We reserve the ownership under the law of this drawing with prohibition Ci riserviamo la proprietá a termini di legge di questo

of even partial reproduction and to make it known to third persons disegno con divieto di riprodurlo anche in parte o di
without our written authorization renderlo noto a terzi senza nostra autorizzazione scritta.
F F.A.T. REVISION E1 06/03/2000 CAPPA QUIRE SOCST
E FINAL E1 19/11/1999 RIVRO QUIRE SOCST
I/O LIST 231_LA_WP_01001F
D TAGS ASSIGNMENT E1 05/05/1999 CAPPA VALGI SOCST
C SECOND REV. P&I E1 20/04/1999 VALGI QUIRE SOCST PANEL: FCS inside control board IP03
DESTINAZ DATA COMPIL. CONTROL. APPROV. DCS type: YOKOGAWA CENTUM
REV DESCRIZIONE - Description Destination Date Drawn up Checked Approved JOB: 231 - YAZD (IRAN)

Signal type Ctr Red Status Tag Name in P&I Tag Name in DCS Range (EU) Description From To Node Nest Slot Channel Nest Type Card type Interlocks/Cle
ANALOGICAL INPUTS (AI)
4-20 mA X R 04_1LIC-04 04_1LIC-04 0 - 100 % 04-B-01 LEVEL CTRL FIELD DCS 1 2 13 1 AMN11 AAM10 Interlock n.27B
4-20 mA X R 04_1PRCA-09 04_1PRC-09 0 - 60 mBar abs 04-C-01 PRESSURE CTRL FIELD DCS 1 2 14 1 AMN11 AAM10
4-20 mA X R 04_1PRC-10 04_1PRC-10 0 - 50 mBar abs EG-4127 PRESSURE CTRL FIELD DCS 1 2 15 1 AMN11 AAM10
4-20 mA X R 04_1PRCA-11 04_1PRC-11 0 - 4 Bar 04-C-01 HEAT. PRESS. CTRL FIELD DCS 1 2 16 1 AMN11 AAM10 Cle n.7
4-20 mA X R 04_1TRCA-08 04_1TRC-08 0 - 400 Degc EG-4115 TEMP. CTRL FIELD DCS 1 3 1 1 AMN11 AAM10
4-20 mA X R 04_1TRCA-16 04_1TRC-16 0 - 400 Degc 04-C-01 TEMP. CTRL FIELD DCS 1 3 2 1 AMN11 AAM10
4-20 mA X R 04_2LRCA-01 04_2LRC-01 0 - 100 % 04-B-02 LEVEL CTRL FIELD DCS 1 3 3 1 AMN11 AAM10 Interlock n.27A
4-20 mA X R 04_2LRCA-03 04_2LRC-03 0 - 100 % 04-R-01 LEVEL CTRL FIELD DCS 1 3 4 1 AMN11 AAM10 Interlock n.76
4-20 mA X R 04_2PRCA-08 04_2PRC-08 0 - 1 mBar abs 04-R-01 PRESSURE CTRL FIELD DCS 1 3 5 1 AMN11 AAM10
4-20 mA X R 04_2TRCA-03 04_2TRC-03 0 - 400 Degc EG-4202 TEMP. CTRL FIELD DCS 1 3 6 1 AMN11 AAM10
4-20 mA X R 04_2TRCA-04 04_2TRC-04 0 - 400 Degc HL AFTER 04-P-P07 TEMP. CTRL FIELD DCS 1 3 7 1 AMN11 AAM10
4-20 mA X R 04_2TRCA-05 04_2TRC-05 0 - 400 Degc HL AFTER 04-P-P06 TEMP. CTRL FIELD DCS 1 3 8 1 AMN11 AAM10
4-20 mA X R 04_2TRC-12 04_2TRC-12 0 - 400 Degc 04-R-01 OUTLET TEMP. CTRL FIELD DCS 1 3 9 1 AMN11 AAM10
4-20 mA X R 04_1TICA-14 04_1TRC-14 0 - 400 Degc 04-C-01 TEMP. CTRL FIELD DCS 1 3 10 1 AMN11 AAM10 Cle n.7
4-20 mA 04_1FRAL-03 04_1FRA-03 0.54 - 5.4 m3/h EG-4118 FLOW FIELD DCS 2 5 1 7 AMN31 AMM12T
4-20 mA 04_1FRAL-04 04_1FRA-04 6 - 60 m3/h EG-4114 FLOW FIELD DCS 2 5 1 8 AMN31 AMM12T
4-20 mA 04_1LIA-03 04_1LIA-03 0 - 100 % 04-C-01 HEATING LEVEL FIELD DCS 2 5 1 9 AMN31 AMM12T
4-20 mA 04_1TI-04 04_1TR-04 0 - 400 Degc HL-4119 TEMP. FIELD DCS 2 5 1 10 AMN31 AMM12T
4-20 mA 04_1TI-05 04_1TR-05 0 - 400 Degc HL-4101 TEMP. FIELD DCS 2 5 1 11 AMN31 AMM12T
4-20 mA 04_1TRA-06 04_1TR-06 0 - 400 Degc EG-4131 TEMP. FIELD DCS 2 5 1 12 AMN31 AMM12T
