Data Input Current Carrying Capacity Overall Dia.: Cable Selection Calculation - LT

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 5

ASHLEY HPDC PLANT AT CHEYAR 1

CABLE SELECTION CALCULATION - LT


DATA INPUT
Current
Carrying Overall
Sl.No. Description
16 sq.mm XLPE Al. Capacity Dia.
1 Ar.Cable
35 sq.mm XLPE Al. 70 20
2 Ar.Cable
50 sq.mm XLPE Al. 117 27
3 Ar.Cable
70 sq.mm XLPE Al. 140 30
4 Ar.Cable
95 sq.mm XLPE Al. 176 34
5 Ar.Cable
120 sq.mm XLPE 221 37
6 Al. Ar.Cable
150 sq.mm XLPE 258 41
7 Al. Ar.Cable
185 sq.mm XLPE 294 46
8 Al. Ar.Cable
240 sq.mm XLPE 339 51
9 Al. Ar.Cable
300 sq.mm XLPE 402 57
10 Al. Ar.Cable
400 sq.mm XLPE 461 63
11 Al. Ar.Cable 542 71
2.5 sq.mm PVC Cu.
1 Ar.sq.mm
4 CablePVC Cu. 24 16
2 Ar.sq.mm
6 CablePVC Cu. 30 18.5
3 Ar. sq.mm
10 Cable PVC Cu. 39 18.5
4 Ar. sq.mm
16 Cable PVC Cu. 52 20
5 Ar. Cable 66 22
25 sq.mm XLPE Al.
1 Ar.Cable 99 24

DATA INPUT

Supply Voltage 0.415 KV

Type of cable XLPE Al. / Cu. Armoured.

Method of laying Cable Trey

Derating Factors as per manufacturers


catlogue

Cables Laid in Racks (Touching Factor) 0.79

Temp. Factor at 45 Deg.C. 0.94

Total Derating factor = ( Touching Factor * Temp.Factor )

CALCULATION

Full load current of the connected load ( A ) = Totel connected load / ( Supply voltage * √3 )

Current carrying capacity after considering


the derating factors = Current rating of the cable * Derating factor Amps

No.of runs considered ( N ) N Runs

Total Current Carrying Capacity ( C ) = Current rating after derated * No. of runsAmps

VOLTAGE DROP CALCULATION

Pithavadian Partners Rev-0 Kausi Consultancy Services


ASHLEY HPDC PLANT AT CHEYAR 2

Length of the cable L Metre


A.C.Resistance of selected cable at max.
operating temp of 90 Deg.C. ( R ) as per
manufacturers catlogue R Ohms/Km.

Reactance of Cable selected ( X ) as per


manufacturers catlogue X Ohms/Km.

Total Impedance of the cable ( Z ) = √(R +X )


2 2
Ohms/Km.

( Full load current * Length * Impedance * √3 ) / ( 1000 *


Voltage drop of the cable (Volts) = No. of runs) Volts

Voltage drop in term of % = (Voltage drop of cable / 415) * 100 %

Current
Ambie Total
Rating
Conne nt No. Current
Connect Current Touchi after
cted Temp. of. Carryin Length Total
Sl.No. Cable size From To ed Load in Amp. ng consider
Load Factor Runs g ( L ) A.C.R Impedan
in KW (A) Factor ing
in KVA @ 45 (N) Capacit esista Reacta ce Voltage Voltag
derating
Deg. C. y(C) nce nce (ohms/k Drop e Drop
factors
(R) (X) m) (V) (%)

4 Runs of 3.5C 400


sq.mm Al. XLPE
1 Cable. Main MV Panel D.G Panel 827 1151 0.61 0.94 310.78 4 1243.13 20 0.1023 0.07 0.1240 1.235 0.30

2 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
2 Cable. Main MV Panel Panel-1 446.5 621 0.79 0.94 342.34 2 684.68 117 0.13 0.071 0.1481 9.323 2.25

2 Runs of 3.5C 185


sq.mm Al. XLPE HPDC
3 Cable. Main MV Panel Panel-2 327 455 0.79 0.94 402.49 2 804.98 110 0.1023 0.07 0.1240 5.372 1.29

2 Runs of 3.5C 240


sq.mm Al. XLPE HPDC
4 Cable. Main MV Panel Panel-3 419.5 584 0.79 0.94 298.53 2 597.05 107 0.162 0.072 0.1773 9.587 2.31

