Aavid OptimumDesignHeatsinks
Aavid OptimumDesignHeatsinks
Seri Lee
Aavid Engineering Inc.
Laconia, New Hampshire 0 3 2 4 7
Abstract mining the optimum fin density for different fin geometry
and flow conditions. Computational techniques were also
An analytical simulation model has been developed for employed in investigating the thermal performance of ex-
predicting and optimizing the thermal performance of bi- truded heat sinks [6, 7].
directional fin heat sinks in a partiaHy confined configura-
tion. Sample calculations are carried out, and parametric Existing convection heat transfer data in the literature
plots are provided, illustrating the effect of various design for extended surfaces invariably require the coolant fluid
parameters on the performance of a heat sink. It is ob- velocity adjacent to the surface be known. In predict-
served that the actual convection flow velocity through fins ing the thermal performance of a heat sink located in
is usually unknown to designers, yet, is one of the parame- a partially confined configuration, such as in, a typical
ters that greatly affect the overaH thermal performance of card-mount environment, however, one of the unknown
a heat sink. In this paper, a simple method of determining and hard-to-estimate parameters is the actual flow veloc-
the fin flow velocity is presented, and the development of ity through the fins. Unless the system is fully confined,
the overall thermai model is described. An overview of dif- so that the entire coolant is channeled through the fins,
ferent types of heat sinks and associated design parameters this surface flow velocity can only be determined by con-
is provided. Optimization of heat-sink designs and typical sidering the amount of flow bypass that results from the
parametric behaviors are discussed based on the sample hydro-dynamic balance across the heat sink. With this
simulation results. in mind, an analytical simulation tool has been developed
for predicting and optimizing the thermal performance of
Introduction hi-directional heat sinks, given a set of readily available
With the increase in heat dissipation from microelec- and measurable input parameters. The model computes
tronic devices and the reduction in overall form factors, for the amount of flow bypass and allows users to carry
it became an essential practice to optimize heat-sink de- out a parametric investigation to optimize the heat-sink
signs with least trade-offs in material and manufacturing performance by choosing one parameter at a time as the
costs. Only a handful of discrete information is available in control variable.
the technical literature regarding the optimization of heat This paper is largely divided into two sections, The first
sinks. Azar and his co-workers [1] reported a method of section deals with general discussions on various types of
design optimization and presented contour plots showing heat sinks, and their relative performance ratings and man-
the thermal performance of an air cooled narrow channel ufacturing costs. The latter section deals with the analyt-
heat sink in terms of fin thickness and channel spacing pa- ical model. Simulation results are compared with existing
rameters. They employed Poiseuille’s equation in relating experiment al measurements, and discussions are made on
the channel flow velocity to the pressure drop, and the op- the effect of various design parameters on the performance
timization method was presented, assuming the pressure and optimization of a heat sink.
drop across the heat sink is known.
I
,4
:
Cost/ Unit
@ 5,0UI Qty.
Amb]ent (Air)
$mo.oo
50.00 Case
, R).
Junct]on (D]e)
where, Q is the total heat dissipated, m is the mass flow Consider a package with a heat sink shown in Fig. 2,
rate through the heat sink, c is the heat capacity of the The overall thermal performance of the system can be
fluid, and AT.. is the average temperature difference be- measured in terms of the total thermal resistance which
tween the heat sink and the ambient fluid. The heat trans- can further be decomposed into three classical components:
fer efficiencies have been measured for a wide range of heat- the junction-to-case resistance, Rj,, the case-to-sink resis-
sink configurations, and their ranges are listed below. tance, Rc~, and the sink-to-ambient resistance, R,a;
● cross-cut patterns Besides the heat-sink material and fluid properties, the
. heat sink material model described herein requires nine input parameters, as
. etc. indicated in Fig. 3. Although the analysis is not limited to
a specific material and coolant fluid, ail the cases presented
in this paper assume aluminum as the material and air for
Characterization and Optimization of Heat Sinks the coolant. ordinarily, the approach flow velocity, ud, is
a result of the balance between the fan capacity and the
In view of achieving an optimum thermal performance, system pressure loss, and is not known a priori, However,
most of the parameters discussed in the previous section once the model is developed, the approach velocity can be
are interdependent of the others. It is often true that varied to produce the pressure drop versus flow velocity
the impact one parameter has on the performance of a relationship for a given system which, in turn, can be used
heat sink cannot be generalized, or even foreseen without
in conjunction with a particular fan curve to determine the
concurrently considering the consequences exhibited in the operating condition of the system,
other parameters. For example; a longer fin height provides
additional surface area for greater heat dissipation and im- In a partially confined configuration, where the flow duct
proves the overali thermal performance. However, if the is larger than the heat-sink cross sectional profile, there will
available volumetric flow rate is fixed, the overall perfor- be a certain amount of flow bypass, and, as a result, the
mance may deteriorate with the fin height; if the available flow velocity through the fins may be substantially differ-
pressure drop is fixed, a longer heat sink in the direction ent from the approach velocity, The amount of flow bypass
of flow may have an adverse effect on the performance by is strongly related to the cross sectional geometry and the
decreasing the actual velocity over the fin surfaces, and; an pressure drop across the heat sink, and this must be deter-
option of having more fins is generally viewed as a way to mined from the hydro-dynamic analysis before the thermal
improve the performance. This is a very dangerous gener- analysis can be carried out.