4-20 mA 04_1TIA-07 04_1TIA-07 0 - 400 Degc WF-4102 TEMP. FIELD DCS 2 5 1 13 AMN31 AMM12T
4-20 mA 04_1TRA-09 04_1TR-09 0 - 400 Degc 04-B-01 TEMP. FIELD DCS 2 5 1 14 AMN31 AMM12T
4-20 mA 04_1TI-10 04_1TR-10 0 - 400 Degc HL-4120 TEMP. FIELD DCS 2 5 1 15 AMN31 AMM12T
4-20 mA 04_1TI-11 04_1TI-11 0 - 400 Degc HL-4102 TEMP. FIELD DCS 2 5 1 16 AMN31 AMM12T
4-20 mA 04_1TRA-12 04_1TR-12 0 - 400 Degc 04-K-01 TEMP. FIELD DCS 2 5 2 1 AMN31 AMM12T Interlock 28A, 28B
4-20 mA 04_1TRA-13 04_1TR-13 0 - 400 Degc PE-3101 TEMP. FIELD DCS 2 5 2 2 AMN31 AMM12T
4-20 mA 04_1TRA-18 04_1TR-18 0 - 400 Degc 04-C-01 HEAT. TEMP. FIELD DCS 2 5 2 3 AMN31 AMM12T
4-20 mA 04_1TI-15 04_1TR-15 0 - 400 Degc 04-C-01 HEATING TOP TEMP. FIELD DCS 2 5 2 4 AMN31 AMM12T
4-20 mA 04_1TRA-23 04_1TR-23 0 - 400 Degc 04-C-01 TEMP. FIELD DCS 2 5 2 7 AMN31 AMM12T
4-20 mA 04_2FRAL-06 04_2FRA-06 2.3 - 23 m3/h EG-4217 FLOW FIELD DCS 2 5 2 8 AMN31 AMM12T
4-20 mA 04_2FRAL-07 04_2FRA-07 0.95 - 9.5 m3/h EG-4221 FLOW FIELD DCS 2 5 2 9 AMN31 AMM12T
4-20 mA 04_2FAL-08 04_2FRA-08 3.8 - 38 m3/h EG-4216 FLOW FIELD DCS 2 5 2 10 AMN31 AMM12T
4-20 mA 04_2FAL-09 04_2FRA-09 0.95 - 9.5 m3/h EG-4212 FLOW FIELD DCS 2 5 2 11 AMN31 AMM12T
4-20 mA 04_2FRAL-10 04_2FRA-10 3.8 - 38 m3/h EG-4219 FLOW FIELD DCS 2 5 2 12 AMN31 AMM12T
4-20 mA 04_2FRAL-12 04_2FRA-12 0.38 - 3.8 m3/h EG FROM AREA01 FLOW FIELD DCS 2 5 2 13 AMN31 AMM12T
4-20 mA 04_2LRA-04 04_2LRA-04 0 - 100 % 04-R-01 LEVEL FIELD DCS 2 5 2 14 AMN31 AMM12T
4-20 mA 04_2LI-07 04_2LI-07 0 - 100 % 04-L-02B LEVEL FIELD DCS 2 5 2 15 AMN31 AMM12T
4-20 mA 04_2TRA-01 04_2TRA-01 0 - 400 Degc 04-B-02 TEMP. FIELD DCS 2 5 2 16 AMN31 AMM12T
4-20 mA 04_2TIA-02 04_2TIA-02 0 - 400 Degc WF-4201 TEMP. FIELD DCS 3 1 1 1 AMN31 AMM12T
4-20 mA 04_2TI-06 04_2TIA-06 0 - 400 Degc 04-R-01 LEFT TEMP. FIELD DCS 3 1 1 2 AMN31 AMM12T
4-20 mA 04_2TRA-13 04_2TR-13 0 - 400 Degc HL-4242 TEMP. FIELD DCS 3 1 1 3 AMN31 AMM12T
4-20 mA 04_2TIA-14 04_2TIA-14 0 - 400 Degc HL-.4241 TEMP. FIELD DCS 3 1 1 4 AMN31 AMM12T
4-20 mA 04_2TRA-16 04_2TRA-16 0 - 400 Degc PH-4201 TEMP. FIELD DCS 3 1 1 5 AMN31 AMM12T
4-20 mA 04_2TRA-17 04_2TRA-17 0 - 400 Degc 04-R-01 RIGHT TEMP. FIELD DCS 3 1 1 6 AMN31 AMM12T
4-20 mA 04_2TI-18 04_2TRA-18 0 - 400 Degc 04-R-01 LEFT TEMP. FIELD DCS 3 1 1 7 AMN31 AMM12T
4-20 mA 04_2TRCA-19 04_2TRA-19 0 - 400 Degc 04-R-01 TEMP. FIELD DCS 3 1 1 8 AMN31 AMM12T
4-20 mA 04_2TI-20 04_2TRA-20 0 - 400 Degc EG-4220 TEMP. FIELD DCS 3 1 1 9 AMN31 AMM12T
4-20 mA 04_2TI-21 04_2TRA-21 0 - 400 Degc EG-4133 TEMP. FIELD DCS 3 1 1 10 AMN31 AMM12T
Page 1/5
We reserve the ownership under the law of this drawing with prohibition Ci riserviamo la proprietá a termini di legge di questo
of even partial reproduction and to make it known to third persons disegno con divieto di riprodurlo anche in parte o di
without our written authorization renderlo noto a terzi senza nostra autorizzazione scritta.
