Multi-turn actuators

SARV 07.1 - SARV 10.1


AUMA VARIOMATIC

Operation instructions

DIN ISO 9001/


EN 29001

Certificate Registration No.


12 100 4269
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

Scope of these instructions: These instructions are valid for multi-turn actuators SARV 07.1 - SARV 10.1
with integral controls AUMA VARIOMATIC.
These operation instructions are only valid for ”clockwise closing”, i.e. driven
shaft turns clockwise to close the valve.

Table of contents
1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Range of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Short description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Commissioning (electrical connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Warnings and notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.6 Further notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Mounting to valve / gearbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5. Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6. Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7. Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8. Setting of the limit switching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.1 Settings for end position CLOSED (black section) . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.2 Settings for end position OPEN (white section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9. Setting of DUO limit switching (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9.1 Settings for direction CLOSE (black section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9.2 Settings for direction OPEN (white section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
10. Setting of torque switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11. Setting of mechanical position indicator (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
12. Setting of the potentiometer (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
13. Setting of the electronic position transmitter RWG (option) . . . . . . . . . . . . . . . . . . . . . . 15
13.1 Setting for 2-wire system 4 - 20 mA and 3- /4-wire system 0 - 20 mA. . . . . . . . . . . . . . . . . . 16
13.2 Setting for 3- / 4- wire system 4 - 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
13.3 Inverse operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
14. Programming AUMA VARIOMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S). . . . . . . . . . 19
15. Electronic positioner (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.2 Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.3 Programming of the positioner board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.4 Positioner adjustment end position CLOSED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
15.5 Positioner adjustment end position OPEN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
15.6 Setting of the sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

16. Setting of the operating time (output speed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23


16.1 Setting of the operating time via internal command signal . . . . . . . . . . . . . . . . . . . . . . . 23
16.2 Setting of the operating time via the speed-interface board (option) . . . . . . . . . . . . . . . . . . 24
16.3 Further functions of the speed-interface board in conjunction with the positioner (option) . . . . . . . 26
17. Signal board (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
18. Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
19. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
20. Certificate of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
21. Declaration of incorporation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

3
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

1. Safety instructions
1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves.
For other applications, please consult us. AUMA is not liable for any possi-
ble damages resulting from use in other than the designated applications.
Such risk lies entirely with the user.
Observance of these operation instructions is considered as part of the ac-
tuator’s designated use.
1.2 Short description AUMA multi-turn actuators type SARV 07.1 - SARV 10.1 have a modular
design. Multi-turn actuators are driven by an electric motor and controlled
with the electronic controls AUMA VARIOMATIC, which are included in the
scope of supply. The limitation of travel is realised via limit switches in both
end positions. Torque seating is also possible in both end positions. The
type of seating is stated by the valve manufacturer.
1.3 Commissioning During electrical operation certain parts inevitably carry lethal voltages.
(electrical connection) Work on the electrical system or equipment must only be carried out by a
skilled electrician himself or by specially instructed personnel under the con-
trol and supervision of such an electrician and in accordance with the appli-
cable electrical engineering rules.
Recommended fuses in mains: 16 A
1.4 Maintenance The maintenance instructions (refer to page 28) must be observed, other-
wise a safe operation of the actuator is no longer guaranteed.
1.5 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries or
damages. Qualified personnel must be thoroughly familiar with all warnings
and notes in these operation instructions.
Correct transport, proper storage, mounting and installation, as well as care-
ful commissioning are essential to ensure a trouble-free and safe operation.
The following refererences draw special attention to safety-relevant proce-
dures in these operation instructions. Each is marked by the appropriate
pictograph.

This pictograph means: Note!


Note marks activities or procedures which have major influence on the cor-
rect operation. Non-observance of these notes may lead to consequential
damage.

This pictograph means: Electrostatically endangered parts (ESD)!


If this pictograph is attached to a printed circuit board, it contains parts
which may be damaged or destroyed by electrostatic discharges. If the
boards need to be touched during setting, measurement or for exchange, it
must be assured that immediately before a discharge through contact with
an earthed metallic surface (e.g. the housing) has taken place.

This pictograph means: Warning!


Warning marks activities or procedures which, if not carried out correctly,
can affect the safety of persons or material.

1.6 Further notes This pictograph means: Procedure may already be performed by
MOV valve manufacturer !
If actuators are delivered mounted to a valve, this step has been done in the
M valve manufacturer’s plant.
Setting must be checked during commissioning!

4
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

2. Technical data
Type of duty: Intermittent duty S5 - 40 % ED - 1500 c/h (according to VDE 0530)
Limit switching: Counter gear mechanism for end positions CLOSED / OPEN
Torque switching: Adjustable torque switching for closing and opening direction
Operating time: Output speed adjustable via controls AUMA VARIOMATIC
Heater in switch compartment: 5 - 20 W, 110 V - 250 V or 24 - 48 V, external supply.
Motors: Electronically commutated special AUMA motor.
Motor protection: Thermistor motor protection.
Electrical connection: Standard: AUMA plug/socket connector 100 with screw cable terminations.
Wiring diagram: Refer to name plate.
Ambient temperature: − 25 °C to + 60 °C
Enclosure protection: Standard: IP 67 according to EN 60 529
Finish coating: Standard: two-component iron-mica combination
1-phase AC (standard voltages and frequencies)
Technical data V 220 - 240 220 - 240
Hz 50 60
Torque for Tripping Valve Stem AUMA Number Minimum Back Handwheel Hand-
modulating torque 1) mounting diameter modulating actuator of duration lash diameter wheel
Weight 4)
both flange type starts 2) of im- reduc-
directions pulse 3) tion

