Hz from 58 to 62 Hz
1% at 600 A with 0.707 < |PF| < 1 on channel 1
5% at 600 A with 0.707 < |PF| < 1 on channel 2

DE58920

Standard measurements with


fault passage indicator

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Substation monitoring

Voltage monitoring and quality control


With the power monitoring unit option, Easergy Flair 200C can indicate power supply faults and provide a log for improved
quality control of the power supplied.
Power off detection thresholds configurable from 5% to 95% of Un
Power on detection thresholds configurable from 70% to 120% of Un
Time for acknowledging power off and on configurable from 20 to 800 ms.

Digital inputs/outputs for substation


monitoring and control
6 configurable digital inputs:
Standard input:
goes to 1 when the digital input is active
FPI input:
goes to 1 when the digital input is active and causes the external
indicator to flash.
Each digital input has its associated counter.

3 configurable digital outputs:


Standard output:
the output is maintained when the associated variable goes to 1
Pulse output:
activation of the command generates on the output a pulse of duration
configurable between 50 ms and 5 s in increments of 5 ms.
Dual output:
2 outputs are used. This choice offers a simple solution for controlling
certain switches by means of double-bit commands.

DE58917EN

Example of substation
monitoring point:
LV
switchboard

RM6 24 kV
MV
switchboard

Transformer protection: TGPT2


Door opening
Switch position
LV outgoer fuse tripping

Public
lighting
cabinet

Public lighting fault.

MV/LV transformer

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

schneider-electric.com

Easergy Flair 200C


Substation monitoring

Archives, indications and alerts for optimum operation


and maintenance
All internal data (variables) and data coming from equipment connected to the Modbus local area network can be recorded
with time stamping.
This information can be transmitted to the remote control centre and/or archived in logs for consultation and downloading (in
the form of .xls files), by connecting a microcomputer locally or remotely.

Variable recording criteria:


Events: information transmitted to the SCADA system
These variables are recorded in the events log. They are transmitted to the remote control centre according to the protocol
exchange conditions
Alarms: spontaneous transmission
These variables are recorded in the alarm log. They trigger spontaneous dial-up to the remote control centre and can send
an SMS or an email according to the configuration
System: can be consulted locally, is designed for operation and maintenance: storing in memory of transmission events,
transmission errors, change of system configuration, etc.

For all the logs, when the maximum storage capacity is reached, the most
recent event erases the oldest event.

Time setting and event time stamping


Flair 200C time setting is performed:
Locally with a laptop PC;
Via the remote control system;
Via the Ethernet network.

Events

10000

Alarms

2 000

System

6000

Mesures

PE57508EN

Event storage capacity

With management of:


Time zones
Summer/winter time difference.
Precision of event time stamping:
Resolution: 1 ms
Discrimination between 2 events: 10 ms.

Event log

30000

schneider-electric.com10

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Digital control and monitoring of substation

Easergy Flair 200C offers full access to all status and measurement
information and the controls of connected devices.
They are treated as an internal variable on which specific processing operations can be performed: archiving, monitoring,
control, alarms, etc.

Example of substation
communicating equipment:
Sepam protective relay
Power monitoring unit
LV circuit breaker
Customer counter
(or counting digital input)
Public lighting management.

LV
circuit-breaker

SM6 24 kV
MV switchboard

Metering
frame

PE57573En

MV/LV transformer

Easergy Flair 200C, with an optional Ethernet port or a Modbus Master


RS232/485 local communication port, allows:
Interfacing of substation communicating equipment with the remote
control centre via the communication protocols and media available
in the Easergy Flair 200C catalogue. In this case, Easergy Flair 200C
serves as a communication concentrator and gateway.
Monitoring and control of equipment from a PC connected to
Internet via the Easergy Flair 200C Web server (GSM/GPRS or PSTN
transmission media).
Recording and time stamping of variables. Easergy Flair 200C offers
various possibilities for time setting, polling and time stamping of
changes of state depending on the external devices:
-- Sepam type slave, Wade range, Easergy range. These slaves
manage event time stamping and their clocks can be synchronized
by Easergy Flair 200C. The events with their associated dates are
read by Easergy Flair 200C every second.
-- Other slaves. For slaves not managing event time stamping, the
analogue or digital data are read and then generated as timestamped events by the Flair 200C.
Characteristics of a local area network
Protocol