F F.A.T. REVISION E1 06/03/2000 CAPPA QUIRE SOCST
E FINAL E1 19/11/1999 RIVRO QUIRE SOCST
I/O LIST 231_LA_WP_01001F
D TAGS ASSIGNMENT E1 05/05/1999 CAPPA VALGI SOCST
C SECOND REV. P&I E1 20/04/1999 VALGI QUIRE SOCST PANEL: FCS inside control board IP03
DESTINAZ DATA COMPIL. CONTROL. APPROV. DCS type: YOKOGAWA CENTUM
REV DESCRIZIONE - Description Destination Date Drawn up Checked Approved JOB: 231 - YAZD (IRAN)

Signal type Ctr Red Status Tag Name in P&I Tag Name in DCS Range (EU) Description From To Node Nest Slot Channel Nest Type Card type Interlocks/Cle
4-20 mA 04_2TI-22 04_2TRA-22 0 - 400 Degc EG-4236 TEMP. FIELD DCS 3 1 1 11 AMN31 AMM12T
4-20 mA 04_2TR-26 04_2TRA-26 0 - 400 Degc 04-K-03 TEMP. FIELD DCS 3 1 1 12 AMN31 AMM12T
4-20 mA 04_2TRA-27 04_2TRA-27 0 - 400 Degc 04-R-01 BOTT. LEFT TEMP. FIELD DCS 3 1 1 13 AMN31 AMM12T
4-20 mA 04_2TI-28 04_2TIA-28 0 - 400 Degc 04-R-01 TEMP. FIELD DCS 3 1 1 14 AMN31 AMM12T
4-20 mA 04_2EAL-S01A 04_2IIA-S01A 0- 166 A POLYMER PUMP CURRENT FIELD DCS 3 1 1 15 AMN31 AMM12T Interlock n.37
4-20 mA 04_2EAL-S01A 04_2SIA-S01A 0 - 100 RPM POLYMER PUMP SPEED FIELD DCS 3 1 1 16 AMN31 AMM12T Interlock n.37
4-20 mA 04_2EAL-R01A 04_2IIA-R01A 0 - 132 A FINISHER R01A CURRENT FIELD DCS 3 1 2 1 AMN31 AMM12T Interlock n.28A
4-20 mA 04_2EAL-R01A 04_2SIA-R01A 0 - 10 RPM FINISHER R01A SPEED FIELD DCS 3 1 2 2 AMN31 AMM12T
4-20 mA 04_2EAL-R01B 04_2IIA-R01B 0 - 32 A FINISHER R01B CURRENT FIELD DCS 3 1 2 3 AMN31 AMM12T Interlock n.28B
4-20 mA 04_2EAL-R01B 04_2SIA-R01B 0 - 10 RPM FINISHER R01B SPEED FIELD DCS 3 1 2 4 AMN31 AMM12T
4-20 mA 04_3LIA-01 04_3LIA-01 0 - 100 % 04-B-03 LEVEL FIELD DCS 3 1 2 5 AMN31 AMM12T
4-20 mA 04_3PIA-13 04_3PIA-13 0 - 6 Bar PW-4311 PRESSURE FIELD DCS 3 1 2 6 AMN31 AMM12T
4-20 mA 04_3PI-14 04_3PI-14 0 - 12 Bar SM-4304 PRESSURE FIELD DCS 3 1 2 7 AMN31 AMM12T
4-20 mA 04_3TRA-06 04_3TRA-06 0 - 400 Degc SM-4304 TEMP. FIELD DCS 3 1 2 8 AMN31 AMM12T
4-20 mA 04_3TI-08A 04_3TI-08A 0 - 400 Degc PW-4318 TEMP. FIELD DCS 3 1 2 9 AMN31 AMM12T
4-20 mA 04_3TI-08B 04_3TI-08B 0 - 400 Degc PW-4317 TEMP. FIELD DCS 3 1 2 10 AMN31 AMM12T
4-20 mA 04_3TI-09A 04_3TI-09A 0 - 400 Degc PW-4319 TEMP. FIELD DCS 3 1 2 11 AMN31 AMM12T
4-20 mA 04_3TI-09B 04_3TI-09B 0 - 400 Degc PW-4316 TEMP. FIELD DCS 3 1 2 12 AMN31 AMM12T
4-20 mA 04_3TI-10A 04_3TI-10A 0 - 400 Degc PW-4320 TEMP. FIELD DCS 3 1 2 13 AMN31 AMM12T
4-20 mA 04_3TI-10B 04_3TI-10B 0 - 400 Degc PW-4315 TEMP. FIELD DCS 3 1 2 14 AMN31 AMM12T
4-20 mA 04_3TI-11 04_3TR-11 0 - 400 Degc 04-B-03 TEMP. FIELD DCS 3 1 2 15 AMN31 AMM12T

ANALOG OUTPUTS (AO)


4-20 mA X N.C. 04_1LV-04 04_1LV-04 0 - 100 % 04-B-01 LEVEL CTRL DCS FIELD 2 1 8 1 AMN11 AAM50 Interlock n.27
4-20 mA X N.A. 04_1PV-09 04_1PV-09 0 - 100 % 04-C-01 PRESSURE CTRL DCS FIELD 2 1 9 1 AMN11 AAM50
4-20 mA X N.A. 04_1PV-10 04_1PV-10 0 - 100 % EG-4127 PRESSURE CTRL DCS FIELD 2 1 10 1 AMN11 AAM50
4-20 mA X N.C. 04_1PV-11 04_1PV-11 0 - 100 % 04-C-01 HEAT. PRESS. CTRL DCS FIELD 2 1 11 1 AMN11 AAM50 Cle n.7
4-20 mA X N.A. 04_1TV-08 04_1TV-08 0 - 100 % EG-4115 TEMP. CTRL DCS FIELD 2 1 12 1 AMN11 AAM50
4-20 mA X N.C. 04_1TV-16 04_1TV-16 0 - 100 % 04-C-01 TEMP. CTRL DCS FIELD 2 1 13 1 AMN11 AAM50
4-20 mA X N.C. 04_2LV-01 04_2LV-01 0 - 100 % 04-B-02 LEVEL CTRL DCS FIELD 2 1 14 1 AMN11 AAM50
4-20 mA X N.C. 04_2LV-03 04_2LV-03 0 - 100 % 04-R-01 LEVEL CTRL DCS FIELD 2 1 15 1 AMN11 AAM50
4-20 mA X N.A. 04_2PV-08 04_2PV-08 0 - 100 % 04-R-01 PRESSURE CTRL DCS FIELD 2 1 16 1 AMN11 AAM50
