Professional Documents
Culture Documents
Scaling Design Methods To Improve Transformers
Scaling Design Methods To Improve Transformers
,
Geneseo, N.Y.
T
he size, performance and cost of a power Despite much published literature concerning the evalua-
electronic system are closely linked to the tion of transformer loss and energy at high frequencies, con-
like parameters of the magnetic components. tinued widespread interest in transformer design methods
Since custom power transformers are widely indicates that many designers seek more intuitive techniques
used, transformer design is a frequent design to evaluate tradeoffs and assure an optimal configuration.
process that has a significant impact on system performance. This interest is understandable because many methods lead
Yet most high-frequency transformers use less than 25% of the designer to make repeated trial configurations until
the available core window for efficient current conduction. obtaining a satisfactory result. While Finite Element Analysis
Two factors cause this relatively poor utilization: insulation (FEA) and commercial software facilitate the evaluation
requirements and eddy current losses. of many trial configurations, the designer’s imagination of
Insulation requirements generally limit the total winding improved configurations is fueled by understanding and
conductor cross-sectional area to less than half of the available insight.
core window. Induced high-frequency eddy currents often A transformer design approach using normalized loss
increase the apparent winding resistances by 50% or more. and energy densities inspires concepts of equivalent winding
Therefore, less than 25% of the available core window is used thicknesses that intuitively display optimal conductor and
effectively (Fig. 1). Interleaved windings, multifilar conduc- interleaving configurations.
tors, Litz wire and other approaches can decrease eddy current
effects. However, these techniques add additional insulation Low-Frequency Transformer Design
penalties, which further reduce the net cross-sectional win- Classical transformer design methods evaluate the
dow area available for the winding conductors. potential volt-ampere (VA) capacity of a selected core
in comparison to the VA requirement of a given power
supply application. The VA capacity of a selected core is
Typical Core Window Utilization
fundamentally limited by a consideration of losses with
100%
respect to temperature rise or efficiency requirements. At low
frequencies, currents within conductors are largely uniform
75% throughout the conductors’ cross-sections. Therefore,
Insulation
and Shields dissipation for a given winding is readily calculated using the
material resistivity and the geometric parameters of length
50% and cross-section for the conductor. At low frequencies, for
coils with multiple windings having uniform mean lengths of
Eddy Current Loss Penalty turn, minimum total loss is achieved by selecting appropriate
25% conductors for each winding to yield uniform current density
Net Conductor Area throughout the coil. For uniform resistivity, mean length of
turn and current density, the low-frequency dissipation of
0%
a coil is given by:
Low-frequency coil loss = ρ × Cond VOL × J
2
Fig. 1. Typical core window utilization in a high-frequency transformer.
�x IW = GW��
Secondary
�y 2 IW = 2 GW��
Normalized
Primary
Conductor
Thickness
IL = GI��
dominant insulations are those that isolate windings from LFME NORM ∑ NIi
core (bobbin), windings from other windings (interwinding) PORTION
and layers from other layers (interlayer). The conductor For a specific application and a transformer having given
thickness of the normalized winding can be estimated by conductor and core regions, the normalized expression
reducing the available core window height by the anticipated for low-frequency winding loss can be combined with an
bobbin, interwinding and interlayer thicknesses. empirically derived core loss result to yield:
This approach may be extended to low-frequency Total low-frequency transformer loss =
magnetic energy in the coil. For a normalized, nonmagnetic, F
FCOIL × N p2 + CORE
single-portion primary conductor, having uniform mean N nP
Amplitude
Amplitude
Dissipation Model 00 2 4 6 8
Magnetic Energy Model 00 2 4 6 8
40% 150%
Effective Winding Thickness Ratio
Fig. 4. Loss-equivalent thickness for a bridge transformer primary. Fig. 5. Energy-equivalent thickness for a bridge transformer primary.
∆yy
∆
where FCOIL and FCORE are parameters relating exponential e0 (R = 0, B) × µ 0 δ(NI)2
functions of primary turns (NP) to coil and core losses, ∆x
respectively, and n is the empirically derived exponential where is the skin depth for the conductor material
variation of core loss with magnetic flux density. Without at the specified frequency, x represents the width of the
a constraint of core saturation, the value of primary turns conductor layer, y represents the mean length of turn of the
that minimizes this expression for total low-frequency conductor layer, R is the ratio of sinusoidal surface magnetic-
transformer loss is given by: field intensities, B is the ratio of conductor thickness to skin
depth, and p0 and e0 are the dimensionless density functions
n × FCORE
NP = n +2 for loss and magnetic energy, respectively.