Standard
ISO 5210 speed
max. min. max. (Special max. min/max max. min. kg
Nm Nm Nm DIN 3210) mm 1/min c/h ms ms mm (approx.)
F 07 SARV 07.1-...3/32 8:1
15 15 30 F 10 26 1500 50 75 160 23
(G 0) SARV 07.1-...4/45 4:1
F 07 SARV 07.5-...3/32 8:1
30 30 60 F 10 26 1500 50 75 160 23
(G 0) SARV 07.5-...4/45 4:1
F 10 SARV 10.0-...3/32 8:1
30 30 60 (G 0) 40 1500 50 75 200 27
SARV 10.0-...4/45 4:1
F 10 SARV 10.1-...1,5/16 8:1
60 60 120 (G 0) 40 1500 50 75 200 27
SARV 10.1-...2/22 4:1

Electrical data
Torque for Tripping Valve Stem AUMA Motor type Electr. power Current at
modulating torque 1) mounting diameter modulating actuator consumption max. speed and
both flange type at max. max. torque
directions torque 5)

Standard 220 - 240 V


ISO 5210 speed 50 / 60 Hz
max. min. max. (Special max. min/max
Nm Nm Nm DIN 3210) mm 1/min approx. W max. A
F 07 SARV 07. 1-...3/32 500 4
15 15 30 F 10 26 VEC 56-12-32-R
(G 0) SARV 07. 1-...4/45 600 5
F 07 SARV 07.5-...3/32 700 6
30 30 60 F 10 26 VEC 56-12-32-R
(G 0) SARV 07.5-...4/45 900 7
F 10 SARV 10.0-...3/32 700 6
30 30 60 (G 0) 40 VEC 56-12-32-R
SARV 10.0-...4/45 900 7
F 10 SARV 10.1-...1,5/16 700 6
60 60 120 (G 0) 40 VEC 56-12-32-R
SARV 10.1-...2/22 900 7
1) adjustable 3) for identical direction of rotation 5) motor and controls
2) with 40% ED, for nominal voltage and 4) with motor, output drive B 1 and
20 °C ambient temperature controls AUMA VARIOMATIC

Recommended fuses in mains: 16 A.

5
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

3. Transport and storage .. Transport to place of installation in sturdy packing.

.
Do not attach ropes or hooks to the handwheel for the purpose of lifting by
hoist.

..
If multi-turn actuator is mounted on valve, attach ropes or hooks for the
purpose of lifting by hoist to valve and not to multi-turn actuator.
Store in well-ventilated, dry room.

..
Protect against floor dampness by storage on a shelf or on a wooden
pallet.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to unfinished surfaces.

If multi-turn actuators are to be stored for a long time (more than 6 months),

.
the following points must be observed additionally:

.
Prior to storage: Protect unfinished surfaces, especially of output drive
parts and mounting surface with long-term corrosion protection agent.
Check for corrosion approximately every 6 months. If first signs of
corrosion show, apply new corrosion protection.

After mounting, connect actuator immediately to electrical system, so that


condensation is prevented by the heater.

.
4. Mounting to valve / gearbox

.
MOV Prior to mounting the multi-turn actuator must be checked
for damage.
M Damaged parts must be replaced by original spare parts.

The easiest position for mounting is when the valve shaft / gearbox shaft
points upright. But mounting can be done in any other position as well.

The multi-turn actuator is delivered ex works in position CLOSED (limit

.
switch CLOSED tripped).

Check if mounting flange fits the valve/gearbox.

Spigot at flanges should be loose fit!

For output drive type A (figure A), thread must match valve stem. If not or-
dered explicitly with threads, stem nut is unbored or with pilot bore when de-
livered. Finish machining of stem nut refer to page 7.

Figure A

Output drive type A


stem nut

80.3

80.01/ 80.02

80.2

6
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

The output drive types B1, B2, B3 or B4 (figure B) are delivered with bore
and keyway (usually according to ISO 5210).

Figure B

Output drive type B 1 / B 2 Output drive type B 3 / B 4


plug sleeve bore with keyway

.. Check if bore and keyway match input shaft of valve/gearbox.

..
Thoroughly degrease mounting faces of multi-turn actuator and valve /
gearbox.
Apply a small quantity of grease to input shaft of valve / gearbox.
Place actuator on valve / gearbox and fasten. Fasten bolts (at least
quality 8.8, refer to table 1) evenly crosswise.

Finish machining of stem nut (output drive type A):

.
The output drive flange does not have to be removed from the actuator.

.
Remove spigot ring (80.2, figure A) with help of wrench or similar tool
from the mounting flange.

..
Take off stem nut (80.3) together with thrust bearing (80.01) and thrust
bearing races (80.02).
Remove thrust bearing and thrust bearing races from stem nut.

..
Drill and bore stem nut and cut thread
When fixing in the chuck, make sure stem nut runs true!
Clean the machined stem nut.

.
Apply ball bearing grease to thrust bearing and race and place them on
stem nut.

..
Re-insert stem nut with thrust bearings into the mounting flange. Ensure
that dogs are placed correctly in the slots of the hollow shaft.
Screw in spigot ring until it is firm against the shoulder.
Press a few squirts of grease into the grease nipple with a grease gun.

Table 1

8.8 TA (Nm)
M 6 10
M 8 25
M 10 50
M 12 87
M 16 220

7
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

5. Manual operation Manual operation may only be engaged when motor is not
running. Switching over while motor is running can lead to
damage at multi-turn actuator (figure C)!

. Lift change-over lever in the center of the handwheel up to max. 85°, while
slightly turning the handwheel until manual operation enganges (figure D).

Figure C Figure D

Manual force is sufficient for operating the change-over


lever. Using an extension is neither necessary nor
permitted. If too much force is applied, this may damage the
change-over mechanism.