4-20 mA X N.A. 04_2TV-03 04_2TV-03 0 - 100 % EG-4202 TEMP. CTRL DCS FIELD 2 2 1 1 AMN11 AAM50
4-20 mA X N.C 04_2TV-04 04_2TV-04 0 - 100 % HL AFTER 04-P-07 TEMP. CTRL DCS FIELD 2 2 2 1 AMN11 AAM50
4-20 mA X N.C. 04_2TV-05 04_2TV-05 0 - 100 % HL AFTER 04-P-06 TEMP. CTRL DCS FIELD 2 2 3 1 AMN11 AAM50
4-20 mA X N.C. 04_2TV-12 04_2TV-12 0 - 100 % 04-R-01 OUTLET TEMPER. CTRL DCS FIELD 2 2 4 1 AMN11 AAM50 Interlock n.28A/28B
4-20 mA 04_2EAL-R01A 04_2SET-R01A 0 - 100 % FINISHER SPEED SET DCS MCC 3 4 1 9 AMN31 AMM52T
4-20 mA 04_2EAL-R01B 04_2SET-R01B 0 - 100 % FINISHER SPEED SET DCS MCC 3 4 1 10 AMN31 AMM52T
4-20 mA 04_2EAL-S01A 04_2SET-S01A 0 - 100 % POLYMER PUMP SPEED SET DCS MCC 3 4 1 11 AMN31 AMM52T

DIGITAL INPUTS (DI)


Vfc N.C. 04_1FAL-01 04_1FAL-01 EC-4101 LOW FLOW FIELD DCS 4 1 1 7 AMN32 ADM12C
Vfc N.C. 04_1FAL-02 04_1FAL-02 EC-4102 LOW FLOW FIELD DCS 4 1 1 8 AMN32 ADM12C
Vfc N.C. 04_1FAL-05 04_1FAL-05 WC-4106 LOW FLOW FIELD DCS 4 1 1 9 AMN32 ADM12C
Vfc N.C. 04_1LAH-01 04_1LAH-01 04-C-01 HIGH LEVEL FIELD DCS 4 1 1 10 AMN32 ADM12C
Vfc N.C. 04_1LAH-02 04_1LAH-02 04-C-01.3 HIGH LEVEL FIELD DCS 4 1 1 11 AMN32 ADM12C
Vfc N.C. 04_1LIAL-03 04_1LAL-03 04-C-01 HEATING LOW LEVEL FIELD DCS 4 1 1 12 AMN32 ADM12C
Vfc N.O. 04_1LAL-05 04_1LAL-05 04-B-01 LOW LEVEL FIELD DCS 4 1 1 13 AMN32 ADM12C
Vfc N.C. 04_1PDAH-13 04_1PDH-13 04-F-04 Dp switch FIELD DCS 4 1 1 14 AMN32 ADM12C Interlock n.22
Page 2/5
We reserve the ownership under the law of this drawing with prohibition Ci riserviamo la proprietá a termini di legge di questo
of even partial reproduction and to make it known to third persons disegno con divieto di riprodurlo anche in parte o di
without our written authorization renderlo noto a terzi senza nostra autorizzazione scritta.
F F.A.T. REVISION E1 06/03/2000 CAPPA QUIRE SOCST
E FINAL E1 19/11/1999 RIVRO QUIRE SOCST
I/O LIST 231_LA_WP_01001F
D TAGS ASSIGNMENT E1 05/05/1999 CAPPA VALGI SOCST
C SECOND REV. P&I E1 20/04/1999 VALGI QUIRE SOCST PANEL: FCS inside control board IP03
DESTINAZ DATA COMPIL. CONTROL. APPROV. DCS type: YOKOGAWA CENTUM
REV DESCRIZIONE - Description Destination Date Drawn up Checked Approved JOB: 231 - YAZD (IRAN)

Signal type Ctr Red Status Tag Name in P&I Tag Name in DCS Range (EU) Description From To Node Nest Slot Channel Nest Type Card type Interlocks/Cle
Vfc N.O. 04_1PAH-14 04_1PAH-14 04-C-01 HEATING HIGH PRES. FIELD DCS 4 1 1 15 AMN32 ADM12C
Vfc N.O. 04_1PAH-15 04_1PAH-15 EG-4216 HIGH PRESSURE FIELD DCS 4 1 1 16 AMN32 ADM12C
Vfc N.C. 04_2FAL-04 04_2FAL-04 WC-4211 LOW FLOW FIELD DCS 4 1 1 17 AMN32 ADM12C
Vfc N.C. 04_2FAL-05 04_2FAL-05 WC-4205 LOW FLOW FIELD DCS 4 1 1 18 AMN32 ADM12C
Vfc N.C. 04_2FAL-11 04_2FAL-11 WC-4213 LOW FLOW FIELD DCS 4 1 1 19 AMN32 ADM12C
Vfc N.C. 04_2FAL-13 04_2FAL-13 WC-4215 LOW FLOW FIELD DCS 4 1 1 20 AMN32 ADM12C
Vfc N.C. 04_2FAL-14 04_2FAL-14 04-P-10 LOW FLOW FIELD DCS 4 1 1 21 AMN32 ADM12C
Vfc N.C. 04_2FAL15 04_2FAL15 04-B-11B OUT LOW FLOW FIELD DCS 4 1 1 22 AMN32 ADM12C
Vfc N.C. 04_2FAL16 04_2FAL16 04-R-01 OUT LOW FLOW FIELD DCS 4 1 1 23 AMN32 ADM12C
Vfc N.O. 04_2LAL-02 04_2LAL-02 04-B-02 HIGH LEVEL FIELD DCS 4 1 1 24 AMN32 ADM12C
Vfc N.O. 04_2LAL-05 04_2LAL-05 04-B-11A LOW LEVEL FIELD DCS 4 1 1 25 AMN32 ADM12C
Vfc N.O. 04_2LIA-06 04_2LAL-06 04-B-11B LOW LEVEL FIELD DCS 4 1 1 26 AMN32 ADM12C
Vfc N.O. 04_2PAH-05 04_2PAH-05 EG-4219 HIGH PRESSURE FIELD DCS 4 1 1 27 AMN32 ADM12C
