EASUN REYROLLE

Relay

Relay

Relay
Figure 11. Star connected bank, two limbs per phase
EASUN REYROLLE

Relay

Relay

Relay
Figure 12. Star connected bank, two limbs per phase, alternative
EASUN REYROLLE

R
Y Relay
B

Figure 10. Split star connected bank


EASUN REYROLLE

Relay

Figure 8. Star connected bank


EASUN REYROLLE

Relay

Figure 9. Delta connected bank


EASUN REYROLLE

XC
RL XL
I
>
I

>
Vs
Vr’ Load Vr

Figure 1. Equivalent circuit of a transmission line with


a series capacitor at the receiving end
EASUN REYROLLE

IXL IRL

Vs

Voltage rise
= Vc sin 

Vr
 IXC =Vc
Vr’
I Figure 2. Vector diagram
EASUN REYROLLE

Distance
Load point

With capacitor

Voltage drop

Without capacitor

Figure 3. Effect of series capacitor on line voltage drop


EASUN REYROLLE

RL XL
IL
>
Ir

>
Vs XC
Load Vr

Figure 4. Equivalent circuit of a transmission line with


a shunt capacitor at the receiving end
EASUN REYROLLE

IcXL
Vs
IcRL

Vr IrXL
IrRL
IL
IC
Ir
Voltage drop due to load current

Figure 5. Vector diagram


EASUN REYROLLE

Capacitor
voltage rise

voltage Distance Load point

Resultant
voltage drop

Voltage drop
due to load current

Figure 6. Effect of shunt capacitor on line voltage drop


EASUN REYROLLE

• REACTIVE POWER EQUIPMENTS

 SERIES CAPACITORS

 SHUNT CAPACITORS

 SHUNT CONNECTED REACTORS

 SYNCHRONOUS MACHINES
EASUN REYROLLE

• TYPE OF CAPACITORS

 TANK TYPE

 UNIT TYPE

• TYPE OF CONNECTIONS

 SERIES CONNECTED

 SHUNT CONNECTED
EASUN REYROLLE

PROTECTION REQUIREMENTS

• FOR SERIES CAPACITORS

 UNBALANCE PROTETION

 SPARK GAP PROTECTION

 SHORT CIRCUIT PROTECTION


EASUN REYROLLE

EFFECTS OF COMPENSATION ON THE LINE


REACTANCE WITH SERIES CAPACITORS

 INCREASED LINE CARRYING CAPACITY

 IMPROVED LOAD SHARING IF TWO OR MORE


PARALLEL FEEDERS ARE CONNECTED

 IMPROVED VOLTAGE REGULATION AT THE POINT


OF INSTALLATION
EASUN REYROLLE

EFFECTS OF REDUCING THE PHASE ANGLE OF V


&I WITH SHUNT CAPACITORS
 REDUCED LINE CURRENT LOSSES DUE TO THE
REACTIVE POWER
 REDUCED TRANSMISSION LINE CURRENT, TO A
VALUE LESS THAN THE LOAD CURRENT
 IMPROVED POWER FACTOR OF THE TRANSMITTED
POWER
 REDUCED VOLTAGE DROP UNIFORMLY ALONG THE
LINE, A CONTRAST TO THE STEP IN VOLTAGE ACROSS
THE TERMINALS OF THE SERIES CAPACITOR
EASUN REYROLLE

PROTECTION REQUIREMENTS

• FOR SHUNT CAPACITORS

 UNBALANCE PROTETION
 STAR CONNECTED BANK
 DELTA CONNECTED BANK
 SPLIT STAR CONNECTED BANK
 STAR CONNECTED BANK TWO LIMBS PER PHASE

 THERMAL OVERLOAD PROTECTION


EASUN REYROLLE

PROTECTION REQUIREMENTS

• FOR SHUNT CAPACITORS

 DIFFERENTIAL PROTECTION

 OVERCURRENT PROTECTION

 OVER VOLTAGE PROTECTION

 HV CONNECTIONS PROTECTION
EASUN REYROLLE

SERIES VS SHUNT CONNECTION


 REGULATION USING SERIES CAPACITOR DEPENDS ON
REACTIVE POWER OF THE LOAD. STABILITY IS
IMPROVED WHEN THE TOTAL LINE REACTANCE IS HIGH
 REGULATION DUE TO SHUNT CAPACITOR DEPENDS ON
THE REACTANCE OF THE SYSTEM. INCREASE IN
VOLTAGE IS ACHIEVED ONLY IF THE REACTANCE IS
SUBSTANTIAL
 FOR CONTINUOUS AUTOMATIC VOLTAGE REGULATION
IN A SYSTEM, SERIES CAPACITOR INSTALLATION IS
RECOMMENDED
EASUN REYROLLE

SERIES VS SHUNT CONNECTION


 VOLTAGE REGULATION WILL BE IN DELAYED STEPS
FOR SHUNT CAPACITOR BANKS DUE TO NUMBER OF
SECTIONS IN SERVICE
 REACTIVE POWER FROM SERIES CAPACITOR IS
DEPENDENT ON THE LINE CURRENT
 LINE VOLTAGE DETERMINES THE COMPENSATION FOR
SHUNT CAPACITORS
 SHUNT CAPACITOR CAN BE CONNECTED TO LV SIDE OF
A TRANSFORMER