LC WTP127R2 e 0906
LC WTP127R2 e 0906
LC WTP127R2 e 0906
■Dimensions(mm)
Terminal type
6.35
4.5
Contents indicated (including the recycle marking,
Battery case resin: Flame-retardant (UL94V-0)
etc) are subject to change without notice.
3 25℃
Terminal 250M
■Characteristics
20 hour rate 7.2Ah 60
Capacity 10 hour rate 6.5Ah 0℃
(25 ℃) 3 hour rate 5.8Ah 30
1 hour rate 4.9Ah
Fully charged battery
(minute)
Internal Resistance 21 mΩ 10
(25 ℃)
-15℃
Temperature 40 ℃ 102% 5
Dependency of 25 ℃ 100%
3
Capacity 0℃ 85%
(20 hour rate) -15 ℃ 65%
After 3 months 91% 1
Self Discharge 0.1 0.3 1 3 10 30 100
After 6 months 82%
(25 ℃)
After 12 months 64% Discharge current(A)
■Charging Method
**Control voltage: 13.6V~13.8V at 20℃~25℃ with temperature compensation, Initial current: 1.08A or smaller
**Please consult us for the right control voltage if the ambient temperature is different.
Data in this sheet are for reference only and are not guaranteed values.
1/1 2009.06