Vfc N.C. 04_2PDAH-09 04_2PDAH-09 04-F-05 Dp switch FIELD DCS 4 1 1 28 AMN32 ADM12C Interlock n.25
Vfc N.O. 04_1CV-13B 04_1ZSH-13B VALVE 04-CV-13B OPEN FIELD DCS 4 1 2 3 AMN32 ADM12C Interlock n.22
Vfc N.O. 04_1CV-13B 04_1ZSL-13B VALVE 04-CV-13B CLOSED FIELD DCS 4 1 2 4 AMN32 ADM12C Interlock n.22
Vfc N.O. 04_2CV-09B 04_2ZSH-09B VALVE 04-CV-09B OPEN FIELD DCS 4 1 2 9 AMN32 ADM12C Interlock n.25
Vfc N.O. 04_2CV-09B 04_2ZSL-09B VALVE 04-CV-09B CLOSED FIELD DCS 4 1 2 10 AMN32 ADM12C Interlock n.25
Vfc N.C. 04_2LAH-09 04_2LAH-09 04-B-12 HIGH LEVEL FIELD DCS 4 1 2 11 AMN32 ADM12C Interlock n.112
Vfc N.C. 04_2LAL-08 04_2LAL-08 04-B-12 LOW LEVEL FIELD DCS 4 1 2 12 AMN32 ADM12C Interlock n.112
Vfc N.C. 04_2FAL-17 04_2FAL-17 FIELD DCS 4 1 2 13 AMN32 ADM12C
Vfc N.C. 04_1EAL-P01A 04_1ESI-P01A 04-P-01A RUN MCC DCS 4 1 2 15 AMN32 ADM12C
Vfc N.C. 04_1EAL-P01A 04_1ISH-P01A 04-P-01A FAULT MCC DCS 4 1 2 16 AMN32 ADM12C
Vfc N.O. 04_1EAL-P01A 04_1HC-P01A 04-P-01A LOC/REM MCC DCS 4 1 2 17 AMN32 ADM12C
Vfc N.C. 04_1EAL-P01S 04_1ESI-P01S 04-P-01S RUN MCC DCS 4 1 2 18 AMN32 ADM12C
Vfc N.C. 04_1EAL-P01S 04_1ISH-P01S 04-P-01S FAULT MCC DCS 4 1 2 19 AMN32 ADM12C
Vfc N.O. 04_1EAL-P01S 04_1HC-P01S 04-P-01S LOC/REM MCC DCS 4 1 2 20 AMN32 ADM12C
Vfc N.C. 04_1EAL-P02A 04_1ESI-P02A 04-P-02A RUN MCC DCS 4 1 2 21 AMN32 ADM12C
Vfc N.C. 04_1EAL-P02A 04_1ISH-P02A 04-P-02A FAULT MCC DCS 4 1 2 22 AMN32 ADM12C
Vfc N.O. 04_1EAL-P02A 04_1HC-P02A 04-P-02A LOC/REM MCC DCS 4 1 2 23 AMN32 ADM12C
Vfc N.C. 04_1EAL-P02S 04_1ESI-P02S 04-P-02S RUN MCC DCS 4 1 2 24 AMN32 ADM12C
Vfc N.C. 04_1EAL-P02S 04_1ISH-P02S 04-P-02S FAULT MCC DCS 4 1 2 25 AMN32 ADM12C
Vfc N.O. 04_1EAL-P02S 04_1HC-P02S 04-P-02S LOC/REM MCC DCS 4 1 2 26 AMN32 ADM12C
Vfc N.C. 04_1EAL-P03A 04_1ESI-P03A 04.1-P-03A RUN MCC DCS 4 1 2 27 AMN32 ADM12C
Vfc N.C. 04_1EAL-P03A 04_1ISH-P03A 04.1-P-03A FAULT MCC DCS 4 1 2 28 AMN32 ADM12C
Vfc N.O. 04_1EAL-P03A 04_1HC-P03A 04.1-P-03A LOC/REM MCC DCS 4 1 2 29 AMN32 ADM12C
Vfc N.C. 04_1EAL-P03S 04_1ESI-P03S 04.1-P-03S RUN MCC DCS 4 1 2 30 AMN32 ADM12C
Vfc N.C. 04_1EAL-P03S 04_1ISH-P03S 04.1-P-03S FAULT MCC DCS 4 1 2 31 AMN32 ADM12C
Vfc N.O. 04_1EAL-P03S 04_1HC-P03S 04.1-P-03S LOC/REM MCC DCS 4 1 2 32 AMN32 ADM12C
Vfc N.C. 04_2EAL-R01A 04_2ESI-R01A 04-R01A RUN MCC DCS 4 1 3 1 AMN32 ADM12C Interlock 28A
Vfc N.C. 04_2EAL-R01A 04_2ISH-R01A 04-R01A FAULT MCC DCS 4 1 3 2 AMN32 ADM12C Interlock 28A
Vfc N.O. 04_2EAL-R01A 04_2HC-R01A 04-R01A LOC/REM MCC DCS 4 1 3 3 AMN32 ADM12C Interlock 28A
Vfc N.C. 04_2EAL-R01B 04_2ESI-R01B 04-R01B RUN MCC DCS 4 1 3 4 AMN32 ADM12C Interlock 28B
Vfc N.C. 04_2EAL-R01B 04_2ISH-R01B 04-R01B FAULT MCC DCS 4 1 3 5 AMN32 ADM12C Interlock 28B
Vfc N.O. 04_2EAL-R01B 04_2HC-R01B 04-R01B LOC/REM MCC DCS 4 1 3 6 AMN32 ADM12C Interlock 28B
Vfc N.C. 04_2EAL-P04A 04_2ESI-P04A 04-P-04A RUN MCC DCS 4 1 3 7 AMN32 ADM12C
Vfc N.C. 04_2EAL-P04A 04_2ISH-P04A 04-P-04A FAULT MCC DCS 4 1 3 8 AMN32 ADM12C
Vfc N.O. 04_2EAL-P04A 04_2HC-P04A 04-P-04A LOC/REM MCC DCS 4 1 3 9 AMN32 ADM12C
Vfc N.C. 04_2EAL-P04S 04_2ESI-P04S 04-P-04S RUN MCC DCS 4 1 3 10 AMN32 ADM12C
Page 3/5
We reserve the ownership under the law of this drawing with prohibition Ci riserviamo la proprietá a termini di legge di questo
of even partial reproduction and to make it known to third persons disegno con divieto di riprodurlo anche in parte o di
without our written authorization renderlo noto a terzi senza nostra autorizzazione scritta.