2 × FCOIL Although p0 and e0 are functions involving complex terms,
Therefore, low-frequency transformer design involves the resultant expressions are similar to the low-frequency
normalized empirical core loss data and estimation of expressions presented earlier because they largely depend
effective total conductor volume considering insulation, on simple geometric factors and the square of the amp-
clearances, electrostatic shields and other coil cross-sectional turn product. As a mathematical approach for calculation
area penalties. of dissipation, effective conductor thickness can be taken
as the skin depth divided by the loss-density function. The
High-Frequency Transformer Design loss-density function adjusts the effective thickness as a
High-frequency power electronic applications cause added result of induced magnetic-field and current distributions
transformer design considerations. Coil loss is significantly within the conductor layer. In truth, conductor thickness is
affected by induced eddy currents within the conductors as a not changing with excitation. The theoretical convenience
result of magnetic-field intensities. Further, high-frequency of equivalent thickness is merely a simplifying calculation
excitation and circuit topology requirements generate method to evaluate net dissipation and stored energy effects
constraints on leakage inductance (stray magnetic energy). in a conductor layer. Effective thickness represents the effects
The inherent complex waveshapes necessitate consideration of complex current density and magnetic-field distributions,
of dc and higher-order harmonic components. which vary greatly within the conductor cross-sections.
For a single-conductor layer, having one conductor surface Therefore, the dimensionless density functions yield intuitive
at zero magnetic-field intensity, high-frequency conductor calculations of loss and magnetic energy using the equivalent
loss and magnetic-energy storage can be calculated using the low-frequency expressions. Further derivations will be
concept of dimensionless density functions[1]: required to consider the general case for a multiple-layer
Conductor layer power = winding undergoing complex excitation.
∆y
∆y
p0 (R = 0, B) × ρ (NI)2 Nonsinusoidal Currents
∆x × δ
Transformer winding current may contain a bias
component, and in this event, the winding current can be
Conductor layer magnetic energy = represented by the harmonic decomposition:
Amplitude
Amplitude
Dissipation Model 1 Magnetic Energy Model 1
6-� Thick Single-Turn Reference 6-� Thick Single-Turn Reference
Interlayer Insulation = 0.5 � 00 2 4 6 8
Layer Insulation = 0.5 � 00 2 4 6 8
Phase Phase
Interwinding Insulation = � Interwinding Insulation = �
40% 150%
5 Layers
Effective Winding Thickness Ratio
Fig. 6. Loss-equivalent thickness for a bridge transformer secondary. Fig. 7. Energy-equivalent thickness for a bridge transformer secondary.
IDC = α 0 × IRMS where nl is the number of layers, G1 is the interlayer
IRMS1 = α1 × IRMS insulation thickness and GW is the interwinding insulation
thickness for the selected winding portion.
IRMSk = α K × IRMS
Although the expressions for loss and magnetic energy
where IRMSk is the RMS current value at the kth harmonic, invoke complex density terms that appear formidable, let’s
IRMS is the RMS value of the complex waveshape, and K is turn our attention to simple graphical methods using concepts
the ratio of the RMS value of the kth harmonic to the RMS of effective normalized winding thickness and normalized
value of the complex waveshape. winding height. These concepts are readily accomplished
The equivalent loss-density function for a given layer is using common computer methods and facilitate graphical
then given by: recognition of optimal coil designs considering insulation
(1 − R)2
p0 equiv (R , B1 ) = α 02 + ∑ i α 02 p0 (R , i × B1 ) and eddy current penalties.
B1 i
where B1 is the ratio of conductor thickness to skin depth Equivalent Thickness Methods
for the first harmonic. As described earlier, the transformer design process
Similarly, the equivalent ac magnetic-energy density involves the calculation of coil loss in consideration of a VA
function for a given layer is: requirement arising from circuit application conditions. For
low frequencies, the total coil loss can be evaluated using the
αi2
e0 equiv (R , B1 ) = ∑ R,, i × B1 )
e0 (R product of the single-turn resistance of a volume-equivalent
i i single-turn conductor and the square of the amp-turn product
These equivalent density functions can be used to derive through the conductor cross-section. We will seek a similar
expressions for loss- and energy-equivalent conductor intuitive calculation method for loss and magnetic energy in
thicknesses: a winding portion undergoing complex excitation.
Loss-equivalent thickness = To this end, we will develop a graphical relationship
δ between the effective winding thicknesses and the physical
2 utilization of an available winding height. This graphical
n nL
1
∑ equiv 1 −
n p0 equiv ,B
n 1
approach facilitates the selection of optimal layers and winding
n =1 L interleaves, including the effects of layer-insulation thickness
and considering constraints of maximum leakage-inductance
Magnetic-energy-equivalent thickness = energy and maximum coil height. Loss and magnetic energy
can then be evaluated following the expressions for low
[
δ 3 × GW +
G I (2n L − 1)(n L − 1)
2 nL
frequency applied to a normalized conductor having the
appropriate equivalent thickness.
