Ter minolog y
Appendix 1
Terminolog y
A p p e n d i x 1 - Te r m i n o l o g y
and actuates an output after a desired count has been
The curve showing the operating value of the reached.
characteristic quantity corresponding to various values
or combinations of the energising quantities CSV
Character (or Comma) Separated Values format. A
Characteristic Impedance Ratio (C.I.R.) widely used format for the exchange of data between
The maximum value of the System Impedance Ratio up different software, in which the individual data items a
to which the relay performance remains within the separated by a known character – usually a comma
prescribed limits of accuracy
CT
Characteristic quantity Current Transformer
A quantity, the value of which characterises the
operation of the relay, for example, current for an Current transducer
overcurrent relay, voltage for a voltage relay, phase angle A transducer used for the measurement of a.c. current
for a directional relay, time for an independent time CVT
delay relay, impedance for an impedance relay Capacitor Voltage Transformer. A voltage transformer
Check protection system that uses capacitors to obtain a voltage divider effect. • A1 •
An auxiliary protection system intended to prevent Used at EHV voltages instead of an electromagnetic VT
tripping due to inadvertent operation of the main for size/cost reasons
protection system DAC
CHP Digital to Analogue Converter
Combined Heat and Power DAR
Circuit insulation voltage Delayed auto-reclose
The highest circuit voltage to earth on which a circuit of D AT
a transducer may be used and which determines its Digital Audio Tape
voltage test
DBMS
Class index Data Base Management system
The number which designates the accuracy class
DCF77
Closing Impulse time LF transmitter located at Mainflingen, Germany,
The time during which a closing impulse is given to the broadcasting a time signal on a 77.5kHz frequency
CB
A microprocessor optimised in both hardware The range of values of the characteristic quantity or
architecture and software instruction set for the quantities, or of the energising quantities to which the
processing of analogue signals digitally, through use of relay will respond and satisfy the requirements
the DFT and similar techniques concerning it, in particular those concerning precision
Digital Signal Processing Effective setting
A technique for the processing of digital signals by The ‘setting’ of a protection system including the effects
various filter algorithms to obtain some desired of current transformers. The effective setting can be
characteristics in the output. The input signal to the expressed in terms of primary current or secondary
processing algorithm is usually the digital representation current from the current transformers and is so
of an analogue signal, obtained by A/D conversion designated as appropriate
Directional relay Electrical relay
A protection relay in which the tripping decision is A device designed to produce sudden predetermined
dependent in part upon the direction in which the changes in one or more electrical circuits after the
• A1 • measured quantity is flowing appearance of certain conditions in the electrical circuit
or circuits controlling it
Discrimination
The ability of a protection system to distinguish between NOTE: The term ‘relay’ includes all the ancillary
power system conditions for which it is intended to equipment calibrated with the device
operate and those for which it is not intended to operate
Electromechanical relay
Distortion factor An electrical relay in which the designed response is
The ratio of the r.m.s. value of the harmonic content to developed by the relative movement of mechanical
the r.m.s. value of the non-sinusoidal quantity elements under the action of a current in the input
circuit
DNP
Distributed Network Protocol. A proprietary EMC
communication protocol used on secondary networks Electro-Magnetic Compatibility
between HMI, substation computers or Bay Computers
Embedded generation
and protective devices
Generation that is connected to a distribution system
DOL (possibly at LV instead of HV) and hence poses particular
Direct-on-Line problems in respect of electrical protection
A p p e n d i x 1 - Te r m i n o l o g y
(PC) (desktop or portable) with keyboard, screen and
FBD
pointing device
Functional Block Diagram: One of the IEC 61131-3
programming languages HRC
High Rupturing Capacity (applicable to fuses)
Fiducial value
A clearly specified value to which reference is made in HSR
order to specify the accuracy of a transducer. (For High Speed Reclosing
transducers, the fiducial value is the span, except for
HV
transducers having a reversible and symmetrical output
High Voltage
when the fiducial value may be either the span or half
the span as specified by the manufacturer. It is still HVDC
common practice, however, for statements of accuracy High Voltage Direct Current
for frequency transducers to refer to ‘percent of centre- I
scale frequency’ and, for phase angle transducers, to an Current
error in electrical degrees.)
ICCP • A1 •
FPI Term used for IEC 60870-6-603 protocol
Fault Passage Indicator
ICT
Frequency transducer Interposing Current Transformer (software implemented)
A transducer used for the measurement of the frequency
of an a.c. electrical quantity I . D . M . T.