F F.A.T. REVISION E1 06/03/2000 CAPPA QUIRE SOCST
E FINAL E1 19/11/1999 RIVRO QUIRE SOCST
I/O LIST 231_LA_WP_01001F
D TAGS ASSIGNMENT E1 05/05/1999 CAPPA VALGI SOCST
C SECOND REV. P&I E1 20/04/1999 VALGI QUIRE SOCST PANEL: FCS inside control board IP03
DESTINAZ DATA COMPIL. CONTROL. APPROV. DCS type: YOKOGAWA CENTUM
REV DESCRIZIONE - Description Destination Date Drawn up Checked Approved JOB: 231 - YAZD (IRAN)

Signal type Ctr Red Status Tag Name in P&I Tag Name in DCS Range (EU) Description From To Node Nest Slot Channel Nest Type Card type Interlocks/Cle
Vfc N.C. 04_2EAL-P04S 04_2ISH-P04S 04-P-04S FAULT MCC DCS 4 1 3 11 AMN32 ADM12C
Vfc N.O. 04_2EAL-P04S 04_2HC-P04S 04-P-04S LOC/REM MCC DCS 4 1 3 12 AMN32 ADM12C
Vfc N.C. 04_2EAL-P05A 04_2ESI-P05A 04-P-05A RUN MCC DCS 4 1 3 13 AMN32 ADM12C
Vfc N.C. 04_2EAL-P05A 04_2ISH-P05A 04-P-05A FAULT MCC DCS 4 1 3 14 AMN32 ADM12C
Vfc N.O. 04_2EAL-P05A 04_2HC-P05A 04-P-05A LOC/REM MCC DCS 4 1 3 15 AMN32 ADM12C
Vfc N.C. 04_2EAL-P05S 04_2ESI-P05S 04-P-05S RUN MCC DCS 4 1 3 16 AMN32 ADM12C
Vfc N.C. 04_2EAL-P05S 04_2ISH-P05S 04-P-05S FAULT MCC DCS 4 1 3 17 AMN32 ADM12C
Vfc N.O. 04_2EAL-P05S 04_2HC-P05S 04-P-05S LOC/REM MCC DCS 4 1 3 18 AMN32 ADM12C
Vfc N.C. 04_2EAL-P06A 04_2ESI-P06A 04-P-06A RUN MCC DCS 4 1 3 19 AMN32 ADM12C
Vfc N.C. 04_2EAL-P06A 04_2ISH-P06A 04-P-06A FAULT MCC DCS 4 1 3 20 AMN32 ADM12C
Vfc N.O. 04_2EAL-P06A 04_2HC-P06A 04-P-06A LOC/REM MCC DCS 4 1 3 21 AMN32 ADM12C
Vfc N.C. 04_2EAL-P06S 04_2ESI-P06S 04-P-06S RUN MCC DCS 4 1 3 22 AMN32 ADM12C
Vfc N.C. 04_2EAL-P06S 04_2ISH-P06S 04-P-06S FAULT MCC DCS 4 1 3 23 AMN32 ADM12C
Vfc N.O. 04_2EAL-P06S 04_2HC-P06S 04-P-06S LOC/REM MCC DCS 4 1 3 24 AMN32 ADM12C
Vfc N.C. 04_2EAL-P07A 04_2ESI-P07A 04-P-07A RUN MCC DCS 4 1 3 25 AMN32 ADM12C
Vfc N.C. 04_2EAL-P07A 04_2ISH-P07A 04-P-07A FAULT MCC DCS 4 1 3 26 AMN32 ADM12C
Vfc N.O. 04_2EAL-P07A 04_2HC-P07A 04-P-07A LOC/REM MCC DCS 4 1 3 27 AMN32 ADM12C
Vfc N.C. 04_2EAL-P07S 04_2ESI-P07S 04-P-07S RUN MCC DCS 4 1 3 28 AMN32 ADM12C
Vfc N.C. 04_2EAL-P07S 04_2ISH-P07S 04-P-07S FAULT MCC DCS 4 1 3 29 AMN32 ADM12C
Vfc N.O. 04_2EAL-P07S 04_2HC-P07S 04-P-07S LOC/REM MCC DCS 4 1 3 30 AMN32 ADM12C
Vfc N.C. 04_2EAL-P09 04_2ESI-P09 04-P-09 RUN MCC DCS 4 1 3 31 AMN32 ADM12C
Vfc N.C. 04_2EAL-P09 04_2ISH-P09 04-P-09 FULT MCC DCS 4 1 3 32 AMN32 ADM12C
Vfc N.O. 04_2EAL-P09 04_2HC-P09 04-P-09 LOC/REM MCC DCS 4 1 4 1 AMN32 ADM12C
Vfc N.C. 04_2EAL-P10A 04_2ESI-P10A 04-P-10A RUN MCC DCS 4 1 4 2 AMN32 ADM12C