. Release change-over lever (snaps back into initial position by spring


action). If change-over lever does not snap back, assist with hand, so that
change-over lever is brought back into initial position (figure E).

Figure E Figure F

. Manual operation remains engaged until motor is started again. Then

.
motor operation is engaged automatically.

Turn handwheel into desired direction (figure F).

Only operate manually when change-over lever is in initial


position!

. Manual operation is automatically disengaged when motor is started

8
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

6. Electrical connection Work on the electrical system or equipment must only be


carried out by a skilled electrician himself or by specially
instructed personnel under the control and supervision of
such an electrician and in accordance with the applicable
electrical engineering rules.

AUMA actuators SARV are operated by the electronic controls


AUMA VARIOMATIC. The controls may either be mounted di-
rectly to the actuator or to a separate wall bracket.
Figure G
The electrical connection to the power supply is made at a
plug / socket connector with screw cable terminations as
AUMA plug/socket connector
standard.
(customer connection XK)

When installing the AUMA VARIOMATIC on a wall bracket, ob-


serve the following points:
1) For position feedback an electronic position transmitter
(RWG) in 3-wire system must be used.
2) For the connection of actuator and AUMARVARIOMATIC on
wall bracket, use additionally suitable flexible and screened
AUMA VARIOMATIC connecting cables.
3) The max. permissible cable length between multi-turn

.
actuator and AUMA VARIOMATIC is 25 m.

.
Switch
Check if type of current, supply voltage and frequency
compartment cover correspond to motor data (refer to motor name plate).

.
Remove plug cover (AUMA plug / socket connector)
(figure G).

.
Loosen screws and remove socket carrier from plug
cover.

.
Insert cable glands suitable for connecting cables.

Enclosure protection IP 67 is only ensured if suitable


cable glands are used.

. Connect cables according to order related wiring diagram CI S. . . KMS


14TP . . .. The wiring diagram belonging to the actuator is attached to the
handwheel in a weather-proof bag, together with the operation
instructions. In case the wiring diagram is not available, it can be obtained
from AUMA (state commission no., refer to name plate).

.
2
Cross sectional areas: controls cables max. 2,5 mm ,
2
power supply max. 6 mm .

.
Connect heater via external voltage source so that condensation is
prevented.
Only the same potential can be switched through the two circuits of the
switch. Different potentials require tandem switches.
Versions with gold-plated microswitches (option) may only be loaded with

.
small voltages (50 V DC / 400 mA).
MOV

The valve manufacturer specifies whether switching off in the end


M positions should be via limit switch (limit seating) or torque switch

.
(torque seating).

..
For the connection of position transmitters (potentiometers) screened
cables must be used.
Insert socket carrier and fasten.
Clean sealing faces at plug cover, terminal compartment cover and check

..
if O-ring is o.k.. Apply a thin film of non-acidic grease (e.g. Vaseline) to
the sealing faces.
Place cover and fasten 4 bolts evenly crosswise.
Fasten cable glands securely to ensure enclosure protection IP 67.

9
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

7. Test run These operation instructions are valid for ”clockwise closing”, i.e. driven

..
shaft turns clockwise to close the valve.

..
Set selector switch to position ‘OFF’ (figure H).
Switch on supply voltage.

.
Engage manual operation as described under clause 5 on page 8.
Move actuator manually into both end positions of the valve.
Check if limit switching is set correctly. When limit switching is set
correctly, the appropriate LED at the local controls is illuminated for each
end position (figure H). If both LEDs are illuminated at the same time or if
no LED is illuminated when the end position is reached, the limit setting
must be set as described in clause 8 on page 11.

.When limit switching is set correctly:


Perform test run at local controls with selector switch in position ”LOCAL”
via push-buttons

Figure H

Local controls
AUMA plug/socket connector LEDs:
(Customer connection XK) OPEN
FAULT
CLOSED
Push-buttons:
OPEN
STOP
CLOSE
Selector switch:
AUMA VARIOMATIC LOCAL-OFF-REMOTE

Switch
compartment cover

10
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

8. Setting of the limit switching

.
Figure J1 Indicator disc Cover

Engage manual operation as described under

.
clause 5 on page 8.

Remove switch compartment cover and, if


installed, pull off indicator disc (figure J1). Open
Mark end spanner (ca. 10 mm) may be used as lever.

..
8.1 Settings for end position CLOSED (black section)
MOV Turn handwheel clockwise until valve is closed.
M Press down and turn setting spindle A (figure J2) with screw driver (5 mm)
in direction of arrow, thereby observe pointer B. While a ratched is felt
and heard, the pointer B moves 90° every time up to point C.
When pointer B is 90° from point C, continue turning slowly. If pointer B
does not move anymore, stop turning and release setting spindle. In case
of having turned too far, continue turning and approach switching point
anew.
Figure J2

.
8.2 Settings for end position OPEN (white section)

.
MOV Turn handwheel counter-clockwise until valve is open, then turn back
approximately 1/2 a turn.
M Press down and turn setting spindle D (figure J3) with screw driver (5
mm) in direction of arrow, thereby observe pointer E. While a ratched is
felt and heard, the pointer E moves 90° every time up to point F.
When pointer R is 90° from point F, continue turning slowly. If pointer E
does not move anymore, stop turning and release setting spindle. In case
of having turned too far, continue turning and approach switching point
anew.

11
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

. Perform electrical test run to check seating in the end position.

Red test buttons T and P (figure J2) serve for operating the microswitches
of torque and limit switching. In case a fault occurs, perform emergency
switch-off by turning both test buttons the appropriate direction of the arrow
DÖL/DSR
.

9. Setting of DUO limit switching (option)


MOV

Switching point (intermediate position) must be approached


M from the same direction as afterwards in electrical

.
operation.

