QEA

Exhaust Air
Mixing Box

QRA
QSA
Return Air
Blower

CONDITIONED
QBP SPACE
td =75oF
RH =60%

QR
o
td =95 F
QOA QSA
tw =82oF
Qcc Supply Air
Outdoor Air Blower
Mixing Box
Cooling Coil
Qcc - Air Flow at Cooling Coil

ERSH
Qcc 
1.09 t d  t adp 
Where:
Qcc = Air Flow at Cooling Coil in cfm
ERSH = Effective Room Sensible Heat in Btu/hr
FBP = By-Pass Factor
td = Design Dry Bulb Temperature in oF
tadp = Apparatus Dew Point Temperature in oF
ERSH = Effective Room Sensible Heat

Computed from the Actual Sensible Load in the Conditioned Space


taken from ASHRAE Handbook Fundamentals Edition
tadp – apparatus dew point temperature
Taken from the Psychrometric Chart
Temperature in the Process at saturation point

Apparatus
Dew Point
RE – Refrigerating Capacity

RE  4.45  Qcc   hEC  hLC 


Where:
RE = Refrigerating Capacity in Btu/hr
Qcc = Air Flow at Cooling Coil in cfm
hEC = Enthalpy entering coil in Btu/lb
hLC = Enthalpy leaving coil in Btu/lb
hEC

hLC E
R
tECd – dry bulb temperature entering coil

QR t d  QOAtOA
t ECd 
QCC
Where:
tECd = dry bulb temperature entering coil in oF
QR = Return Air Flow in cfm
QOA = Outdoor Air Flow in cfm
tOA = Outdoor Air Temperature in oF
QCC = Air Flow at Coiling Coil in cfm
tLCd – dry bulb temperature leaving coil

t LCd  t adp  FBP   t ECd  t adp 

Where:
tLCd = dry bulb temperature leaving coil in oF
tECd = dry bulb temperature entering coil in oF
tadp = apparatus dew point temperature in oF
FBP = By-Pass Factor