EXACTING
PERFORMANCE
High Energy & Surface Mount
MOVs
CKE manufactures a wide range of metal oxide
varistors (MOVs) for your unique requirements.
From low voltage radial lead styles to high
energy packages, we build to OEM specs
or provide direct replacements.
Lucernemines, PA 15754
(724) 479-3533
(724) 479-3537 (Fax)
info@cke.com
2
Amplitude
2
1 Magnetic Energy Model 1
Dissipation Model 00
6-� Thick Single-Turn Reference 00 6-� Thick Single-Turn Reference 2 4 6 8
35% 125%
5 Layers
30%
4 Layers 100%
25% 3 Layers 5 Layers
2 Layers 75%
20%
3 Layers
4 Layers
15% 50% 2 Layers
10% 1 Layer
1 Layer 25%
5%
0% 0%
0 1/4 1/2 3/4 1 0 1/4 1/2 3/4 1
Available Winding Height Available Winding Height
Fig. 8. Loss-equivalent thickness for a forward transformer primary. Fig. 9. Energy-equivalent thickness for a forward transformer primary.
interlayer- and interwinding-insulation thicknesses of half a Fig. 4 shows that maximum loss-equivalent-wind-
skin depth each. Figs. 4 and 5 pertain to the primary winding ing thickness is achieved when 88% of the winding
of a transformer used in a bridge configuration operating at height is used with five conductor layers. For this con-
62.5% duty cycle. The current was normalized to yield unity figuration, the loss-equivalent-winding thickness is 28% of
RMS value. the available winding height. However, as a result of
magnetic energy stored in insulation the normalized dissipation and en- Military and Space Level
regions, the corresponding magnetic- ergy storage for equivalent single-turn LAN Magnetics
energy-equivalent-winding thickness conductors. These results are readily LAN 10baseT, 10 /100base T
is 92% of the available winding height scaled for the specific application using MIL-PRF-27, MIL-PRF-21038,
(Fig. 5). Interleaving effects can be the square of the amp-turn product MIL-STD-981 Compliance
readily evaluated by considering con- through the cross-section. ISO 9001 / 9002
structions that fit within a fraction The secondary current of the bridge
of the available winding height. For transformer contains a dc bias compo-
> Free white paper and catalog
example, a simple interleave of two por- nent because rectifier elements force
Visit us on the web for our
tions can be examined by considering unidirectional currents. Figs. 6 and 7 free White Paper entitled
winding configurations that fit within display the results for one of the half “Measuring Transformer
Distributed Capacitance” &
half of the available winding height. secondaries again operating at 62.5% Catalog or call 888-889-5391.
In Fig. 4, when winding height is duty cycle. The significant dc compo- datatronicsromoland.com
limited to 50%, two layers provide a nent causes thicker conductors to have
maximum equivalent thickness of 20%. greater benefit; therefore, two por-
However, two portions can be used tions of a single layer each provide the
with an interleave strategy to double lowest winding dissipation with a
�����������
with two single-layer portions, yield-
������������������ ing a total magnetic-energy-equiva-
lent thickness of 17%. Note that this
��� �������� equivalent thickness is correlated to the
RMS current of the total waveshape,
�������������������� �������� including the dc bias component.
The forward-converter application
also generates a significant bias
component in the current waveshape.
For a duty cycle of 35.2%, Fig. 8
Transformer Examples
Two transformers were designed
using the methods outlined earlier.
Fig. 10 summarizes total transformer
dissipation at 80°C as a function of duty
cycle for a bridge transformer operating
at 150 kHz and providing 12 V at 60 A.
Fig. 11 displays the results at 25°C for a
forward transformer operating at 100
kHz and providing 20 V at 5 A.
Open-circuit test methods were
used to measure core loss at each of the
harmonic components of application
voltage. Short-circuit test methods
were used to measure ac resistance and
evaluate ac winding loss at each of the
����� harmonic components of application
�������������� current. DCR test methods were
used to evaluate dc loss of windings
���
conducting bias currents. Figs. 10 and
�������������� 11 summarize total dissipation using
�������� these comprehensive methods. Both
��������������������� transformers achieve efficiencies in
excess of 99%. PETech
��������
���������������������� References
1. Quinn, V. “New Technology Reduces
Eddy Current Dissipation in Windings,”
Properties and Applications of Magnetic
Materials Conference Record, 2005.