R/LD-20

23 February, 2011

Project Name: New Project

Quick Layout - Project Data Sheet

Project Data

Room Length: 6.00 m Ceiling Reflectance: 0.80


Room Width: 4.00 m Wall Reflectance: 0.50
Ceiling Height: 2.70 m Floor Reflectance: 0.20
Workplane Height: 0.70 m Maintenance Factor: 1.00

Luminaire Type Summary

Number Luminaire Type Catalogue Number

3 INDUSTRIAL ISE1424HSB

Illuminance Data Summary

Average Illuminance (Eave): 420 lx


Maximum Illuminance (Emax): 532 lx at x = 1.92 m, y = 3.13 m
Minimum Illuminance (Emin): 277 lx at x = 0.50 m, y = 5.50 m
Uniformity 1 - Emin / Emax: 0.520 (1 : 1.92)
Uniformity 2 - Emin / Eave: 0.659 (1 : 1.52)
Total lamp flux: 14700 lm
Total lamp flux per unit area: 612 lm / squ. m
Utilance: 69 %
Total electrical power: 294 W
Total electrical power per unit area: 12.3 W / squ. m

CGLux v2.14 Copyright © OPT Australia 1997-2002

All calculation results are based on the nominal values of lamps, ballasts, luminaires and other design
assumptions (M.F. / R.F.). Any deviations in these parameters may affect the illumination design.