Download as pdf
Download as pdf
You are on page 1of 1
§ EMERSON. May 31, 2008, Certificate of Compliance 2006 International Building Code All Liebert Equipment -- Precision Air Conditioning, Uninterruptible Power Supplies and Distribution Equipment -- has been designed to comply with the structural design requirements defined in chapter 16 of the 2006 International Building Code (2003 1BC) when installed under the under the following conditions: * Building Occupancy Categories |, 11,11! or IV (Sometimes referred to as Seismic Use Group) Seismic Design Category A, B or C Seismic Importance factor 1.0 It is assumed the method of attachment of our equipment to the structure is a rigid attachment per ASCE standard 7-98 section 9.6.3.3. (If the equipment is to be flexibly attached or vibration isolation is being utilized please consult the factory.) If the general compliance certification conditions initially listed above do not meet your specific needs please contact us with your specific requirements. Please provide the following building parameters © Seismic Use Group, © Seismic Design Category Application importance factor. (We will assume 1.0 if not specified) Sos and Sox Planned method of attachment (We will assume rigid unless specified) We also currently provide the ability to fasten and certify our equipment up to Seismic Zone 4 per the 1997 UBC. ck Marketing Liebert Corp. GiLiebert™