Inspection/
2 Runs of 3.5C 185 Quality die
sq.mm Al. XLPE maintainan
5 Cable. Main MV Panel ce Panel 290 403 0.79 0.94 251.74 2 503.48 175 0.265 0.072 0.2746 16.791 4.05

2 Runs of 3.5C 300


sq.mm Al. XLPE
6 Cable. Main MV Panel BBT-3 484.6 674 0.79 0.94 342.34 2 684.68 140 0.13 0.071 0.1481 12.108 2.92

Pithavadian Partners Rev-0 Kausi Consultancy Services


ASHLEY HPDC PLANT AT CHEYAR 3

Current
Ambie Total
Rating
Conne nt No. Current
Connect Current Touchi after
cted Temp. of. Carryin Length Total
Sl.No. Cable size From To ed Load in Amp. ng consider
Load Factor Runs g ( L ) A.C.R Impedan
in KW (A) Factor ing
in KVA @ 45 (N) Capacit esista Reacta ce Voltage Voltag
derating
Deg. C. y(C) nce nce (ohms/k Drop e Drop
factors
(R) (X) m) (V) (%)

1 Runs of 3.5C 300


sq.mm Al. XLPE
7 Cable. Main MV Panel BBT-2 230 320 0.79 0.94 342.34 1 342.34 147 0.13 0.071 0.1481 12.068 2.91

1 Runs of 3.5C 50
sq.mm Al. XLPE
8 Cable. Main MV Panel PSB-1 24 33 0.79 0.94 103.96 1 103.96 40 0.567 0.077 0.5722 1.324 0.32

1 Runs of 3.5C 120 Office


sq.mm Al. XLPE Block &
9 Cable. Main MV Panel Canteen 134 186 0.79 0.94 218.32 1 218.32 84 0.325 0.072 0.3329 9.029 2.18

1 Runs of 3.5C 95
sq.mm Al. XLPE
10 Cable. Main MV Panel MLSB 96 134 0.79 0.94 164.11 1 164.11 45 0.41 0.074 0.4166 4.337 1.05

1 Runs of 3.5C 95
sq.mm Al. XLPE ETP & STP
11 Cable. Main MV Panel Panel 100 139 0.79 0.94 164.11 1 164.11 100 0.41 0.074 0.4166 10.039 2.42

2 Runs of 3.5C 185


sq.mm Al. XLPE Machining
12 Cable. Main MV Panel Panel-1 345.2 480 0.79 0.94 251.74 2 503.48 140 0.265 0.072 0.2746 15.989 3.85

1 Runs of 3.5C 120


sq.mm Al. XLPE Compresso
13 Cable. Main MV Panel r Panel 112.5 157 0.79 0.94 191.59 1 191.59 112 0.325 0.072 0.3329 10.107 2.44

2 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
14 Cable. Main MV Panel Panel-4 436.5 607 0.79 0.94 342.34 2 684.68 117 0.13 0.071 0.1481 9.114 2.20

2 Runs of 3.5C 185


sq.mm Al. XLPE HPDC
15 Cable. Main MV Panel Panel-11 293.25 408 0.79 0.94 251.74 2 503.48 93 0.265 0.072 0.2746 9.023 2.17

2 Runs of 3.5C 185


sq.mm Al. XLPE
16 Cable. Main MV Panel BBT-4 301 419 0.79 0.94 251.74 2 503.48 165 0.265 0.072 0.2746 16.432 3.96

Pithavadian Partners Rev-0 Kausi Consultancy Services


ASHLEY HPDC PLANT AT CHEYAR 4

Current
Ambie Total
Rating
Conne nt No. Current
Connect Current Touchi after
cted Temp. of. Carryin Length Total
Sl.No. Cable size From To ed Load in Amp. ng consider
Load Factor Runs g ( L ) A.C.R Impedan
in KW (A) Factor ing
in KVA @ 45 (N) Capacit esista Reacta ce Voltage Voltag
derating
Deg. C. y(C) nce nce (ohms/k Drop e Drop
factors
(R) (X) m) (V) (%)

1 Runs of 3.5C 185


sq.mm Al. XLPE
17 Cable. Main MV Panel BBT-5 165 230 0.79 0.94 251.74 1 251.74 116 0.265 0.072 0.2746 12.665 3.05

2 Runs of 3.5C 300


sq.mm Al. XLPE
18 Cable. Main MV Panel BBT-1 435 605 0.79 0.94 342.34 2 684.68 132.7 0.13 0.071 0.1481 10.302 2.48

