Air Handling Units: I-Arrangements
Air Handling Units: I-Arrangements
I- Arrangements
1- Year – Round Commercial AHU
1-Mixing plenum
1-Mixing plenum 1-Mixing plenum
2-Filter G4
2-Cooling Coil 2-Electric Heater
3-Cooling Coil
4-Electric Heater
5-Supply Fan
2- Year – Round Commercial AHU Central Heating
Panel Filter Cooling Coil
G4 SHF= 0.9 : 0.7 Heating Coil
Mixing Box
Supply Fan
Sand trap
louvers
1-Mixing plenum
1-Mixing plenum 2-Filter G4 1-Mixing plenum
2-Cooling Coil 3-Cooling Coil 2-Electric Heater
4-Electric Heater
5-Supply Fan
6- Sound attenuator
5- Year – Round AHU in Dry Summer Climate
1-Mixing plenum
2-Filter G4
1-Mixing plenum 1-Mixing plenum
3-Precooling Coil
2-Precooling Coil 2-Heating Coil
4-Heating Coil
3-Air Washer 3-Air Washer
5-Air Washer
6-Eliminator
7-Supply Fan
6- Year – Round AHU Year- Round Humidity Control
Pharmaceutical Clean Single Room Class “ C “
Cooling Coil
SHF= 0.7 : 0.6 Empty Module
Panel Filter Steam Humidifier
G4 Bag Filter Heating / Reheating HEPA Filter
Mixing Box
F9 Coil Supply Fan H13
Sand trap
louvers
Sand trap
louvers
Swirl Diffuser
With Treminal HEPA Filter
H13
Mixing Box
Sand trap
louvers
2- Filter G4 2- Filter G4
4-Reheating Steam
Coil 3-After Cooler Coil
1-Fresh Intake
2- Filter G4
3-Decisscent Wheel ( 1 )
4-After Cooler Coil ( 1 )
5-Decisscent Wheel ( 2 )
6-After Cooler Coil ( 2 )
7-Supply Fan
8-Rigid Bag Filter F9
14- Year – Round AHU Year-Round Cooling
Mixing Box
With Modulating
Dampers ( winter )
1-Mixing plenum
1-Mixing plenum
2-Filter G4
2-Chilled Water Spray 1-Mixing plenum
3-Air Washer /
Chilled Water 2-Air Washer
Spray
4-Eliminator
5-Supply Fan
II- Modules Specifications
Specifications
Computer Computer
Main Specifications
Psychrometric Calculations
• Supply Air Rate m3/ hr
• Outside Air Rate in m3 / hr
• Cooling Capacity in tons-ref ( or kW )
• Heating Capacity in kW
• Steam Humidifier Capacity in kg / hr
• Washer Capacity make-up water in lit / min
Cooling Coils
1. Air Rate
2. Heating Capacity
3. Air Inlet Condition
4. Maximum Steam Pressure or Temperature
Air Washer
1. Air Rate
2. Water Consumption
3. Air Inlet Condition
4. Operating Wet bulb
5. Wetting Ratio
6. Humidifying Efficiency
Filters
Coarse Dust Filter ( G ) < 7 μm > 0.7 μm
Rated Substitution
Rated ΔP Pa Type
Efficiency ΔP Pa
60 -65 % 150 30 G1
65 – 75 % 180 50 G2
75 – 90 % 250 75 G3
90 – 95 % 250 150 G4
Filters
Fine Dust Filter ( F ) < 0.7 μm > 0.5 μm
Air Rate is recommended
Rated Substitution
Rated ΔP Pa Type
Efficiency ΔP Pa
50 – 60 % 350 85 F5
60 – 80 % 350 100 F6
80 – 90 % 350 120 F7
90 – 95 % 450 150 F8
95 – 98 % 450 250 F9
Filters
High Efficiency Filter ( HEPA ) ( H < 0.5 μm)
Air Rate is recommended
Rated Substitution
Rated ΔP Pa Type
Efficiency ΔP Pa
Rated Substitution
Rated ΔP Pa Type
Efficiency ΔP Pa