Move valve to desired intermediate position.

.
9.1 Settings for direction CLOSE (black section)
Turn setting spindle G (figure J3) with screw driver (5 mm) in direction of
arrow, thereby observe pointer H. While a ratched is felt and heard, the
pointer H moves 90° every time up to point C.
When pointer H is 90° from point C, continue turning slowly. If pointer H
does not move anymore, stop turning and release setting spindle. In case
of having turned too far, continue turning and approach switching point
anew.

.
9.2 Settings for direction OPEN (white section)
Turn setting spindle K (figure J3) with screw driver (5 mm) in direction of
arrow, thereby observe pointer L. While a ratched is felt and heard, the
pointer L moves 90° every time up to point F.
When pointer L is 90° from point F, continue turning slowly. If pointer L
does not move anymore, stop turning and release setting spindle. In case

.
of having turned too far, continue turning and approach switching point
anew.
Perform electrical test run to check correct setting for the intermediate
positions.

Figure J3

*) Option

12
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

10. Setting of torque switching


MOV .. Set torque must suit the valve!

.
When multi-turn actuator is delivered by a valve
M manufacturer, setting was made during testing.
This setting should only be changed with the consent of
the valve manufacturer!

Figure K

Setting CLOSED Setting OPEN

O P O P

.. Loosen both lock screws O at the torque dial (figure K).


Turn torque dial (P) to set it to the required torque (1 da Nm = 10 Nm).
Example:
Figure K shows the following setting:

.
3,5 da Nm = 35 Nm for direction CLOSE
3,5 da Nm = 35 Nm for direction OPEN
Tighten lock screws O again

. The torque switches can also be operated in manual


operation. When appropriately controlled electrically, the

.
tripping of the torque switch is stored and thus an
electrical start in a specific direction is prevented.
The torque switching acts as overload protection over full
travel, also when stopping in the end positions by limit

.
switch.

.
If applicable, press indicator disc on shaft and perform setting as
described under clause 11, page 14.

.
Clean sealing faces at cover and housing; check if O-ring is in good
condition. Apply a thin film of non-acidic grease to the sealing faces.
Place cover on switch compartment and fasten hex. bolts evenly
crosswise.

13
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

11. Setting of mechanical position indicator (option)


MOV Indicator disc rotates approximately 180° at full travel from OPEN to CLOSE
or vice versa.
M A suitable reduction gearing was installed in our works. If the turns per
stroke need to be changed at a later date, the reduction gearing may have

..
to be exchanged, too.

Move valve to end position CLOSED.

..
Turn lower indicator disc until symbol CLOSED is in alignment with the
mark on the indicator glass of the cover (figure L).
Move actuator to end position OPEN.
Hold lower indicator disc in position and turn upper disc with symbol
until it is in alignment with the mark on the indicator glass of the cover.

Figure L
Indicator disc Cover

Mark

12. Setting of the potentiometer (option)


.. Move valve to end position CLOSED.

.
Remove switch compartment cover and, if installed, pull off indicator disc
as described under clause 8, page 11.
Turn potentiometer (R2) clockwise to end position (Figure M, page 15).
End position CLOSED corresponds to 0 %, end position OPEN to 100 %.

Due to the ratio of the reduction gearings for the position


transmitter the complete resistance range is not always
utilized for the whole travel. Therefore an external possibility

..
for adjustment (setting potentiometer) must be provided.

Perform fine-tuning of the zero point at external setting potentiometer.


When using AUMA power supply unit PS 01 and indication instrument

..
with percentage scale, perform fine-tuning of zero point at power supply
unit.

.
Operate valve in motor mode to end position OPEN.
Perform fine-tuning of maximum value at external setting potentiometer.
When using AUMA power supply unit PS 01 and indication instrument

.
with percentage scale, perform fine-tuning of maximum value at power
supply unit.

.
If applicable, press indicator disc on shaft and perform setting as
described under clause 11.

.
Clean sealing face, check O-Ring, apply a thin film of non-acidic grease to
sealing face.
Fit and fasten switch compartment cover.

14
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

Figure M

Cover plate

R2

13. Setting of the electronic position transmitter RWG (option)

The electronic position transmitter is set in our factory according to the sig-
nal range stated in the order. Perform a subsequent adjustment according
to subclause 13.1 or 13.2.

After mounting the multi-turn actuator on the valve check setting and adjust,
if necessary.

Technical RWG 4020


data 3-/4- wire system 2-wire system
Output I 0 - 20 mA, 4 - 20 mA 4 - 20 mA
Supply 24 V DC, ±15% 14 V DC + (I x RB),
Uv
voltage smoothed max. 30 V
24 mA at 20 mA 20 mA
max. current drawn I
output current
max. ext. resistance RB 600 Ω (Uv - 14 V) / 20 mA

Figure N: Positioner board


max
(0/4 mA) (20 mA)
N R2 M

1 2 3 4
RD
BK
YE

5 6 7

3- and 4- wire system Measuring Measuring-


point 1 point 2
2- wire system
+ -
0/4 - 20 mA
For change-over also change wiring

15
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

..
13.1 Setting for 2-wire system 4 - 20 mA and 3- /4-wire system 0 - 20 mA

.
Connect voltage to AUMA VARIOMATIC.
Move valve to end position CLOSED.

.
Remove switch compartment cover and, if installed, pull off
indicator disc as described under clause 8, page 11.

.
For actuators with measuring points not accessible from the
outside, remove cover plate (figure O).
Connect ammeter for 0 - 20 mA to measuring points (figure N,
page 15 or figure O).
In end position CLOSED of 3- or 4-wire system, the value after
setting is 0 mA, for 2-wire system it is 4 mA.

