PROJECT PROPOSED TWO STOREY RESIDENCE

LOCATION SAN ROQUE, TERESA, RIZAL


OWNER MR & MRS. ARNOLD
CKT. AMPERE LOAD PROTECTION NUMBER & SIZE OF WIRES &
LOAD DESCRIPTION VOLT VOLT AMPERE
NO. A B C 3P AT AF P CONDUIT
1 6-200W CONVENIENCE OUTLETS 230 1200 5.2174 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
2 5-200W CONVENIENCE OUTLETS 230 1000 4.3478 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
3 5-100W LIGHT OUTLETS 230 500 2.1739 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
4 9-100W LIGHT OUTLETS 230 900 3.913 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
5 SPARE 230 1000 4.3478 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
6 SPARE 230 1000 4.3478 20 100 2P 3- 3.5 mm2 in 15 mmØ conduit
24.348
I £ = 24.348 + .25 ( 13.04 ) = 27.608 Amps
USE : 60 AT ,100 AF , 230 VOLTS , 1Ø, 60 HZ, 5 KAIC MAIN CIRCUIT BREAKER
2 - 8.0 mm2 + 3.5.0 mm2 FEEDER WIRE in 25 mmØ conduit pipe