MINIMUM CLEARANCES

ANNEXURE- 1(b)
(Min. value in meters)
System Voltage 33 66 110 132 220 400 ± 500 800 Remarks
( in kV)
1 Clearances to Ground
a Across Street 6.1 6.1 6.1 6.1 7.0 8.8 12.5 12.4 IE Rule 77
b Along Street 5.8 6.1 6.1 6.1 7.0 8.8 12.5 12.4 --do--
c Other Areas 5.2 5.5 6.1 6.1 7.0 8.8 12.5 12.4 --do--
2 Clearance to Buildings
a Vertical ( from 3.66 3.97 4.58 4.58 5.49 7.32 11.59 10.90* IE Rule 79
highest object) *Vertical clearance
to be obtained at
maximum (still air)
final sags ( at
maximum
temperature or ice
loaded conductor @
0º)
b Horizontal ( From 1.83 2.14 2.75 2.75 3.66 5.49 10.98 9.15# #Horizontal
nearest point) clearance to be
obtained at worst
load condition with
maximum deflected
conductor position
including conductor
string if any.
3 At crossing with
a Tramway/ Trolly 3.05 3.36 3.76 3.97 4.78 6.44 -- 10.14 IE Rule 78
bus
b Telecom lines -- 2.44 2.75 2.75 3.05 4.48 -- 7.90 IE Rule 78
c Railways
Above Track 14.1 14.1 14.6 14.6 15.4 17.9 -- 22.00 Regulations for
power line crossings
of railway tractions
1987.
Over crane 1.5 2.0 2.25 2.5 3.5 6.0 -- 9.5 --do--
4 Right of way width 15.0 18.0 22.0 27.0 35.0 52.0 52.0 85.0
5 Between lines when crossing each other ( derived )
a 250V 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
b 650V 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
c 11kV 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
d 22kV 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
e 33kV 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
f 66kV 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
g 110kV 2.44 2.44 2.75 3.05 4.58 6.10 10.8 10.0 IE Rule 87
h 132kV 3.05 3.05 3.05 3.05 4.58 6.10 10.8 10.0 IE Rule 87
i 220kV 4.58 4.58 4.58 4.58 4.58 6.10 10.8 10.0 IE Rule 87
j 400kV 6.10 6.10 6.10 6.10 6.10 6.10 10.8 10.0 IE Rule 87
k ± 500 kV 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.0 IE Rule 87
l 800kV 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 IE Rule 87
6 Clearance over For 110kV – 19 Mtr + 1cm for every additional kV ( Reference G.I.R. J – 42011/B(2) 86 GPD dt
navigational river 24.1187
7 Clearance over -- -- -- 4.30 5.10 6.40 6.75 9.40 Ref. CBIP handbook
Non-navigational Maximum Height of
river floating body above
HFL = 3.0 mtr