The circuit (external load) must be connected (observe


max. ext. resistance RB), or the appropriate poles at the
AUMA plug/socket connector must be linked (refer to
wiring diagram C IS...KMS 14TP...), otherwise it is not

.
possible to measure a value.

.
Turn potentiometer (R2) clockwise to initial position.
Turn potentiometer (R2) whilst decreasing output signal until stop is felt.

.
Turn trimmer potentiometer (N) clockwise, until output current starts to
increase.
Turn back trimmer potentiometer (N), until a residual current of

..
approx. 0,1 mA (or 4,1 mA in case of 2-wire system) is reached. This
ensures that the signal remains above the dead and live zero point.

.
Move valve to end position OPEN.
Set to end value 20 mA with trimmer potentiometer (M).

..
Approach end position CLOSED anew and check minimum value (0 mA
or 4 mA). If necessary, correct the setting.
In case cover plate (figure O) has been removed, fit anew.

.
If applicable, press indicator disc on shaft and perform setting as
described under clause 11, page 14.

.
Clean sealing face, check O-Ring, apply a thin film of non-acidic grease to
sealing face.
Fit and fasten switch compartment cover.

If the maximum value is not reached, the selection of the


reduction gearing must be checked.

Figure O
N (0/4 mA) M (20 mA)
R2

Cover plate

Measuring Measuring
point 1 (+) point 2 (–)
0/4 - 20 mA 0/4 - 20 mA

16
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

..
13.2 Setting for 3- / 4- wire system 4 - 20 mA

.
Connect voltage to AUMA VARIOMATIC.
Move valve to end position CLOSED.

.
Remove switch compartment cover and, if installed, pull off
indicator disc as described under clause 8, page 11.

.
For actuators with measuring points not accessible from the
outside, remove cover plate (figure O).
Connect ammeter for 0 - 20 mA to measuring points (figure N,
page 15 or figure O).

The circuit (external load) must be connected (observe


max. ext. resistance RB), or the appropriate poles at the
AUMA plug/socket connector must be linked (refer to
wiring diagram C IS...KMS 14TP...), otherwise it is not

.
possible to measure a value.

.
Turn potentiometer (R2) clockwise to initial position.
Turn potentiometer (R2) whilst decreasing output signal until stop is felt.

.
Turn trimmer potentiometer (N) clockwise, until output current starts to
increase.

..
Turn back potentiometer (N), until a rest current of approx. 0,1 mA
is reached.

..
Move valve to end position OPEN.
Set to end value 16 mA with trimmer potentiometer (M).
Move valve to end position CLOSED.
Set potentiometer (N) from 0,1 mA to initial value 4 mA.

.
This results in a simultaneous shift of the end value by 4 mA, so that the
range is now 4 - 20 mA.

..
Approach both end positions anew and check setting. If necessary,
correct the setting.
In case cover plate (figure O) has been removed, fit anew.

.
If applicable, press indicator disc on shaft and perform setting as
described under clause 11, page 14.

.
Clean sealing face, check O-Ring, apply a thin film of non-acidic grease to
sealing face.
Fit and fasten switch compartment cover.

If the maximum value is not reached, the selection of the


reduction gearing must be checked.

13.3 Inverse operation For inverse operation exchange the connections 7 (red/RD) and 5
(black/BK) at positioner board (figure N, page 15).

17
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

14. Programming AUMA VARIOMATIC


. Remove 4 screws at VARIOMATIC (Figure P / 8.1) and take off cover.

Figure P: Actuator SAR with controls AUMA VARIOMATIC

Local controls

AUMA VARIOMATIC

Switch
compartment cover

. In the factory push-to-run operation REMOTE and push-to-run operation

.
LOCAL are programmed (refer to table 2).
MOV

The type of seating - limit or torque seating (DIP switch S1 pos. 5 and

.
M pos. 6) must be determined by the valve manufacturer.

Set desired programming according to table 2 at DIP switch S1


(figure Q).

If no positioner (figure S, page 20) or speed-interface board


(figure W, page 24) is fitted, the DIP switch S1 pos. 7 must
always be in position ”ON”.

Figure Q: VARIOMATIC standard

Potentiometer Diagnosis LED (green): Diagnosis LED (red): Diagnosis LED (green):
for setting of Illuminated when Motor protection Enable REMOTE (option)
OPERATING TIME ready tripped always installed,
illuminated during normal
operation

DIP switch S1
for programming
ON
1234 56 7

Diagnosis LEDs for


active REMOTE
Logic board control commands:
run command STOP (red)
Cover plate run command OPEN (green)
standard run command CLOSE (yellow)

. Replace cover and fasten 4 bolts (figure P / 8.1) evenly crosswise.

18
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

Table 2 DIP switch S1


Programming
(on logic board)
Direction CLOSE Direction OPEN
ON ON
OFF OFF
Self-retaining REMOTE 1234 56 7 1234 56 7
ON ON
Push-to-run operation OFF OFF
REMOTE 1234 56 7 1234 56 7
ON ON
OFF OFF
Self-retaining LOCAL 1234 56 7 1234 56 7
ON ON
Push-to-run operation OFF OFF
LOCAL 1234 56 7 1234 56 7

for end position for end position


Type of seating
CLOSED OPEN
ON ON
OFF OFF
limit seating 1234 56 7 1234 56 7
ON ON
OFF OFF
torque seating 1234 56 7 1234 56 7

For installed positioner:


ON
Speed dependent OFF
on error variable 1234 56 7
ON
Speed not dependent OFF
on error variable 1234 56 7

14.1 Programming with BUS board installed (MODBUS, PROFIBUS and INTERBUS S)

Refer to separate instructions for appropriate bus system.

