A PRESENTATION ON

ENERGY SAVING

IN

BASEMENT CAR PARK VENTILATION

FOR

THE ADMINISTRATIVE BUILDING AT

GREAMS ROAD , CHENNAI.

 
 
 
 

ADMIN BUILDING AT GREAMS ROAD, CHENNAI 


 

 Proposed Hi-Tech Admn. Bldg Consists of 2 Towers- G+8 / G+5 and has a common lower and
upper level Basement
 Capacity of Basement – Parking for 157 cars & 97 two-wheelers.
 Area of Basement (covers Towers 1&2)
o Lower Basement   4664 sq.m
o Upper Basement   4437 sq.m

 Ceiling height of basements -  2.2 Mtr

 
 
 
 

 Car Parking area in Basements are fully enclosed.


 Enclosed Under-ground parking area requires Mechanical Ventilation.
 In absence of Ventilation, Parking facility presents several Internal Air Quality problems.
 Most serious is the emission of high levels of Carbon-Monoxide(CO)
 CO is easily absorbed by Haemoglobin in Human Blood and can Inhibit Oxygen delivery to Body
and can cause adverse health effects varying from headache to death
 
 
 
 

 The NATIONAL BUILDING CODE OF INDIA – 2005 Specifies the following parameters for
Ventilation:

           CO level- within 29mg/cu.m (25 ppm) with

           Peak level not to exceed 137 mg/cu.m.(125 ppm) 

    As per ASHRAE Max Level for CO

          8 hrs exposure – 25ppm

          1 Hour exposure- 35 ppm

    Air change requirement as per NBC for Basement Car Parking :

 9 to 12 ACPH under normal conditions

( For Design purpose 10 ACPH is used)

 30 ACPH in case of fire emergency

 
 
 
 

DUCTED VENTILATION 

 The Conventional Ventilation System is the ducted Ventilation system. This has:

    -Provision of Fresh air fan and Exhaust Air Fans with ducting arrangement as per requirement.

- To be operated based on timing control.

    - Full capacity of Fans has to be operated irrespective of Smoke level or CO Concentration.

 
 
 
 


DUCTLESS VENTILATION 

The Modern method of Ventilation system is the Ductless Ventilation system in which :

    - No Ducts are required.

    - Only Fresh Air Fans, Exhaust Air Fans and Jet Fans

     required.

    - CFD(Computational Fluid Dynamics) analysis, is

     utilised to decide the number and location of Jetfans for

     effective and optimum performance.

    - A group of approximately 4 Nos of Jet Fans are

     controlled by one CO Sensor and Integrated with IBMS.

    - When the CO level exceeds threshold value, CO Sensors extends signal to IBMS and accordingly the
corresponding group of Jet Fans are triggered.

    - When CO level exceeds threshold value in approximately 50% of CO Sensors per Basement , then
Fresh Air/ Exhaust Fans are switched ON through IBMS along with jet fans

 
 
 
 

ADVANTAGES OF DUCTLESS VENTILATION 

 No ducts: duct system and accessories are eliminated.


 Improved air quality and efficient Operation
 Optimum use of Car Park Space & Optimisation of Head room for Vehicles and Pedestrians.
 Flexibility in installation,quicker installation
 Effective smoke management
 During Fire Conditions, the volume of air to be handled is of the order of 1.25 lakh CFM. Under
this situation ductless system fares better compared to ducted system.

 
 
 
 

How energy saving is achieved in Ductless Ventilation? 


 Ducts are associated with pressure drop,hence higher size F.A/E.F. are reqd.
 Jetfans are located using CFD Analysis in a manner that they help FA/EF to suck/exhaust air
respectively, hence smaller size(HP) FA/EFreqd.
 During low traffic in Basement, depending upon CO level concentration, only a group of Jetfans
may be switched ON by IBMS to distribute/ dilute CO concentration, while in ducted system
higher capacity FA/EF have to be kept ON most of the time.

 
 
 
 

JET FAN

 
 
 
 

10  

Construction / Characteristics of a Jet Fan 

1 - Casing made of Sheet Steel

2- Special silencers at the inlet and outlet side

3- Inlet cone(s)

4- Protection guard(s)

5- mounting brackets for ceiling suspension

 Suitable for 300deg C operation for 1 hour


 Speed  :  1450 / 2900 rpm – Dual speed
 CFM  :  1900 / 3800
 KW  : 0.3 / 1.5
 Sound level :  53 /  71 dB
 Area Served by each Fan – 280 sq.mtr.(Approx)

 
 


 
 
 
 

11  

Comparison between Ducted & Ductless system: 

 
 
 
 

12  

Comparison between Ducted & Ductless system: 


 

 Ducted system

    Operating Cost :

 Assumption : All Fans Operation for 2 Hours (Peak Hour), for Balance 6 Hours (Lean Period) Half
an Hour ON & Half an Hour OFF.
 So, Total operating time=5 hrs/day.
 Total unit consumption assuming 5hrs operation/day
   =134.7 KW x 5 hrs = 673.5 KWH/day.
 Running cost per annum assuming Rs.7/- per unit rate
   = 673.5 x 25 days X 12 months X Rs.7/-

 
                      

 = Rs. 14,14,350/- per annum.


 
 
 
 

13  

Comparison between Ducted & Ductless system:

 
 
 
 

14  

Comparison between Ducted & Ductless system: 


 

 Ductless system
 Operating cost :
 I.Peak 2 hrs - All jet fans, fresh/exhaust fans ON.
 a) Jet fans(32X0.3KW) =9.6 KWX2hrs  =  19.2 units
 b) Fresh air and exhaust fan =77.0 KW X 2hrs =   154.0 units

 II. For balance 6 hrs (Fresh air & Exhaust fan OFF)

    a)25% (2 groups i.e. approx. 8 fans ) jet fans ON

          for 2 hrs  =9.6KWX25%x2hrs =   4.8 units

    b)12.5% (1 group i.e. approx. 4 fans ) jet fans ON

          for 2 hrs = 9.6KWX12.5%x2hrs= 2.4 units

    c) For 2 hours (consisting of 4 durations of ― hr. each)

          all Fans are OFF =    Nil .

    .     Total units/day   =  180.40 units  

    Energy cost/annum   = 180.40X 25 days X 12 months X Rs.7/-      = Rs. 3,78,840.00

    Maintanence Cost for Jet fans p.a = Rs. 75,000.00

    Total Operating Cost per annum  = Rs. 4,53,840.00 

 
 
 
 

15  

Calculation of Payback period 


 
 

                                  Ducted  Ductless 

1. Fresh air & Exhaust fans   Rs. 50.90 lakhs Rs. 43.43 lakhs

2. Ducting and electrical panel and cabling,

cable tray,CO sensors.   Rs. 20.00 lakh Rs. 15.00 lakhs

3. Jet fans      NIL  Rs. 32.00 lakhs 

                Total cost  Rs. 70.90 lakhs Rs. 90.43 lakh 

Capital cost for ducted System    Rs. 70.90 lakhs

Capital cost for ductless System    Rs. 90.43 lakhs

Additional capital cost     Rs. 19.53 lakhs 

Savings in Operating cost/ Annum

by providing jet fans     = Rs. (14,14,350/- - 4,53,840/-)

                               = Rs. 9,60,510/- per annum.

Pay back period   = 19.53 x 12 months

                             9.60

                            = 24.41 months     

                      Or Say 24 months