Vfc N.C. 04_2EAL-P10A 04_2ISH-P10A 04-P-10A FAULT MCC DCS 4 1 4 3 AMN32 ADM12C
Vfc N.O. 04_2EAL-P10A 04_2HC-P10A 04-P-10A LOC/REM MCC DCS 4 1 4 4 AMN32 ADM12C
Vfc N.C. 04_2EAL-P10B 04_2ESI-P10B 04-P-10B RUN MCC DCS 4 1 4 5 AMN32 ADM12C
Vfc N.C. 04_2EAL-P10B 04_2ISH-P10B 04-P-10B FAULT MCC DCS 4 1 4 6 AMN32 ADM12C
Vfc N.O. 04_2EAL-P10B 04_2HC-P10B 04-P-10B LOC/REM MCC DCS 4 1 4 7 AMN32 ADM12C
Vfc N.C. 04_2EAL-V01 04_2ESI-V01 04-V-01 RUN MCC DCS 4 1 4 8 AMN32 ADM12C
Vfc N.C. 04_2EAL-V01 04_2ISH-V01 04-V-01 FAULT MCC DCS 4 1 4 9 AMN32 ADM12C
Vfc N.O. 04_2EAL-V01 04_2HC-V01 04-V-01 LOC/REM MCC DCS 4 1 4 10 AMN32 ADM12C
Vfc N.C. 04_2EAL-S01A 04_2ESI-S01A 04-S-01A RUN MCC DCS 4 1 4 11 AMN32 ADM12C Interlock 37
Vfc N.C. 04_2EAL-S01A 04_2ISH-S01A 04-S-01A FAULT MCC DCS 4 1 4 12 AMN32 ADM12C Interlock 37
Vfc N.O. 04_2EAL-S01A 04_2HC-S01A 04-S-01A LOC/REM MCC DCS 4 1 4 13 AMN32 ADM12C Interlock 37
Vfc N.C. 04_3EAL-P08A 04_3ESI-P08A 04-P-08A RUN MCC DCS 4 1 4 14 AMN32 ADM12C
Vfc N.C. 04_3EAL-P08A 04_3ISH-P08A 04-P-08A FAULT MCC DCS 4 1 4 15 AMN32 ADM12C
Vfc N.O. 04_3EAL-P08A 04_3HC-P08A 04-P-08A LOC/REM MCC DCS 4 1 4 16 AMN32 ADM12C
Vfc N.C. 04_3EAL-P08S 04_3ESI-P08S 04-P-08S RUN MCC DCS 4 1 4 17 AMN32 ADM12C
Vfc N.C. 04_3EAL-P08S 04_3ISH-P08S 04-P-08S FAULT MCC DCS 4 1 4 18 AMN32 ADM12C
Vfc N.O. 04_3EAL-P08S 04_3HC-P08S 04-P-08S LOC/REM MCC DCS 4 1 4 19 AMN32 ADM12C
Vfc N.C. 04_2FAN-R01A 04_2ESI-R01A-F 04-R-01A FAN RUN MCC DCS 4 1 4 20 AMN32 ADM12C
Vfc N.C. 04_2FAN-R01A 04_2ISH-R01A-F 04-R-01A FAN FAULT MCC DCS 4 1 4 21 AMN32 ADM12C
Vfc N.C. 04_2FAN-R01A 04_2HC-R01A-F 04-R-01A FAN LOC/REM MCC DCS 4 1 4 22 AMN32 ADM12C
Vfc N.C. 04_2FAN-S01A 04_2ESI-S01A-F 04-S-01A FAN RUN MCC DCS 4 1 2 5 AMN32 ADM12C
Vfc N.C. 04_2FAN-S01A 04_2ISH-S01A-F 04-S-01A FAN FAULT MCC DCS 4 1 2 6 AMN32 ADM12C
Vfc N.C. 04_2FAN-S01A 04_2HC-S01A-F 04-S-01A FAN LOC/REM MCC DCS 4 1 2 7 AMN32 ADM12C
Vfc N.C. 04_2EAL-P11 04_2ESI-P11 04-P-11 RUN MCC DCS 4 1 4 23 AMN32 ADM12C Interlock n.112
Vfc N.C. 04_2EAL-P11 04_2ISH-P11 04-P-11 FAULT MCC DCS 4 1 4 24 AMN32 ADM12C Interlock n.112
Page 4/5
We reserve the ownership under the law of this drawing with prohibition Ci riserviamo la proprietá a termini di legge di questo
of even partial reproduction and to make it known to third persons disegno con divieto di riprodurlo anche in parte o di
without our written authorization renderlo noto a terzi senza nostra autorizzazione scritta.