Table 3 DIP switch S1


Programming
(on logic board)
Self-retaining REMOTE (not applicable for BUS systems)
ON
Push-to-run operation OFF
REMOTE 1234 56 7
ON
OFF
Self-retaining LOCAL 1234 56 7
ON
OFF
Push-to-run operation LOCAL 1234 56 7

for end position for end position


Type of seating
CLOSED OPEN
ON ON
OFF OFF
limit seating 1234 56 7 1234 56 7
ON ON
OFF OFF
torque seating 1234 56 7 1234 56 7

external (via Bus) internal


ON ON
Nominal output speed 1) OFF
1234 56 7
OFF
1234 56 7

1) PROFIBUS-FMS and Set switch position S1 pos. 7 to ”ON”.


MODBUS (no nominal output speed possbible via bus)
Profibus DP and
INTERBUS-S switch position S1 pos. 7 to OFF.

19
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

15. Electronic positioner (option)


15.1 Technical data Command signal (input sig. E1, nominal value) 0/4 - 20 mA (option 0 - 5 V)
Feedback (input signal E2, actual value) 4 - 20 mA (option 0 - 5 V)
Sensitivity (dead band) ∆E 0,25 - 2,5 %
Time delay toff 0,5 - 10 s

.
Input resistance 250 Ohm

.
15.2 Setting To set the positioner, remove 4 screws (figure P / 8.1, page 18) and take
off cover.

.
For the functions of the LEDs installed on positioner board: refer to
figure S.
MOV Check programming of the logic board according to pages 18/19, clause
14: DIP switch S1 on the logic board: Pos. 1 and pos. 3 must be in pos.
M ”OFF” (figure S).
If no speed variation is desired, the DIP switch S1 pos. 7 must be in
position ”ON”. If an error-dependent speed variation is required (figure R),
set DIP switch S1 pos. 7 to ”OFF”.
Figure R: Speed dependent on error variable
100%
operating
speed

control deviation (error) 100%

Figure S: VARIOMATIC with positioner


Potentiometer Diagnosis LED (green): Diagnosis LED (red): Diagnosis LED (green)
Illuminated when 1)
for setting of Motor protection Enable REMOTE (option)
OPERATING TIME ready tripped always installed,
illuminated during normal
operation

DIP switch S1
for programming V24: Run command OPEN (green)
V23: Run command CLOSE (yellow)
1234567

V35: Permissible number of starts


exceeded (red)
V37: Signals E1 or E2
Logic board not available (red)
R88: Delay time
Cover plate
positioner

1) Enable REMOTE (option) see corresponding wiring diagram:


Analogue command signal or run command via local controls are

.
not accepted without external enable signal (24V DC).

.
15.3 Programming of the positioner Remove cover plate (Figure S).
board
Set switch S2 pos. 5 (figure T1, page 22) according to input signal E1
(nominal value):

.
0 - 20 mA: position ”OFF”
4 - 20 mA: position ”ON”
Set switch S2 pos. 6 for E2 (actual value) = 4 mA to position ”ON”.
(for E2 position feedback via potentiometer 0 - 5 V in position ”OFF”)
In standard version switch S3 (figure T1, page 22) for command signal E1
= 0/4 - 20 mA, i.e. end position ”OPEN” = 20 mA, must be in position 1.
Version for inverse operation (i.e. end position ”OPEN” = 0/4 mA) must be
ordered accordingly from the factory.

20
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

Programming for faults:

.
Behaviour on loss of input signal E1 and / or
on loss of feedback signal E2
Pre-condition: Signals 4 - 20 mA

Process related (desired) Programming:


behaviour: (Figure T1, page 22)

fail as is, i.e. actuator stops imme-


diately and remains at this position.

fail close, i.e. actuator drives valve


to position CLOSED.

fail open, i.e. actuator drives valve


to position OPEN.

Before commencing the positioner adjustment it must be


ensured that the limit and torque switching of the actuator
(clauses 8-10) as well as the feedback (clauses 12 and 13)
have been set.

.
.
15.4 Positioner adjustment Set selector switch (local controls) to position I (LOCAL).
end position CLOSED

.
Run multi-turn actuator by depressing push-button to end position
CLOSED.
Connect input signal E1(nominal value) (0 or 4 mA).

.
Missing signal E1 and / or E2 is indicated by LED E1/E2 < 4 mA
(figures T1+T2 / V37).
To measure the nominal value E1 connect Voltmeter (0 - 5 V) to the
measuring points M1 and M2 (figure T1, page 22).

.
For E1 (nominal value) = 0 mA: measure 0 V.
For E1 (nominal value) = 4 mA: measure 1 V.
To measure the actual value E2 connect voltmeter to measuring points
M3 and M4.
For E2 (actual value) = 4 mA: measure 1 V.

.
If measured value is not correct: Perform feedback adjustment according
to page 14 clause 12, or page 15 clause 13.
Set potentiometer R35 (∆E) and R31 (sens) to minimal value by turning
counter-clockwise.

If Possible LED indications: Then Required setting in end position CLOSED:


(refer to figures T1 and T2) (refer to figures T1 and T2)
LEDs are not illuminated Turn potentiometer “0” (R25) slightly clockwise until
LED (V23 yellow) lights up
LED (V24 green) is Turn potentiometer “0” (R25) slightly clockwise until
illuminated LED (V24) goes out and LED (V23 yellow) lights up
LED (V23 yellow) is Turn potentiometer “0” (R25) counter-clockwise until LED
illuminated (V23) goes out.
Then turn potentiometer “0" (R25) slightly clockwise until LED
(V 23 gelb) lights up again.

