Joint Calibration M/S Saif Power Ltd.

03-03-2011

3/3/2011 15:04 CALIB.MODE. FALSE TO TRUE STATUS CHANGE


3/3/2011 15:04 WE.DP.FROZEN 0 TO 0.3549407 VC
3/3/2011 15:04 WE.SP.FROZEN 0 TO -1.071023 VC
3/3/2011 15:04 WE.RTD.FROZEN 0 TO 65.50462 VC
3/3/2011 15:04 DP ZERO CALIBRATION 0 AT 0.351
3/3/2011 15:27 DP SPAN CALIBRATION 400 AT 399.832
3/3/2011 15:28 DP VERIFICATION 400 AT 400.041
3/3/2011 15:28 DP VERIFICATION 0 AT 0.025
3/3/2011 15:28 DP VERIFICATION 100 AT 99.948
3/3/2011 15:29 DP VERIFICATION 200 AT 200.03
3/3/2011 15:29 DP VERIFICATION 300 AT 300.007
3/3/2011 15:36 SP ZERO CALIBRATION 0 AT -1.144
3/3/2011 15:52 SP SPAN CALIBRATION 550 AT 549.806
3/3/2011 15:53 SP VERIFICATION 450 AT 450.067
3/3/2011 15:53 SP VERIFICATION 400 AT 400.033
3/3/2011 15:54 SP VERIFICATION 430 AT 430.001
3/3/2011 16:53 T ZERO ADJUSTMENT 32 AT 41.332
3/3/2011 17:00 CALIB.MODE. TRUE TO FALSE STATUS CHANGE
3/3/2011 17:00 WE.DP.FROZEN 0.3549407 TO 0 VC
3/3/2011 17:00 WE.SP.FROZEN -1.071023 TO 0 VC
3/3/2011 17:00 WE.RTD.FROZEN 65.50462 TO 0 VC

Note:-
Joint Calibration performed on 03-03-2011 at 1700 hrs, the results are as under:

Differential Pressure = Found OK


Static Pressure = Found OK
Temperature = Difference of 9 0F on higher side observed

As per M/S Saif Power request the existing flow computer FLOW BOSS 103 having persistent
communication problem has been replaced with BRISTOL CONTROL WAVE EFM flow computer on
03-03-2011 at 1500 hrs. Joint Calibration of newly installed flow computer was performed and
found ok except the temperature transmitter that reads 9 0F on higher side; this temperature
error will be compensated in billing of the volume passed till the problem is resolved.

SNGPL REPRESNTATIVE SAIF POWER REPRESNTATIVE

Muhammad Jawad Mughal

Metering Engineer (T) Sec-IV