Inverse Definite Minimum Time
Full duplex communications
A communications system in which data can travel I G BT
simultaneously in both directions Insulated Gate Bipolar Transistor
Gateway I/O
The Gateway is a computer which provides interfaces Input/Output
between the local computer system and one or several IED
SCADA (or RCC) systems Intelligent Electronic Device. Equipment containing a
GIS microprocessor and software used to implement one or
Gas Insulated Switchgear (usually SF6) more functions in relation to an item of electrical
NOTE: All relays require some time to operate; it is When set for a given control point it means that the
possible, within the above definition, to discuss the commands can be issued from this point
operating time characteristics of an instantaneous relay Lock-out (auto-reclose)
I n s u l a t e d G a t e B i p o l a r Tr a n s i s t o r Prevention of a CB reclosing after tripping
A special design of transistor that is suitable for handling Long-term stability
high voltages and currents (relative to an ordinary The stability over a period of one year
transistor). Frequently used in static power control
equipment (inverters, controlled rectifiers, etc) due to the Low-speed auto-reclose
flexibility of control of the output See Delayed Auto-Reclose
Intrinsic error LV
An error determined when the transducer is under Low Voltage
reference conditions Main protection
Inverse time delay relay The protection system which is normally expected to
operate in response to a fault in the protected zone
• A1 • A dependent time delay relay having an operating time
which is an inverse function of the electrical Maximum permissible values of the input
characteristic quantity current and voltage
Inverse time relay with definite minimum Values of current and voltage assigned by the
t i m e ( I . D . M . T. ) manufacturer which the transducer will withstand
An inverse time relay having an operating time that indefinitely without damage
tends towards a minimum value with increasing values MCB
of the electrical characteristic quantity Miniature Circuit Breaker
IRIG-B MCCB
An international standard for time synchronisation Moulded Case Circuit Breaker
ISO Mean-sensing transducer
International Standards Organisation A transducer which actually measures the mean
K-bus (K-bus Courier) (average) value of the input waveform but which is
Term used for the Courier protocol on K-Bus interface for adjusted to give an output corresponding to the r.m.s.
K-Relay range manufactured by AREVA value of the input when that input is sinusoidal
A p p e n d i x 1 - Te r m i n o l o g y
A substation located at the electrical interface of two
sections of electrified railway. It contains provision for Overhead line
the coupling of the sections electrically in the event of O LTC
loss of supply to one section On Load Tap Changer.
ModBus O n L o a d Ta p C h a n g e r
Proprietary communication protocol used on secondary A tap changer that can be operated while the
networks between HMI, substation computers or Bay transformer is supplying load.
Computers and protective devices
Opening time
MPSS The time between energisation of a CB trip coil and the
Mid Point Sectioning Substation (electrified railways) instant of contact parting
Multi-element transducer Operating current (of a relay)
A transducer having two or more measuring elements. The current at which a relay will pick up
The signals from the individual elements are combined to Operating time (CB)
produce an output signal corresponding to the The time between energisation of a CB trip coil and arc • A1 •
measurand extinction
Multi-section transducer Operating time (relay)
A transducer having two or more independent measuring With a relay de-energised and in its initial condition, the
circuits for one or more functions time which elapses between the application of a
Multi-shot reclosing characteristic quantity and the instant when the relay
A reclosing scheme that permits more than one reclosing operates
operation of a CB after a fault occurs before lock-out Operating time characteristic
occurs The curve depicting the relationship between different
MV values of the characteristic quantity applied to a relay
Medium Voltage and the corresponding values of operating time
A p p e n d i x 1 - Te r m i n o l o g y
Platinum resistance temperature probe The limiting value of the characteristic quantity at which
the relay returns to its initial position
R
Resistance Residual current
The algebraic sum, in a multi-phase system, of all the
R.M.S.-sensing transducer
line currents
A transducer specifically designed to respond to the true
r.m.s. value of the input and which is characterised by Residual voltage
the manufacturer for use on a specified range of The algebraic sum, in a multi-phase system, of all the
waveforms line-to-earth voltages
Ratio correction Response time
A feature of digital/numerical relays that enables The time from the instant of application of a specified
compensation to be carried out for a CT or VT ratio that change of the measurand until the output signal reaches
is not ideal and remains at its final steady value or within a specified
band centred on this value
Rating
The nominal value of an energising quantity that appears Reversible output current • A1 •
in the designation of a relay. The nominal value usually An output current which reverses polarity in response to
corresponds to the CT and VT secondary ratings a change of sign or direction of the measurand
RCD Ripple content of the output
Residual Current Device. A protection device which is With steady-state input conditions, the peak-to-peak
actuated by the residual current value of the fluctuating component of the output
RCP r. m . s .
Remote Control Point. The Remote Control Point is a Root Mean Square
SCADA interface. Several RCP’s may be managed with
RMU
different communication protocols. Physical
Ring Main Unit
connections are done at a Gateway or at substation
computers or at a substation HMI ROCOF
Rate Of Change Of Frequency (protection relay)
Reactive power (var) transducer
A transducer used for the measurement of reactive RSVC
electrical power Relocatable Static Var Compensator
A p p e n d i x 1 - Te r m i n o l o g y
Ve c t o r g r o u p c o m p e n s a t i o n
TF
A feature of digital and numerical relays that
a) Transfer Function of a device (usually an element of a
compensates for the phase angle shift that occurs in
control system
transformers (including VT’s) due to use of dissimilar
b) Transient Factor (of a CT) winding connections – e.g. transformers connected
delta/star
Through fault current
The current flowing through a protected zone to a fault Vo l t a g e t r a n s d u c e r
beyond that zone A transducer used for the measurement of a.c. voltage
Time delay VT
A delay intentionally introduced into the operation of a Voltage Transformer
relay system
X
Time delay relay Reactance
A relay having an intentional delaying device
Z
TPI Impedance • A1 •
Tap Position Indicator (for transformers)
Transducer (electrical measuring
transducer)
A device that provides a d.c. output quantity having a
definite relationship to the a.c. measurand
Tr a n s d u c e r w i t h o f f s e t z e r o ( l i v e z e r o )
A transducer which gives a predetermined output other
than zero when the measurand is zero
Tr a n s d u c e r w i t h s u p p r e s s e d z e r o
A transducer whose output is zero when the measurand
is less than a certain value
Unit electrical relay
A single relay that can be used alone or in combinations