21
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

15.5 Positioner adjustment end . Run multi-turn actuator by depressing push-button (local controls) to

.
end position OPEN.
position OPEN
Measure 5 V at measuring points M4 and M3. (Figure T1).
If measured value is not correct: Perform feedback adjustment according

..
to page 14 clause 12, or page 15 clause 13 and continue with page 21
subclause 15.4.
Connect max. command signal E1 = 20 mA.
Measure 5 V at measuring points M1 and M2. (Figure T1)
If measured value is not 5 V, check the externally supplied command
signal.

If LED indications: Then Required setting in end position OPEN:


(refer to figures T1 and T2) (refer to figures T1 and T2)
LED's are not illuminated Turn potentiometer „max” (R28) slightly counter-clockwise until
LED (V24 green) lights up.
LED (V24 green) is Turn potentiometer „max” (R28) clockwise until LED (V24)
illuminated goes out.
Then turn potentiometer „max” (R28) slightly counter-clockwise until
LED (V24) lights up again.
LED (V23 yellow) is Turn potentiometer „max” (R28) slightly counter-clockwise until
illuminated LED (V23) goes out and LED (V24 green) lights up.

.
..
15.6 Setting of the sensitivity Set selector switch to position II (REMOTE) at local controls (figure P,
page 18).
Supply command signal to any value between 0/4 and 20 mA.
Set dead band with potentiometer ∆E (P9) so that multi-turn actuator does
not readjust after a single control operation:
- turning clockwise results in reduced sensitivity (dead band increased)

When setting E the following must be observed by all


means:
If the number of starts is too high, this can lead to
unnecessary wear at the valve and actuator. Therefore the
highest possible sensitivity (dead band) which is permitted

.
for the process must be set.

To prevent an exceeding of the max. permissible number of starts


(1 500 c/h) in extreme cases, a time delay between 0,5 s (left stop) and
10s (right stop) may be set with potentiometer t-off (R88).
Figure T1: Positioner board Bild T2: Cover plate positioner
R35

R35
R25

R25
R28

R31

R28

R31

S3 ENABLE
FREIGABE
STELLZEIT
OPERATING
TIME - +
V24 V24
V23 READY
V23
BEREIT
S2 V35
J
Mess- V35
V37 V37
punkte

M1 R88
E1 M2{ R88
M3
E2 M4{

22
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

16. Setting of the operating time (output speed)


16.1 Setting of the operating time via internal command signal

Figure U: Actuator SAR with controls AUMA VARIOMATIC

Local controls

AUMA VARIOMATIC

Switch
compartment cover

.. Loosen 4 screws (8.1) and remove cover (figure U).


Set required operating time at potentiometer ”OPERATING TIME”
(figure V).
Short operating time: turn counter-clockwise.

.
Long operating time: turn clockwise.
Speed ranges see technical data sheet
Replace cover and fasten 4 bolts (8.1) evenly crosswise.

Figure V: VARIOMATIC standard

Potentiometer Diagnosis LED (green): Diagnosis LED (red): Diagnosis LED (green):
for setting of Illuminated when Motor protection Enable REMOTE (option)
OPERATING TIME ready tripped always installed,
illuminated during normal
operation

DIP switch S1
for programming
ON
1234 56 7

Diagnosis LEDs for


active REMOTE
Logic board control commands:
run command STOP (red)
Cover plate run command OPEN (green)
standard run command CLOSE (yellow)

23
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

16.2 Setting of the operating time via the speed-interface board (option)

(refer to order-related wiring diagram CI S...KMS 14TP...)


With the speed-interface board the operating time (speed) can also be
pre-determined through an external signal, either analogue (command sig-
nal E3 = 0 - 20 mA or 4 - 20 mA) or binary (command signal n1, n2).

The simultaneous use of the analogue and the digital


operating time set signal is not possible!

.. Loosen 4 screws (8.1) and remove cover (figure U, page 23).


The speed-interface board (figure W) is situated directly above the logic
board. Depending on the version (with or without positioner), remove the
boards above it (cover plate, positioner board and additional board).

FigureW: Speed-interface board

Range switch S1-2.2 Potentiometer R9: Potentiometer R10:


(component A2.2) for setting of the binary for setting of the binary
for analogue nominal nominal operating time n1 nominal operating time n2
operating time E3

Dot visible: LED’s:


4 - 20 mA V4: nominal operating
Dot not visible: time n1
0 - 20 mA V6: nominal operating
time n2

DIP switch S1 Range switch S2-2.2


for programming (component A2.2)
ON for analogue nominal
operating time E3

Dot visible:
positioner
Logic board
Dot not visible:
Speed-interface interface board
board

Potentiometer R16: Measuring point MP2 Measuring point MP1


adjustment analogue
nominal operating time E3

Setting . Check on the logic board whether the DIP switch S1, pos. 7 (nominal

.
on logic board: output speed) is in position ”OFF”. If necessary, correct the switch position
(see clause 14, pages 18/19).
Set the potentiometer ”OPERATING TIME” (figure V, page 23) on the
logic board to the fully clockwise position (max. speed) to make use of the
entire range of operating time. If the minimal operating time (max. speed)
has to be limited to a higher value as the operating time possible by the
actuator (see technical data sheet), set potentiometer to this value (e.g. to
avoid water hammer).

Setting on the When using the option positioner (see clause 15, page 20) set the selector
speed-interface board: switch S2-2.2 (figure W) on the speed-interface board to position
‘positioner’. For all other versions the switch S2-2.2 has to be set to position
‘speed-interface board’.

24
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

Analogue The analogue operating time range E3 (refer to wiring diagram CI S...KMS
nominal operating time E3: 14TP...) can be set with the switch S1-2.2 (figure W) to either 0 - 20 mA or
4 - 20 mA.

