Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Model: C175 D5e Frequency: 50 Fuel Type: Diesel

Generator set data sheet

Our energy working for you.


Spec sheet: Noise data sheet (Open/enclosed): Airflow data sheet: Derate data sheet (Open/enclosed): Transient data sheet: Standby SS20-CPGK ND50-OS550 / ND50-CS550 AF50-550 DD50-OS550 / DD50-CS550 TBA Prime kVA (kW) 160 (128) 1/2 5.3 24 3/4 7.6 35 Full 9.7 44 1/4 2.4 11 1/2 4.6 21 3/4 6.6 30 Full 8.4 38

Fuel consumption
Ratings Load gph L/hr

kVA (kW) 175 (140) 1/4 2.8 13

Engine
Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm BMEP at set rated load, kPa Bore, mm Stroke, mm Rated speed, rpm Piston speed, m/s Compression ratio Lube oil capacity, L Overspeed limit, rpm Regenerative power, kW Governor type Starting voltage

Standby rating Cummins QSB7G3 4 Cycle; In-line; 6 Cylinder Diesel

Prime rating

Turbo Charged and Charge Air Cooled 174 2075 107 124 1500 6.2 17.3:1 17.5 1800 50 14 Electronic 12 Volts DC 149 1779

Fuel flow
Maximum fuel flow, L/hr Maximum fuel inlet restriction, mm Hg Maximum fuel inlet temperature (C) 106 127 71

Air
Combustion air, m3/min Maximum air cleaner restriction, kPa 11.76 3.74 10.92

2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Exhaust
Exhaust gas flow at set rated load, m3/min Exhaust gas temperature, C Maximum exhaust back pressure, kPa

Standby rating 31.38 563 10.13

Prime rating 28.38 537

Standard set-mounted radiator cooling


Ambient design, C Fan load, KW m Coolant capacity (with radiator), L Cooling system air flow, m3/sec @ 12.7mmH2O Total heat rejection, BTU/min Maximum cooling air flow static restriction mmH2O 45 13 36.37 3.1 1396 0.12 1242

Open set derating factors kVA (kW)


Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50CS550. 27C Standby Prime 175 (140) 160 (128) 40C RTF RTF 45C RTF RTF Open 1517 1556 50C RTF RTF Enclosed 2387 2991 55C RTF RTF

Weights*
Unit dry weight kgs Unit wet weight kgs

* Weights represent a set with standard features. See outline drawing for weights of other configurations

Dimensions
Standard open set dimensions Enclosed set standard dimensions

Length 2656 3980

Width 1000 1100

Height 1653 2062

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Alternator data
Feature code B681 Connection1 Wye, 3 Phase Temp rise degrees C 163/125 Duty2 S/P Alternator UCI274F Voltage 380-415V

Ratings definitions
Emergency Standby Power (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Limited-Time running Power Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528. Prime Power (PRP): Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Base Load (Continuous) Power Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.

Formulas for calculating full load currents:


Three phase output Single phase output

kWx1000 Voltagex1. 73x0.8

kWxSingleP haseFactor x1000 Voltage

See your distributor for more information. Cummins Power Generation Manston Park, Columbus Avenue Manston, Ramsgate Kent CT12 5BF, UK Telephone: +44 (0) 1843 255000 Fax: +44 (0) 1843 255902 E-Mail: cpg.uk@cummins.com Web: www.cumminspower.com

2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

You might also like