alization, because, in most cases, having excessive fins in-
Flow Bypass ‘
duce a higher pressure drop across the heat sink, resulting
in a severe reduction in flow velocity and/or a significant Using Ut to represent the average flow velocity through
increase in flow bypass over the heat sink. the fin region and ignoring the friction loss along the duct
surfaces, one can obtain the following expression for the
In order to demonstrate and examine the relationship unknown Uj by simultaneously satisfying the mass and
between various parameters and design constraints, let us momentum balances over the control surfaces surrounding
consider a typical situation where a hi-directional heat sink the system:
is placed in a rectangular flow duct of (W x H), as depicted
in Fig. 3. From an analytical modeling stand point, one (2aj - l)U; -2aju~+ l=(l-a~)2*=0 (3)
can use a numerical method which typically requires in the
order of 50,000 to 100, OOO discretized elements and hours where at = (w x h)/(W x H) is the fin area ratio, Uf =
of computation per each case [7]. The benefit of using a nu- LJj /Ud is the normalized fin flow velocity, AP f denotes the
merical method includes the ability to obtain detailed local loss due to the friction through the fin region, and p is the
information over the entire problem domain, and the pos- fluid density.
sibility of achieving a better accuracy. However, in most
applications, the ability to optimize and quickly narrow Since APt can be described as a function only of U!,
H
1-
.---- - - - - - 7
u
\\ \\ \\ \\ \\ \-. \\ YX \\ \\ \\ x. -.\ \\ \\ \\ \\ a
lj
WY \A
— Present
I
g 0.50
m>
3
~ 0.25
u
w
N 9 ■
=
I
● 6
● ●
I
I ❑
–0.25 I , , 1 , , ,
0 2000 4000 6000 0.001 001 01
Re I Dimensionless Fln Length, L“
Figure 4: Comparison of Flow Bypass for Different Number Figure 5: Comparison of Channel Heat Transfer for Differ-
of Fins ent Number of Fins and Fin Heights
(4)
the above expression is an implicit equation for Uj, and,
therefore, requires an iterative procedure. With an as- where As is the total exposed surface area including the
sumed initial value of Uj, one can readily determine the area of the base plate exposed between fins.
pressure drop using correlations or graphical data available
in the literature. In the present study, APf is determined The parallel plate Nusselt number, defined as
by interpolating the friction charts provided in reference 9
for different channel aspect ratios. The entrance and exit (5)
.
pressure losses are estimated from reference 10.
where g is the fin spacing, has been computed for the
Only a limited data are available in the literature that cases examined by Wirtz et al. [9], Two different fin den-
~ quantify the effect and amount of flow bypass. Wirtz et sities and three fin heights were tested. Figure 5 shows
al. [5] reported a set of flow results that were backed out a comparison of the present predictions with the mea-
from the thermal measurements on longitudinal heat sinks. surements as a function of the dimensionless fin length,
Their test geometry consists of 13 rows and 7 columns of ~.
= If /(2gh?ez~ Pr). Pr is the fluid Prandtl number, and
square packages placed in an open circuit wind tunnel with Re2~ = Uf 2g/v k the parallel plate Reynolds number.
a heat sink mounted on a central element of the seventh The figure reveals good agreement for low values of L*
row. Although the test geometry, where the measurement which corresponds to high flow velocities. The prediction
sample was placed in the wake of the upstream packages, is becomes conservative when the flow velocity is decreased
not identical to the single element case considered herein, at high L* values. These differences observed at high L*,
the behavior of flow bypass was expected to be similar, or at low flow velocities, are expected to be due to a combi-
and the results are compared in Fig. 4 for different fin nation of the buoyancy effect and radiation heat transfer.
densities. Readers are advised to consult reference 5 for
the other dimensions. In the figure, (1 – Uf ) represents the
Case Studies and Discussion
normalized amount of flow bypaas over the heat sink, and
R el = ud//v, where v is the fluid kinematic viscosity. As To examine the effect of various design parameters, let
can be seen from the figure, the agreement is excellent. us consider the case depicted in Fig. 3 with the following
dimensions as the default case.
Thermal Analvsis .
