CLIENT: - M/S PEPSICO HOLDING PVT. LTD.

PROJECT: - AQUFINA (PHASE-III) PLANT AT MAHUL- MUMBAI.

Bus Bar Calculation for Main LT Panel

A. Bus Bar size calculation for 3200A Rating Panel: -

CONDITIONS
Rating Current: 3200Amp.
System: 415Vac, TPN, 50Hz.
Fault Level: 50KA. For 1 Sec.

Operation Temp: 40°C rise over 45°C ambient.

CONSIDERATION
Enclosure size: 1400mm. wide X 400mm. height
Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.
Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)

CALCULATION
1. AC Current rating for Dual Al. Flats 200x10mm considered = 4750Amp.
(As per Table – 8.4 as INDAL hand
book)

2. Ambient correction factor (k1) 45°C rise over 35°C (ambient) = .88
(As per Table – 5 as INDAL hand book)

If ambient Temp. 45°C instead of 35°C than De-rating Factor = 1-θ° C x α


θ = Temp difference = 45°C - 35°C = 10
α = Resistance-Temp. Coefficient for Al. Bus= 0.00403
k1A = 1-10 x 0.00403 = 0.96

MILESTONES SWITCHGEARS PVT. LTD.


Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.
3. Enclosure correction factor (k2) ratio of total conductor bus bar cross-
section to enclosure cross-section.
(3 x 2 x 200 x 10) x 100
--------------------------------- = 2%
1400 x 400
De-rating factor for enclosure = 0.82
(As per Table – 5 as INDAL hand book)

4. Correction factor (k3) for busbar material = 1


5. Up-rating factor (k4) for PVC Sleeving bus bar = 1

6. Total Combined De-Rating factor = k1xK1Axk2xk3xk4


= 0.88 x 0.96 x 0.82 x 1 x 1
= 0.693

So, actual rating of considered busbar = 4750 x 0.693 = 3291Amp.

Conclusion: -
It means 2:200x10mm Al. Bus Bar is much sufficient for
3200A Rating as per actual operating conditions.

B. Minimum Conductor size for Stand 50KA Fault: -

While considering short circuit condition, assuming a steady state average


temperature of 75°C and final temperature of 160°C then required bus
section:

CALCULATION: (As per table – 17)

Let θ f =Final conductor temp after the fault = 160°C.


θ I = Initial conductor temp before the fault = 75°C.
A = Cross sectional area of conductor (Sq. inch) =?
T = Duration of fault (sec.) = 1 Sec.
Isc = Short circuit current = 50KA.

A θ f + 258

Or Isc = 14 x 10 ------ log10 ----------------



T θ I + 258

MILESTONES SWITCHGEARS PVT. LTD.


Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.
Isc x T
Or A= ----------------------------------------------
θ f + 258

14 x 10  log10 ----------------


θ I + 258

50,000 x 1
Or A= ---------------------------------------------- = 0.93 in
160 + 258

14 x 10  log10 ----------------


75 + 258

Or A= 600 mm. Considered bus section = 2x200x10 = 4000mm.

Conclusion: -
It means 2:200x10mm Al. Bus Bar is much sufficient for
stand 50KA Fault Current for 1Sec.

C. TEMPERATURE RISE CALCULATION OF


CONDUCTORS: -

Max. Temperature at full Load condition: -


i.e. When 3200Amp. Flows thru steady state temperature of 45
C.

Full Load Current


T max = Ambient X ------------------------------------------------------- X Allow T rise
Actual Current Rating of used Conductors

45 + (3200 / 3291) x 40 = 82.8C which is within the limit of 85C


[45+40].

Summary: Hence the designed bus bar for Main Panel


is OK & within the safe limit.

Reference: INDAL hand book


And IS: 8623 (Part – 1) of 1993.

MILESTONES SWITCHGEARS PVT. LTD.


Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.
Bus Bar Calculation for Bus Duct

A. Bus Bar size calculation for 3200A Rating Bus


Duct: -

CONDITIONS
Rating Current: 3200Amp.
System: 415Vac, TPN, 50Hz.
Fault Level: 50KA. For 1 Sec.

Operation Temp: 40°C rise over 45°C ambient.

CONSIDERATION
Enclosure size: 750mm. wide X 450mm. height
Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.
Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)

CALCULATION

1. AC Current rating for Dual Al. Flats 200x10mm considered = 4750Amp.


(As per Table – 8.4 as INDAL hand book)

2. Ambient correction factor (k1) 45°C rise over 35°C (ambient) = .88
(As per Table – 5 as INDAL hand book)

If ambient Temp. 45°C instead of 35°C than De-rating Factor = 1-θ° C x α


θ = Temp difference = 45°C - 35°C = 10
α = Resistance-Temp. Coefficient for Al. Bus= 0.00403
k1A = 1-10 x 0.00403 = 0.96

MILESTONES SWITCHGEARS PVT. LTD.


Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.
3. Enclosure correction factor (k2) ratio of total conductor bus bar cross-
section to enclosure cross-section.
(3 x 2 x 200 x 10) x 100
--------------------------------- = 3.5%
750 x 450
De-rating factor for enclosure = 0.78
(As per Table – 5 as INDAL hand book)

4. Correction factor (k3) for bus bar material = 1


5. Up-rating factor (k4) for Black Matt Painted bus bar = 1.2

6. Total Combined De-Rating factor = k1xK1Axk2xk3xk4


= 0.88 x 0.96 x 0.78 x 1 x 1.2
= 0.79

So, actual rating of considered bus bar = 4750 x 0.79 = 3752Amp.

Conclusion: -
It means 2:200x10mm Al. Bus Bar is much sufficient for
3200A Rating as per actual operating conditions.

Summary: Hence the designed bus bar for Bus Duct is


OK & within the safe limit.

Reference: INDAL hand book


And IS: 8623 (Part – 1) of 1993.

Bus Bar Calculation for Other Panels [Main Bus]

Current Rating Max.


Used
as per INDAL- [Approx] Actual
Sl. Current
Used Bus Bar Size: Hand Book Total De- Current
No. Rating in
Table No. 8.4 Rating Rating
Amp.
in Amp. Factor
2x100x10 – For
1.0 1600Amp
Ph. 2650Amp. 0.7 1855Amp
.
1x100x10 – For N.
2.0 100x10 – For Ph.
800Amp. 1565Amp. 0.7 1095Amp
100x6 – For N.
3.0 80x10 – For Ph.
630Amp. 1250Amp. 0.7 875Amp
80x6 – For N.