SCHEDULE OF LOADS

GENERAL NOTES:
1.

2
3.
4.
5.
6.
7.
8.
9.

10.
11.

12.

ALL WORKS SHALL COMPLY WITH THE PROVITIONS OF THE PHILIPPINE REPUBLIC
CODE WITH RULES AND REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES
IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCE WITH THE RULES AND
REGULATIONS OF THE UTILITY COMPANY CONCERNED.
ALL ELECTRICAL INSTALLATIONS SHALL BE DONE UNDER DIRECT SUPERVISIONS
OF A DULY LICENSED ELECTRICAL ENGINEER.
ALL WIRING SHALL BE IN RIGID STEEL CONDUIT UNLESS OTHERWISE INDICATED,
CONDUIT MUST BE REAMED, THREADED, CLEANED COATED WITH SUITABLE JOINT
COMPOUND.
SERVICES TO PREMISES SHALL BE 220 VOLTS, SINGLE PHASE, 2 WIRE + GROUND
AS INDICATED IN THE PLAN.
PANELBOARDS CABINET SHALL BE PROPERLY GROUNDED.
THE CONTRUCTOR SHALL BE VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE
ENTRANCE FOR CONNECTION TO POWER SUPPLY.
UNLESS OTHERWISE SPECIFIED THE MINIMUM SIZE OF CONDUCTOR SHALL BE NO.3.5MM
THW & 15MM DIA EMT CONDUIT PIPE.
ALL MATERIALS SHALL BE NEW AND AND OF DULY APPROVED BY THE PHILIPPINE
STANDARD BUREAU AND SHALL BE CORROSION RESISTANT.
ALL CONDUIT RUNS, CONVENIENCE AND LIGHTING OUTLETS INDICATED AND LOCATED
IN THIS PLAN ARE DIAGRAMMATIC, EXACT LOCATIONS IN WALL CEILING AND FLOOR,
SHALL BE DETERMINED IN THE FIELD BY THE SUPERVISION OF FIELD ENGINEER OR
OWNER.
STANDARD TYPES OF ACCESSORIES SPLICING DEVICES, TERMINATION AND OTHER
APPLIANCES FOR THE ENTIRE ELECTRICAL INSTALLATION SHALL BE CASED.
ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE
FINISHED FLOOR.
A.
PANEL BOARD - 1.50M A. C.O. / OUTLETS - AS INDICATED
B.
SWITCH
- 1.40M
B. LIGHTING
- AS INDICATED
WIRES / CABLES INSTALLATIONS SHALL BE COLOR CODED AS FOLLOWS:
LINE A
BLACK
LINE C
YELLOW
LINE B
RED
GROUNDING
GREEN

CIRCUIT
NUMBER

LIGHTING PANEL
LIGHT

C.O.

LED
STRIP

SWITCHES
S1

S2

SIZE OF CIRCUIT
BREAKER

NO. & SIZE OF


CONDUCTOR

SIZE OF EMT
CONDUIT

PHASE

VOLT

220

I 1 = 15W LED STRIP LIGHT

15 VA / 220 = 0.06 A

15 A

3.5 MM2 THHN

1/2" DIA

220

I 2 = 300W JUICER +500W REF. +2(300W) BLENDER +


30W POS + 22W WATER PUMP
1452W / 220V = 6.60 A

15 A

5.5 MM2 THHN

1/2" DIA

COMPUTATIONS

S3

CT

I T =0.06 + 6.6 0 =

6.66 A

TO KWM
PANEL BOARD
BOLT-ON TYPE

USE 8.0 MM2 THHN WIRE

20AMP
MAIN
CKT 1
L.O.

15AMP

CKT 2
C.O.

15AMP

ELECTRICAL SPECIFICATION:
1.
2.
3.
4.
5.
6.
7.
8.
9.

SINGLE LINE DIAGRAM

ALL ELECTRICAL INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF


THE LATEST EDITIONS OF THE PHILIPPINE ELECTRICAL CODE AND WITH
THE RULES AND REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION.
ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR
LOCATION PURPOSES.
SERVICE ENTRANCE TO THE UNIT SHALL BE 220V SINGLE PHASE. ALL WIRING
INSTALLATIONS SHALL BE IN EMT PIPES (UNLESS SPECIFIED).
ALL SPECIAL PURPOSE OUTLETS SHALL BE OF PROPER TYPE RATING AND
READILY ACCESSIBLE. ADEQUATE AND EFFECTIVE EQUIPMENT GROUND SHALL
BE PROVIDED MIN. WIRE SIZE OF.
NO. 3.5MM THW FOR LIGHTING AND NO.5.5 MM2 THHN FOR OUTLETS.
FOR CONVENIENCE OUTLET(UNLESS SPECIFIED) USE GREEN COLORED WIRE
FOR GROUNDING CONDUCTOR.
NO ALTERATIONS ARE ALLOWED UNLESS WITH WRITTEN APPROVAL FROM THE
OWNER AUTHORIZED ELECTRICAL ENGINEER.
BRANCH CIRCUITS SHALL NOT BE LOADED MORE THAN 80% OF ITS AMPACITY
RATING.
ALL ELECTRICAL INSTALLATIONS SHALL BE DONE UNDER THE DIRECT
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR BY A
LICENSED MASTER ELECTRICIAN.

PROJECT TITLE:

FRUITFULL COUNTER
LOCATION: ROBINSONS PLACE BUTUAN

LEGEND:
M

KILO-WATT HOUR METER


PANEL BOARD
CIRCUIT BREAKER
CONVENIENCE OUTLET

ELECTRICAL LAY OUT PLAN

CIRCUIT HOMERUN
LED STRIP LIGHT

SHEET CONTENT:

OWNER:

PREPARED BY:

APPROVED BY:

AS SHOWN

THIRSTY
SCALE:

SHEET NO.

JOHN PAGES
DATE:

DATE:

E1