Generator Set Data Sheet: Fuel Consumption
Generator Set Data Sheet: Fuel Consumption
Fuel consumption
Ratings Load gph L/hr
Engine
Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm BMEP at set rated load, kPa Bore, mm Stroke, mm Rated speed, rpm Piston speed, m/s Compression ratio Lube oil capacity, L Overspeed limit, rpm Regenerative power, kW Governor type Starting voltage
Prime rating
Turbo Charged and Charge Air Cooled 174 2075 107 124 1500 6.2 17.3:1 17.5 1800 50 14 Electronic 12 Volts DC 149 1779
Fuel flow
Maximum fuel flow, L/hr Maximum fuel inlet restriction, mm Hg Maximum fuel inlet temperature (C) 106 127 71
Air
Combustion air, m3/min Maximum air cleaner restriction, kPa 11.76 3.74 10.92
2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Exhaust
Exhaust gas flow at set rated load, m3/min Exhaust gas temperature, C Maximum exhaust back pressure, kPa
Weights*
Unit dry weight kgs Unit wet weight kgs
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Dimensions
Standard open set dimensions Enclosed set standard dimensions
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Alternator data
Feature code B681 Connection1 Wye, 3 Phase Temp rise degrees C 163/125 Duty2 S/P Alternator UCI274F Voltage 380-415V
Ratings definitions
Emergency Standby Power (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Limited-Time running Power Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528. Prime Power (PRP): Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Base Load (Continuous) Power Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.
See your distributor for more information. Cummins Power Generation Manston Park, Columbus Avenue Manston, Ramsgate Kent CT12 5BF, UK Telephone: +44 (0) 1843 255000 Fax: +44 (0) 1843 255902 E-Mail: cpg.uk@cummins.com Web: www.cumminspower.com
2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.