1 Runs of 3.5C 400


sq.mm Al. XLPE Machining
19 Cable. Main MV Panel Panel-2 274 381 0.79 0.94 402.49 1 402.49 135 0.1023 0.07 0.1240 11.049 2.66

4 Runs of 3.5C 400


sq.mm Al. XLPE
20 Cable. Main MV Panel D.G Panel 725 1009 0.61 0.94 310.78 4 1243.13 25 0.1023 0.07 0.1240 1.353 0.33

2 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
21 Cable. Main MV Panel Panel-7 436.5 607 0.79 0.94 342.34 2 684.68 141 0.13 0.071 0.1481 10.984 2.65

2 Runs of 3.5C 185


sq.mm Al. XLPE HPDC
22 Cable. Main MV Panel Panel-8 293.25 408 0.79 0.94 251.74 2 503.48 145 0.265 0.072 0.2746 14.068 3.39

1 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
23 Cable. Main MV Panel Panel-9 218.25 304 0.79 0.94 342.34 1 342.34 145 0.13 0.071 0.1481 11.295 2.72

1 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
24 Cable. Main MV Panel Panel-5 218.25 304 0.79 0.94 342.34 1 342.34 110 0.13 0.071 0.1481 8.569 2.06

2 Runs of 3.5C 300


sq.mm Al. XLPE HPDC
25 Cable. Main MV Panel Panel-6 435 605 0.79 0.94 342.34 2 684.68 105 0.13 0.071 0.1481 8.151 1.96

1 Runs of 3.5C 95 Melting


sq.mm Al. XLPE Furnace
26 Cable. D.G Panel Panel-1 100 139 0.79 0.94 164.11 1 164.11 170 0.41 0.074 0.4166 17.067 4.11

Pithavadian Partners Rev-0 Kausi Consultancy Services


ASHLEY HPDC PLANT AT CHEYAR 5

Current
Ambie Total
Rating
Conne nt No. Current
Connect Current Touchi after
cted Temp. of. Carryin Length Total
Sl.No. Cable size From To ed Load in Amp. ng consider
Load Factor Runs g ( L ) A.C.R Impedan
in KW (A) Factor ing
in KVA @ 45 (N) Capacit esista Reacta ce Voltage Voltag
derating
Deg. C. y(C) nce nce (ohms/k Drop e Drop
factors
(R) (X) m) (V) (%)

1 Runs of 3.5C 185


sq.mm Al. XLPE HPDC
27 Cable. D.G Panel Panel-12 160 223 0.79 0.94 251.74 1 251.74 75 0.265 0.072 0.2746 7.940 1.91

1 Runs of 3.5C 185


sq.mm Al. XLPE HPDC
28 Cable. D.G Panel Panel-13 169.5 236 0.79 0.94 251.74 1 251.74 135 0.265 0.072 0.2746 15.141 3.65

1 Runs of 3.5C 50
sq.mm Al. XLPE 30 KVA
29 Cable. D.G Panel INVERTER 20 28 0.79 0.94 103.96 1 103.96 45 0.567 0.077 0.5722 1.241 0.30

1 Runs of 3.5C 240


sq.mm Al. XLPE HPDC
30 Cable. D.G Panel Panel-10 208 289 0.79 0.94 298.53 1 298.53 145 0.162 0.072 0.1773 12.884 3.10

1 Runs of 3.5C 185


sq.mm Al. XLPE Utility
31 Cable. D.G Panel Panel-1 175.5 244 0.79 0.94 251.74 1 251.74 45 0.265 0.072 0.2746 5.226 1.26

1 Runs of 3.5C 95 Melting


sq.mm Al. XLPE Furnace
32 Cable. D.G Panel Panel-2 65 90 0.79 0.94 164.11 1 164.11 170 0.41 0.074 0.4166 11.093 2.67

1 Runs of 3.5C 240


sq.mm Al. XLPE HPDC
33 Cable. D.G Panel Panel-14 208 289 0.79 0.94 298.53 1 298.53 110 0.162 0.072 0.1773 9.774 2.36

1 Runs of 3.5C 400 Holding


sq.mm Al. XLPE Furnace
34 Cable. D.G Panel Panel 273 380 0.79 0.94 402.49 1 402.49 105 0.1023 0.07 0.1240 8.562 2.06

1 Runs of 3.5C 185


sq.mm Al. XLPE Utility
35 Cable. D.G Panel Panel-2 155 216 0.79 0.94 251.74 1 251.74 45 0.265 0.072 0.2746 4.615 1.11

Pithavadian Partners Rev-0 Kausi Consultancy Services