Modbus/Modbus TCP Master

Number of slaves

31 in an RS485 link/20 in an Ethernet link

Maximum number of variables

Digital Inputs/Outputs: 400


Double-bit digital Inputs/Outputs: 200
Analog Inputs/Outputs: 300

Examples of connected equipments:

Example of variable configuration page

Modbus/Modbus TCP protocols

Sepam
protection relay

PowerLogic
power meter

Twido
programmable
logic controller

Advantys OTB
input/output
module

schneider-electric.com11

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Characteristics

Easergy Flair 200C designed to meet customers technical requirements


Electrical characteristics
Power supply

Inputs/Outputs

Dielectric

Electromagnetic

Voltage
Battery

Type
Battery life from 20C to
+70C
Lifetime at 20C

6 inputs
3 outputs

IEC 60255-5

AC supply input

IEC 60255-5

Current Transformer input

IEC 60255-5

Rapid transients

IEC 61000-4-4

Electrostatic discharge
Radiated electromagnetic field
Radio frequency in common mode
50 Hz magnetic field

IEC
IEC
IEC
IEC

Surge

IEC 61000-4-5

Immunity to voltage dips

IEC 61000-4-11

61000-4-2
61000-4-3
61000-4-6
61000-4-8

120/240 Vac 20% +10%; 50/60 Hz


Sealed spiral lead maintenance-free type: 4 V; 2.5 Ah
Minimum 4 h (minimum 3 h with Ethernet option)
10 years
Insulated, dry loop polarized at 5 V internally
Insulated (50 Hz/1 min.): 1.5 kV
30 VA (maximum 60 Vdc or 125 Vac)
Insulation (50 Hz/1 min.): 10 kV
Surge (1.2/50 s): 20 kV
Insulation (50 Hz/1 min.): 2.5 kV
Surge (1.2/50 s): 5 kV
4 kV on mains, sensor and RS485 (criterion A)
2 kV on logical inputs/outputs and external indicator
terminal (standard indicator unit) (criterion A)
1 kV on GSM/GPRS antenna (criterion B)
Level 3; 8 kV in air; 6 kV at contact (criterion A)
80 MHz; 3 GHz; 10 V/m (criterion A)
0.15 MHz to 80 MHz; 10 Vac (criterion A)
30 A/m continuous-duty and 300 A/m from 1 to 3 s (criterion A)
2 kV level 3 in common mode (criterion A)
1 kV level 2 in differential mode (criterion A)
Voltage dip:

30% reduction for 0.5 period (criterion B)


60% reduction for 5 periods (criterion C)
60% reduction for 50 periods (criterion C)

Power cuts:
Pulse magnetic field immunity
Damped oscillatory wave immunity

IEC 61000-4-9
IEC 61 000-4-12
level 3; criterion A

greater than 95%, 250 periods (criterion C)


1000 A/M Level 4 (criterion A)
2.5 kV in common mode
1 kV in differential mode

Environmental characteristics
Temperature
Relative humidity
Salt spray test
Storage temperature

IEC
IEC
IEC
IEC
IEC

60068-2-1 /
60068-2-2
60068-2-30
60068-2-11
60068-2-14

20C to + 70C
95%; 144 h ((6 x 12-h cycles at 55C + 12 h at 25C)
168 h
40C to +70C; maximum variation of 5C per min.

Mechanical characteristics
Cubicle material
Vibrations
Dimensions
Weight (typical)
Protection index

Polycarbonate
IEC 60068-2-6
HxWxD
IEC 60529

10 to 2000 Hz; 2 g peak-to-peak


333.5 x 210 x 104 mm
2.5 kg
IP21 (IP2X with cubicle open); IK07

schneider-electric.com12

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Programmable automation system

The Flair 200C is fitted with various devices allowing to perform specific
tailored functions or applications:
Calculation formulas available as a standard feature in the equipment.
An IEC 61131-3 programmable logic controller available as an option, and including a RTU control programming workshop
and a possible communication between equipment.

EM100043EN

Calculation formulas
The calculation formulas are available as a standard feature in the Flair
200C.They can be used in the Flair 200C to create relatively simple logic
equations not requiring a programme to be written in PLC language.

Example
Typical applications that can be created with
the calculation formulas:
Calculation of analogue values to
determine averages, alarms or any other
calculation based on variables.
Combinations of variables, such as:
-- Combining phase and neutral faults
rather than indicating them separately
-- Defining a synthesis of internal faults
-- Managing other equipment of the MV
substation such as the light control,
etc.
Use of a Digital Output (DO) for external
indication of earth fault and/or phase fault
presence.

