Technical Data Sheet Genset 1400

TWINGEN 1400kVA (2x700kVA)


1800 RPM/60 Hz/380 volts

Genset Dimensions
Length
M
6,0
Width
M
2,42
Height
M
2,53
Weight
Kg
12T
Package Performance
Power rating Standby
kVA/kW
1400/1120
Power rating Prime Power (PRP)
kVA/kW
1250/1000
Power rating Continuos Operation (COP)
kVA/kW
937/750
Fuel Consumption
Tank Capacity
L
2000*
100% load with fan
g/kWh
209*
75% load with fan
g/kWh
202*
50% load with fan
g/kWh
204*
Cooling System
Engine Coolant Temperature
C
103
Air-on temp
C
58
Air flow restriction (system)
kPa
0
Air flow (maximum @ rated speed for standard
kg/s
24,6*
radiator arrangement)
Engine coolant capacity with radiator
L
120*
Engine coolant capacity without radiator
L
66*
Exhaust System
Air Consuption
m3/min
93,2*
Exhaust stack gas temperature
C
512
Exhaust gas flow rate
m3/min
235,2*
Max allowable air intake restriction
kPa
5
Heat Rejection
Heat rejection to coolant (total)
kW
496*
Heat rejection to exhaust (total)
kW
1000*
Heat rejection to atmosphere from engine
kW
48*
Alternator
Insulation class
C
180
Output in three phases - Standby
1546*
kVA
Output in three phases Prime Power
1514*
kVA
Output in three phases Continuos Power
1382*
kVA
+
Accuracy (stability) of Voltage Regulation
0,5%
%
According to: IEC 60034 - NBR 5117 - NEMA MG1 - VDE530 ISO8528 - CSA. MG1 - VDE530 - ISO8528 - CSA.
Lube System
Oil Capacity
Min (L)
Mx (L)
64*
84*
Circuit Braker 2 units
SCHNEIDER NS16H1
Make and Type
Number of Poles
3 poles
Rating
A
1600
Rated insulation voltage
Min (V)
Mx (V)
1000
1250
Closing Time
ms
< 50
Rated ultimate breaking capacity
kA rms
H1=42
Rated service breaking capacity Ics = Icu x
%
100
Engine Arrangement
2x TAD1642GE, 700kVA-560 kW Documento N 21388261 Index 03
Radiator Arrangement
2x Cooling package, fan 890mm
* Values multiplied by 2, considering the Twingen arrangement (2 engines of 700kVa)