F F.A.T. REVISION E1 06/03/2000 CAPPA QUIRE SOCST
E FINAL E1 19/11/1999 RIVRO QUIRE SOCST
I/O LIST 231_LA_WP_01001F
D TAGS ASSIGNMENT E1 05/05/1999 CAPPA VALGI SOCST
C SECOND REV. P&I E1 20/04/1999 VALGI QUIRE SOCST PANEL: FCS inside control board IP03
DESTINAZ DATA COMPIL. CONTROL. APPROV. DCS type: YOKOGAWA CENTUM
REV DESCRIZIONE - Description Destination Date Drawn up Checked Approved JOB: 231 - YAZD (IRAN)

Signal type Ctr Red Status Tag Name in P&I Tag Name in DCS Range (EU) Description From To Node Nest Slot Channel Nest Type Card type Interlocks/Cle
Vfc N.O. 04_2EAL-P11 04_2HC-P11 04-P-11 LOC/REM MCC DCS 4 1 4 25 AMN32 ADM12C Interlock n.112

DIGITAL OUTPUTS (DO)


Vfc N.O. 04_1LAL-03 04_1LAL-03 04-R-01 HEATING LEVEL DCS MCC 4 4 2 16 AMN32 ADM52C
Vfc N.C. 04_1CV-01 04_1CV-01 PISTON 01 COMMAND DCS FIELD 4 4 2 17 AMN32 ADM52C Interlock n.23
Vfc N.C. 04_1CV-02 04_1CV-02 PISTON 02 COMMAND DCS FIELD 4 4 2 18 AMN32 ADM52C Interlock n.24
Vfc N.C. 04_1CV-13A 04_1CV-13A VALVE 04-CV-13A COMMAND DCS FIELD 4 4 2 19 AMN32 ADM52C Interlock n.22
Vfc N.C. 04_1CV-13B 04_1CV-13B VALVE 04-CV-13B COMMAND DCS FIELD 4 4 2 20 AMN32 ADM52C Interlock n.22
Vfc N.C. 04_2CV-01 04_2CV-01 PISTON 01 COMMAND DCS FIELD 4 4 2 21 AMN32 ADM52C Interlock n.26
Vfc N.C. 04_2CV-09A 04_2CV-09A VALVE 04-CV-09A COMMAND DCS FIELD 4 4 2 22 AMN32 ADM52C Interlock n.25
Vfc N.C. 04_2CV-09B 04_2CV-09B VALVE 04-CV-09B COMMAND DCS FIELD 4 4 2 23 AMN32 ADM52C Interlock n.25
Vfc N.O. 04_2FAN-R01A 04_2ST-R01A-F START 04-R-01A FAN DCS MCC 4 4 2 24 AMN32 ADM52C
Vfc N.O. 04_1EAL-P01A 04_1ST-P01A START 04-P-01A DCS MCC 4 4 2 25 AMN32 ADM52C
Vfc N.O. 04_1EAL-P01S 04_1ST-P01S START 04-P-01S DCS MCC 4 4 2 26 AMN32 ADM52C
Vfc N.O. 04_1EAL-P02A 04_1ST-P02A START 04-P-02A DCS MCC 4 4 2 27 AMN32 ADM52C
Vfc N.O. 04_1EAL-P02S 04_1ST-P02S START 04-P-02S DCS MCC 4 4 2 28 AMN32 ADM52C
Vfc N.O. 04_1EAL-P03A 04_1ST-P03A START 04-P-03A DCS MCC 4 4 2 29 AMN32 ADM52C
Vfc N.O. 04_1EAL-P03S 04_1ST-P03S START 04-P-03S DCS MCC 4 4 2 30 AMN32 ADM52C
Vfc N.O. 04_2EAL-R01A 04_2ST-R01A START 04-R01A DCS MCC 4 4 2 31 AMN32 ADM52C
Vfc N.O. 04_2EAL-R01B 04_2ST-R01B START 04-R01B DCS MCC 4 4 2 32 AMN32 ADM52C
Vfc N.O. 04_2EAL-P04A 04_2ST-P04A START 04-P-04A DCS MCC 4 4 3 1 AMN32 ADM52C
Vfc N.O. 04_2EAL-P04S 04_2ST-P04S START 04-P-04S DCS MCC 4 4 3 2 AMN32 ADM52C
Vfc N.O. 04_2EAL-P05A 04_2ST-P05A START 04-P-05A DCS MCC 4 4 3 3 AMN32 ADM52C
Vfc N.O. 04_2EAL-P05S 04_2ST-P05S START 04-P-05S DCS MCC 4 4 3 4 AMN32 ADM52C
Vfc N.O. 04_2EAL-P06A 04_2ST-P06A START 04-P-06A DCS MCC 4 4 3 5 AMN32 ADM52C
Vfc N.O. 04_2EAL-P06S 04_2ST-P06S START 04-P-06S DCS MCC 4 4 3 6 AMN32 ADM52C
Vfc N.O. 04_2EAL-P07A 04_2ST-P07A START 04-P-07A DCS MCC 4 4 3 7 AMN32 ADM52C
Vfc N.O. 04_2EAL-P07S 04_2ST-P07S START 04-P-07S DCS MCC 4 4 3 8 AMN32 ADM52C
Vfc N.O. 04_2EAL-P09 04_2ST-P09 START 04-P-09 DCS MCC 4 4 3 9 AMN32 ADM52C
Vfc N.O. 04_2EAL-P10A 04_2ST-P10A START 04-P-10A DCS MCC 4 4 3 10 AMN32 ADM52C
Vfc N.O. 04_2EAL-P10B 04_2ST-P10B START 04-P-10B DCS MCC 4 4 3 11 AMN32 ADM52C
Vfc N.O. 04_2EAL-V01 04_2ST-V01 START 04-V-01 DCS MCC 4 4 3 12 AMN32 ADM52C
Vfc N.O. 04_2EAL-S01A 04_2ST-S01A START 04-S-01A DCS MCC 4 4 3 13 AMN32 ADM52C
Vfc N.O. 04_3EAL-P08A 04_3ST-P08A START 04-P-08A DCS MCC 4 4 3 14 AMN32 ADM52C
Vfc N.O. 04_3EAL-P08S 04_3ST-P08S START 04-P-08S DCS MCC 4 4 3 15 AMN32 ADM52C
Vfc N.O. 04_2EAL-P11 04_2ST-P11 START 04-P-11 DCS MCC 4 4 3 16 AMN32 ADM52C
Vfc N.O. 04_2FAN-S01A 04_2ST-S01A-F START 04-S-01A FAN DCS MCC 4 4 3 17 AMN32 ADM52C