These formulas can be used to create logic equations based on


combinations of variables more simply than a PLC programme. The
variable types that can be used are the same as for PLC programmes
(existing variables or virtual variables created specifically).
The following functions can be incorporated in the formulas:
Mathematical functions: absolute value, square root, natural logarithm,
base-10 logarithms, exponentials, powers, integer part, etc.
Statistical functions: smallest and largest values, sum and average of
values, etc.
Logic functions: set duration pulse, status copy after a set time, status hold
for a set time, etc.
Time/date functions: current date and time, character string converted
into date and time, time between two executions of formulas, test whether
current day is a working day, etc.
Other functions: values bounded by min and max, delta between previous
and current value.

schneider-electric.com13

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Programmable automation system

RTU Control programmable logic controller

The existing variables of the Flair 200C that can be used in the
programmes are: TSD, TSS, TM, TSL, DI, DO.
Virtual variables can also be created for the PLC programmes. They can
also be type: DI, DO, DDI, DDO, AI, AO.

EM100042EN

Optionally, the Flair 200C can incorporate the IEC 61131-3 programmable logic controller. This allows the user to create
specific tailored client applications.

A specific development platform (RTU Control) is provided (on the


Easergy CD supplied with the equipment) to create or modify a PLC
programme from the following programming languages:
SFC Sequential Function Chart
EM100041EN

FBD Function Block Diagram


LD Ladder Diagram
ST Structured Text
Il

Instruction List

The platforms programme can be loaded onto the equipment and then
checked via the Flair 200C Web server.

DM101151EN

A specific page is used to manage the programme (start, stop) as well as


the associated variables and another page is used to create and manage
the calculation formulas.

Embedded
PLC
RTU Control :
development
platform

Programs
download

Variables exchanges

T200/F200C software

Inputs/outputs from internal I/O


or from an external PLC

Communication between equipment


The programmable automation system option also includes a complementary function for communication between equipment
including a Modbus exchange via a TCP/IP link between Flair 200Cs and/or T200s connected on the same MV loop.
This communication allows the exchange of a data table between these Flair 200Cs and/or T200s. This communication
between equipment is typically used for self-healing network applications.
A specific page on the Flair 200C server is used to define the exchange table and this functions operating parameters.

schneider-electric.com14

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Communication

Open to all SCADA systems


Easergy Flair 200C can manage both a serial type protocol and IP protocols (Example: IEC 870-5-101 and IEC 870-5-104).
It is thus possible to mix serial and IP transmission media on a given application.
Two versions or two different protocols are embedded (e.g. IEC 101/104 and DNP3), thereby allowing switch over the other
protocol in total security.

A communications catalogue that is constantly enriched:


IEC 870-5-101 and
IEC 870-5-104 protocols
Two transmission modes are available for each
configuration:
Asymmetric (Master/Slave mode)
Symmetric (Master/Master mode)(1)

DNP3 serial and TCP protocols(2)


Level supported for commands and replies: 3
Transmission in Master/Slave mode if
unsolicited response operation is not used

SCADA
Communication networks:
GSM/GPRS, Ethernet, PSTN, Radio...

Transmission in Master/Master mode(1) if this


type of operation is used.

Modbus serial and TCP protocols(2)

IEC, Modbus, DNP3


protocols, etc

Transmission in Master/Slave mode


Transmission in Master/Master mode(1) with
the report by exception function.

Modbus/Modbus TCP protocol RS485

or Ethernet

Other proprietary protocols


We have extensive experience of interoperability
of our protocols via our numerous projects
worldwide (contact us).

Example of communication network and protocols

(1) Master-Master: this option is used to limit exchanges with non-permanent transmission media (Radio, GSM, GPRS, PSTN). A device
speaks only when it has something to say. On the other hand, the SCADA no longer controls the data flow and collisions between messages
can occur when several devices take control to speak at the same time. Easergy Flair 200C includes collision avoidance algorithms to deal
with this problem.
(2) In GPRS, the protocols manage the Permanent or Semi-permanent transmission mode. The Modbus TCP/IP and DNP IP protocols can
also manage the transmission mode Non permanent serving to limit data flows.

schneider-electric.com15

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Communication

An extensive choice of modems


Integrated modems
Modems and com. port
RS232 serial interface

Technical characteristics
Non-insulated
Maximum transmission speed: 38400 bit/s

Main functions
Direct link and management of external transmission
devices:
Direct: radio modem
Hayes: telephone, GSM
Signals management:
Rx, Tx, DCD, DTR, DSR, RTS, CTS, RI

Voice modem (PSTN)

Standard V.32 bis


300 to 14400 bits/s
Insulation: 8 kV

Message repetition (3)


Main dial-up No.
Backup dial-up No.

