5 SETTINGS 5.

6 GROUPED ELEMENTS

Multiplier for Pickup Current


1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR

Figure 5–86: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC

SETTING
PHASE TOC1
FUNCTION:
Disabled=0
Enabled=1

SETTING
PHASE TOC1
BLOCK-A :
Off=0

SETTING
PHASE TOC1
BLOCK-B:
5
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled

AND PHASE TOC1 DPO

827072A4.CDR

Figure 5–87: PHASE TIME OVERCURRENT 1 SCHEME LOGIC

GE Multilin T60 Transformer Protection System 5-165