Upon determining the amount of flow bypass and the aver- od = 1.0 m / s
age fin flow velocity, the Colburn j factor can now be deter- W X H = 100 mm x 50 mm
mined, again in this study, by interpolating the graphical
wxh = 50 mm x 25 mm
data provided in reference 9. Noting that the heat transfer
coefficient, h~, used in the definition of Colburn j factor N@~, h!, lj = 10, 1.25 mm,20 mm, 100 mm
is based on the log-mean-temperature difference, the effec-
tive heat transfer coefficient, h, based on the temperature The parametric behavior, responding to a chosen vari-
difference between the heat sink and the inlet fluid temDer-
. able with all others unchanged, is investigated. Due to the
4 ‘3
E
L
k
L
2 20 : 2.0
[ 0.2
0.0 0.0 I
I r I 1 ! [ 1 / 0.0
0 10 20 30 40 50 60 70 80 90 100
Number of Fins Fin Length (mm)
Figure 6: Parametric Performance as a Function of Num- Figure 7: Parametric Performance as a Function of Fin
ber of Fins Length
lack of space, only a few calculations are presented and dis- between 4 and 5 fins.
cussed. Figures 6 to 8 show the resulting sink-to-ambient
thermal resistance RSa, fin flow velocity Ut, and the pres- The performance behavior as a function of fin length is
sure drop across the heat sink-assembly APj as a function shown in Fig. 7. Initially, the performance improves as the
of the chosen variable. The thermal resistance is defined total convective surface area increases with the fin length.
as However, “the rate of return on investment” diminishes as
AT,= 1 the length becomes longer. This is due to the temperature
R s a —=
=
(6)
Q ?lj hfL rise in the air stream between fin surfaces combined with
where qf represents the fin efficiency. Each parametric run a reduction in flow velocity that resulted from a higher
takes a few seconds using a personal computer. pressure drop across the heat sink. This diminishing return
on investment is also observed in Fig. 8 which shows the
As expected, Fig. 6 reveals the existence of an optimum behavior as a function of approach velocity U~.
number of fins. As the number of fins increases, the to-
tal convective surface area increaaes and, as a result of Finally, Fig. 9 reveals the importance of flow manage-
the greater pressure drop, the fin flow velocity simultane- ment. This shows identkal case shown in Fig. 6 except
ously decreases. Initially, the performance gain from the the duct dimensions are reduced down to the cross sec-
increase in surface area is greater than that lost from the tional dimensions of the heat sink. This case simulates a
reduction in fin flow velocity. The net effect is an improve- fully confined configuration where the entire flow is chan-
ment in thermal performance. However, as the number neled through the fins with no flow bypass. As compared
of fins continue to increase, the net effect reverses, and to the case shown in Fig. 6, the thermal performance has
the performance decreases beyond the optimum number improved significantly and, unlike the case where the flow
of fins. Although the optimum number of fins suggested bypass was allowed, the thermal performance continues to
by the simulation is 12, the recommended number of fins improve with the number of fins. In this case, however, the
should be slightly less (i.e. 10). The thermal gain expected penalty is in the increase in the pressure drop, requiring a
from 10 to 12 fins is so small in this case that having two stronger fan to maintain the same approach flow velocity:
additional fins would not likely justify the additional cost note that the scale of the right-side vertical axis has been
.~curred by extra material and, more importantly, the dif- doubled to accommodate the large increase in the pressure
ferent manufacturing method that must be employed to drop. In any of the above cases, the actual operating point
with a given fan can be found by superimposing the fan
produce the heat sink with more than 11 fins. The fin
height-t-gap aspect ratio of this heat sink with more than performance curve and locating the point of intersection
11 fins exceeds the maximum ratio of 6 attainable with a along the pressure curve.
cost effective, standard extrusion method.
Summary
The change in flow regime from turbulent to laminar
may occur as the number of fins increases and the fin spac- Different types of heat sinks are examined, and their rel-
ing becomes smaller. This phenomenon is reflected in the ative performance and cost ranges are presented. An an-
figure as a momentary lag in the performance improvement alytical simulation model and a method of computing the
. >
0
- 5.0
v
c
a)
: 4.0 -
1 I 5 0
ou
w
a)
v
c
o
5.0-
40-
-2.0
-1.6
.-
m
J?
3.0- 3.0- -1.2
5
E E z
b
~ 2 . 0 - -2.0 2.0 - -0.8
[:
r
0.0 I f 1 I 0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 0 5 10 15 20
Approach Velocity (m/s) Number of Fins
thermal performance ofa heat sinkin a partially confined 7. Mansingh, V., and Hassur, K., “Thermal Analysis of a
configuration are described. The model is validated by Pin Grid Array Package,” Proceedings of the 1993 In-
comparing the results with existing experimental data, and ternational Electronics Packaging Conference, Vol. 1,
sample cases are presented with discussions on the para- pp. 410-419.
metric behavior and optimization of-hi-directional heat
sinks. 8. Aavid Catalog No. 1200, Thermal Management,
Edited by H.T. Fox, 1989, Aavid Engineering, Inc.