.
After a change, adjustment of the max. value (20 mA) is necessary.
The adjustment is performed as follows:
Connection of 24 V DC +/- 10 % to the analogue input of the

.
speed-interface board (see wiring diagram CI S...KMS 14TP...)
max. current input ≤ 30mA

..
Connection of 20 mA at nominal operating time E3 of the speed-interface
board (see wiring diagram CI S...KMS 14TP...)
Measure voltage between MP1 and MP2 (figure W).
Adjust the voltage to 10,00 V +/- 0,01 V by using the potentiometer R16
(figure W).

Binary Two inputs are available for the setting of the operating time via binary sig-
nominal operating n1, n2 nals.

.
The adjustment of the two operating times is performed as follows:
Control of the binary nominal operating time n1 by
Connection of 24 V DC to the binary input n1 of the speed-interface board

.
(see wiring diagram CI S...KMS 14TP...)
A visual check of the connected signal with LED V4 is possible (figure W).
The setting of the operating time is done via potentiometer R9 (figure W),
clockwise rotations equals higher speed = shorter operating time.

.
Control of the binary nominal operating time n2 by
Connection of 24 V DC to the binary input n2 of the speed-interface board

.
(see wiring diagram CI S...KMS 14TP...)
A visual check of the connected signal with LED V6 is possible (figure W).
The setting of the operating time is done via potentiometer R10 (figure
W), clockwise rotations equals higher speed = shorter operating time.

.
.
During simultaneous control of n1 and n2, the shortest
operating time has priority.
Without control of n1 and n2, the max. operating time is
available.

.
.
When operated via local controls, the actuator always runs
with max. speed (shortest operating time).
Control of the set speed (operating time) is only possible
via REMOTE commands.

25
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

.
16.3 Further functions of the speed-interface board in conjunction with the positioner (option)

Remote change-over of the nominal operating time

This function is only possible in combination with the


analogue or binary nominal operating time (selector switch
S2-2.2 in position ‘positioner’, figure W).

The nominal operating time can be changed between the


operating time determined by the positioner and by the customer via the
speed-interface board with a + 24 V DC signal from Remote.

Voltage Function
for connection
internal nominal operating time
at AUMA
by positioner
plug / socket 0 V DC
(operating time dependent on error variable)
connector
XK
refer to wiring external nominal operating time
diagram by speed interface board 3)
CI S... 24 V DC
(analogue or binary nominal operating time)

. Change-over AUTO/REMOTE

The positioner can be completely switched off remotely with a + 24 V DC


signal. This permits the use of the binary control signals (OPEN, STOP,
CLOSE) in conjunction with the analogue or digital nominal output speed.

Voltage Function

for connection Run commands


at AUMA by positioner1)
0 V DC
plug / socket (operating time dependent on error variable)
connector XK
refer to wiring
diagram Run commands
CI S... by binary REMOTE commands 2) 3)
24 V DC
(OPEN, STOP, CLOSE and analogue or
binary nominal operating time)

1) The binary control signals must be externally deactivated


(customer) as long as the positioner is active.

2) This function is only possible in combination with the


analogue or binary nominal operating time (selector
switch S2-2.2 in position ‘positioner’, figure W, page 24).

3) If there is no external signal connected, the actuator runs


with its slowest speed (i.e. its longest operating time).

26
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

17. Signal board (option) Signal boards with the option Running indication (blinker transmitter) offer
the possibility to switch over from impulse to continuous signal by way of a
sliding switch (see wiring diagram CI S...KMS 14TP...).
The signal board (figure X) is accessible after taking off the green cover
plate (figure Q, page 18, or figure S, page 20).

Figure X: Signal board


switch for running indication (blinker transmitter)
OFF ON

18. Fuses Fuses (figure Y) are accessible after removing the local controls
(figure P, page 18)

Figure Y: Fuses

Fuses: F1 F2
(Figure Y)
20 x 5 20 x 5 F2
F1
10 A T; 1 A T;
250 V 250 V

Recommended fuses in mains: 16 A

Disconnect actuator from the mains before changing the


fuses.

27
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

19. Maintenance After commissioning, check for damages on paint of multi-turn actuator. Do
a thorough touch-up to prevent corrosion. Original paint in small quantities
can be supplied by AUMA.

AUMA multi-turn actuators require very little maintenance.


Precondition for reliable service is correct commissioning.

Seals made of elastomers are subject to aging and must therefore regularly
be checked and, if necessary, exchanged.

It is also very important that the O-rings at the covers are placed correctly
and cable glands fastened firmly to prevent ingress of dirt or water.

.
We recommend:

.
If operated seldom, perform a test run about every 6 months. This assures
that the actuator is always ready to operate.
Approximately six months after commissioning and then every year check

.
bolts between actuator and valve/gearbox for tightness. If required,
re-tighten applying the torques given in table 1, page 7.
At intervals of approx. 6 months press in several squirts of ball bearing
grease at the lubrication nipple with grease gun.

Lubrication of the valve stem must be done separately.

The gear housing is filled with lubricant in the factory.

A grease change is recommended after 4 - 6 years.

28
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

20. Certificate of conformity

29
Multi-turn actuators SARV 07.1 - SARV 10.1
AUMA VARIOMATIC Operation instructions

21. Declaration of incorporation

30
Multi-turn actuators SARV 07.1 - SARV 10.1
Operation instructions AUMA VARIOMATIC

31
nge
t ra SA 07.1 - SA 48.1 SG 05.1 - SG 12.1
duc max 32 000 Nm max 1 200 Nm
pro
r
Ou

Multi-turn actuators Part-turn actuators

AS 6 - AS 50 GST 10.1 - GST 40.1


max 500 Nm max 16 000 Nm

Part-turn actuators Spur gearboxes

GSM 40.3 - GSM 125.3 GK 10.2 - GK 40.2


max 5 600 Nm max 16 000 Nm

Worm gearboxes Bevel gearboxes