Relay classes:

IEC example 30 VA 5P20

30 VA = Rated burden
5P20 = 5 % error at 20 x rated current and 1% at
rated current

IEEE example C800 (5 A rated current)


C = 10% error at rated and 20 x rated current
800 = Reference voltage
5A x 20 x 8 ohm = 800 V
5A = Rated current
20 = Over current factor
8 ohm = Rated burden
8 ohm = 52 x 8 = 200 VA