FSK radio modem

FSK modulation V23


200 or 600-1200 baud
Reception level: -30 to +10 dBm on 600 Ohm
Transmission level: -10 dBm or 0 dBm
Receive access impedance: 600 Ohm or high impedance

Signals management:
Rx, Tx, squelch, DCD, RTS
Parity, frame errors

FFSK modulation
1200-2400 baud
Reception level: -30 to +10 dBm on 600 Ohm
Transmission level: -10 dBm or 0 dBm
Receive access impedance: 600 Ohm or high impedance

Signals management:
Rx, Tx, squelch, Send Cd
Parity, frame errors

Multidrop private dedicated


line modem (DL)

FSK V.23 modulation: 600 - 1200 bd


V.24 interface
2-wire half-duplex or 4-wire full-duplex transmission
Line impedance: 600 Ohms or high impedance (10 kOhm)
Carrier loss detection: 10 ms
Carrier presence detection: 15 ms
Isolation: 8 kV

Management:
Parity, frame errors

GSM/GPRS modem

Dual-band modem GSM and GPRS (or four bands 900/1800/850/1900 MHz, availability to be confirmed)

Transmission data:

FFSK radio modem

Triple-band collinear aerial with 6-dB gain and 5-m cable


- Indoor/outdoor installation

Ethernet port

10 base T/100 base T - TX (RJ45)


10/100 Mbits

Test mode:
Carrier generation

Test mode:
Carrier generation

Message repetition (3)


Main call no.
Backup call number
SMS transmission (in GSM)
Management of IP protocols
Management of

IP protocols

External modems and transmission devices


Flair 200C manages all types of external modem and transmission devices via the RS232 or Ethernet link.

schneider-electric.com16

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C

DE58914EN

Web server

On-site
maintenance

Local and remote operation and


maintenance by embedded Web server
Easergy Flair 200C incorporates a web data server in HTML page form for
data configuration and monitoring. All that is needed to log on to the Flair
200C is a PC provided with a web browser.

GSM/GPRS, PSTN,
Ethernet/Intranet

GSM/GPRS
Ethernet

Remote access is possible via GSM, GPRS, Ethernet and PSTN


transmission networks, and can be implemented in parallel from the
remote control centre.
Thanks to this remote access and its capability to send e-mails and sms,
the Flair 200C offers you a cost-efficient solution to monitor your MV
substation without SCADA system.
In local connection mode, pages are refreshed automatically upon a
change of state or cyclically. The embedded web server allows local
monitoring of the substation.

User-friendly operation and control


E-mail
alert

SMS
alert

Maintenance
and operation
services

In parallel to network operation and control from the SCADA system,


equipment operation can be controlled via 3 pages:
Display of states and measurements
Commands: reset fault detectors and other digital outputs, reset or
preset fault or energy counters. Command sending is secured (selection
and confirmation)

PE57505EN

Consultation of archived data with saving to PC in CSV file form for


analysis.
The views are refreshed regularly or automatically upon a change of state.

Secure multilingual server


The home page allows you to select the server menu language.
The available languages in standard configuration are:
English, French, Spanish, Portuguese, etc.
Data literals are customizable
Data access is secured by password.
Welcome page - Web server

Three access levels can be defined: Administrator, Operator, Monitoring.

schneider-electric.com17

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C

PE57506EN

Web serveur

Easier maintenance
Updating of software versions or change of protocol by downloading from
a PC.
Two software versions are saved. It is possible to switch between the two
versions.
Analysis of system Event Log file:
-- Storage of transmission events (to determine the origin of a
recurring communication fault)
-- Indication of transmission errors (CRC error, collisions, PSTN line
out of order, switchover to redundancy, etc.)
-- Indication of system events (start-up, resetting, change of
configuration, etc.).

PE57510EN

Equipment status monitoring page

Communication analyser. This analyser allows observation of frames


exchanged with the remote control centre and any Modbus/Modbus TCP
slaves in the substation.

Rapid, reliable setup


Downloading of data configurations
Configuration is performed by downloading a configuration file. The
equipment is delivered with factory settings.

Preparation of typical configuration settings.


