XRRatio

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

T2G

jim phillips

technical training group

It has been said that we only use 10 percent of our brain. Here is some information to
Short Circuit help you fill the other 90 percent. Brainfiller.comtm

The X/R Ratio


Jim Phillips, P.E.
Background incorrect short circuit calculation leads to a mis-application of
Short circuit calculations are actually just an elaborate overcurrent protection. The diagrams below illustrates a
version of Ohm’s Law. One of the key components in the comparison of adding impedances including magnitude and
calculation process is to determine the total impedance of angle vs. adding the magnitudes only. The diagram on the
the circuit from the utility/source, through the transmission right compares the total impedance using angles and the
system, transformers, conductors, down to the point in total impedance of just adding the magnitudes of a conductor
question such as a panel or switchboard location. The and source.
impedances of the various circuit elements, have both
resistance and reactance and is often referred to as the
“complex impedance” or “polar notation”. A complex
impedance value can be represented graphically by plotting to
r
du
the resistance along the horizontal axis and the reactance Co
n
Z
along the vertical axis as illustrated below. The total
magnitude of the impedance is the hypotenuse of the
l
ta
To

resulting triangle. The X/R ratio is the amount of reactance X


Z

Z Source
divided by the amount of resistance R which also happens to
be the Tangent of an angle created by reactance and
resistance in a circuit. Magnitude and Angle
ce

Tan-1 X/R = Θ
n

or
eda
X - Reactance

ut
nd

Sin Θ * Z = X
Co
Im p

Cos Θ * Z = R
Z-

ce

l
ur

ta

Z = SqrtΘ(R2 + X2)
To
So

Z
Z

R - Resistance Magnitude Only

When calculating short circuit currents, there are usually Source of X/R Data
many impedances that must be added together. Last month Let’s take the following example where we want to add the
we determined how to calculate the equivalent source source impedance of 0.97% and an X/R ratio of 15 to the
impedance and add it to a transformer’s impedance. I kept it transformer impedance of 5.75% and an X/R ratio of 7.
simple by adding only the magnitudes. i.e. we added 5.75% Before we begin, where did these X/R ratios come from?
of the transformer and 0.97% of the source and ignored the Quite often the X/R ratios are difficult to obtain.
angles and individual X and R components. However, each
of these impedances has a specific amount of reactance and The transformer X/R ratio is usually not available unless you
resistance and an X/R ratio (even when calculated as a have good test data obtained when the transformer was
percent value). originally built and tested. In the absence of actual test data,
a good source of “reasonable” X/R data is from IEEE Std.
The problem with adding only the magnitudes of impedances 242 – IEEE Recommended Practice for Protection and
is the total impedance will be artificially high leading to a Coordination of Industrial and Commercial Power Systems.
lower (and incorrect) calculated short circuit current. This This book contains a table of suggested X/R ratios based on
has the potential of creating a dangerous condition if an transformer kVA size and voltage. The values are based on

For more information about T2G Technical Training Group’s Copyright © 2005 T2G Technical Training Group
programs, contact us at 800-874-8883 or www.t2ginc.com You can contact Jim Phillips, P.E. at: jim@jimphillipspe.com
T2G
jim phillips

technical training group

It has been said that we only use 10 percent of our brain. Here is some information to
Short Circuit help you fill the other 90 percent. Brainfiller.comtm

The X/R Ratio


Jim Phillips, P.E.
ANSI C57 which is the predominant standard for Total Resistance R of the Source and Transformer
transformers. According to IEEE Std. 242, a 1500 kVA Rtotal = 0.0645% + 0.8131%
transformer with a secondary voltage < 600 Volts and a Rtotal = 0.8776%
primary voltage of up to 15,000 Volts, the suggested X/R
ratio is 7.0. This means that there is 7 times more reactance Total Reactance X of the Source and Transformer
than resistance in the transformer impedance. Xtotal = 0.9679% + 5.6919%
Xtotal = 6.6598%
The source X/R ratio can be even more elusive. Many utility
companies can provide short circuit currents, impedances Total Impedance Z of the Source and Transformer
2 2
and X/R ratios and this makes the calculation effort easier. Ztotal = Sqrt ( Rtotal + Ztotal )
2 2
However, many utilities might only provide the short circuit Ztotal = Sqrt ( 0.8776% + 6.6598% )
current. Last month our problem stated the source short Ztotal = 6.7174%
circuit current (from the utility) was 6,740 Amps at 13.2 kV
and no X/R ratio was provided. How should we handle the In another article we only added the magnitudes of the
source X/R ratio when it is not provided? A very common impedances and the result was:
assumption is to use an X/R ratio of between 12 and 15.
-1
The inverse tangent (Tan ) of 15 is 86.1859 degrees which 6.72% = 0.97% + 5.75%
is almost 90 degrees. This is generally considered a
conservative assumption since adding an impedance with a Breaking the impedance into R and X components, the
steep angle to an impedance with a shallow angle will yield correct impedance is 6.7174%. This is so close the original
an overall impedance with a smaller magnitude. 6.72% from last month, you might think this isn’t really worth
the extra effort. For the case where the X/R ratios give
Example Calculation angles that are close, there is little difference between the
In another article we calculated a short circuit current of two methods such as our case where we have an X/R of 15
26,845 Amps. This month we will revisit that example and which is 86.1859° and 7 which is 81.8699°.
include the X/R and angles. The new short circuit current
Θ In most cases, however, there is usually a greater difference
results will be slightly higher. The main formulas for this
example are: in angles such as when factoring in smaller transformers and
Θ = Arctan X/R low voltage conductor. It is quite often the case that adding
X = Sin θ * Z an impedance of a high X/R and angle with an impedance of
R = Cos θ * Z or X / (X/R) a low X/R and angle can introduce serious error and lead to
artificially low calculated short circuit values. This is a
Source R and X potentially dangerous situation so factor in the X/R ratio!
%Z = 0.97 and X/R = 15 The X/R ratio is also used to determine how much
Arctan 15.00 = 86.1859° asymmetry there is in a short circuit waveform which is
important in conducting short circuit tests.
X = Sin 86.1859 * 0.97% = 0.9978 * 0.97% = 0.9679% ________________________________________________
R = Cos 86.1859 * 0.97% = 0.0665 * 0.97% = 0.0645%
Legal Stuff - The information contained in this article is
Transformer R and X copyrighted material by Technical Training Group. The
%Z = 5.75 and X/R = 7 information is for general guidance only and neither
Arctan 7.00 = 81.8699° Technical Training Group nor Jim Phillips, P.E makes any
warranty expressed or implied and assumes no liability what
X = Sin 81.8699* 5.75 % = 0.9899 * 5.75 % = 5.6919% so ever for it’s use. Sorry everyone, too many lawyers out
R = Cos 81.8699* 5.75 % = 0.1414 * 5.75 % = 0.8131% there.

For more information about T2G Technical Training Group’s Copyright © 2005 T2G Technical Training Group
programs, contact us at 800-874-8883 or www.t2ginc.com You can contact Jim Phillips, P.E. at: jim@jimphillipspe.com

You might also like