Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

MACHINE -

ANNUAL RELAY TEST


DATE OF TEST:
DATE OF PREVIOUS TEST:

87 G (Generater differencial)
Make
Type
SL.No:
Terminal Details:-
Aux Supply : A3 & A4
CT Terminal : R-A5 , Y-A7 , B-A9 , N-A6, A8, A10
Contact no: A1 & A2 (Trip)
F1 & F2 (Auxilary Relay)
Settings:-
Vs = 65V ; Vs = (25+(8+32)×1 = 65V
Testing:-
( I ) Pick up & Drop off

Obtained
Applied Expected
Pick up Drop off
AØ 65 V

BØ 65 V

CØ 65 V

( II ) Contact closing Time check:-

Applied Expected Obtained


Voltage Time Trip Anuncation
AØ - 65 v Instant

BØ - 65 v Instant

CØ - 65 v Instant
59 G ( Over Ovltage )
Make
Type
SL.No:
Terminal Details:-
Voltage Terminal : 9 & 10
Instant Contact : 5 & 6 - Annoncation
2 & 3 - Trip
Time Delay Contact : 7 & 8 - Annoncation
3 & 4 - Trip
Testing :-
Pick up & Drop off Test :-

piick up Drop off


Expected Obtained Expected Obtained
Instant contact 154 v 144.4 v

Time Delay contact 121 v 115.9 v

You might also like