Configuration Save/Restore page

An off-line configurator allows customer configuration settings to be


prepared from typical data. The data are saved to PC in text format.

Partial configuration of equipment.


The Easergy Flair 200C configurator accepts a partial text file for the
modification of a variable, for example. This improves the reliability of
installed base revision for a change of settings (e.g. communication
settings).

Equipment data saving to PC

schneider-electric.com18

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Order form

Configure your Easergy Flair 200C


Fill only one box per option (put a x as per
1 - Number of

channels

x)

01
02

2 - PowerMeter

A
B

- Power Supply

4 - Protocols

M2
I2
D2
xx

5 - Modem

2
4
G
F
B
C

6 - Ethernet port

Z
E

7 - Local area network

Z
R

8 - Detector type

Z
A
D

9 - IEC 61131-1 programmable logic controller

Z
P

10 - Factory database language

FR
EN
SP
PO
CH
GE
TU
PK

1 channels
2 channels
Without
With
Standard
Modbus et Modbus TCP
CEI 870-5-101 and CEI 870-5-104
DNP3 and DNP3 TCP
Other, contact us
Non-insulated RS232
RS232/485 insulated 2,5 kV
Quadriband GSM/GPRS with antenna and 5 m cable
PSTN
V23 FSK Radio modem: 600-1200 bauds
FFSK Radio modem: 1200-2400 bauds
Without
With
Without
Modbus Master RS485 modem, insulated 2 kV (R)
Without fault detection
Ammetric
ICC
Without
With
French
English
Spanish
Portuguese
Chinese
German
Turkish
Poland

To work out the reference of your Flair 200C, copy below the codes located to the left of the boxes you have checked
beforehand.

Reference of your configured Easergy Flair 200C :


1


F2

10
Z-

Quantity :

schneider-electric.com19

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Order form (accessories)

Accessories
The Flair 200C is compatible with all current sensors of the Easergy range
and available commercially.
Easergy Flair 200C is calibrated in factory with the Easergy sensors to
assure you the announced performance.
Two ranges of opening and self-locking sensors are available in the
Easergy Flair 200C catalogue in the form of ready-to-connect kits.

DE58911

Setup type

Type A setup
com I3 I2 I1

Current sensors

High-performance
sensors
Resin-coated CTs
of the Easergy T200
monitoring and
control unit range

MF1 standard sensors


CTs with protected
blades of the Easergy
Flair detector range

Type B setup
com Io I3 I1

External indicator terminals


Standard indicator
unit
Mounted outside the
substation

Internal indicator unit


Mounted inside the substation,
provided with a 30 cm
fibre-optic light guide

Type C setup
com Io I3 I1

Standard sensors: split CTs - IP20


Standard sensors

Reference

Quantity

Setup type A

Kit of 3 MF1 split phase CTs


+ connection cable

59968

Setup type B

Kit of 2 MF1 split phase CTs


+ 1 MFH earth CT
+ connection cable
Kit of 1 MFH split earth CT
+ connection cable

MV258152

Setup type C

L1 L2 L3

MV258153

High-performance sensors: Resin-coated CTs - IP43


High-performance
sensors

Setup type A

Kit of 3 split phase CTs


+ connection cable

MV258171

Setup type B

Kit of 3 closed phase CTs for RM6

MV258172

Setup type C

Kit of 2 split phase CTs


+ 1 earth CT
+ connection cable

MV258173

Setup type D

Kit of 1 split earth CT


+ connection cable

MV258174

Standard indicator unit (BVE)

59988

USB configuration cable, 3 m

T200 -CFG- USB

Ethernet configuration cable, 3 m

T200-CFG- ETH-3

Ethernet configuration cable, 10 m

T200-CFG- ETH-10

External indicator terminals

Configuration cables

schneider-electric.com20

MV ELECTRICAL NETWORK MANAGEMENT // EASERGY RANGE

Easergy Flair 200C


Protecting the environment

Make energy safer, more reliable,


more efficient and more productive
Schneider Electric has staked out unique positions
to serve the markets emerging needs, with
solutions that deliver energy savings of up to 30%,
reliable, uninterrupted power and easy
on-site or remote control of installations.

Schneider Electric Industries SAS


35, rue Joseph Monier
92506 Rueil Malmaison (France)
Phone: +33 (0) 1 41 29 70 00
www.schneider-electric.com

Document Number ENMED305014EN - 062016 2016 Schneider Electric. All rights reserved.