Problem Symptoms:
Slide Valve PID Controller 1170TIC1050 output oscillate (Hunting) when the controller was
transferred from Manual Mode to Auto Mode.
Problem Analysis:
During the manual operation of the slider valve the Load/Unload command of the operator is
going directly to the slider valve. The PID Controller 1170TIC1050 is by-passed but still in Auto Mode.
Because of this condition, the controller output goes to 100% if PV>SP or 0% if PV<SP. The controller
output can only be seen at the UCP panel and can only be change manually at UCP with an Engineering
Access Level.
Once the operator at CCR switched the control of the slide valve from Manual Mode to Auto
Mode, the controller gives a 100% or 0% command to the slider valve depending on the PV-SP condition.
This scenario causes an upset on the process and makes the controller to oscillate on a cyclic
degenerative manner.
We able to put the controller in Auto Mode because we manipulate the controller output
manually at UCP using an Engineering Access Level.